Page 1: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

AIR CONDITIONING SYSTEMS

HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

http://Global.MitsubishiElectric.com

MEE05K440

MITSUBISHI ELECTRIC MULTIPLE SPLIT TYPE AIR CONDITIONERS Series

The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series 9000 of the International Standard Organization (ISO) based on a review of Quality management for the production of refrigeration and air conditioning equipment.

ISO Authorization SystemThe ISO 9000 series is a plant authorization system relating to quality management as stipulated by the ISO. ISO 9001 certifies quality management based on the "design, development, production, installation and auxiliary services" for products built at an authorized plant.

The Air Conditioning & Refrigeration Systems Works acquired environmental management system standard ISO 14001 certification.

The ISO 14000 series is a set of standards applying to environmental protection set by the International Standard Organization (ISO).

New publication effective Oct 2006Specifications subject to change without notice

http://Global.MitsubishiElectric.com/

FM33568 / ISO 9001;2000

Certificate Number EC97J1227

Page 2: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Air conditioning is an ideal way of

controlling the temperature, movement

and cleanliness of air inside any

building, large or small. With today's

buildings being so well insulated and

increasingly full of electronic equipment,

the need for effective climate control is

greater than ever. Not only does it cool

in the summer months, but air conditioning

can also heat, doing away with the

need for separate heating systems

altogether. More and more people today

are enjoying the benefits of comfortable

working and living environments made

possible with air conditioning.

VRF system

VRF stands for Variable Refrigerant Flow.

A VRF air conditioning system modulates the

flow of refrigerant depending upon the capacity

requirements of the building. A VRF system

comprises of condensing unit sited externally

and a series of multiple heating to the

occupied space.

I nverter driven technology

At Mitsubishi Electric we strive to continually

meet the increasing demands of our customers,

being the first in the industry to offer highly

advanced ‘inverter driven’ systems. Using

inverter technology our systems produce just

the right amount of output to match the exact

requirement of any building. These systems

work so efficiently that they don’t waste

valuable energy by over-heating or over-

cooling, resulting in greatly reduced running

costs. Alternative systems that may appear

cheaper, can often cost substantially more to

run, making us the most cost effective choice

all round.

I ntelligent Power Module (IPM) technology

The City Multi range from Mitsubishi Electric

provides precise control of energy input,

through utilization of Intelligent Power Module

(IPM) technology. Employing this technology it

is possible to closely match the building

requirements, achieving more accurate control

of the occupied space. By using incremental

1Hz steps of capacity control, the amount of

power input required is significantly reduced,

resulting in greatly improved COP’s.

R410A refrigerant

As scientific evidence points to man-made

chemicals for the damage caused to the ozone

layer, we only use chlorine-free refrigerants

that are safe and have ‘zero ozone depletion

potential’. Accordingly, as our systems require

less energy to run, they have a significantly

lower indirect global warming potential too. In

short, our constant investment and product

development possible, whilst protecting the

environment at the same time.

Known the world over, the name

Mitsubishi is a trusted household name

associated with a variety of products

and services. Founded in 1907, the

company known today as Mitsubishi

Electric, quickly rose to the forefront of

the air conditioning industry - a position

we still enjoy today. We pride ourselves

on offering some of the most energy

efficient systems available on the

market.

Page 1 Page 2

Our Latest Technologies

Unsurpassed air conditioning

from Mitsubishi Electric

Page 3: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Sophisticated yet simple technology

VRF system

Our answer to VRF

Designed and manufactured to the highest standards, the

City Multi range offers one of the most reliable air

conditioning systems available. Simple to install and easy to

maintain, this range provides ideal solutions you can trust to

protect your investment.

Reliable

>All the City Multi outdoor units are made in Japan under stringent control.

Page 3 Page 4

Mitsubishi Electric sets the boundaries of VRF technology with the City Multi range, which is available using

R410A refrigerant with zero ODP (Ozone Depletion Potential). The range has been specifically designed for

today’s building requirements and addresses key market issues such as energy efficiency, adaptability and

reliability. With user friendly control systems utilizing Internet technology and integrated cooling and ventilation

indoor units, City Multi is the benchmark and market leader in VRF technology.

VRF is a multi and direct expansion type air conditioning system that one outdoor unit can be connected with

multiples of indoor units. The amount of refrigerant can be changed freely according to the load in the indoor unit

because inverter compressor is used in the outdoor unit. Zoning in a small office is easily made possible with

indoor unit whose minimum capacity is very small. Energy conservation is easily handled because individual

indoor unit can stop and start its operation as needed. Indoor unit has a lot of models in order to suit various

interior design needs. Appliance to control separating heat of cooling in evaporation from heat in condensation is

becoming important in air conditioning in the building.

Outdoor unitJoint

Header

Inverter driven compressor

PEFY-VMS

PEFY-VMR

ON 27˚c

ON 25˚c

ON 25˚c

OFF

OFF

ON 23˚c

ON 26˚c

Controller

Indoor unit

Page 4: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Unbeatable Efficiency

I nverter Driven Compressor Technology - now up to 50HP

Using inverter driven technologysaves energy for several reasons:

The unique Heat Interchange Circuit (HIC) enhances efficiency by providing additional sub-cooling and allows the

expansion device to control more effectively the refrigerant distribution, thereby increasing the operating efficiency

and reducing the volume of refrigerant in each system.

Heat Interchange Circuit

The compressor varies its speed to match the indoor cooling and/or heating demand and therefore only consumes

the energy that is required.

When an inverter driven system is operating at partial load, the energy

efficiency of the system is significantly higher than that of a

standard fixed speed, non inverter system.

The fixed speed system can only operate at 100%, and

partial load conditions prevail for the majority of the time.

Therefore fixed speed systems cannot match the annual

efficiencies of inverter driven systems.

Using proven single inverter driven compressor

technology, the City Multi range is favoured by the

industry for low starting currents (only 15 amps for a

16HP THM-A outdoor unit), a smooth transition across

the range of compressor frequencies and for

eliminating systems.

100%

15%

15Hz Cooling:97HzHeating:102Hz

Heating / Cooling Capacity

Linear CapacityControl

Compressor Frequency

LowStartingCurrents

LowStartingCurrents

City Multi Refrigerant CircuitCondenser

High temperature

Supercooled heat exchanger

Low temperature

Electric expansion valve

Medium temperature

Bypass

Electric expansionvalve

Hea

t exc

hang

er

Compressor

Accumulator

Evaporator

Common Refrigerant CircuitCondenser

Expansionvalve

Compressor

Accumulator

Evaporator

Page 5 Page 6

>All the City Multi compressors are inverter-driven type (4~50HP).

Page 5: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

3.68

Total Energy Conservation

Comparison of COP (energy efficiency) – 10HP system

The difference between THM-A and previous Mitsubishi Electric modelsTechnology is key when increased efficiency is demanded. The City Multi THM-A range is able to deliver this in simple ways.

The importance of COP

The THM-A range from Mitsubishi Electric provides precise control of energy input, through utilization of Intelligent

Power Module (IPM) technology. Employing this technology it is possible to closely match the building

requirements, achieving more accurate control of the occupied space. By using incremental 1Hz steps of capacity

control, the amount of power input required is significantly reduced, resulting in greatly improved COP’s.

In addition, IPM technology ensures effective performance under part load conditions, a condition that most

systems will be in for the majority of the normal working life cycle. By taking account the efficiency at both part

load, and peak load conditions, R410A City Multi is designed to provide unbeatable year round/seasonal efficiency.

A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant

circuit (low pressure loss) including new accumulator design also adds a few more points to the efficiency scale.

Enhancements to the heat interchange circuit, an inverter driven fan motor and a heat exchanger design again add

vital increases to overall system efficiency and COP’s.

COP stands for “Co-efficient of performance”. It is a measure of the useful energy a system can deliver compared

to the energy it consumes. It is calculated by dividing the energy output by the energy input of a system. The

higher the figure then the more efficient the system is deemed to be, with commensurate reduced running costs.

Mitsubishi Electric VRF models, the world's highest energy-efficient ACs, will undoubtedly reduce millions of tons

of CO2 emissions.

0R22

2.0

2.5

3.0

3.5

4.0

4.5

5.0

As of September, 2006 (based on internal survey)

Our equivalent product 8 years before

23%Energy Saving

COP

2.85

Page 7 Page 8

I ntelligent Power Module (IPM) Technology

Industry leading high COP (Coefficient of Performance) is realized

IndustryLeaderIndustryLeader

Page 6: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

For the Environment

History of refrigerantR22, an HCFC-based refrigerant, has been a popular choice for most chillers. R22 has been targeted by the

Montreal Protocol to be phased out in new equipment. Additionally, the European Union and other countries

governments are enforcing a ban of HCFC-based refrigerants for new installations.

Because of these restrictions, R410A refrigerants is increasingly available. R410A is a blend of HFCs, which do not

deplete the ozone but may contribute to global warming.

Technical aspects of refrigerantR410A is a more efficient refrigerant as it has a higher specific heat capacity when compared to R407C or R22.

This higher energy carrying capacity allows for smaller pipe sizes, longer pipe runs and reduces the volume of

refrigerant within a system. This is a major factor when complying with EN378, a European standard concerning

safety and environmental requirements in the design, manufacture, installation, operation, maintenance and

disposal or refrigerating systems.

Enhancing environmental care(measures for the RoHS Directive and the refrigerant reduction)

Every unit is in compliance with the RoHS Directive,* which stands for the restriction of hazardous substances:

Lead-free soldering is used to avoid Lead Groundwater Contamination on the print board. The amount of

refrigerant on the unit has also been reduced to enhance environmental care.

* RoHS Directive: the restriction of the use of certain hazardous substances in electrical and electronic equipment that has been sold in EU since July 2006

Page 9 Page 10

Efficient R410A refrigerant

Page 7: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

A Comprehensive City Multi Range

T he City Multi range Solutions for more demanding applications

Product Range – Outdoor Units

The City Multi range is Mitsubishi Electric’s answer to large scale VRF (Variable Refrigerant Flow) applications.

The efficiency of City Multi (in particular the new R410A THM-A Series models) is second to none and offers a

substantial increase in energy efficiency and corresponding EER/COP ratings.

The City Multi Y Series range offers a simple and

flexible solution where there is a demand for

a changeover capability between heating

and cooling, ensuring a constant,

comfortable indoor climate.

It also provides a modular ap-

proach to air conditioning re-

quirements – providing an

ideal solution for new build,

refurbishment projects

and phased installations.

With a wide range of 60

indoor units and 13 out-

door units, that include

single phase 4, 5 and

6HP models, the choice

is impressive.

OutdoorUnits

IndoorUnits

Page 11 Page 12

HEAT PUMP

COP

cooling / heating

HEAT PUMP

COP

HEAT PUMP

COP

HEAT PUMP

COP

8HPPUHY-P200THM-A

3.90/4.13

10HPPUHY-P250THM-A

3.41/3.95

12HPPUHY-P300THM-A

3.68/3.98

14HPPUHY-P350THM-A

3.07/3.71

4HPPUMY-P100VHM

3.35/3.42

5HPPUMY-P125VHM

3.24/3.69

6HPPUMY-P140VHM

2.90/3.23

22HPPUHY-P550TSHM-A

3.49/3.73

24HPPUHY-P600TSHM-A

3.15/3.75

26HPPUHY-P650TSHM-A

3.25/3.81

28HPPUHY-P700TSHM-A

3.06/3.70

16HPPUHY-P400THM-A

3.39/4.04

18HPPUHY-P450THM-A

3.06/3.84

20HPPUHY-P500TSHM-A

3.16/3.67

36HPPUHY-P900TSHM-A

3.02/3.94

38HPPUHY-P950TSHM-A

3.50/4.03

40HPPUHY-P1000TSHM-A

3.47/4.00

42HPPUHY-P1050TSHM-A

3.26/3.89

30HPPUHY-P750TSHM-A

3.16/3.83

32HPPUHY-P800TSHM-A

3.03/3.79

34HPPUHY-P850TSHM-A

3.17/4.01

50HPPUHY-P1250TSHM-A

2.97/3.87

44HPPUHY-P1100TSHM-A

3.10/3.85

46HPPUHY-P1150TSHM-A

3.00/3.78

48HPPUHY-P1200TSHM-A

3.07/3.84

Page 8: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Due to the compact design of outdoor unit, industry leading space saving is realized. Therefore, the new outdoor unit can be installed more freely than the conventional model.

Page 13 Page 14

The manageability of the outdoor unit has been

improved due to drastic reduction in unit weight,

leading to easy transportation, installation, and

reduction in withstand load.

The downsized outdoor unit can be transported through a 800mm wide door.

Industry leading weight saving is realized.

8-14HP outdoor units

10HP outdoor unit

As of September, 2006 (based on internal survey)

Approx. 230kg Approx. 185kg

Easy to transport

City Multi makes it easy.

Approx. 45kg reduction in weight

The narrow space between buildings

makes it difficult to use a crane.

8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP

Weight(kg) 185 185 210 210 240 240 370 395 395 420 420

30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP 50HP

Weight(kg) 450 450 480 480 635 635 660 660 660 690 690

800 (31-1/2)

1400 (55-1/8)

850

(33-

15/3

2)

The unit can easily be transported even into slender buildings.

Depth760

(29-29/32)

mm (in.) mm (in.)

Height1650

(64-31/32)

Height1650

(64-31/32)

Width920

(36-7/32)

Compact Design of New Outdoor Unit10

(13/32)10(13/32)

10(13/32)10(13/32)

60

IndustryLeaderIndustryLeader

11 (14/

32")

11 (14/

32)

Example of 6-people lift.

Page 9: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

The Strength of City Multi

F eatures and Benefits

Increased Pipe Lengths

New Fan DesignLow Noise Levels

City Multi VRF systems led the introduction of larger single fan rotors some ten years ago, achieving substantially

lower noise levels over multiple designs. Continuing the development in the areas of blade shape and weight,

Mitsubishi Electric have managed to achieve even higher performance and lower noise levels. To reduce noise

levels further and comply with inner city residential noise regulations, all outdoor units include Night Set-back

mode. This function works by lowering the fan speed and compressor frequency proportionally with reduction in

demand.

Total system pipe lengths of up to 300m(984ft) and furthest pipe lengths of 150m(492ft) make the City Multi Y

series system one of the most flexible VRF systems in the market

New inverter driven outdoor fan motor

The compressor compartment is sealed by metal panels to attain a low noise level in all directions.

Newly designed refrigerant circuit (low pressure loss)

Highly efficient R410A Scroll compressor

R410A R22

Y Series

Total Pipe Length 300(984) 240(787)

Furthest Piping Length 150(492) 120(393)

LowNoise LowNoise

Low NoiseLow Noise

Furthest piping length 175m[574ft] (equivalent length) (actual length 150m[492ft])

between indoor units top-bottom differential15m[49ft]

Outdoor unit

Indoor unit

Top-bottom differential 50m[164ft]

Y Series

Page 15 Page 16

NewImprovedFigures

NewImprovedFigures

m(ft)

Page 10: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

The Strength of New City Multi

R410A Pipe Sizing

The new models have a smaller foot print and service

space requirement than the R22 models.

Operating range in cooling is from an outdoor

temperature of -5˚C[23˚F], while that in heating has

expanded to an outdoor temperature of -20˚C[-4˚F]

Heating Operation RangeAt low ambient temperature the guaranteed operating range in heating is now lowered to -20˚C[68˚F]

Blue Fin TreatmentThe anti-corrosion Blue Fin treatment of the heat exchanger is especially

effective in urban environments where the build up of traffic pollutions can

damage the aluminum fins reducing the capacity and life expectancy of the

unit. All City Multi R410A outdoor units have been treated in this fashion.

As R410A has a higher specific heat capacity than R22,

the pipework is smaller. This means the pipe itself is

cheaper, easier to install and therefore less riser space is

required within the building.

Conventional

Conventional CITY MULTI

Gaspiping

φ28.58(φ1-1/8)

Liquidpiping

φ12.7(φ1/2)

mm(in.)

Gaspiping

φ22.2(φ7/8)

Liquidpiping

φ9.52(φ3/8)

8-14HP systems1.21m2

16/18HP systems1.84m2

50%reduction

-20˚C[-4˚F] -10˚C[14˚F] 0˚C[32˚F] 10˚C[50˚F] 20˚C[68˚F] 30˚C[86˚F] 40˚C[104˚F]

In cooling mode

Outdoor temperature(dry bulb temperature)

Outdoor temperature(wet bulb temperature)-20˚C

[-4˚F]15.5˚C[60˚F]

In heating mode

-5˚C[-23˚F]

43˚C[109˚F]

Effective Use of Space

Page 17 Page 18

18HP

1.84m2 2.77m2

Based on 10HP model

760(29-29/32)

300(11-26/32)

450(17-23/32)

920 (36-7/32)

1510(59-14/32)

760(29-29/32)

300(11-26/32)

450(17-23/32)

1220 (48-1/32)

1510(59-14/32)

760(29-29/32)

300(11-26/32)

450(17-23/32)

1220 (48-1/32)

1510(59-14/32)

1990 (117-23/32)

840(33-1/18)

100(3-30/32)

450(17-23/32)

mm (in.)

mm (in.)

Page 11: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 19 Page 20

Remote Controller

Remote Controller

Individual Remote Controller

Centralized Remote Controller

The need for control is paramount in order to optimise the performance of any air conditioning system and minimise its running costs. Mitsubishi Electric offer a wide range of control options designedto do just this.

Operating an air conditioning system without

the right control can prove costly. It's therefore

important to ensure that every system is

correctly specified to the degree of control it

requires. Mitsubishi Electric have a wide range

of controls available 'off-the-shelf' and where

needed, individual control systems can be

specifically designed to suit.

Good controls will benefit any application,

largeor small. Air conditioning products need

toreact to a variety of factors: different room

sizes, usage and staff levels; changes in the

climate; electronic equipment and lighting ...the

list goes on. So whatever the application,

optimum control of air conditioning systems is

essential and will result in a constant,

comfortable environment, which inturn is both

energy and cost efficient.

A degree of differenceWhen an air conditioning system is not

properly controlled,it will not run as efficiently

as it should. For every degree that the system

deviates from the required temperature,energy

costs can rise by up to 5%. Specify one of the

many control options from Mitsubishi Electric

to ensure air conditioning works as intended,

whilst giving the optimum amount of control.

The simpler, the betterWith the array of comprehensive control

systems available from Mitsubishi Electric,it

becomes simple to design and install air

conditioning systems. From a simple hand

heldcontroller to a G50 system - you are in

control.

The importance of control

Page 12: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 21 Page 22

: Each group / Batched : Each group : Block (City Multi indoor unit only) : Batched handling (for maintenance)

: Batched only : Not available : Not used : G-50A license registration possible. ✕ –

*3: Interlock setting from local remote controller. *4: From schedule setting *5: When PAC-YT32PTA is connected.*2: Installation possible at Initial setting tool.*1: For group operation, cross-over wring is required between indoor unit.

Integrated Communications Control with Mitsubishi's Unique Transmission Network (M-NET)

Local remote controller System controller

Remote controllerSimpleremote

controller

Wirelessremote

controller

Systemremote

controllerCentralized controller

ON/OFFremote

controller

Start / Stop

Operation mode

Temperature setting

Permit / Prohibit direction

Fan speed

Air flow direction

ON/OFF

Error flashing

Error content

Filter sign

Operating hour

Operation mode

Set temperature

Indoor temperature (intake)

Permit / Prohibit

Fan speed

Air flow direction

Weekly

Annual (Designated day setting)

One day

Times of stops / Starts per day

Times of stops / Starts per week

Auto off timer

Minimum setting unit (minutes)

Error history

Daily / Monthly reports

Electricity charges

Set temperature range limit

Auto lock

Ventilation (group / interlocked)

Group setting

Block setting

Revision of electricity charges

Start / Stop

Fan speed

Ventilation mode

Status

Fan speed

Ventilation mode

Ope

ratio

nM

onito

ring

Sch

edul

ing

Rec

ordi

ngO

ther

sC

ontr

ol a

ndm

anag

emen

t

Vent

ilatio

n(g

roup

/ in

terlo

cked

)Ve

ntila

tion

(gro

up /

inte

rlock

ed)

Ope

ratio

nM

onito

ring

PAR-21MAA

1G/16units 1G/16units 1G/16units 1G/16units 16/5050/50 2000G/2000unitsGB-50A browser

50G/50units

PAR-F27MEA PAC-SE/YT51CRA PAR-FL32MAPAR-FA32MA PAC-YT40ANRAPAC-SF44SRA GB-50A

GB-50A browser

50G/50units

GB-50A TG-2000A

Model

No. of units controllable(Groups (G) / units)

12

84

/

/

/

/

/ ✕

/ ✕

/

1

/

/

/

/ ✕

/ ✕

/

/

12

84

1

3/3

21/21

/

/

/

/ ✕

/ ✕

/

10

✕ ✕

1/1

✕ /

10

1/1

10

8

56

1

✕ /1*

*2

Scheduletimer

50G/50U

PAC-YT34STA

16

112

5

/

*4

*4

*4

*2

*2

*2

/

/

/

/ ✕

/ ✕

✕✕

/

/

12

84

1

*2

*2

*2

*2

/

//

✕/

*3

/

/

/ ✕

/

/

/ ✕

*5

Groupremote

controller

8G/16units

PAC-SC30GRA

✕/48

/ ✕

✕ /

/

/

/

/ ✕

/ ✕

*5

*5

✕/30

*5*5

*5

*5

✕/336*5

Remote ControllerRemote Controller

System Controller

MELANSMALANS has a large line-up, including local remote controllers, timers, grouping controllers, central controllers, and centralized integrated software, PLC and its software, as well as BMS interface hardware and software etc. The combination of the MELANS products can fulfill the requirements of small-scaled control system, middle-scaled control system up to 2000 indoor units, and/or large-scaled opening system affiliated to a BMS system. Moreover, with central controller G-50A/GB-50A, PC browser and long distance remote control (monitoring and operating) via net-work is possible and easy.

C entralized Remote ControllerI ndividual Remote Controller

LMAP02 BACnetTM interface softwarePAC-YG31CDA

Interface

MITSUBISHI ELECTRIC's CITYMULTI can be easily connected to the building management system through BACnetTM.

LON WORKSTM transmission line

BACnetTM transmission line

EthernetIntegrated centralized control software TG-2000A

M-N

ET

MITSUBISHI ELECTRIC's Air-conditionaer Network System (MELANS) leads air conditioner management a PC

browser and Network era.

System Remote Controller

ScheduleTimer

All of the local remote controllers feature liquid crystal and LED displays and easy to operate.

RemoteController

SimpleRemoteController

WirelessRemote Controller

PAR-F27MEA

PAR-FA32MAPAC-SE51CRAPAC-YT51CRA

PAR-FL32MA

PAR-21MAA

OUTDOOR UNITY :PUHY

INDOOR UNITPLFY-VAMPLFY-VLMDPMFY-VBMPEFY-VMRPEFY-VMSPDFY-VMPEFY-VML

PEFY-VMHPCFY-VGMPKFY-VAM / VGM / VFM PFFY-VLEMPFFY-VLRMFresh Air Intake type

A ir-Conditioning Control System

This is a specialized air condi-tioning management system, in which up to 2000 indoor units can be centrally controlled.

ON/OFFRemote Controller

PAC-YT40ANRAPAC-SF44SRA PAC-YT34STA

G-50A GB-50A

GroupRemote Controller

PAC-SC30GRA

Page 13: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 23 Page 24

Remote ControllerRemote Controller

Control SystemsIndividual Control Systems

MA remote controller

Non-polarized2-wire

Non-polarized2-wire

MA remote controller

Example of system configuration

M-NET

Wired MA remote controller PAR-21MAA

New display-Larger,easier-to-see characters• Dot matrix liquid crystal screen displays complete operating status.

• Digital display lets you set temperature in 1˚C/˚F increments.• Weekly Timer: up to 8 ON/OFF/Temperature Settings can be

made per day. The time can be set in 1-minute increments.• Equipped with a thermostat sensor in the remote controller

that makes possible more comfortable room temperature con-trol.

• Enables you to select cool/heat/fan operation mode with the indoor remote controller of your choice without using the cool/heat selector.

• Ability to limit the set temperature (upper and lower tempera-ture can be set.)

• Ability to restrict setting changes (either all changes or all ex-cept ON/OFF)

• Constantly monitors for malfunctions in the system, and is equipped with a “self-diagnosis function” that lets you know by error code immediately when a malfunction occurs.

• Dimensions: 100 x 120 x19 mm

Various control systems can be offered with indoor unit remote controller.

Lossnay

Remotecontroller

Remotecontroller

Outdoor unit

Cooling/Heating mode switch control

Remotecontroller

Remotecontroller

Remotecontroller

Remotecontroller

Remotecontroller

Remotecontroller

Cooling/Heating mode of the outdoor unit can be switched with the remote controller for indoor unit.

Two-remote-controllercontrolBy connecting with two re-mote controllers, an outdoor unit can be controlled freely either from the one in the room or from the one in the control room. (Last setting override) Group control is possible by using two remote controllers.

Remote controlRemote controller wiring can be extended up to 200m, which makes it possible for the indoor unit remote controllers to be instal-led at one place without being separated.

Interlocking controlTotal enthalpy heat exchanger (Lossnay) can be operated and controlled with in-door unit remote controller. Cleaning time for an air wash unit is displayed on the controller when the unit is connected.

Group controlA remote controller can control up to 16 indoor units at the same time.(Automatic address setting)

Dot liquid crystal display

● Display example [Operation mode]

● Display example [Cool mode]

ON/OFF TEMP.

˚F

˚F

TIME SUN

WEEKLYSIMPLE

AUTO OFF

[Japanese]

[Russian][English]

[Itarian]

[German]

[Chinese]

[Spanish]

[French]

Various information is displayed and conveyed clearly, enabling more accurate operation of the air conditioner.

Dot Liquid Crystal Display (LCD)The dot liquid crystal display enables quick under-standing of the operation state.

Multi-language DisplayIn addition to English, contents can be displayed in sev-en other languages.This function makes the remote controller very useful in fa-cilities where foreigners are present.

Multi Language Display Example

Page 14: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 25 Page 26

PAC-SE51CRA

PAR-FL32MA PAR-FA32MA

Simple remote controller PAC-SE51CRA(M-NET) / PAC-YT51CRA(MA)

Wireless remote controller PAR-FL32MA / PAR-FA32MA

Remote ControllerRemote Controller

Wired ME remote controller PAR-F27MEA

Example of system configuration

Example of system configuration

Example of system configuration

• This remote control requires that wiring is connected to only one outdoor unit.

• Group operation with multiple outdoor units is possible. Grouping can be changed freely, which makes dividing rooms for tenant easier.

• Daily timerRepeated ON / OFF timer every day.

• Auto OFF timer0:30, 1:00, 1:30, 2:00...4:00 one touch timer.

• Function lockAll functions or all functions except ON / OFF can be selected.

• Limit setting of room temperature.• Dimensions:130 x 120 x 19 mm

• No need to configure addresses for group operation.• Lit LED keeps you informed of operation - blinking even

gives you the error code via the number of blinks.• Can be used with the MA remote controller.

*When used in group configurations, wiring between indoor units is required.

*Combining ME remote controller and/or LOSSNAY remote-controller in a group is not possible.

• Optional LCD temperature setting and display in 1˚C /1˚F unit.

• Dimensions:153 x 57 x 18 mm

• Control: START/STOP, room temperature and fan speed• The only wiring required is cross-over wiring based on

two-wire signal lines.• Room temperature sensors are built-in.• LCD temperature setting and display in 1˚C /1˚F unit.• Can operate all types of indoor units

*Since this system has no operation mode switching, test op-eration, self-diagnosis or interlock setting functions, it should always be used in conjunction with the PAR-21MAA or other centralized controller.

*Combining ME remote controller and/or LOSSNAY remotecontroller in a group is not possible.

• Dimensions:120 x 70 x 41 mm

Control SystemsIndividual Control Systems

ME R/C ME R/C

UP

Central controller

Power supply unit

SimpleMA R/C

SimpleMA R/C

Signal receiving unit

Signal receiving unit

Non-polarized2-wire

Non-polarized2-wire

Non-polarized2-wire

Wireless remote controller

Wireless remote controller

Signal receiving unit

Wireless remote controller

Page 15: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 27 Page 28

CentralizedRemote Controller

System exampleSystem example

Systemremote

controller

R / C : Remote Comtroller R / C : Remote Comtroller

PZ-52SFPZ-52SF

LOSSNAY

Power supplyunit

LOSSNAYLOSSNAY

PAR-21MAA PAR-21MAA

UP

Systemremote

controller

Schedule timer

Power supplyunit

Simple PAC-SE51CRA

PAR-F27MEA

PAR-21MAA

LOSSNAY

UP

System remote controller PAC-SF44SRA Schedule timer PAC-YT34STA

Remote ControllerRemote Controller

FUNCTION

UNITS

ON/OFF

MODE SELECTION

TEMPERATURE SETTING

FAN SPEED SETTINGS

AIR FLOW DIRECTION

PERMIT/PROHIBIT FUNCTION

INDOOR RETURN AIR TEMPERATURE

ERROR INDICATION

VENTILATION INTERLOCK

EXTERNAL INPUT

EXTERNAL OUTPUT

DESCRIPTION PAC-SF44SRA

50 units/50 groupMax No.Units

Run and stop operationSwitches between Cool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on the indoor unit. Auto mode is available with only R2 and WR2 systemsSets the groups temperature control.Cool/Dry:19-30˚CHeat:17-28˚CAuto:19-28˚C4 speed - Lo-Mi1-Mi2-Hi2 speed - Lo-HiAir Flow angles:100˚-80˚-60˚-40˚ and auto swingRun/Stop,Temperature Setting,Mode Selection and Filter Reset functions can be prohibited via a higher level system controllerMeasures the intake temperature of the master unit within the group Displays a 4 digit code and the affected unit addressAllows the group to be interlocked with a heat recovery Lossnay unitHardwired connections available

Hardwired connections available

One system controller is available for use when you need to control up to fifty indoor units from one location. The PAC-SF44SRA also has hardwired connection available (On/Off input, fire alarm input, run output, fault output).

Mitsubishi Electric controllers are complimented by a weekly programmable timer, being able to control up to fifty indoor units. The PAC-YT34STA also has hardwired connection available (On/Off input, fire alarm input, run output, fault output).

System Controller

FUNCTION

UNITS

ON/OFF

MODE SELECTION

TEMPERATURE SETTING

CURRENT TIME

ERROR INDICATION

EXTERNAL INPUT

EXTERNAL OUTPUT

DESCRIPTION PAC-YT34STA

50 units/50 groupMax No.Units

Run and stop operationSwitches between Cool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on the indoor unit. Auto mode is available with only R2 and WR2 systemsSets the groups temperature control.Cool/Dry:19-30˚CHeat:17-28˚CAuto:19-28˚CSet the timeDisplays a 4 digit code and the affected unit addressHardwired connections available

Hardwired connections available

Programmable Timer

Displays

On/Off/Fire AlarmOn/Off/Faults

Operation Operation Displays

On/Off/Fire AlarmOn/Off/Faults

• Dimensions:130 x 120 x 19 mm

• Dimensions:130 x 120 x 19 mm

Page 16: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

System example

Page 29 Page 30

ON/OFFremote

controller

LOSSNAY

PZ-52SF

PAC-YT51CRA

PAR-F27MEA

PAR-21MAA

ON/OFF remote controller PAC-YT40ANRA Group remote controller PAC-SC30GRA

Remote ControllerRemote Controller

CentralizedRemote Controller

System example

Connect to the centralized transmission line

R/C:Remote Controller

UP

Power supply unit

Group remotecontroller

PAR-21MAA PAR-21MAA

Connect to the indoor/outdoor transmission line

Group remotecontroller

PAR-21MAA PAR-21MAAR/C:Remote Controller

FUNCTION

ON/OFFOPERATION MODE SWITCHINGTEMPERATURE SETTINGFAN SPEED SETTINGAIR FLOW DIRECTION SETTINGMANUAL OPERATION PROHIBIT/PERMIT(ON/OFF, OPERATION MODE, SETTING

TEMPERATURE, FILTER RESET)

SPECIFIC MODE OPERATION PROHIBIT(COOLING PROHIBIT, HEATING PROHIBIT,

COOLING/HEATING PROHIBIT)

ROOM TEMPERATURE DISPLAY

ERROR DISPLAY

SCHEDULE OPERATIONVENTILATION OPERATION(INDEPENDENT)

VENTILATION OPERATION(INTERLOCKED)

EXTERNAL OUTPUT(ERROR OUTPUT, OPERATION OUTPUT)

CONNECTION POSITION

DESCRIPTION

Run and stop operation for the air conditioner unitsNot availableNot availableNot availableNot available

Compatible only with external input.

Not available

Not availableLED flashes during failure.(The error code can be confirmed by removing the cover.)Not availableGroup operation of only LOSSNAY units possible.*Only ON/OFF of group.The LOSSNAY will run in interlock with the operation of indoor unit.*The fan rate and mode cannot be changed. The LED will turn ON only during operation after interlocking."ON/OFF" and "error/normal" are output with the level signal.*The optional output cable is required.

Indoor/outdoor transmission line: ConnectableCentral system transmission line: Connectable (Power supply unit (PAC-SC50KUA) is needed.)

OPERATIONS DISPLAY

Just press a switch to start. All of the units can be started stopped by pressing the main switch, and each unit in the group can be started stopped with individual switched.

Up to 8 groups can be operated (maximum of 16 units/. Just by pressing RAC-SC30GRA switches, groups can be started and stopped as a batch.

• Dimensions:130 x 120 x 19 mm

• Dimensions:130 x 120 x 19 mm

FUNCTION

UNITS

ON/OFF

MODESELECTION

TEMPERATURE SETTING

FAN SPEED SETTINGS

AIR FLOW DIRECTION

PERMIT/PROHIBIT FUNCTION

INDOOR RETURN AIR TEMPERATURE

ERROR INDICATION

VENTILATION INTERLOCK

DESCRIPTION

Max No.Units

Run and stop operationSwitches betweenCool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on theindoor unit. Auto mode is available with only R2 and WR2 systemsSets the groups temperaturecontrol.Cool/Dry:19-30˚CHeat:17-28˚CAuto:19-28˚C4 speed - Lo-Mi1-Mi2-Hi2 speed - Lo-HiAir Flow angles: 100°-80°-60°-40° and auto swingRun/Stop,Temperature Setting,Mode Selectionand Filter Reset functions can be prohibitedvia a higher level system controllerMeasures the intake temperature of themaster unit within the groupDisplays a 4 digit code and the affectedunit addressAllows the group to be interlocked with a heatrecovery Lossnay unit

PAC-SC30GRA

OPERATIONS

16 units/ 8 groupDISPLAY

Page 17: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 31 Page 32

Remote ControllerRemote Controller

System Structure

Public telephoneline

�����

Router

Ethernet City Multi

M-NET

Remote monitoring via aWeb browser

Web browser

������

City Multi

M-NET

Provider

Provider

Operation

Example of display icons (air conditioner icons)

Stop

Occurrence of abnormality

Operation/Occurrence of a filter sign

In timer operation

Lossnay on

Under energy-saving control

Up to 50 units of packaged air conditioners can free-ly be monitored and operated! Furthermore, it has enabled the Monitoring and Op-eration Via a Web Browser on a Personal Computer connected to it using a LAN or telephone line!

First in the industryWith Web Server Functions!

* Microsoft is a trademark or trademark of Microsoft corporation.

• Simple and FlexibleThis new generation controller is suitable for small to large systems with simple to complex functions available.

• Web BrowserEnables monitoring and operation of air conditioning units us-ing a PC with Microsoft® Internet Explorer.

• Remote AccessAllows users to remotely monitor and operate the air condi-tioning units using a PC connected to a telephone line.

• Auto AlarmIn the case of any malfunction, necessary information will be sent to a mobile phone and/or personal computer by e-mail.

• Easy to UpgradeVarious new functions will be introduced gradually and can easily be down loaded into any existing G-50A/GB-50A.

Example: Energy MonitoringDemand ControlAnnual Schedule

G-50A (with display)

GB-50A

Central controller G-50A/GB-50A

FUNCTION

G50 Centralised Controller

G50 Software OptionsG50 - Saving Energy

G50 - Peak Cut

G50 - Personal Web

G50 - BacNet

Energy Saving Capability

Peak Cut Control

Virtual Remote Controllers

Bacnet interface

DESCRIPTION

Up to 50 indoor units can be connected

Run and Stop operation for a single group

Switches between Cool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on the indoor unit.

Auto modeis available with only R2 and WR2 systems

Sets the groups temperature control.Cool/Dry:19-30˚C,Heat:17-28˚C,Auto:19-28˚C

4 speed:Lo-Mi1-Mi2-Hi,2 speed:Lo-Hi

Air Flow angles:100˚-80˚-60˚-40˚ and auto swing

Maximum of 3 time sequences with 3 Start/Stop times per day for all groups can be allocated

Individual prohibit operations for each remote controller function (Run/Stop, Temperature Setting,Mode Selection

and Filter Reset) can be activated

Displays the measured intake temperature from each group

Displays a 4 digit code and the affected unit address.An error log is held showing the last 64 date stamped alarms

Allows each unit within the group to operate in test mode

Allows the group to be interlocked with a heat recovery Lossnay unit

Reduce the setpoint band of each individual unit (exp.23˚C to 25˚C)

Automatically switch heat pump outdoor unit to cooling or heating mode depending on the requirements

Commission the G50 from the web pages

Two types of login available (Administrator & Guest).Administrator able to allow specific function access to guest

Hardwired connections are available for : Inputs: Level Signal-Batch Start/Stop,Batch Emergency Stop

Pulse Signal-Batch Start/Stop,Enable/Disable Local R/C

Outputs: Start/Stop Status,Error/Normal Status

PAC-SC50KUA

G50 -Web Monitor

G50 - Email

G50 - Schedule

G50 - Change

Control and Monitor the G50 via Internet Explorer 5 or 6

Enable E-mail activation on fault conditions

Weekly / Annual Scheduling and Night Set Back

Energy Charge

MAX No.OFINDOOR UNITS

ON/OFF

MODE SELECTION

TEMPERATURE SETTING

FAN SPEED SETTING

AIR FLOW DIRECTION

TIMER OPERATION

PERMIT/PROHIBIT FUNCTION

INDOOR RETURN AIR

TEMPERATURE

ERROR INDICATION

TEST RUN FUNCTION

VENTILATION INTERLOCK

WEB SETPOINTLIMIT

WEB AUTOCHANGEOVER

WEB INITIALSETTING

WEB LOGIN

EXTERNAL INPUT/OUTPUT

POWER SUPPLY UNIT

CentralizedRemote Controller

Power supply unit PAC-SC50KUA

UP

POWER RATING

MODEL

WEIGHT

SERIAL No.

2.11kg

POWER SUPPLY UNIT

MITSUBISHI ELECTRIC CORPORATION

PAC-SC50KUA

Power supply unit PAC-SC50KUA

UP

POWER RATING

MODEL

WEIGHT

SERIAL No.

2.11kg

POWER SUPPLY UNIT

MITSUBISHI ELECTRIC CORPORATION

PAC-SC50KUA

Page 18: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 33 Page 34

Integrated centralized control software TG-2000A

1

2

3

4

5

6

7

8

Charge license

Web monitorlicense

Schedulelicense

Input G-50A

12VDC

M-NET

Example of Basic System Configuration. Main features of TG-2000A

Power supply unit PAC-SC50KUA

3-phase 208/230V(3-wire)

RS-232CRS-485

Indoor unit system watt-hour meter

Outdoor unit system watt-hour meter

Uninterruptive power supply (UPS)

Integrated centralized controlsoftware installation

Central controller personal computerTG-2000A

Indoor unit watt-hour meter

Single-phase 208/230V

Single-phase 208/230V

power sourceIndoor unit system

watt-hour meter

Outdoor unit system watt-hour meter

PLC (with electric amount count software)

Uninterruptible power supply (UPS)

Integrated centralized controlsoftware installation

Central control personal computerTG-2000A

Indoor unit watt-hour meter

Converter

Compatible with TG-2000A Ver. 4.10 and higher * The electric amount count software or separately procured parts must be used with the designated PLC.

The TG-2000A can realize the following functions using the G-50A/GB-50A option (license).

* Operation/monitor* Annual/weekly schedule* Charge* Energy saving *1* Peak cut *1*1: Compatible with TG-2000A Ver. 4.10 and higher,

G-50A Ver. 2.51 or later.

UP

POWER RATING

MODEL

WEIGHT

SERIAL No.

2.11kg

POWER SUPPLY UNIT

MITSUBISHI ELECTRIC CORPORATION

PAC-SC50KUA

Remote ControllerRemote Controller

CentralizedRemote Controller

Up to 2000 indoor units (40 G-50A/GB-50A units) can be operated and monitored simultaneously.The air-conditioner layout can be displayed on the screen, making control and operation easier.The annual and weekly schedules can be set. Two schedules, such as the summer master and winter master, can be saved in the weekly schedule.Air-conditioning charges can be calculated based on the multiple air-conditioner usage results. The power apportionment percentage data and apportioned power rate can be calculated for each indoor unit using the power apportionment function, and can be output as a CSV format file. * Power apportionment charging is not possible with the old model, A control or K control.

Charging without WHM : The user manually inputs the power rate to calculate the air-conditioning charges. (Using a tool)

RS-485 WHM charging : The RS-485 WHM value is automatically tabulated to calculate theair-conditioning charges.

PLC + pulse WHM charging : The pulse output WHM value is automatically tabulated by the PLC to calculate the air-conditioning charges.

Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation changeover" and "performance save operation (60% to 90%)" functions.Energy saving operation matching the amount of power in use is possible by using the PLC's electric amount count software.Night set-back operation is possible with schedule settings. *1*4General equipment can be operated and monitored. *2General equipment can be schedule-controlled when using PAC-YG21CDA with PLC.For details of PLC refer to Installation Manual of PAC-YG21CDA. *3

*1: Compatible with TG-2000A Ver. 4.10 and higher, G-50A Ver. 2.51 and higher.*2: Compatible with TG-2000A Ver. 4.30 and higher, G-50A Ver. 2.51 and higher.*3: Compatible with TG-2000A Ver. 4.60 and higher, G-50A Ver. 2.70 and higher.*4: With Night Set-Back function,the CITY MULTI system can run at heating mode with target temperature set

to 12˚C/54˚Funder schedule control. This function can protect the room from dropping down to extremelylow temperature at mid-night.

Page 19: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 35 Page 36

�������� M-NET���� ��

����

�� ����

����

Example of System ConfigurationSystem design made simple through integration ofvarious devices into a total control configuration.

Outdoor unit

M-NET LON WORKS

(78kdps)

208-230V60Hz

Remotecontroller

Indoor units

Remotecontroller

Indoor units

Remotecontroller

Indoor units

Remotecontroller

Indoor units

Remotecontroller

Lighting

SecurityCenter

control device

CITY MULTI System

Outdoor unit

Indoor units

Max. 50 indoor units

LON WORKS

The building management system is connected to the CITY MULTI air conditioning system using LON WORKS , which is widely used on

field networks, allowing for an open network and savings in construction to face.

LON WORKSProtocol converterbetween LON WORKS

and M-NET

LONWORKS (LMAP02) BACnet TM interface(PAC-YG31CDA)

Example of Basic System Configuration.

LAN

G-50A

Centralmonitor

BMS

TG-2000A(Optional)

Web Browser(Optional)

BACnet interface softwarePAC-YG31CDA

G-50A

M-NET

M-NET

PAC-SC50KUAPower supply unit

WHMWHM

TM

TMBACnet

��

LON, LON WORKS and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other countries.

CITY MULTI can easily combine into a Building Management System (BMS) via the LonWorksTM and M-NET adapter LMAP02. LonWorksTM is an opened transmission protocol widely used at BMS, and related equipment control.CITY MULTI is therefore compatible with large-scaled BMS management via LonWorksTM.

One LM ADAPTER unit can connect up to 50 Groups/50 indoor units.

Using a single LONWORKS adapter (LM ADAPTER), you can connect up to a maximum of 50 indoor units.

MITSUBISHI ELECTRIC's CITYMULTI can be easily connect to the building management system through BACnetTM. BACnetTM is the appropriate transmission method and used in many of the backbone networks and also it is easy to combine with other equipment corresponding to BACnetTM.

One BACnetTM

interface software manages up to 500 Groups/500 Indoor units. (10 G-50A/GB-50A units).

Remote ControllerRemote Controller

FUNCTION NETWORK VARIABLE NETWORK VARIABLE

Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30˚C,Heating 17-28˚C,Auto 19-28˚CLo-Mi1-Mi2-HiOn/Off,Mode,SetpointNormal/Reset

Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30˚C,Heating 17-28˚C,Auto 19-28˚CLo-Mi1-Mi2-HiOn/Off,Mode,Setpoint4 Character code - Indicates all unit alarms---

ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITFILTER DIRTY RESET

ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITFAULT CODEFILTER SIGNROOM TEMPERATURETHERMO

LONWORKS INTERFACE®

Control

Monitoring

FUNCTION NETWORK VARIABLE NETWORK VARIABLE

Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30˚C,Heating 17-28˚C,Auto 19-28˚CLo-Mi1-Mi2-HiOn/Off,Mode,SetpointNormal/Reset

Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30˚C,Heating 17-28˚C,Auto 19-28˚CLo-Mi1-Mi2-HiOn/Off,Mode,SetpointHorizontal - 60˚-80˚-100˚ swing4 Character code - Indicates all unit alarms--

ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITFILTER DIRTY RESET

ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITAIRFLOW DIRECTIONFAULT CODEFILTER SIGNROOM TEMPERATURE

BACnet INTERFACE®

Control

Monitoring

Page 20: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 37 Page 38

Indoor unit

I ndoor unit

Ceiling cassette type 4-way airflow

Ceiling cassette type 2-way airflow

Ceiling cassette type 1-way airflow

Ceiling concealed type

Ceiling suspended type

Wall mounted type

Floor standing type

Ceiling cassette (4way air flow)

Ceiling concealed

Ceiling cassette (2way air flow)

Ceiling cassette (1way air flow)

Ceiling suspended

Wall mounted

Floor standing

PKFY-P VAM-EPKFY-P VGM-EPKFY-P VFM-E

PFFY-P VLEM-E

PDFY-P VM-E

PEFY-P VMR-E-L/R

���� ������� � ��� ���

PLFY-P VAM-E

PFFY-P VLRM-E

Model

Capacity

P20 P25 P32 P40 P50

2.2kW 2.8kW 3.6kW 4.5kW 5.6kW

Model

Capacity

P63 P80 P100 P125

7.1kW 9.0kW 11.2kW 14.0kW

Model

Capacity

P20 P25 P32 P40 P50

2.2kW 2.8kW 3.6kW 4.5kW 5.6kW

Model

Capacity

P63 P71 P80 P100 P125

7.1kW 8.0kW 9.0kW 11.2kW 14.0kW

Model

Capacity

P20 P25 P32 P40 P50 P63 P71

2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW

Model

Capacity

P80 P100 P125 P140 P200 P250

9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW

Model

Capacity

P20 P25 P32 P40 P50 P63 P100

2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 11.2kW

Model

Capacity

P20 P25 P32 P40 P50 P63

2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW

Model

Capacity

P20 P25 P32 P40

2.2kW 2.8kW 3.6kW 4.5kW

Model

Capacity

P80 P140 P200 P250

9.0kW 16.0kW 22.4kW 28.0kW

Model

Capacity

P40 P63 P100 P125

4.5kW 7.1kW 11.2kW 14.0kW

OA Processing Units

PEFY-P VML-E

PEFY-P VMH-EPEFY-P VMS-E

PEFY-P VMH-E-F

PLFY-P VLMD-E

PMFY-P VBM-E

PCFY-P VGM-E

Fresh Air Intake���

���

Page39 - Page40 Page55 - Page56

Page41 - Page42 Page57 - Page58

Page43 - Page44 Page59 - Page60

Page45 - Page54 Page61 - Page62

Page 21: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 39 Page 40

SpecificationsIndoor unit

4-, 3-, or 2-way outlet selection

Fixed airflow direction per vane

Motorfor the vane

*Optional air outlet shutter plate is necessary for two-or three-way airflow settings. The noise level may increase during two- or three-way airflow setup.

72 airflow patterns

850mm(33-1/2in.)

������ ����

INDOOR UNITCeiling cassette type4-way airflow

The new power cassette VAM offers 72 different airflow patterns, making it ideal for applications with ceilings up to 4.2 m(13-13/16ft) in height.

Drain water pipe lifted to 850mm(33-1/2in.)

The 72 different airflow patterns provide the best solution for varying room layouts and air-conditioning requirements. For ex-tra versatility, you can also select from two-, three- or four-way outlets. What's more, the addition of separate motors to the in-dividual vanes enables manual control that-together with re-mote control vane settings-make possible highly customized and flexible airflow patterns.

First in the industry to offer 72 airflow patterns

Easy Installation

Superb Features

Specifications according to ceiling height and number of vents

4-way

3-way

2-way

Power Cassette VAM

Standard High ceiling 1 High ceiling 2

3.2

3.6

4.0

3.6

4.0

4.2

4.2

4.2

---

4.2(13-13/16)

4-way high ceiling 2

3.6(11-13/16)

m (ft)

3-way standard

3.2(10-1/2)

4-way standard

The airflow of the VAM power cassette is powerful enough to warm atrium-type ceilings up to 4.2 m(13-13/16ft) in height.

Wide-flow air outlet delivers a comforting breeze

Outstanding Specifications

Specifications

Note:

PLFY-P32VAM-E PLFY-P40VAM-E PLFY-P50VAM-E PLFY-P63VAM-E

3.612,300

3.73,1504.0

3,40013,6000.120.120.590.59

4.515,400

4.74,0005.0

4,30017,100

5.619,100

5.85,0006.3

5,40021,500

7.124,200

7.36,3008.0

6,90027,3000.160.160.780.78

Power source

Cooling capacity

Heating capacity

Powerconsumption

Current

External finish(Munsel No.)

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4

Type

Airflow rate(Low-Mid2-Mid1-High)

External static pressureTypeOutput

Gas(Flare)

Liquid(Flare)

0.140.140.68

0.68

22<5> (49<12>)

Turbo fan11-12-13-14 12-13-14-16

ø12.7 (1/2)

14-15-16-18

Single phase induction motor

ø6.35 (1/4) ø9.52 (3/8)

O.D. 32 (1-1/4) <VP-25>

27-28-29-31 27-28-30-32 28-29-31-33

ø12.7 (1/2) / ø15.88 (5/8)(Compatible)

ø6.35 (1/4) / ø9.52 (3/8)(Compatible)

258<30> ✕ 840<950> ✕ 840<950>10-3/16<1-3/16> ✕ 33-1/8<37-7/16> ✕ 33-1/8<37-7/16> 11-3/4<1-3/16> ✕ 33-1/8<37-7/16> ✕ 33-1/8<37-7/16>

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

❇3

❇3

PLFY-P80VAM-E PLFY-P100VAM-E PLFY-P125VAM-E

9.030,700

9.38,00010.0

8,60034,1000.180.180.860.86

11.238,20011.6

10,00012.5

10,80042,7000.300.301.431.43

14.047,800

14.512,500

16.013,80054,600

0.340.341.641.64

Panel : 0.70Y 8.59/0.97

24<5> (53<12>)Cross fin (Aluminum plate fin and copper tube)

16-18-20-22

ø15.88(5/8)

0

0.070 0.120

PP Honeycomb

30-32-35-37

32<5> (71<12>)

19-22-25-27 21-24-27-29

183-200-217-233388-424-459-494

200-217-233-267424-459-494-565

233-250-267-300494-530-565-636

267-300-333-367565-636-706-777

317-367-417-450671-777-883-953

350-400-450-483742-848-953-1024

33-36-39-41 35-38-41-43

ø15.88 (5/8) / ø19.05 (3/4) (Compatible)

298 (30) ✕ 840 (950) ✕ 840 (950)

~ 220-240V 50Hz / ~ 220-230V 60Hz

CoolingHeatingCoolingHeating

❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DBHeating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling capacity indicates the maximum value at operation under the following conditionCooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB.Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 External dimension/ net weight are shown in <unit/panel> , and airflow rate/noise level are in (low-middle2-middle1-high).

❇4 It is measured in anechoic room.

Page 22: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 41 Page 42

Specifications

Specifications

Note:

INDOOR UNITCeiling cassette type2-way airflow ������ �����

Fresh air can be taken in to the main unit directly (optional ac-cessories needed.

The drain can be positioned anywhere up to 600mm(23-5/8in.) from the ceiling's surface, providing greater freedom with long cross-piping and allowing more versatility with piping layouts.

Equipped with drain water lift-up mechanism as standard

Terminal block on outside of main unit makes wiring easier

Newly designed decorative panel with air flow switching and swing functions as a standard feature

Compact unit and low noise level attained! Fresh air directly taken in

The slimline body is highly suitable for installation in narrow ceiling spaces and for replacing obsolete air-conditioning equipment in older buildings. The main unit is only 290mm(11-7/16in.) height.

Slim body - only 290mm(11-7/16in.) height

Ceiling surface

Drain heightmax. 593(23-3/8)

Main unit height - 290(11-7/16)

593

��

(11-7/16in.)

Slim body of 290mm(11-7/16in.) height.

❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DBHeating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(97.1˚F)WB,Outdoor 35˚C(95˚F)DB Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 The figure in < > indicates panel's

❇4 It is measured in anechoic room.

mm (in.)

Indoor unit

PLFY-P20VLMD-E PLFY-P25VLMD-E PLFY-P32VLMD-E PLFY-P40VLMD-E~ 220-240V 50Hz / ~ 220-230V 60Hz

Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59/0.97) Service Panel: Galvanizing (0.7Y 8.59/0.97)290<20> ✕ 776<1,080> ✕ 634<710>

11-7/16<13/16> ✕ 30-9/16<42-9/16> ✕ 25<28>23 <6.5> (51<15>)

Cross finTurbo fan ✕ 1

0Single phase induction motor

0.015PP honeycomb fabric (long life filter)

ø12.7 (1/2)ø6.35 (1/4)

O.D.32 (1-1/4)

6.5-8.0-9.5108-133-158230-283-335

7.0-8.5-10.5117-142-175247-300-371

24 <6.5> (53<15>)

2.27,5002.3

2,0002.5

2,2008,500

0.072 / 0.0750.065 / 0.0690.36 / 0.370.30 / 0.32

2.89,6002.9

2,5003.2

2,80010,900

0.072 / 0.0750.065 / 0.0690.36 / 0.370.30 / 0.32

3.612,300

3.73,1504.0

3,40013,600

0.072 / 0.0750.065 / 0.0690.36 / 0.370.30 / 0.32

4.515,400

4.74,000

5.04,30017,100

0.081 / 0.0850.074 / 0.079

0.40 / 0.420.34 / 0.37

27-30-3328-31-34

29-33-3630-34-37

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)mm(in.)mm(in.)dB(A)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

❇3

CoolingHeatingCoolingHeating

Type

Airflow rate (Lo-Mid-Hi)

External static pressureTypeOutput

Gas(Flare)Liquid(Flare)

❇4220V,240V230V

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

❇3

CoolingHeatingCoolingHeating

TypeAirflow rate(P50~P100:Lo-Mid-Hi)(P125:Lo-Mid2-Mid1-Hi)External static pressureTypeOutput

Gas(Flare)

Liquid(Flare)

❇4220V,240V230V

PLFY-P63VLMD-E PLFY-P80VLMD-E PLFY-P100VLMD-E PLFY-P125VLMD-E

~ 220-240V 50Hz / ~ 220-230V 60Hz

Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59 / 0.97) Service Panel: Galvanizing (0.7Y 8.59 / 0.97)

Turbo fan ✕ 1 Turbo fan ✕ 2

ø15.88 (5/8)

ø9.52 (3/8)

10.0-13.0-15.5167-217-258353-459-547

17.5-21.0-25.0292-350-417618-742-883

0.030 (at 240V)

15.5-18.5-22.0258-308-367547-653-777

0Single phase induction motor

0.020 (at 240V)0.020

7.124,200

7.36,3008.0

6,90027,300

0.101 / 0.1050.094 / 0.0990.49 / 0.510.43 / 0.46

28 <7.5> (62<17>)

9.030,700

9.38,00010.0

8,60034,100

0.147 / 0.1560.140 / 0.1500.72 / 0.740.66 / 0.69

44 <12.5> (98<28>)Cross fin

11.238,20011.6

10,00012.5

10,80042,700

0.157 / 0.1860.150 / 0.1800.75 / 0.880.69 / 0.83

47 <12.5> (104<28>)

14.047,800

14.512,500

16.013,80054,600

0.28 / 0.280.27 / 0.271.35 / 1.351.33 / 1.33

290<20> ✕ 1,708<2,010> ✕ 606<710>11-7/16<13/16> ✕ 67-1/4<79-3/16> ✕ 23-7/8< 28>

56 <13.0> (124<29>)

Sirocco fan ✕ 424.0-27.0-30.0-33.0

400-450-500-550848-953-1,059-1,165

0.078 ✕ 2 (at 240V)Synthetic fiber unwoven

cloth filter (long life)

O.D.32 (1-1/4)33-36-3934-37-40

PLFY-P50VLMD-E

PP honeycomb fabric (long life filter)

5.619,100

5.85,0006.3

5,40021,500

0.082 / 0.0860.075 / 0.0800.41 / 0.430.35 / 0.38

27 <7.5> (60<17>)

31-34-3732-35-38

32-37-3933-38-40

40-42-44-46(Lo-Mid2-Mid1-Hi)

ø15.88 (5/8)ø12.7 (1/2)

ø 6.35 (1/4)

36-39-4237-41-43

290<20> ✕ 946<1,250> ✕ 634<710>11-7/16<13/16> ✕ 37-1/4<49-1/4> ✕ 25< 28>

290<20> ✕ 1,446<1,750> ✕ 634<710>11-7/16<13/16> ✕ 56-15/16<68-15/16> ✕ 25< 28>

9.0-11.0-12.5150-183-208318-388-441

Power source

Cooling capacity

Heating capacity

Powerconsumption

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filterRefrigerantpipe diameterDrain pipe diameterNoise level(Lo-Mid-Hi)

Power source

Cooling capacity

Heating capacity

Powerconsumption

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level(Lo-Mid-Hi)

Page 23: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 43 Page 44

Specifications

Specifications

Note:

❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DBHeating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DBHeating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 External dimension / net weight are shown in <panel>, and airflow rate/noise level are in (low-middle2-middle1-high).

❇4 It is measured in anechoic room.

mm (in.)

198(7-13/16)

PMFY-VBM230

(9-11/16)

max.402

(15-7/8)max.600

(23-5/8)

Compact and lightweight body perfect for limited ceiling space applications.

Unit body size has been standardized for all models at 854mm for easier installa-tion. Body weight is only 14kg for the main unit and 3kg for the panel, making this unit one of the lightest in the industry.

Compact size for smooth installation and maintenance

Newly developed airflow control technolo-gy reduces noise level to only 27dB (P20VBM) for industry-leading quiet oper-ation.

Quiet operation

The drain can be positioned anywhere up to 600mm(23-5/8in.) from the ceiling's surface.

Drain lift-up mechanism

������ �����

INDOOR UNITCeiling cassette type1-way airflow

Indoor unit

Power source

Cooling capacity

Heating capacity

Powerconsumption

Current

External finishDimension H ✕ W ✕ DNet weightHeat exchanger

Fan

Motor

Air filterRefrigerantpipe diameterDrain pipe diameterNoise level (Lo-Mid2-Mid1-Hi)

0.0440.0440.210.21

Panel : 0.98Y8.99/0.63230<30> ✕ 812<1,000> ✕ 395<470> (9-1/16<1-3/16> ✕ 32<39-3/8> ✕ 15-9/16<18-9/16>)

14 <3.0> (31<7>)Cross fin (Aluminum plate fin and copper tube)

Line flow fan ✕ 17.3-8.0-8.6-9.3

122-133-143-155258-283-304-328

0Single phase induction motor

0.028PP Honeycomb fabric

ø12.7 (1/2)ø6.35 (1/4)

O.D. 25 (1) <VP-20>32-34-36-37

4.515,400

4.74,000

5.04,30017,1000.0540.0540.260.26

7.7-8.7-9.7-10.7128-145-162-178272-307-343-378

33-35-37-39

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mm(in.)kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)mm(in.)mm(in.)dB(A)

Type

Airflow rate(Low-Mid2-Mid1-High)

External staticpressureTypeOutput

CoolingHeatingCoolingHeating

❇1❇1❇2❇2❇1❇1❇1

❇3

❇3

❇3

❇4

Gas(Flare)Liquid(Flare)

2.89,6002.9

2,5003.2

2,80010,900

2.27,5002.3

2,0002.5

2,2008,5000.0420.0420.200.20

3.612,300

3.73,1504.0

3,40013,600

~ 220-240V 50Hz / ~ 220V 60Hz

6.5-7.2-8.0-8.7108-120-133-145230-254-283-307

27-30-33-35

PMFY-P25VBM-E PMFY-P32VBM-E PMFY-P40VBM-EPMFY-P20VBM-E

Page 24: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 45 Page 46

Specifications

INDOOR UNITCeiling concealedtype������ �������

Prepared a contact for a card key. It’s possible to operate / stop by taking a card key in and out.

Realizing the low level noise that is NC21 around a bed and N22 around a desk when the high notch.It contributes to create a quiet indoor environment.*Outlet is elbow-constructed using a glass wool duct.The noise level is changed by the room size or the setting con-dition of the unit.

Operable by card key switch Ultra low noise

Energy-saving by prevention of forgetting the switch off

Enables to install for symmetric design room

Both of Left piping / Right piping, control box, are available.It's selectable for layout of each room.Plus easy maintenance from the access door in the prefabrica-ted bath.*Seen from an anterior view, the pipe and control box are on the right side of –R type.

Compact & Simple operation remote controller is available.*This remote controller can operate only start / stop, indoor tem-perature control and wind speed control. Centralized remote controller must be used together.Enables a prevention to forget the switch in a vacant room off by the centralized remote controller like G-50.

Problem solver for residential hotels, museums, libraries, or hospitals where low noise is especially a must!

Noise measurement pointNoise measurement pointNoise measurement pointCard KeySwitchCard KeySwitch

InletInlet

Noise measurement pointNoise measurement pointNoise measurement point

*According to the data measured in Mitsubishi Electric laboratory

��

Indoor unit

Specifications

Note:

❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBHeating : Indoor 20˚C (68˚F) DB, Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WB

❇2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27˚C (80.6˚F) DB/19.5˚C (67.1˚F) WB,Outdoor 35˚C (95˚F) DB Heating : Indoor 21˚C (69.8˚F) DB,Outdoor 7˚C (44.6˚F) DB/6˚C (42.8˚F) WB

❇3 The external static pressure is set to 100Pa (at 220V) / 150Pa (at 230, 240V) at factory shipment.

❇4 Measured in anechoic room. Noise levels of the unit with a rear air inlet. (Noise levels are higher than the unit with a bottom air inlet.)

Static Presure

5Pa

Width

640mm25-6/32in.

Ultra Low Noise

Piping connectionL modelR model

0.018 0.023

Power source

Cooling capacity

Heating capacity

Powerconsumption

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameter

Noise level (Lo-Mid-Hi) ❇4

Gas(Flare)Liquid(Flare)

220V230V240V

TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/min

Pa

kW

mm(in.)

mm(in.)

mm(in.)

dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

❇3

1-phase 220/230/240V 50Hz 220/230V 60Hz2.8

9,6002.9

2,5003.2

2,80010,900

0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29Galvanized

292 ✕ 640 ✕ 580-

18 (40)Cross fin (Aluminum fin and copper tube)

Sirocco fan ✕ 1

PEFY-P20VMR-E-L PEFY-P25VMR-E-L PEFY-P32VMR-E-L

2.27,5002.3

2,0002.5

2,2008,500

0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29

3.612,300

3.73,150

4.03,40013,600

0.07 / 0.080.07 / 0.080.34 / 0.380.34 / 0.38

5

1-phase induction motor

PP Honeycomb fabric (washable)

ø6.35 (1/4)

ø12.7(1/2)

O.D. 26 (1)

4.8-5.8-7.9 4.8-5.8-9.3

20-25-3021-26-3222-27-30

20-25-3321-26-3522-27-33

0.018 0.023

Power source

Cooling capacity

Heating capacity

Powerconsumption

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameter

Noise level (Lo-Mid-Hi) ❇4

Gas(Flare)Liquid(Flare)

220V230V240V

TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/min

Pa

kW

mm(in.)

mm(in.)

mm(in.)

dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

❇3

1-phase 220/230/240 V 50Hz 220/230V 60Hz2.8

9,6002.9

2,5003.2

2,80010,900

0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29Galvanized

292 ✕ 640 ✕ 580-

18 (40)Cross fin (Aluminum fin and copper tube)

Sirocco fan ✕ 1

PEFY-P20VMR-E-R PEFY-P25VMR-E-R PEFY-P32VMR-E-R

2.27,5002.3

2,0002.5

2,2008,500

0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29

3.612,300

3.73,150

4.03,40013,600

0.07 / 0.080.07 / 0.080.34 / 0.380.34 / 0.38

5

1-phase induction motor

PP Honeycomb fabric (washable)

ø6.35 (1/4)

ø12.7 (1/2)

O.D. 26(1)

4.8-5.8-7.9 4.8-5.8-9.3

20-25-3021-26-3222-27-30

20-25-3321-26-3522-27-33

Page 25: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 47 Page 48

Specifications

Specifications���

Note:

❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor : 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B.) Outdoor : 35˚CD.B. (95˚FD.B. )Heating : Indoor : 20˚CD.B. (68˚FD.B.) Outdoor : 7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)

Pipe length : 7.5m (24-9/16ft) Height difference : 0m (0ft)

❇2 Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB, Outdoor: 35˚C(95˚F)DBHeating Indoor: 21˚C(69.8˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 The external static pressure is set to 15 Pa at factory shipment.

Increased design flexibility for the places where low noise operation is especially needed from an ultra thin body.

Changeable static pressure(4 stage 5-15-35-50Pa)

Can be installed easily in tight spaces, such as ceiling cavities or drop-ceilings.

Ultra low height unit with 200mm (7-28/32in.) high

������ ���

INDOOR UNITCeiling concealedtype

Changeable air flow rate (3 stage low-middle-high)

Drain lift-up pump is attached as standard.

Filter is attached as standard.

Reduced noise thanks to the use of newly designed centrifugal fan and coil

dB(A)Noise level table (Standard static pressure)

Mor

e th

an 2

0mm

Mor

e th

an 2

0mm

Make the access door at the appointed position properlyfor service maintenance.

Ceiling surface Access door

P20272522

Capacity P25272522

P32302825

Noise LevelHighMidLow

Fan Speed

Indoor unit

Static Presure

5~50Pa

Height

200mm7-28/32in.

Width

900mm35-14/32in.

Low Noise

0.080.39

2.27,5002.3

2,0002.5

2,2008,500

0.060.28

0.080.39

0.060.28

0.090.44

0.070.33

0.110.53

0.090.42

0.130.63

0.110.52

0.140.68

0.120.57

kW

BTU/hkW

kcal/hkW

kcal/hBTU/h

kWA

Pa

kWm3/min

mmIn. kg

mm(in.)mm(in.)mm(in.)

dB<A>

Power source

Cooling capacity

Heating capacity

Power input Current

Fan ❇3

External finish External dimension H ✕ W ✕ D Net weight

Drain piping diameter Noise level (Lo-Mid-Hi) (mesured in anechoic room) Air filter Heat exchanger

Type ✕ Quantity External static press Motor type Motor output Airflow rate(Lo-Mid-Hi)

Liquid Gas

1-phase 220-240V 50Hz 1-phase 220-230V 60Hz

5-15-35-50DC brushless motor

0.096

Galvanized200 ✕ 900 ✕ 700

7-7/8 ✕ 35-7/16 ✕ 27-9/16

O.D. 32 (1-1/4)

PP Honeycomb fabric (washable)Cross fin (Aluminium fin and copper tube)

3.612,300

3.73,1504.0

3,40013,600

Sirocco fan ✕ 3

7.5-8.5-10

25-28-30

ø6.35 (ø1/4) Brazedø12.7 (ø1/2) Brazed

2.89,6002.9

2,5003.2

2,80010,900

23 24

4.55.04.7

4,0005.0

4,30017,100

8-9.5-11

28-30-33

5.66.35.8

5,0006.3

5,40021,500

9.5-11-13

ø6.35 (ø1/4) Brazedø12.7 (ø1/2) Brazed

30-32-35

6-7-8

22-25-27

7.18.07.3

6,3008.0

6,90027,300

Sirocco fan ✕ 4

12-14-16.5

200 ✕ 1100 ✕ 7007-7/8 ✕ 43-5/16 ✕ 27-9/16

28ø9.52 (ø3/8) Brazedø15.88 (ø5/8) Brazed

30-33-36

PEFY-P20VMS-E PEFY-P25VMS-E PEFY-P32VMS-E PEFY-P50VMS-EPEFY-P40VMS-E PEFY-P63VMS-E

❇1❇1❇2❇2❇1❇1❇1

Refrigerant piping diameter

Page 26: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 49 Page 50

Specifications

Specifications

Note:

Cooling/heating capacity indicates the maximum value at operation under the following condition.

❇1 Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB, Outdoor: 35˚C(95˚F)DBHeating Indoor: 20˚C(68˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB, Outdoor: 35˚C(95˚F)DBHeating Indoor: 21˚C(69.8˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 The external static pressure is set to 50Pa at factory shipment.

❇4 The value for Models 20-80 are that at the external static pressure of 100Pa, while the value for Models 100-125 are that at the external static pressure of 130Pa.

❇5 The figure in ( ) indicates noise level at 240V/50Hz.

❇6 It is measured in anechoic room.

Long room

L-shaped roomsRoom with fixed ceiling fixtures

Max.600

(23-5/8)

110-300

(4-3/8~11-13/16)

mm (in.)

Maintenance panelwith air intake Maintenance panel

with air intake

Canvas duct forbottom section

A rear intake canalso be used

Maintenance panelMaintenance panel

Square duct flange Rear intake filter box

A bottom intake canalso be used

Rear intake filter box

System ceiling

Square duct flange

Blower unit(With auto-vanes)

Maintenancepanel withair intake

������ ����

INDOOR UNITCeiling Concealed Type

Achieving creative air conditioning design through a rich array of system materials.

Multiple installation patterns for assorted applications and locationsAir outlet side compatible

with a variety of ducts (optional)

Slim 295mm main unit with optional drain up mechanism ensures

up to 600 mm(23-5/8in.) of lift

Adjustable setting of external static pressure to meet system configuration

and installation conditions

Static pressure settings can be increased to adjust to all kinds of ducts as well as functional upgrade option (high perfor-mance filter etc). An increase from the standard 50Pa to 130 Pa is possible to cope with various layout configurations.*For P100~P125

Flexible installation for a variety of layouts

Indoor unit

Max.416(16-7/16)

184(16-7/16)

Bottom intake (using canvas duct)

Ceiling chamber system (1)

Hanging ceiling installation

Bottom intake (directly attached to panel)

All-duct system

Ceiling chamber system (2)

Static Presure

30~100(130)Pa

Gas(Flare)Liquid(Flare)

TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWBTU/h

kWkcal/h

kWkWAA

mmin.

kg(lbs)

m3/min

Pa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

Power source

Cooling capacity

Heating capacity

Power consumption(50/60Hz)

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) ❇6

0.13 / 0.150.13 / 0.150.60 / 0.710.60 / 0.71

295 ✕ 960 ✕ 73511-5/8 ✕ 37-13/16 ✕ 28-15/16

Sirocco fan ✕ 2

10.0-11.0-12.5-14.0

34-36-37-39

2.27,5002.3

2,0002.5

8,5002.6

2,250

2.89,6002.9

2,5003.2

10,9003.3

2,8000.11 / 0.120.11 / 0.120.53 / 0.580.53 / 0.58

295 ✕ 710 ✕ 73511-5/8 ✕ 28 ✕ 28-15/16

Sirocco fan ✕ 1

6.0-6.5-7.5-8.5

28-30-33-36

25.5 (57)

ø12.7 (1/2)

ø6.35 (1/4)

ø12.7 (1/2)

ø6.35 (1/4)

~ 220-240V 50Hz / ~ 220V 60Hz3.6

12,3003.7

3,1504.0

13,6004.1

3,550

Galvanizing

27 (60)Cross fin (Aluminum plate fin and copper tube)

30 / 50 / 100

Single phase induction motor0.075 (at 240V)

Synthethic fiber unwoven cloth filter (long life)

O.D. 32 (1-1/4) <VP-25>

5.619,100

5.85,000

6.321,500

6.55,600

34 (75)

4.515,400

4.74,0005.0

17,1005.2

4,500

32 (71)

❇1❇1❇2❇2❇1❇1❇2❇2

❇3

❇4❇5

Gas(Flare)Liquid(Flare)

TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWBTU/h

kWkcal/h

kWkWAA

mmin.

kg(lbs)

m3/min

Pa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

Power source

Cooling capacity

Heating capacity

Powerconsumption

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) ❇6

7.124,200

7.36,3008.0

27,3008.3

7,1000.14 / 0.170.14 / 0.170.68 / 0.820.68 / 0.82

12.5-14.0-16.0-18.0

30-34-36-39

8.027,300

8.37,1009.0

30,7009.3

8,0000.15 / 0.180.15 / 0.180.72 / 0.880.72 / 0.88

295 ✕ 1,160 ✕ 73511-5/8 ✕ 45-11/16 ✕ 28-15/16

39 (86)

13.5-15.5-17.5-19.5

30 / 50 / 100

0.078 (at 240V)

ø15.88 (5/8)

32-35-37-40

~ 220-240V 50Hz / ~ 220V 60Hz9.0

30,7009.3

8,00010.0

34,10010.5

9,0000.17 / 0.210.17 / 0.210.82 / 1.010.82 / 1.01Galvanizing

Cross fin (Aluminum plate fin and copper tube)Sirocco fan ✕ 2

14.5-16.5-18.5-21.0

Single phase induction motor

Synthethic fiber unwoven cloth filter (long life)

ø9.52 (3/8)

O.D. 32 (1-1/4) <VP-25>34-37-40-42

14.047,800

14.512,500

16.054,600

16.314,000

0.33-0.38 / 0.390.33-0.38 / 0.391.55-1.63 / 1.841.55-1.63 / 1.84

24.0-34.0(Lo-Hi)

0.190 (at 240V)

40-45 (42-46) ❇5

11.238,20011.6

10,00012.5

42,70013.0

11,2000.27-0.31 / 0.290.27-0.31 / 0.291.28-1.34 / 1.361.28-1.34 / 1.36

19.5-28.0(Lo-Hi)

0.140 (at 240V)

34-42 (37-44) ❇5

335 ✕ 1,510 ✕ 77513-1/4 ✕ 59-1/2 ✕ 30-9/16

52 (115)

50 / 100 / 130

ø 15.88 (5/8)

❇1❇1❇2❇2❇1❇1❇2❇2

❇3

❇4

PDFY-P20VM-E PDFY-P25VM-E PDFY-P32VM-E PDFY-P40VM-E PDFY-P50VM-E

PDFY-P63VM-E PDFY-P71VM-E PDFY-P80VM-E PDFY-P100VM-E PDFY-P125VM-E

Page 27: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 51 Page 52

Specifications

Specifications

Note: In the case of bottom inlet, the operating noise is louder than in the case of rear inlet.

Hole pitch

Access door

20/25/32 Model

100(3-15/16) or more

225(8-7/8)

30(1-3/16)

mm (in.)

20(13/16) or more

Service space:500(19-11/16) or more

245(9-11/16)+Drain covering configurationheight

P20

36

29

25

Capacity P25

36

29

25

P32

40

29

25

NoiseLevel

dB(A)Noise level table

High

Mid

Low

FanSpeed

������ �����

Increased design flexibility for hotel and residential use from an thin body.

Reduced noise thanks to the use of newly designed centrifugal fan

Drainage lines may be connected on either the right or left side.

Low static pressure (5Pa) meets an application requiring direct air flow

Changeable air flow rate (3 stage low-middle-high)

Flexible installation by rear or bottom return air inlet.

Perfect for use in hotels and other places where line placement is a problem.

Filter is attached as standard.

Can be installed easily in tight spaces, such as ceiling cavities or drop-ceilings.Notes: Drain lift-up pump not applicable.

Low height unit with 225mm(8-7/8in.) high

Indoor unit

Note:

Cooling/heating capacity indicates the maximum value at operation under the following condition.

❇1 Cooling/heating capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB, Outdoor: 35˚C(95˚F)DBHeating Indoor: 20˚C(68˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB, Outdoor: 35˚C(95˚F)DBHeating Indoor: 21˚C(69.8˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.

❇4 The value are that at 240V.

❇5 It is measured in anechoic room.

Static Presure

5Pa

Width

720mm28-11/32in.

Power source

Cooling capacity

Heating capacity

Power consumption(50/60Hz)

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Mid-Hi) ❇5

Gas(Brazing)Liquid(Brazing)

Type

Airflow rate(Lo-Mid-Hi)

External static pressureTypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)

mm(in.)

dB(A)

❇1❇1❇2❇2❇1❇1❇1

PEFY-P20VML-E PEFY-P25VML-E PEFY-P32VML-E

2.27,5002.3

2,0002.5

2,2008,500

~ 220-240V 50Hz / 60Hz2.8

9,6002.9

2,5003.2

2,80010,900

Galvanizing225 ✕ 720 ✕ 550

8-7/8 ✕ 28-3/8 ✕ 21-11/1618 (40)

Cross fin (Aluminum plate fin and copper tube)Sirocco fan ✕ 1

5Single phase induction motor

PP Honeycomb fabric (washable)

ø12.7 (1/2)

ø6.35 (1/4)

R1 (External thread)

0.05 / 0.060.05 / 0.060.24 / 0.280.24 / 0.28

3.612,300

3.73,150

4.03,40013,600

0.07 / 0.090.07 / 0.090.32 / 0.420.32 / 0.42

4.8-5.8-9.580-97-158

170-205-335

0.032

25-29-40

0.023

25-29-36

4.8-5.8-7.980-97-132

170-205-279

Page 28: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 53 Page 54

Specifications

Specifications

Note:

Capacity P50

34

27

P63

38

32

P71

39

32

P80

41

35

P100

42

34

P125

42

34

P140

42

34

NoiseLevel

dB(A)Noise level table (Standard static pressure 220V)

High

Low

P40

34

27

Externalstatic

pressure(Pa)

220V

230/240V

380V

400/415V

P40 P50 P63 P71

50/100/200

100/150/200

110/220

130/260

P80 P100 P125 P140 P200 P250

MAX.550

(21-11/16)

222(8-3/4)

328(12-15/16)

Increased design flexibility from sufficient external static pressure allow authentic duct air- conditioning with an elegant interior layout.

Maximum external static pressure 200Pa

Reduced noise thanks to the use ofnewly designed centrifugal fan

The additional external static pressure capacity provides flexibility for duct extension, branching and air outlet configuration.

Drain up mechanism (option) ensures up to 550mm (21-11/16in.) of lift

The introduction of an upper drain mechanism allows the drain con-nection to be raised as high as 550mm(21-11/16in.), allowing more freedom in piping layout design and reducing horizontal piping re-quirements.

������ �����

All maintenance to the unit, includ-ing fan inspection and fan motor removal, can be conducted from the inspection opening on one side.

One-side maintenance

FanSpeed

Indoor unit

Cooling/heating capacity indicates the maximum value at operation under the following condition.❇1 Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB, Outdoor: 35˚C(95˚F)DB

Heating Indoor: 20˚C(68˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB❇2 Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB, Outdoor: 35˚C(95˚F)DB

Heating Indoor: 21˚C(69.8˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB❇3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment. ❇4 The value are that at 240V.❇5 The external static pressure is set to 220Pa (at 380V) /260Pa (at 400, 415V) at factory shipment.❇6 The value are that at 415V.❇7 It is measured in anechoic room.❇4 The value are that at 240V.❇5 The external static pressure is set to 220Pa (at 380V) /260Pa (at 400, 415V) at factory shipment.❇6 The value are that at 415V.❇7 It is measured in anechoic room.

mm (in.)

Static Presure

100~200(260)Pa

Power source

Cooling capacity

Heating capacity

Power consumption(50/60Hz)

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter (option)

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Hi) ❇5

Gas(Brazing)Liquid(Brazing)

220V230,240V

220V230,240V

Type

Airflow rate(Lo-Hi)

External staticpressure ❇3TypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPaPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇4

PEFY-P40VMH-E PEFY-P50VMH-E PEFY-P63VMH-E PEFY-P71VMH-E PEFY-P80VMH-E PEFY-P100VMH-E PEFY-P125VMH-E PEFY-P140VMH-E

4.515,400

4.74,0005.0

4,30017,100

44 (98)

ø 12.7 (1/2)

ø 6.35 (1/4)

5.619,100

5.85,0006.3

5,40021,500

380 ✕ 750 ✕ 90015 ✕ 29-9/16 ✕ 35-7/16

ø 12.7 (1/2)

ø 6.35(1/4)

7.124,200

7.36,3008.0

6,90027,300

0.24 / 0.300.24 / 0.301.12 / 1.381.12 / 1.38

Sirocco fan ✕ 113.5-19.0225-317477-671

0.12

32-3836-41

8.027,300

8.37,1009.0

7,70030,700

0.26 / 0.330.26 / 0.331.20 / 1.511.20 / 1.51

15.5-22.0258-367547-777

0.14

ø15.88 (5/8)

32-3935-41

9.030,700

9.38,00010.0

8,60034,100

0.32 / 0.400.32 / 0.401.47 / 1.831.47 / 1.83

18.0-25.0300-417636-883

0.18

35-4138-43

11.238,20011.6

10,00012.5

10,80042,700

14.047,800

14.512,500

16.013,80054,600

380 ✕ 1,200 ✕ 90015 ✕ 47-1/4 ✕ 35-7/16

70 (155)

Sirocco fan ✕ 2

0.26

ø15.88 (5/8)

34-4238-44

16.054,600

16.314,000

18.014,00061,400

0.48 / 0.590.48 / 0.592.35 / 2.702.35 / 2.70

28.0-40.0467-667989-1413

0.48 / 0.580.48 / 0.582.34 / 2.662.34 / 2.66

26.5-38.0442-633

936-1342

O.D. 32 (1-1/4)

Galvanizing380 ✕ 1,000 ✕ 900

15 ✕ 39-3/8 ✕ 35-7/1650 (111)

Cross fin (Aluminum plate fin and copper tube)

50 / 100 /200100 / 150 / 200

Single phase induction motor

Synthethic fiber unwoven cloth filter (long life)

0.19 / 0.230.19 / 0.230.88 / 1.060.88 / 1.06

10.0-14.0167-233353-494

0.08

27-3431-37

45 (100)

O.D. 32 (1-1/4)

ø9.52 (3/8)

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPaPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)dB(A)

PEFY-P200VMH-E PEFY-P250VMH-E

~ 220-240V 50Hz / 60Hz

Power source

Cooling capacity

Heating capacity

Power consumption(50/60Hz)

Current

External finish

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter(option)

Refrigerantpipe diameter

Drain pipe diameter

Noise level ❇7

Gas(Brazing)Liquid(Brazing)

380V400,415V

380V400,415V

Type

Airflow rate

External staticpressure ❇5TypeOutput

CoolingHeatingCoolingHeating

❇1❇1❇2❇2❇1❇1❇1

❇6

22.476,40023.3

20,00025.0

21,50085,300

0.99 / 1.140.99 / 1.141.62 / 1.861.62 / 1.86

58.0967

2048

0.76

ø19.05 (3/4)

42 (110Pa) / 45 (220Pa)44 (130Pa) / 47 (260Pa)

28.095,50029.1

25,00031.5

27,100107,500

1.23 / 1.411.23 / 1.412.0 / 2.32.0 / 2.3

72.012002543

1.08

ø22.2 (7/8)

50 (110Pa) / 52 (220Pa)52 (130Pa) / 54 (260Pa)

3N ~ 380-415V 50Hz / 60Hz

Galvanizing470 ✕ 1,250 ✕ 1,120

18-9/16 ✕ 49-1/4 ✕ 44-1/8100 (221)

Cross fin (Aluminum plate fin and copper tube)Sirocco fan ✕ 2

110 / 220130 / 260

3-phase induction motor

Synthethic fiber unwoven cloth filter (long life)

ø9.52 (3/8)

O.D. 32 (1-1/4)

Page 29: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 55 Page 56

Specifications

Specifications

Swing

Auto vane

Ceiling height 2.7(8-7/8) 3.5(11-1/2)

m (ft)

Standard High ceiling

Direct suspension with attachment fixture attached

1. Leave attachment fixture attached to main unit.2. Suspend the attachment fixture from the suspension bolts.3. Simply tighten the nuts to secure the unit.

Suspension bolts

Attachment fixture

Ceiling surface

Air outlet

*A one-touch suspension is also available: simply suspend the main unit from the attachment fitting after securing the latter to the ceiling.

Designed for ultra-quiet operation and easy maintenance, provides exceptionally comfortable air-conditioning.

Keeps airflow at optimum level according to ceiling height

Drain piping can be connected in one of two directions, to the left or the right of the unit

The most suitable airflow can be selected for ceilings up to 3.5m high, enhancing air-conditioning efficiency and comfort.

������ ����

INDOOR UNITCeiling Suspended Type

Seek and slim with stylishly curved lines, the PCFY series blends right into any interior. It also features a single air outlet which allows the auto vane to act as a shutter when the unit is turned off.

Extra slim, extra stylish

The auto vane swings up and down automatically to distribute air more evenly to every corner of the room.

Auto vane distributes air evenly

The new direct suspension system eliminates the task of remov-ing the attachment fixture from the main unit, greatly shortening installation time.

Greatly simplified installation

Indoor unit

Note: ❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DBHeating Indoor: 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DBHeating Indoor: 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 airflw rate/noise level are shown in (low-middle 2-middle 1-high). ❇4 It is measured in anechoic room.

Power source

Cooling capacity

Heating capacity

Power consumption

Current

External finish(Munsel No.)

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4

Gas(Flare)Liquid(Flare)

Type

Airflow rate(Lo-Mid2-Mid1-Hi)

External staticpressure TypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

PCFY-P40VGM-E PCFY-P63VGM-E PCFY-P100VGM-E PCFY-P125VGM-E

4.515,400

4.74,0005.0

4,30017,1000.100.100.460.46

210 ✕ 1,000 ✕ 6808-5/16 ✕ 39-3/8 ✕ 26-13/16

27 (60)

Sirocco fan ✕ 28-10-11-12

133-167-183-200253-353-388-424

0.054

ø12.7 (1/2)

ø6.35 (1/4)

29-33-36-38

7.124,200

7.36,3008.0

6,90027,3000.130.130.600.60

210 ✕ 1,310 ✕ 6808-5/16 ✕ 51-5/8 ✕ 26-13/16

34 (75)

12-14-16-18200-233-267-300424-494-565-636

0.070

ø15.88 (5/8)

32-34-37-39

11.238,20011.6

10,00012.5

10,80042,7000.160.160.730.73

270 ✕ 1,310 ✕ 68010-11/16 ✕ 51-5/8 ✕ 26-13/16

37 (82)

18-20-23-25300-333-383-417636-706-812-883

0.090

ø9.52 (3/8)

36-38-41-43

14.047,800

14.512,500

16.013,80054,600

0.240.241.101.10

270 ✕ 1,620 ✕ 68010-11/16 ✕ 63-13/16 ✕ 26-13/16

43 (95)

Sirocco fan54 ✕ 426-28-32-35

433-467-533-583918-989-1130-1236

0.150

37-39-42-44

~ 220-240V 50Hz / ~ 220V 60Hz

0.70Y 8.59 / 0.97

Cross fin (Aluminum plate fin and copper tube)Sirocco fan ✕ 3

0Single phase induction motor

PP Honeycomb (long life)

I.D. 26 (1) <VP-25>

ø15.88 (5/8) / ø19.05 (3/4) (Compatible)

Page 30: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 57 Page 58

Specifications

Specifications

Front grille opens out

P20Capacity P25 P32 P40 P50

VAM

VGM

VFM

P63 P100

Capacity range

3

1

2

������ ���������� ��������� ����

INDOOR UNITWall Mounted Type

Elegant Design and Compact Dimensions Ideal for Offices, Stores and Residential Uses.

PKFY-P VFM

PKFY-P VGMPKFY-P VAM

Width reduced by 20% to a compact 990mm(39in.). Extra compactness has been achieved thanks to a 20%(260mm(10-1/4in.))reduction in which compared with previ-ous models.

Compact design with 990mm(39in.) width (PKFY-P VGM)

The front power supply box allows electri-cal wiring work to be done after the in-door unit has been installed. For easier installation, all the screws required for se-curing the indoor unit to the wall are ac-cessible from the front of the unit.

Front power supply box for easier wiring even after installation

All piping including drainage can be con-nected from the rear, right, base, and left of the unit, providing much greater flexibil-ity out piping and selecting installation site.

5-way piping provides more flexibility in selecting installation sites

Compact 295mm(11-5/8in.) high body fits snugly in even limited

spaces (PKFY-P VAM)

Lightweight 8.5kg(20lbs) unit easy to transport and install (PKFY-P VAM)

Auto-flap shutter enhances good looks

In room air conditioning style, the grille opens out allowing the filter to be re-moved. The filter and open grille can therefore be thoroughly and easily cleaned.

Among the quietest in the industryAirflow passage configuration that assures quiet operations1. The unit incorporates a random pitch cyclic fan. By chang-

ing fan intervals reduction in airflow. Optimal design of the airflow passage gives a shorted fan diameter and allows a highly compact installation.

2. Thanks to a highly practical casing configuration, airflow generated by the fan is distributed uniformly.

3. Due to careful positioning of the vertical vane axis, air is blown evenly from the fan. This prevents mixing with sec-ondary air, and also suppresses condensation.

Quiet operation (PKFY-P VGM)

Front grille opens out - easy filter cleaning (PKFY-P VGM)

Indoor unit

Note: 1. Cooling/heating capacity indicates the maximum value at operation under the following condition❇1 Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB, Outdoor: 35˚C(95˚F)DB

Heating Indoor: 20˚C(68˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB❇2 Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB, Outdoor: 35˚C(95˚F)DB ❇3 Airflow rate/noise level are in (low-high).❇4 It is measured in anechoic room.

Power source

Cooling capacity

Heating capacity

Power consumption

Current

External finish(Munsel No.)

Dimension

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Hi) ❇3 ❇4

Gas(Flare)Liquid(Flare)

TypeAirflow rate(Lo-Hi)External staticpressure TypeOutput

CoolingHeatingCoolingHeating

HeightWidthDepth

kWBTU/hkcal/h

kWBTU/h

kWkWAA

mm(in.)mm(in.)mm(in.)kg(lbs.)

m3/min

Pa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

❇1❇1❇2❇1❇1

❇3

PKFY-P63VFM-E PKFY-P100VFM-E

7.124,2006,3008.0

27,3000.120.120.550.55

340 (13-3/8)1,400 (55-1/8)

235 (9-1/4)24 (53)

15-20

0.040

ø15.88 (5/8)

39-45

11.238,20010,00012.5

42,7000.140.140.640.64

340 (13-3/8)1,680 (66-1/8)

235 (9-1/4)28 (62)

22-28

0.070

ø15.88 (5/8) / ø19.05 (3/4)

41-46

220-230-240V 50Hz / 220V 60Hz

Plastic, white : <3.4Y7.7/0.8>

Cross fin (Aluminum plate fin and copper tube)Line flow fan ✕ 2

0Single phase induction motor

PP Honeycomb (antibacterial)

ø9.52 (3/8)

I.D. 20 (3/4) <VP-20>

Note: ❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DBHeating Indoor: 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DBHeating Indoor: 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 Airflow rate/noise level are in (low-middle2-middle1-high).❇4 It is measured in anechoic room.

Power source

Cooling capacity

Heating capacity

Power consumption

Current

External finish(Munsel No.)Dimension H ✕ W ✕ DNet weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4

Gas(Flare)Liquid(Flare)

Type

Airflow rate(Lo-Hi)

External staticpressure TypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mm(in.)kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

PKFY-P20VAM-E PKFY-P25VAM-E PKFY-P32VGM-E PKFY-P40VGM-E PKFY-P50VGM-E

2.27,5002.3

2,0002.5

2,2008,500

2.89,6002.9

2,5003.2

2,80010,900

4.515,400

4.74,0005.0

4,30017,1000.070.070.320.32

Plastic <PS,ABS> white 0.70Y 8.59/0.97340 ✕ 990 ✕ 235 (13-7/16 ✕ 39 ✕ 6-5/16)

16 (36)

0.030

I.D. 20 (3/4) <VP-20>

5.619,100

5.85,000

6.35,40021,500

9-10-11-12150-167-183-200318-353-388-424

ø 12.7 (1/2) / ø 15.88 (5/8)(Compatible)

ø 6.35 (1/4) / ø 9.52 (3/8)(Compatible)

34-37-40-43

~ 220-240V 50Hz ~ 220V 60Hz3.6

12,3003.7

3,1504.0

3,40013,600

Cross fin (Aluminum plate fin and copper tube)Line flow fan ✕ 1

0Single phase induction motor

PP Honeycomb (long life)

0.040.040.200.20

Plastic 2.60Y 8.66/0.69295 ✕ 815 ✕ 158 (11-5/8 ✕ 32-1/8 ✕ 6-1/4)

8.5 (19)

4.9-5.2-5.6-5.982-87-93-98

173-184-198-208

0.017

I.D.16 (5/8) <VP-16>32-33-35-36

ø12.7 (1/2)

ø6.35 (1/4)

8-9.5-10.5-11.5133-158-175-192283-335-371-406

33-36-38-41

Page 31: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 59 Page 60

Specifications

Neatly installed with pericover concealed.Easy installation in perimeter zone.

Compact unit for easy air conditioning in perimeter zone.

Electronics dry functiondehumidify refreshingly.

������ ������

������ �����

INDOOR UNITFloor standing type

INDOOR UNITFloor mounted concealed type

Standardized design with mild lines.Supports various types of spaces from office buildings and shop buildings to hospitals.Water vapor permeable film humidifier can be installed.Remote control can be installed onto the main unit.

The compact body of 220mm(8-11/16in.) in depth can be easily installed in the perimeter zone for effective air condition-ing in the perimeter zone.

Optimum dehumidification depending on indoor temperature to prevent over-cool-ing. Refreshing dehumidification can be attained.

The body is concealed in the pericover to pursue harmony with the interior.The compact body of 220mm(8-11/16in.) in depth can be easily installed in the perimeter zone.

Compact unit for easy air conditioning in perimeter zone.

Optimum dehumidification depending on indoor temperature to prevent over-cooling. Re-freshing dehumidification can be attained.

Electronics dry function dehumidify refreshingly to prevent over-cooling.

Floor mounted lowboy type effective in perimeter zone.

Indoor unit

Specifications

Note: ❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DBHeating Indoor: 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DBHeating Indoor: 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB

❇3 Air flow rate/noise level are in (Low-High)❇4 Measured point : 1m51m, Power supply : AC240V/50Hz

·1dB(A) lower at AC230V/50Hz·2dB(A) lower at AC220V/50Hz·3dB(A) lower at 1.5m51.5m point

❇5 It is measured in anechoic room.

Power source

Cooling capacity

Heating capacity

Power consumption

Current

External finish(Munsel No.)

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Low-High) ❇3 ❇4 ❇5

Gas(Flare)Liquid(Flare)

Type

Airflow rate(Lo-Mid2-Mid1-Hi)

External staticpressure TypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

PFFY-P20VLEM-E

2.27,5002.3

2,0002.5

2,2008,500

ø12.7 (1/2)

ø6.35 (1/4)

0.04 / 0.060.04 / 0.060.19 / 0.250.19 / 0.25

630 ✕ 1,050 ✕ 22024-13/16 ✕ 41-3/8 ✕ 8-11/16

23 (51)

Sirocco fan ✕ 15.5-6.592-108

194-230

0.015

34-40

630 ✕ 1,410 ✕ 22024-13/16 ✕ 55-9/16 ✕ 8-11/16

PFFY-P25VLEM-E

2.89,6002.9

2,5003.2

2,80010,900

PFFY-P32VLEM-E

3.612,300

3.73,1504.0

3,40013,600

0.06 / 0.070.06 / 0.070.29 / 0.300.29 / 0.30

25 (56)

7.0-9.0117-150247-318

0.018

35-40

PFFY-P40VLEM-E

4.515,400

4.74,0005.0

4,30017,100

0.065 / 0.0750.065 / 0.0750.32 / 0.330.32 / 0.33

26 (58)

9.0-11.0150-183318-388

0.030

PFFY-P50VLEM-E

5.619,100

5.85,0006.3

5,40021,500

0.085 / 0.090.085 / 0.090.40 / 0.410.40 / 0.41

30 (67)

12.0-14.0200-233424-494

0.035

ø12.7 (1/2)

ø6.35 (1/4)

PFFY-P63VLEM-E

7.124,200

7.36,300

8.06,90027,300

0.1 / 0.110.1 / 0.110.46 / 0.470.46 / 0.47

32 (71)

12.0-15.5200-258424-547

0.063

ø15.88 (5/8)

ø9.52 (3/8)

40-46

~ 220-240V 50Hz / ~ 208-230V 60Hz

Acrylic paint (5Y 8/1)630 ✕ 1,170 ✕ 220

24-13/16 ✕ 46-1/8 ✕ 8-11/16

Cross fin (Aluminum plate fin and copper tube)

0Single phase induction motor

PP Honeycomb fabric (washable)

I.D.26 (1) <Accessary hose O.D.27 (top end :O.D.20)>

Sirocco fan ✕ 2

38-43

Power source

Cooling capacity

Heating capacity

Power consumption

Current

External finish(Munsel No.)

Dimension H ✕ W ✕ D

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameterNoise level (Low-High) ❇3 ❇4 ❇5

Gas(Flare)Liquid(Flare)

Type

Airflow rate(Lo-Mid2-Mid1-Hi)

External staticpressure TypeOutput

CoolingHeatingCoolingHeating

kWBTU/h

kWkcal/h

kWkcal/hBTU/h

kWkWAA

mmin.

kg(lbs.)

m3/minL/scfmPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)

❇1❇1❇2❇2❇1❇1❇1

❇3

PFFY-P20VLRM-E

2.27,5002.3

2,0002.5

2,2008,500

ø12.7 (1/2)

ø6.35 (1/4)

0.04 / 0.060.04 / 0.060.19 / 0.250.19 / 0.25

639 ✕ 886 ✕ 22025-3/16 ✕ 34-15/16 ✕ 8-11/16

18.5 (41)

Sirocco fan ✕ 15.5-6.592-108

194-230

0.015

34-40

639 ✕ 1,246 ✕ 22025-3/16 ✕ 49-1/16 ✕ 8-11/16

PFFY-P25VLRM-E

2.89,6002.9

2,5003.2

2,80010,900

PFFY-P32VLRM-E

3.612,300

3.73,1504.0

3,40013,600

0.06 / 0.070.06 / 0.070.29 / 0.300.29 / 0.30

20 (45)

7.0-9.0117-150247-318

0.018

35-40

PFFY-P40VLRM-E

4.515,400

4.74,0005.0

4,30017,100

0.065 / 0.0750.065 / 0.0750.32 / 0.330.32 / 0.33

21 (47)

9.0-11.0150-183318-388

0.030

PFFY-P50VLRM-E

5.619,100

5.85,0006.3

5,40021,500

0.085 / 0.090.085 / 0.090.40 / 0.410.40 / 0.41

25 (56)

12.0-14.0200-233424-494

0.035

ø12.7 (1/2)

ø6.35 (1/4)

PFFY-P63VLRM-E

7.124,200

7.36,300

8.06,90027,300

0.1 / 0.110.1 / 0.110.46 / 0.470.46 / 0.47

27 (60)

12.0-15.5200-258424-547

0.063

ø15.88 (5/8)

ø9.52 (3/8)

40-46

~ 220-240V 50Hz / ~ 208-230V 60Hz

Galvanizing639 ✕ 1,006 ✕ 220

25-3/16 ✕ 39-5/8 ✕ 8-11/16

Cross fin (Aluminum plate fin and copper tube)

0Single phase induction motor

PP Honeycomb fabric (washable)

I.D.26 (1) <Accessary hose O.D.27 (top end :O.D.20)>

Sirocco fan ✕ 2

38-43

Page 32: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Specifications

Note:

1. The cooling amd heating capacites are the maximum capacites that were obitained by operating in the above air conditions and with a refrigerant pipe of about 7.5m.2 .The actual capacity characteristics vary with the combination of indoor and outdoor units. See the technical infomation.3 .The operating noise is the data that was obitained by measuring it 1.5m from the the bottom of the unit in an anechoic room. (Noise meter A-scale value)4 .The figure of Electrical characteristic , indicates at 220 Pa setting at 415V.5 . When the 100% fresh air indoor units are connected, the maximum connectable indoor units to 1 outdoor unit are as follows

Power source

Cooling capacity

Heating capacity

Power consumption

Current

External finish

Dimension

Net weightHeat exchanger

Fan

Motor

Air filter

Refrigerantpipe diameter

Drain pipe diameter

Noise level ❇2

Gas(Flare)Liquid(Flare)

208, 220V230, 240V

208V220V230V240V

Type

Airflow rate

External staticpressure(Low/Mid/High) TypeOutput

CoolingHeatingCoolingHeating

HeightWidthDepth

kWBTU/h

kWBTU/h

kWkWAA

mm(in.)mm(in.)mm(in.)kg(lbs.)

m3/minL/scfmPaPaPaPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)dB(A)

❇1❇1❇1❇1

PEFY-P80VMH-E-F PEFY-P140VMH-E-F

9.030,700

8.529,000

0.16 / 0.210.16 / 0.210.67 / 0.910.67 / 0.91

1000 (39-3/8)

50 (111)

Sirocco fan ✕ 19.015018

35 / 85 / 17040 / 115 / 19050 / 130 / 21080 / 170 / 220

0.09

ø15.88 (5/8)

27 / 38 / 4333 / 43 / 45

16.0 54,600 15.1

51,500 0.29 / 0.33 0.29 / 0.33 1.24 / 1.48 1.24 / 1.48

1200 (47-1/4)

70 (155)

Sirocco fan ✕ 218.0300636

35 / 85 / 17050 / 115 / 190 60 / 130 / 220

100 / 170 / 240

0.14

ø15.88 (5/8)

28 / 38 / 4334 / 43 / 45

~ 220-240V 50Hz / ~ 208-230V 60Hz

Galvanizing 380 (15)

900 (35-7/16)

Cross fin (Aluminum plate fin and copper tube)

Single phase induction motor

Synthetic fiber unwoven cloth filter (long life)

ø9.52 (3/8)

O.D.32 (1-1/4)

Power source

Cooling capacity

Heating capacity

Power consumption

Current

External finish

Dimension

Net weightHeat exchanger

Fan

Motor

Air filter (option)

Refrigerantpipe diameter

Drain pipe diameter

Noise level ❇2

Gas(Flare)Liquid(Flare)

380V400V415V

380V400V415V

Type

Airflow rate

External staticpressure TypeOutput

CoolingHeatingCoolingHeating

HeightWidthDepth

kWBTU/h

kWBTU/h

kWkWAA

mm(in.)mm(in.)mm(in.)kg(lbs.)

m3/minL/scfmPaPaPa

kW

mm(in.)

mm(in.)

mm(in.)dB(A)dB(A)dB(A)

PEFY-P200VMH-E-F PEFY-P250 VMH-E-F

22.476,40021.2

72,3000.34 / 0.420.34 / 0.420.58 / 0.740.58 / 0.74

28467989

140 / 200150 / 210160 / 220

0.20

ø19.05 (3/4)

ø9.52 (3/8)

39 / 4240 / 4340 / 44

28.0 95,500 26.5

90,400 0.39 / 0.50 0.39 / 0.50 0.68 / 0.86 0.68 / 0.86

35 583

1236 110 / 190 120 / 200 130 / 210

0.23

ø22.2 (7/8)

ø9.52 (3/8)

40 / 4440 / 45

41 / 465

3N~ 380-415V 50Hz / 60Hz

Galvanized 470 (18-9/16) 1250 (49-1/4) 1120 (44-1/8)

100 (221) Cross fin

Sirocco fan ✕ 2

3-phase induction motor

Synthetic fiber unmoven cloth filter (long life type)

O.D.32 (1-1/4)

6. Operational temp range is Cooling:from 21˚C(69.8˚F)DB/15.5˚C(59.9˚F)WB to 43˚C(109.4˚F)DB/35˚C(95˚F)WBHeating: from -10˚C(14˚F)DB to 20˚C(68˚F)DB

❇ Thermo off(Fan) operation automatically starts either when temperature is lower than 21˚C(69.8˚F)DB in cooling mode or when the temperature exceeds 20˚C(68˚F)DB in heating mode.7. As the room temp in sensed by the thermo in the remote controller or the one in the room, be sure to use either remote controller or room thermo.8. Autochangeover function or Dry mode is NOT available. Fan mode operation during the thermo off in Cooling/Heating mode.9. In any case, the air flow rate should be kept lower than 110% of the above chart. Please see "Fan curves" for the details.10. When this nit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.11. Un-conditioned outdoor air such as humid air or cold air blows to the indoor during thermo off operation. Please be careful when positioning indoor unit air outlet grilles, ie take the necessary precautions for cold air, and also insulate rooms for dew condensation prevention as required.12. Air filter must be installed in the air intake side. The filter should be attached where easy maintenance in possible in case of usage of fild supply filters.

Heat pump models

110%(100% in case of heating below-5˚C(23˚F))

Cooling only

110%

( )

Page 61 Page 62

Specifications

Specifications

Indoor unit

Fresh Air can be taken in with temperature control. Ideal for Offices, Stores and Restaurant.

The Fresh Air intake indoor unitcan be installed in any place.

The Fresh Air intake indoor unit can take fresh outdoor air into any building in any place at any time.

* Limits of capacity connectable to outdoor unitMax. 110% of outdoor unit capacity, excepting heating at outdoor temperature of less than -5˚C(23˚F) (100%).

Office, Lobby, Workshop,

Rest room, Nursery home,

Smoking corner,

Kitchen in restaurant

Fresh Air intake indoor unit

Fresh air

OA

Supply airExhaust

air

EA

Installing fresh Air intake indoor unit (Image)

Example

2. Workshop1. Nursery home

Fresh Air intake indoor unit

Fresh Air intakeindoor unit

Workshop

Office

Private room

Passage

Air flow

Ventilating fan

Private room

Fresh air

Polluted air

Exhaustair

Ventilating fan

INDOOR UNITFresh Air Intake Type

������ �������

< Note>Fan remains in operation during Thermo-OFF. Using this model with other type of indoor unit is recommended for Cold Draft prevention because Cold Draft might occur by using only this model that takes in fresh air.

Fresh Air Intake

Page 33: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 63 Page 64

The secret to the unmatched comfort provided Lossnay core is the cross-flow, plate-fin structure off the heat-exchange unit. A diaphragm made of a specially processed paper fully separates inducted and exhausted air supplies, ensuring that only fresh air is introduced to the indoor environment.The superior heat-transfer and moisture permeability of the special paper assure highly effective total heat exchange (temperature and humidity) when inducted? and exhausted air supplies cross in the Lossnay core.

Combine with Lossnay Ventilation System Enhanced Air Quality.Unified Control System Allows Greater Design Freedom.

Stale hot air (exhaust)

Fresh cool air(outdoor)��� ������

��� �������

���� � ����

����� �� ���Fresh warm air (indoor supply air)

Stale warm air (indoor air)

Heat-Exchange Efficiency Obtainable Only with Lossnay.

LGH-15RX4 [150m3/h Single phase 220-240V 50Hz/60Hz]

LGH-25RX4 [250m3/h Single phase 220-240V 50Hz/60Hz]

LGH-35RX4 [350m3/h Single phase 220-240V 50Hz/60Hz]

LGH-50RX4 [500m3/h Single phase 220-240V 50Hz/60Hz]

LGH-80RX4 [800m3/h Single phase 220-240V 50Hz/60Hz]

LGH-100RX4 [1000m3/h Single phase 220-240V 50Hz/60Hz]

LGH-150RX4 [1500m3/h Single phase 220-240V 50Hz/60Hz]

LGH-200RX4 [2000m3/h Single phase 220-240V 50Hz/60Hz]

The Ventilation System for Enhanced Air Quality - Lossnay

LOSSNAYIndoor unit

• Two paths ventilation LOSSNAY simultaneously intakes Fresh Air and exhausts Dirty Air.

• Total energy recoverLOSSNAY returns BOTH sensible heat and latent heat.

LOSSNAY Technology

Mitsubishi developed “ HYPER CORE “ of World No.1

LOSSNAY recovers energy but does NOT return dirty air to indoor by Non porous paper.

• Hyper Performance [HYPER CORE]

Spacer plate

Partition plate

Fresh air induction(fresh air)

Fresh air exhaust(fresh heating/cooling air)

Stale air exhaust(dirty indoor air)

Stale air induction(dirty heating/cooling air)

Sensible heat Latent heat

IndoorsOutdoorsEA SA

RAOA

25µm

A. Two paths ventilation

No dirty air return Mitsubishi has World No.1 Energy exchange efficiency.

High Performance

B. Total Energy transfer

Water moleculeGas (CO2) molecule

Exhaust airflow

Supply airflow Non-porous ultra-thin filmmaterial: 25µm

64.5

70%

60%

15RX4

Ent

halp

y ex

chan

ge e

ffici

ency

(fo

r co

olin

g)

25RX4 35RX4 50RX4 65RX4 80RX4 100RX4 150RX4 200RX4

62.5 62.5

61.5

64.5 64.5 64.5 64.565.5

65

6867 67 67

68

64.5 64.5

UPby 3 to 4

point

Conventional models

RX4

Page 34: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 65 Page 66

ADVANTAGESClean air supply, dirty air exhaust by Two air paths (OA SA and RA EA)Energy recovery by LOSSNAY CoreFree cooling by bypass damperMULTI VENTILATION MODE for multi ventilation request (Power supply, Power supply/exhaust, Power exhaust)

• Without ventilation...Lack of Ventilation makes people sick by dirty indoor air including CO2, Dust, Bacteria.

• If just open windows...Opening windows eliminates dirty air BUT wastes much air-con energy.

• So we recommend LOSSNAY LOSSNAY is simultaneous pursuit of Ventilation and Energy Saving.

EA (exhaust air)

OA (outside air)

SA (supply air)

RA (returt air)

RX4 SERIES

• This is LOSSNAY !

Why LOSSNAY is necessary?

Ventilation Energy Save

UNIT STRUCTURE

LOSSNAY Core

Energy Recovery Image

Bypass damper

How much recover?OA temp. : 0˚C SA temp. : 15.4˚C

(Indoor 20˚C)

15.4˚CThermal energy

Outdoor:0˚C Indoor:20˚C

Air conditioner

Indoor unit

Multi Ventilation Mode for control air volume balance

All LGH models feature the "Multi-ventilation Mode," which allows the air supply/exhaust balance to be varied dynami-cally to suit the usage environment and location. Modes can be selected easily by setting the connectors on the circuit board.

Easy InstallationFlexible duct work is available.

Normal office,etc.

Smaller offices or tenant buildings,etc.

Smoking areas,etc.

Many people in an office Extractor fan working place Priority air exhaust

Power air supply/exhaust Power air supply Power air exhaust

EA OAEA OA

A space is necessary to prevent the influx of rainwater.

Can be installed close to the surface of the wall.

Standard installation Installation

Changing the duct direction

ExchangeableAperture Plate

Collar

LOSSNAY features

* "High" can be further set to "Extra high" using the dip switch.

Ventilation Mode

Power air supply/exhaust mode

Power air supply mode

Power air exhaust mode

Energy-saving ventilation mode

Supply

Airflow

High

High

Low

Low

Exhaust

Airflow

High

Low

High

Low

LOSSNAY

Page 35: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 67 Page 68

Appearance

Model line up

Installation

Specification

M-NET system with City MultiFlexible system, for your multi demand

LOSSNAY ventilation combined with Air-con

LGH-50RX4-E LGH-200RX4-E

Model

Power source

Size L mm

W mm

H mm

Volume m3

Weight kg

Duct diameter [mm]

Air Volume Shi CMH

Static Pressure Shi Pa

Sound level A Shi dB

Sound level B Shi dB

Ex. Effciency Temp. %

Heatin %

Cooling %

15R 25R 35R 50R 65R 80R 100R 150R 200R

200/240V 1Ph 50/60Hz

780 780 888 1016 954 1164 1263 1413 1413

610 735 874 888 908 1004 1164 1004 1231

275 275 317 317 388 398 398 800 800

0.13 0.16 0.25 0.29 0.34 0.47 0.59 1.13 1.39

17 21 30 33 46 61 69 138 161

100 150 150 200 250 250 250 350 350

150 250 350 500 650 800 1000 1500 2000

95 80 150 150 110 140 160 140 150

26 26.5 31 33 34.5 33.5 36 36.5 39

33 34.5 39 41 42.5 44.5 47 49 51.5

77 78 79 77 77 78 79 79 79

70 70 70 67.5 67.5 71 71 72 71

65.5 65 68 64.5 64.5 67 67 68 67

Model: LGH-RX4 series

Power supply unit

Centralized controller Outdoor unit

PAR-F27MEA PAR-F27MEA

Indoor unit Indoor unit

UP

Indoor unit LOSSNAY

Page 36: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 69 Page 70

GUF - For the finest indoor qualityGUF = [ LOSSNAY ] + [ HEATING & COOLING ]

RDH3 SERIESOUTDOOR AIR PROCESSING UNIT GUF type

General

Specification

Lossnay (Energy Recover)

DX Coil(Heating & Cooling)

GUF model image

Indoor unit

The OA Processing Unit is equipped with a new permeable film humidifier developed and patented by Mitsubishi Electric. Steam transmission efficiency has been improved remarkably by lowering the resistance of the material. The use of a 3-layer film that allows only the transfer of steam prevents the production of white powder, so there is no need for the use of a water purifier.

The OA (outdoor-air) Processing Unit creates an optimum indoor-air environment at an unparalleled rate of cost efficiency providing substantial energy savings. Forced air ventilating and humidifying functions unique to this system keep indoor-air fresh and free of contaminants preventing “sick building syndrome” and the spread of airborne viruses such as the flu. Another novel feature of the OA Processing Unit is the “Lossnay core,” a heat-exchange unit that functions to transfer heat efficiently, cutting ventilation load by as much as 70%. This special combination of functionality and performance designed to ensure users ample comfort and year-round health cannot be found anywhere else on the market.

GUF-50RD(H)3 *1 Cooling Capacity 5.29 (DX coil:3.63, Lossnay:1.66)KW Heating capacity 6.42 (DX coil:4.17, Lossnay:2.25)KW 500m3/h Single phase 220-240V 50Hz

GUF-100RD(H)3 *1 Cooling Capacity 10.81 (DX coil:7.32, Lossnay3.49)KW Heating capacity 13.00 (DX coil:8.30, Lossnay:4.70)KW 1000m3/h Single phase 220-240V 50Hz *1 H : Humidifying Type

New Permeable Film Humidifier (RDH3 model)

Outdoor air

Ultra-water repellant cell-based water-vapor transmission filter

Water

Ultra-water repellant cell-based water-vapor transmission filter

Water

Steam

New filter

3-dimensional cloth

Spacer

Humidified air

OA ProcessingUnits

Air filterPrevents clogs in the Lossnay Core.

DX Heat exchangerCools or heats the drawn in outdoor-air.

SA (Supply air)The processed, fresh outdoor-air is vented to the indoor rooms.

RA (Return air)The exhaust fan draws in contaminated indoor-air.

EA (Exhaust air)Heat from the indoor air (both sensible and latent) is recovered by the Lossnay Core and vented outside by the exhaust fan.

The exhaust fan

High efficiency filters (Option)

The supply fan

Maintenance cover

OA (Outdoor air)Fresh, outdoor-air in a quantity required for ventilation is drawn in by the supply fan.

Heat recovery unit(Lossnay Core)Temperature and humidity are exchanged between the supply air and the exhaust air.

Comfortable Level of Humidity for Exceptionable Air Quality

Improvements in the system of airflow patterns and water injection techniques have resulted in a substantial increase in humidifying volume.

Highly Efficient Humidification

Ideal Indoor-Air Quality — For Your Comfort and Health

Model

Power source

Cooling capacity

Figure in < > is the recovery

capacity by LOSSNAY core.

Heating capacity

Figure in < > is the recovery

capacity by LOSSNAY core.

Capacity equivalent to indoor unit

Humidifying capacity

External finish

External dimension H ✕ W ✕ D

Net weight

Heat

exchanger

FAN

Noise level (Low-High)

(measured in anechoic room)

Insulation material

Air filter

Protection device

Refrigerant control device

Diameter of

refrigerant pipe

Diameter of drain pipe

kW

kcal / h

Btu / h

kcal / h

kW

A

kW

kcal / h

Btu / h

kW

A

kg / h

lb / h

mm

in.

kg (lb)

Pa

mmH2O

kW

m3 / min

L / s

cfm

dB <A>

mm (in.)

mm (in.)

mm (in.)

❇1

❇1

❇1

❇2

❇3

❇3

❇3

Power input

Current input

Power input

Current input

Humidifier

LOSSNAY core

Refrigerant coil

Type ✕ Quantity

External

static press.

Motor type

Motor output

Driving mechanism

Airflow rate

(High value)

Supplying air

Exhausting air

Liquid

Gas

GUF-50RDH3 GUF-100RDH3 GUF-50RD3 GUF-100RD3

235-265

1.15

235-265

1.15

P32

2.7

6.0

317 ✕ 1,016 ✕ 1,288

12-1/2 ✕ 40 ✕ 50-3/4

57 (126)

125

12.7

-

500

139

294

33.5-34.5

ø6.35 (ø1/4) Flare

ø12.7 (ø1/2) Flare

480-505

2.20

480-505

2.20

P63

5.4

12.0

398 ✕ 1,231 ✕ 1,580

15-11/16 ✕ 48-1/2 ✕ 62-1/4

98 (217)

135

13.8

-

1,000

139

589

38-39

ø9.52 (ø3/8) Flare

ø15.88 (ø5/8) Flare

235-265

1.15

235-265

1.15

P32

-

-

317 ✕ 1,016 ✕ 1,288

12-1/2 ✕ 40 ✕ 50-3/4

54 (120)

140

14.3

-

500

139

294

33.5-34.5

ø6.35 (ø1/4) Flare

ø12.7 (ø1/2) Flare

480-505

2.20

480-505

2.20

P63

-

-

398 ✕ 1,231 ✕ 1,580

15-11/16 ✕ 48-1/2 ✕ 62-1/4

92 (203)

140

14.3

-

1,000

139

589

38-39

ø9.52 (ø3/8) Flare

ø15.88 (ø5/8) Flare

1-phase 220-240V 50Hz, 1-phase 220V 60Hz

Galvanized, with grey insulation sheet

Partition, Cross-flow structure, Special preserved paper-plate.

Cross fin (Aluminum fin and copper tube)

SA: Centrifugal fan (Sirocco fan) ✕ 1

EA: Centrifugal fan (Sirocco fan) ✕ 1

Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2units

Direct-driven by motor

Polyester sheet

Non-woven fabrics filter (Gravitational method 82%) & Optional part: High efficiency filter (Colorimetric method 65%)

Non-woven fabrics filter (Gravitational method 82%)

Fuse

LEV

VP25

Permeable film humidifier -

<1.83>

<1,600>

<6,200>

<1,400>

<2.01>

<1,700>

<6,900>

5.46

4,700

18,600

4,500

6.18

5,300

21,100

11.17

9,600

38,100

9,300

12.50

10,800

42,700

<3.85>

<3,300>

<13,100>

<3,000>

<4.20>

<3,600>

<14,300>

<1.83>

<1,600>

<6,200>

<1,400>

<2.01>

<1,700>

<6,900>

5.46

4,700

18,600

4,500

6.18

5,300

21,100

<3.85>

<3,300>

<13,100>

<3,000>

<4.20>

<3,600>

<14,300>

11.17

9,600

38,100

9,300

12.50

10,800

42,700

OA Processing Units

Page 37: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 72

Outdoor unit

Page 71

O utdoor unit

Heat Pump Series

S Series (4HP-6HP)

Y Series (20HP-24HP)

Y Series (8HP-14HP)

Y Series (16HP-18HP)

Y Series (26HP-32HP)

Y Series (34HP-36HP)

Y Series (38HP-46HP)

PUHY-P TSHM-A

PUHY-P TSHM-A

PUHY-P TSHM-A

���� ������� � ��� ����

PUMY-P VHM

PUHY-P TSHM-A

PUHY-P THM-A

PUHY-P THM-A

PUHY-P TSHM-A

Y Series (48HP-50HP)

Page73 Page77

Page74 Page78

Page75 Page79

Page76 Page80

Model

Model Name

4HP

PUMY-P100VHM

5HP

PUMY-P125VHM

6HP

PUMY-P140VHM

Model

Model Name

8HP

PUHY-P200THM-A

10HP

PUHY-P250THM-A

12HP

PUHY-P300THM-A

14HP

PUHY-P350THM-A

Model

Model Name

16HP

PUHY-P400THM-A

18HP

PUHY-P450THM-A

Model

Model Name

30HP

PUHY-P750TSHM-A

32HP

PUHY-P800TSHM-A

Model

Model Name

34HP

PUHY-P850TSHM-A(-BS)

36HP

PUHY-P900TSHM-A(-BS)

Model

Model Name

48HP

PUHY-P1200TSHM-A

50HP

PUHY-P1250TSHM-A

Model

Model Name

48HP

PUHY-P1200TSHM-A

50HP

PUHY-P1250TSHM-A

Model

Model Name

38HP

PUHY-P950TSHM-A

40HP

PUHY-P1000TSHM-A

42HP

PUHY-P1050TSHM-A

44HP

PUHY-P1100TSHM-A

46HP

PUHY-P1150TSHM-A

Model

Model Name

20HP

PUHY-P500TSHM-A

22HP

PUHY-P550TSHM-A

26HP

PUHY-P650TSHM-A

28HP

PUHY-P700TSHM-A

24HP

PUHY-P600TSHM-A

❇The PUHY-P-TSHM-A series requires a Twinning kit (optional). Refer to the data book for details.

Page 38: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 73 Page 74

Outdoor unit

������ ���

OUTDOOR UNITS Series

������ ����

OUTDOOR UNITY Series

SpecificationsSpecifications

Power sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal)

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipeExternal finishExternal dimension H ✕ W ✕ DNet weightHeat exchanger

Compressor

FAN

Protection

Refrigerant

Power inputCurrent inputCOP (kW/kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

Liquid (High press.)Gas (Low press.)

TypeStarting methodMotor output

Air flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP./FAN)CompressorType ✕ Original charge

PUMY-P100VHM PUMY-P125VHM PUMY-P140VHM

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB<A>mm(in.)mm(in.)

mm (in.)kg (lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

Power sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal)

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipe

External finish

External dimension H ✕ W ✕ D

Net weightHeat exchanger

Compressor

FAN

Protection

Refrigerant

Power inputCurrent inputCOP (kW/kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

Liquid

Gas

TypeStarting methodMotor outputAir flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP. / FAN)CompressorType ✕ Original charge

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB<A>mm(in.)

mm(in.)

mm(in.)

kg(lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

PUHY-P200THM-A(-BS) PUHY-P250THM-A(-BS) PUHY-P300THM-A(-BS) PUHY-P350THM-A(-BS)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

Outdoor unit

11.29,60038,2003.34

15.4-14.8-14.1, 15.43.35

12.510,80042,7003.66

16.9-16.2-15.5, 16.93.42

P20 ~ P125 / 1 ~ 649 / 51

ø9.52 (ø3/8) Liquidø15.88 (ø5/8) Gas

1,350 ✕ 950 ✕ 330 (53-3/16 ✕ 37-7/16 ✕ 13)127 (280 lb)

2.210016673532

Propeller fan ✕ 20.06 ✕ 2

R410A ✕ 8.5kg (19 lb)

14.012,00047,8004.32

20.0-19.1-18.3, 20.03.24

16.013,80054,6004.33

20.0-19.1-18.3, 20.03.69

P20 ~ P140 / 1 ~ 850 / 52

ø9.52 (ø3/8) Liquidø15.88 (ø5/8) Gas

1,350 ✕ 950 ✕ 330 (53-3/16 ✕ 37-7/16 ✕ 13)127 (280 lb)

2.910016673532

Propeller fan ✕ 20.06 ✕ 2

R410A ✕ 8.5kg (19 lb)

15.513,30052,9005.35

24.7-23.6-22.7, 24.72.9

18.015,50061,4005.58

25.8-24.7-23.6, 25.83.23

P20 ~ P140 / 1 ~ 851 / 53

ø9.52 (ø3/8) Liquid ø15.88 (ø5/8) Gas

1,350 ✕ 950 ✕ 330 (53-3/16 ✕ 37-7/16 ✕ 13)127 (280 lb)

3.310016673532

Propeller fan ✕ 20.06 ✕ 2

R410A ✕ 8.5kg (19 lb)

22.419,30076,4005.73

17.6-16.7-15.93.90

25.021,50085,3006.05

18.6-17.6-16.84.13

P20~P250 / 1~1356

ø9.52 (ø3/8) Flare

ø19.05 (ø3/4) Brazed

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

185 (408)

5.4185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 6.5kg (14 lb + 5 oz)

28.024,10095,5008.20

25.2-23.9-22.83.41

31.527,100

107,5007.96

24.5-23.2-22.23.95

P20~P250 / 1~1657

ø9.52 (ø3/8) Flare(ø12.7 (ø1/2) Flare, total length >=90m)

ø22.2 (ø7/8) Brazed

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

185 (408)

6.7185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 6.5kg (14 lb + 5 oz)

33.528,800

114,3009.10

28.0-26.5-25.33.68

37.532,300

128,0009.40

28.9-27.4-26.23.98

P20~P250 / 1~1659

ø9.52 (ø3/8) Flare(ø12.7 (ø1/2) Flare total length>=40m)

ø22.2 (ø7/8) Brazed

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

8.2185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg (19 lb + 13 oz)

40.034,400136,500

13.0140.1-37.9-36.2

3.07

45.038,700153,500

12.1237.3-35.3-33.8

3.71

P20~P400 / 1~2060

ø12.7 (ø1/2) Flare

ø28.58 (ø1-1/8) Brazed

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

10.101853,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg (19 lb + 13 oz)

3-phase 3-wire 208-220-230V 60Hz

15~24˚C(59~75˚F)- 5~43˚C(23~109˚F)

15~27˚C(59~81˚F)-20~15.5˚C(-4~60˚F)

50~130% of outdoor unit capacity

Salt-resistant cross fin & copper tubeInverter scroll hermetic compressor

Inverter

Pre-coated galvanized steel sheet <MUNSELL 5Y 8/1>

High pressure sensor, High pressure switch 4.15 MPa (601 psi)Over-current protection, Over-heat protection

Discharge thermo protection, Over-current protection

1-phase 220-230-240V 50Hz, 1-phase 220V 60Hz

15 ~ 24˚C (59 ~ 75˚F)- 5 ~ 46˚C (23 ~ 115˚F)

10 to 46˚CD.B. (50 to 115˚FD.B.) : in case of connecting PKFY-P20 / P25 type indoor unit.

15 ~ 27˚C (59 ~ 81˚F)-15 ~ 15˚C (5 ~ 59˚F)

50 ~ 130% of outdoor unit capacity

Galvanized steel sheet <MUNSELL 3Y 7.8/1.1>

Salt-resistant cross fin & copper tubeInverter scroll hermetic comp.

Inverter

High pressure sensor, High pressure switch 4.15 MPaOver-heat protection, Over-current protection

Discharge thermo protection, Over-current protection

Page 39: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 75 Page 76

Outdoor unit

������ �����

OUTDOOR UNITY Series

������ �����

OUTDOOR UNITY Series

SpecificationsSpecifications

Outdoor unit

Power sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal)

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipeExternal finishExternal dimension H ✕ W ✕ DNet weightHeat exchangerCompressor

FAN

Protection

Refrigerant

45.038,700153,50013.24

40.8-38.6-36.93.39

50.043,000170,60012.37

38.1-36.0-34.54.04

P20~P500 / 1~2061

ø12.7 (ø1/2) Flareø28.58 (ø1-1/8) Brazed

1,650 ✕ 1,220 ✕ 760 (65 ✕ 48-1/16 ✕ 29-15/16)240 (529)

10.5225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

50.043,000170,60016.29

50.2-47.5-45.43.06

56.048,200191,10014.55

44.8-42.4-40.53.84

P20~P500 / 1~2062

ø15.88 (ø5/8) Flareø28.58 (ø1-1/8) Brazed

1,650 ✕ 1,220 ✕ 760 (65 ✕ 48-1/16 ✕ 29-15/16)240 (529)

12.0225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

Power inputCurrent inputCOP (kW/kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

LiquidGas

TypeStarting methodMotor outputAir flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP./FAN)CompressorType ✕ Original charge

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB<A>mm(in.)mm(in.)

mm(in.)kg(lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

PUHY-P400THM-A(-BS) PUHY-P450THM-A(-BS) Set namePower sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal)

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipeOutdoor unit 1 and Outdoor unit 2External finishExternal dimension H ✕ W ✕ D

Net weightHeat exchangerCompressor

FAN

Protection

Refrigerant

Twinning kit (optional)

Power inputCurrent inputCOP (kW/kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

LiquidGas

TypeStarting methodMotor outputAir flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP./FAN)CompressorType ✕ Original charge

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB<A>mm(in.)mm(in.)

mm(in.)

kg(lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

PUHY-P500TSHM-A(-BS) PUHY-P550TSHM-A(-BS) PUHY-P600TSHM-A(-BS)

56.048,200

191,10017.68

54.5-51.5-49.33.16

63.054,200

215,00017.12

52.8-49.9-47.73.67

P20~P500 / 1~2060

ø15.88 (ø5/8) Brazedø28.58 (ø1-1/8) Brazed

3-phase 3-wire 208-220-230V 60Hz63.0

54,200215,00018.01

55.5-52.5-50.23.49

69.059,300

235,40018.48

56.9-53.8-51.53.73

P20~P500 / 1~2061

ø15.88 (ø5/8) Brazedø28.58 (ø1-1/8) Brazed

69.059,300235,400

21.8467.3-63.6-60.9

3.15

76.565,800261,000

20.3562.7-59.3-56.7

3.75

P20~P500 / 1~3262

ø15.88 (ø5/8) Brazedø28.58 (ø1-1/8) Brazed

15~24˚C (59~75˚F)- 5~43˚C (23~109˚F)

15~27˚C (59~81˚F)-20~15.5˚C (-4~60˚F)

50~130% of outdoor unit capacity

Pre-coated galvanized steel sheet <MUNSELL 5Y 8/1>

Salt-resistant cross fin & copper tubeInverter scroll hermetic compressor

Inverter

High pressure sensor, High pressure switch 4.15 MPa (601 psi)Over-current protection, Over-heat protection

Discharge thermo protection, Over-current protection

3-phase 3-wire 208-220-230V 60Hz

15~24˚C (59~75˚F)- 5~43˚C (23~109˚F)

15~27˚C (59~81˚F)-20~15.5˚C (-4~60˚F)

50~130% of outdoor unit capacity

Pre-coated galvanized steel sheet <MUNSELL 5Y 8/1>

Salt-resistant cross fin & copper tubeInverter scroll hermetic compressor

Inverter

High pressure sensor, High pressure switch 4.15 MPa (601 psi)Over-current protection, Over-heat protection

Discharge thermo protection, Over-current protection

PUHY-P250THM-A(-BS) PUHY-P300THM-A(-BS)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

185 (408)

6.7185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 6.5kg (14 lb + 5 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg (19 lb + 13 oz)

PUHY-P250THM-A(-BS) PUHY-P350THM-A(-BS)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

185 (408)

6.7185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 6.5kg (14 lb + 5 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

8.2185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg (19 lb + 13 oz)

CMY-Y100VBKCMY-Y100VBK CMY-Y100VBK

PUHY-P250THM-A(-BS)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

185 (408)

6.7185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 6.5kg (14 lb + 5 oz)

PUHY-P250THM-A(-BS)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

185 (408)

6.7185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 6.5kg (14 lb + 5 oz)

Page 40: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 77 Page 78

Outdoor unit

������ �����

OUTDOOR UNITY Series

������ �����

OUTDOOR UNITY Series

SpecificationsSpecifications

Outdoor unit

Set namePower sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal )

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipeOutdoor unit 1 and Outdoor unit 2

External finishExternal dimension H ✕ W ✕ D

Net weightHeat exchangerCompressor

FAN

Protection

Refrigerant

Twinning kit (optional)

Power inputCurrent inputCOP (kW / kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

LiquidGas

TypeStarting methodMotor outputAir flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP./FAN)CompressorType ✕ Original charge

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB <A>mm(in.)mm(in.)

mm(in.)

kg(lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

PUHY-P650TSHM-A(-BS) PUHY-P700TSHM-A(-BS) PUHY-P750TSHM-A(-BS) PUHY-P800TSHM-A(-BS) Set namePower sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal)

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipeOutdoor unit 1 and Outdoor unit 2External finishExternal dimension H ✕ W ✕ D

Net weightHeat exchanger

Compressor

FAN

Protection

RefrigerantTwinning kit (optional)

Power inputCurrent inputCOP (kW/kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

LiquidGas

TypeStarting methodMotor outputAir flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP./FAN)CompressorType ✕ Original charge

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB<A>mm(in.)mm(in.)

mm(in.)

kg(lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

PUHY-P850TSHM-A(-BS) PUHY-P900TSHM-A(-BS)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

PUHY-P450THM-A(-BS)PUHY-P400THM-A(-BS)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

12.0225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

PUHY-P450THM-A(-BS)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

12.0225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

PUHY-P450THM-A(-BS)

Pre-coated galvanized steel sheet <MUNSELL 5Y 8/1>PUHY-P300THM-A

(-BS)PUHY-P350THM-A

(-BS)PUHY-P350THM-A

(-BS)PUHY-P350THM-A

(-BS)PUHY-P400THM-A

(-BS)PUHY-P450THM-A

(-BS)PUHY-P350THM-A

(-BS)

96.082,600

327,60030.26

93.3-88.2-84.33.17

108.092,900

368,50026.92

83.0-78.4-75.04.01

P20~P500 / 1~4264.5

ø19.05 (ø3/4) Brazedø41.28 (ø1-1/2) Brazed

101.086,900

344,60033.35

102.8-97.2-93.03.02

113.097,200

385,60028.65

88.3-83.5-79.93.94

P20~P500 / 1~4265

ø19.05 (ø3/4) Brazedø41.28 (ø1-1/2) Brazed

15~24˚C (59~75˚F)- 5~43˚C (23~109˚F)

3-phase 3-wire 208-220-230V 60Hz

15~27˚C (59~81˚F)-20~15.5˚C (-4~60˚F)

50~130% of outdoor unit capacity

Salt-resistant cross fin & copper tubeInverter scroll hermetic compressor

Inverter

1,650 ✕ 1,220 ✕ 760 (65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

10.5225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

1,650 ✕ 1,220 ✕ 760 (65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

12.0225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

High pressure sensor, High pressure switch 4.15 MPa (601 psi)Over-current protection, Over-heat protection

Discharge thermo protection, Over-current protection

73.062,800249,10022.44

69.2-65.4-62.53.25

81.570,100278,10021.34

65.8-62.2-59.53.81

P20~P500 / 1~3262.5

ø15.88 (ø5/8) Brazedø28.58 (ø1-1/8) Brazed

80.068,800273,00026.11

80.5-76.1-72.83.06

88.075,700300,30023.75

73.2-69.2-66.23.70

P20~P500 / 1~3263

ø19.05 (ø3/4) Brazedø34.93 (ø1-1/4) Brazed

90.077,400307,10029.63

91.3-86.3-82.63.03

100.086,000341,20026.36

81.2-76.8-73.53.79

P20~P500 / 1~3264

ø19.05 (ø3/4) Brazedø34.93 (ø1-1/4) Brazed

85.073,100290,00026.84

82.7-78.2-74.83.16

95.081,700324,10024.75

76.3-72.1-69.03.83

P20~P500 / 1~3263.5

ø19.05 (ø3/4) Brazedø34.93 (ø1-1/4) Brazed

3-phase 3-wire 208-220-230V 60Hz

15~24˚C (59~75˚F)- 5~43˚C (23~109˚F)

15~27˚C (59~81˚F)-20~15.5˚C (-4~60˚F)

50~130% of outdoor unit capacity

Pre-coated galvanized steel sheet <MUNSELL 5Y 8/1>

Salt-resistant cross fin & copper tubeInverter scroll hermetic compressor

Inverter

High pressure sensor, High pressure switch 4.15 MPa (601 psi)Over-current protection, Over-heat protection

Discharge thermo protection, Over-current protection

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg(19 lb + 13 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg(19 lb + 13 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg(19 lb + 13 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

8.2185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg(19 lb + 13 oz)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

10.5225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg(25 lb + 6 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

PUHY-P350THM-A(-BS)

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg(19 lb + 13 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16✕ 29-15/16)

240 (529)

12.0225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg(19 lb + 13 oz)

CMY-Y100VBK

CMY-Y200VBK CMY-Y200VBK

CMY-Y200VBKCMY-Y200VBKCMY-Y100VBK

Page 41: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 79 Page 80

Outdoor unit

������ �����

OUTDOOR UNITY Series

������ �����

OUTDOOR UNITY Series

SpecificationsSpecifications

Outdoor unit

Set namePower sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal )

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipeOutdoor unit 1 and Outdoor unit 2External finish

External dimension H ✕ W ✕ D

Net weightHeat exchanger

Compressor

FAN

Protection

Refrigerant

Twinning kit (optional)

Power inputCurrent inputCOP (kW/kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

LiquidGas

TypeStarting methodMotor outputAir flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP./FAN)Compressor

Type ✕ Original charge

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB<A>mm(in.)mm(in.)

mm (in.)

kg (lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

PUHY-P1200TSHM-A(-BS) PUHY-P1250TSHM-A(-BS)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

Set namePower sourceCooling capacity (Nominal)

Temp. range of coolingHeating capacity(Nominal )

Temp. range of heatingIndoor unitconnectableNoise level (measured in anechoic room)Diameter of refrigerant pipeOutdoor unit 1 and Outdoor unit 2

External finish

External dimension H ✕ W ✕ D

Net weight

Heat exchanger

Compressor

FAN

Protection

Refrigerant

Twinning kit (optional)

Power inputCurrent inputCOP (kW/kW)Indoor Outdoor

Power inputCurrent inputCOP (kW/kW) Indoor temp. Outdoor temp.

Total capacityModel/Quantity

LiquidGas

TypeStarting methodMotor outputAir flow rate

Type ✕ QuantityMotor outputHigh pressure protectionInverter circuit (COMP./FAN)Compressor

Type ✕ Original charge

kWkcal/hBtu/hkWA

W.B.D.B.

kWkcal/hBtu/hkWA

D.B.W.B.

dB<A>mm(in.)mm(in.)

mm(in.)

kg(lb)

kWm3/min

L/scfm

kW

❇1❇1❇1

❇2❇2❇2

PUHY-P950TSHM-A(-BS) PUHY-P1000TSHM-A(-BS) PUHY-P1050TSHM-A(-BS) PUHY-P1100TSHM-A(-BS) PUHY-P1150TSHM-A(-BS)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

Note:

❇1 Nominal cooling conditionsIndoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

❇2 Nominal heating conditionsIndoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WBPipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)

3-phase 3-wire 208-220-230V 60Hz136.0

117,000464,00044.25

136.4-129.0-123.43.07

150.0129,000511,80039.04

120.4-113.8-108.83.84

P20~P500 / 2~4266

ø19.05 (ø3/4) Brazedø41.28 (ø1-5/8) Brazed

3-phase 3-wire 208-220-230V 60Hz140.0

120,400477,70047.04

145.0-137.1-131.22.97

156.5 134,600534,00040.43

124.6-117.8-112.73.87

P20~P500 / 2~4266

ø19.05 (ø3/4) Brazedø41.28 (ø1-5/8) Brazed

15~27˚C (59~81˚F)-20~15.5˚C (-4~60˚F)

50~130% of outdoor unit capacity

15~24˚C (59~75˚F)- 5~43˚C (23~109˚F)

PUHY-P300THM-A

(-BS)

PUHY-P400THM-A

(-BS)

Propeller fan ✕ 1Propeller fan ✕ 1

PUHY-P350THM-A

(-BS)

PUHY-P400THM-A

(-BS)

PUHY-P350THM-A

(-BS)

PUHY-P450THM-A

(-BS)

PUHY-P400THM-A(-BS)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

10.5225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

CMY-Y300VBK

PUHY-P450THM-A(-BS)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

12.0225

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

Pre-coated galvanized steel sheet <MUNSELL 5Y 8/1>

PUHY-P350THM-A(-BS)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg (19 lb + 13 oz)

PUHY-P450THM-A(-BS)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

12.00.045 (230V)

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

PUHY-P450THM-A(-BS)

1,650 ✕ 1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240 (529)

12.00.045 (230V)

3,7507,945

Propeller fan ✕ 10.46 ✕ 1

R410A ✕ 11.5kg (25 lb + 6 oz)

CMY-Y300VBK

PUHY-P350THM-A(-BS)

1,650 ✕ 920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210 (463)

10.1185

3,0836,532

Propeller fan ✕ 10.35 ✕ 1

R410A ✕ 9.0kg (19 lb + 13 oz)

Salt-resistant cross fin & copper tubeInverter scroll hermetic compressor

Inverter

High pressure sensor, High pressure switch 4.15 MPa (601 psi)Over-current protection, Over-heat protection

Discharge thermo protection, Over-current protection

108.092,900368,50030.82

95.0-89.8-85.93.50

119.5102,800407,70029.60

91.2-86.3-82.54.03

P20~P500 / 1~4264

ø19.05 (ø3/4) Brazedø41.28 (ø1-5/8) Brazed

High pressure sensor, High pressure switch 4.15 MPa (601 psi)Over-current protection, Over-heat protection

Discharge thermo protection, Over-current protection

Salt-resistant cross fin & copper tubeInverter scroll hermetic compressor

Inverter

Pre-coated galvanized steel sheet <MUNSELL 5Y 8/1>

PUHY-P250THM-A

(-BS)

PUHY-P300THM-A

(-BS)

PUHY-P400THM-A

(-BS)

PUHY-P300THM-A

(-BS)

PUHY-P300THM-A

(-BS)

PUHY-P350THM-A

(-BS)

PUHY-P400THM-A

(-BS)

Propeller fan ✕ 1

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

185(408)

6.7185

3,0836,532

0.35 ✕ 1

R410A✕ 6.5kg(14 lb+5 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

8.2185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240(529)

10.5225

3,7507,945

0.46 ✕ 1

R410A✕ 11.5kg(25 lb+6 oz)

113.097,200385,600

32.5100.2-94.7-90.6

3.47

127.0109,200433,30031.68

97.7-92.3-88.34.00

P20~P500 / 2~4264.5

ø19.05 (ø3/4) Brazed ø41.28 (ø1-5/8) Brazed

15~27˚C (59~81˚F)-20~15.5˚C (-4~60˚F)

50~130% of outdoor unit capacity

15~24˚C (59~75˚F)- 5~43˚C (23~109˚F)

3-phase 3-wire 208-220-230V 60Hz

PUHY-P300THM-A

(-BS)

Propeller fan ✕ 1

118.0101,500402,60036.11

111.3-105.2-100.73.26

132.0113,500450,40033.87

104.4-98.7-94.43.89

P20~P500 / 2~4265

ø19.05 (ø3/4) Brazedø41.28 (ø1-5/8) Brazed

124.0106,600423,10039.93

123.1-116.4-111.33.10

140.0120,400477,70036.36

112.1-106.0-101.43.85

P20~P500 / 2~4265

ø19.05 (ø3/4) Brazedø41.28 (ø1-5/8) Brazed

130.0111,800443,600

43.3133.5-126.2-120.7

3.00

145.0124,700494,70038.34

118.2-111.7-106.93.78

P20~P500 / 2~4265.5

ø19.05 (ø3/4) Brazedø41.28 (ø1-5/8) Brazed

PUHY-P350THM-A

(-BS)

Propeller fan ✕ 1

CMY-Y300VBK CMY-Y300VBK CMY-Y300VBK CMY-Y300VBK CMY-Y300VBK

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

8.2185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

8.2185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

8.2185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

8.2185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240(529)

10.5225

3,7507,945

0.46 ✕ 1

R410A✕ 11.5kg(25 lb+6 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

10.1185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg

(19 lb+13 oz)

1,650 ✕

1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240(529)

10.5225

3,7507,945

0.46 ✕ 1

R410A✕ 11.5kg(25 lb+6 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

10.1185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240(529)

10.5225

3,7507,945

0.46 ✕ 1

R410A ✕ 11.5kg(25 lb+6 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

10.1185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

920 ✕ 760(65 ✕ 36-1/4 ✕ 29-15/16)

210(463)

10.1185

3,0836,532

0.35 ✕ 1

R410A✕ 9.0kg(19 lb+13 oz)

1,650 ✕

1,220 ✕ 760(65 ✕ 48-1/16 ✕ 29-15/16)

240(529)

12.0225

3,7507,945

0.46 ✕ 1

R410A✕ 11.5kg(25 lb+6 oz)

Page 42: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 82

Optional parts

Page 81

O ptional parts

>>4-way cassette type (PLFY-VAM)

>>2-way cassette type (PLFY-VLMD)

>>Ceiling concealed type (PEFY-VMH)

>>Ceiling concealed type (PDFY-VM)

>>Ceiling suspended type (PCFY-VGM)

>>Fresh air intake type (PEFY-VMH-E-F)

>>1-way cassette type(PMFY-VBM)

OPTIONAL PARTS FOR INDOOR UNITS

DescriptionVAM

Applicable capacityModel

Decoration panel

Multi-function casementHigh-efficiency filter elementAir outlet shutter plate (1 set)

–P32, P40, P50, P63, P80, P100, P125P32, P40, P50, P63, P80, P100, P125

P80, P100, P125P32, P40, P50, P63, P80, P100, P125

SLP-2AAPLP-6AAPAC-SG03TM-EPAC-SG01KFPAC-SG06SP-E

DescriptionPEFY-VMH

RemarksApplicable capacity

Model

PAC-KE04DM-FPAC-KE86LAFPAC-KE88LAFPAC-KE89LAFPAC-KE85LAFPAC-KE63TB-FPAC-KE80TB-FPAC-KE140TB-FPAC-KE250TB-F

Drain lift-up mechanism

Long life filter

Filter box

P40~P250P40, P50, P63P71, P80P100, P125, P140P200, P250P40, P50, P63P71, P80P100, P125, P140P200, P250

DescriptionApplicable capacity

PLFY-VLMD-BModel

Decoration panel

OA duct flange

CMP-40VLW-BCMP-63VLW-BCMP-100VLW-BCMP-125VLW-BPAC-KH11OF

P20, P25, P32, P40P50, P63

P80, P100P125

P20, P25, P32, P40, P50, P63, P80, P100

Description Applicable capacityModel

Decoration panel PMP-40BM P20, P25, P32, P40

Description Applicable capacityModel

High efficiency filter

Drain lift-up mechanism

PAC-SE80KF-EPAC-SE81KF-EPAC-SE82KF-EPAC-SE84DMAPAC-SE85DMAPAC-SH17DM-E

P40P63, P100P125P40P63P100, P125

Necessary when long life filter is used

Description Applicable capacityModel

Long life filter

Filter box

Drain water lift-up kit

PAC-KE88LAFPAC-KE89LAFPAC-KE85LAFPAC-KE80TB-FPAC-KE140TB-FPAC-KE250TB-FPAC-KE04DM-F

P80P140P200, P250P80P140P200/P250P80, P140, P200, P250

Description Applicable capacity RemarksModel

PAC-KD02DM-FAPAC-KD60KDFPAC-KD61KDFPAC-KD63KDFPAC-KD64KDFPAC-KD32EDF-FPAC-KD50EDF-FPAC-KD80EDF-FPAC-KD125EDF-FPAC-KD80RTBPAC-KD81RTBPAC-KD83RTBPAC-KD84RTBPAC-KD85DFPAC-KD86DFPAC-KD88DFPAC-KD89DF

Drain lift-up mechanism

Square shape duct flange

Round shape duct flange

Filter box for rear suction

Canvas duct for bottom suction

P20-P125P20, P25, P32P40, P50P63, P71, P80P100, P125P20, P25, P32P40, P50P63, P71, P80P100, P125P20, P25, P32P40, P50P63, P71, P80P100, P125P20, P25, P32P40, P50P63, P71, P80P100, P125

Necessary when air intake duct or high efficiency filter is used at the rear of the indoor unit

Description Applicable capacity RemarksModel

PAC-KD70TBPAC-KD71TBPAC-KD73TBPAC-KD74TBPAC-KD30AFPAC-KD31AFPAC-KD33AFPAC-KD34AFPAC-KD40AFPAC-KD41AFPAC-KD43AFPAC-KD44AFMCMP-P36DSWHMCMP-P56DSWHMCMP-P90DSWHMCMP-P160DSWH

Filter box for bottom suction

High efficiency filter 65%

High efficiency filter 90%

Maintenance panel with air intake

P20, P25, P32P40, P50P63, P71, P80P100, P125P20, P25, P32P40, P50P63, P71, P80P100, P125P20, P25, P32P40, P50P63, P71, P80P100, P125P20, P25, P32P40, P50P63, P71, P80P100, P125

Nesessary when efficiency filter is used at the bottom of the indoor unit

Page 43: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

Page 83

Optional parts

>>For PUHY series

OPTIONAL PARTS FOR OUTDOOR UNITS Maintaining equipments

OPTIONAL PARTS FOR CONTROL

Page 84

Optional parts

Description RemarksModel

Description Model Total capacity of indoor unit

Branch pipe (Joint)

Branch pipe (Header)

200 or below201-400401-650The 1st branch of P450~P650651 or aboveThe 1st branch of P700~P1250For 4 branchesFor 8 branchesFor 10 branches

High static pressure motor

Twinning kit

PAC-KBU06MT-FCMY-Y100VBKCMY-Y200VBKCMY-Y300VBK

~ 60PaFor PUHY-P500~P700TSHMFor PUHY-P750~P900TSHMFor PUHY-P950~P1250TSHM

Description Model

PAC-SE41TSPAC-SE55RAPAC-YG10HAPAC-SC50KUAPAC-SA88HAPAC-SA89TAPAC-SC36NAPAC-SC37SAPAC-SF46EPLMAP02PAC-YG41CDAPAC-YG11CDAPAC-YG21CDAPAC-YG31CDA

Remote Sensor for A/J/K/M-Net ControlRemote ON/OFF adaptor for Indoor UnitCable for G-50 I/OPower supply unit for G-50 / GB-50Remote Display Adaptor for Indoor UnitTimer Adaptor forOutput signal connectorInput signal connectorTransmission boosterAir conditioner interfacePLC software for demand inputElectric amount count softwarePLC software for general ezipmentBAC netTM interface

Note : Indoor unit capacities The capacity of an indoor unit is the same as the number used for its type identification.

CMY-Y102S-GCMY-Y102L-G1

CMY-Y202-G1

CMY-Y302-G1

CMY-Y104-GCMY-Y108-GCMY-Y1010-G

>>For PUHY series

>>For PUMY-P100 , P125 , P140 VHM

Description Model

Branch Pipe (2 Branch)HeaderHeaderDrain SocketCentralized Drain PanPort Connector (ø9.52 → ø12.7 )Port Connector (ø15.88 → ø19.05)Air Protect Guide ( 2 pcs required )

CMY-Y62-G-ECMY-Y64-G-ECMY-Y68-G-EPAC-SG61DS-EPAC-SG64DP-EPAC-SG73RJ-EPAC-SG75RJ-EPAC-SH63AG-E

Maintenance cycle [Note that maintenance cycle does not mean guarantee period.]Following tables are applicable when using equipments under the conditions below.

1 Normal use without frequent START/STOPs (The number of START/STOPs is assumed to be less than 6

times per hour in normal use.)

2 Operating hours are assumed to be 10 hours per day/2500 hours per year.

Under the following conditions, equipments may not be able to used at all, or maintenance cycle and

replacement cycle of equipments may need to be shortened.

1 When using equipments in high temperature and humidity or in rapid changes in temperature and humidity

2 When using equipments in a big electric change of power voltage, frequency, and waveform distortion (They

cannot be used outside of acceptable range.)

3 When using equipments installed in a place where there is a lot of vibration

4 When using equipments in the air with hazardous gas or oil mist as well as dust, salinity, and sulfur dioxide/

hydrogen sulfide

5 When using equipments with frequent START/STOP or long operating hours

Table 1. Maintenance cycle

Table 2. Replacement cycle

Major components Checking cycle Maintenance cycle

Compressor 20,000 hoursMotor

20,000 hours (Fan, Louver, drain pump)

Bearing1 year

15,000 hours

Electric board 25,000 hoursHeat exchanger 5 years

Major components Checking cycle Maintenance cycle

Expansion valve 20,000 hoursValve

20,000 hours (solenoid valve, four-way valve)

1 yearSensor

5 years(thermistor, presser sensor)

Drain pan 8 years

Sudden unpredictable accident may occur even if check-up is performed.

Replacement cycle of consumable components[Note that replacement cycle does not mean guarantee period.]

Major components Checking cycle Replacement cycle

Long-life filter 5 yearsHigh-performance filter 1 year

Fan belt1 year

5,000 hoursSmoothing capacitor 10 years

Fuse 10 yearsCrank case heater 8 years

Note1 This table shows major components. Refer to the maintenance contract for details.Note2 This maintenance cycle shows a period in which products are expected to require no maintenance. Use this cycle for planning maintenance (budgeting the

maintenance expense etc.) Checking/ Maintenance cycle may be shorter than the one on this table depending on the contents of maintenance check contract.

Note1 This table shows major components. Refer to the maintenance contract for details.

Note2 This replacement cycle shows a period in which products are expected to require no replacements. Use this cycle for planning maintenance (budgeting expenses for replacing equipments etc.)

Page 44: AIR CONDITIONING SYSTEMS - Mitsubishi Ar Condicionadomitsubishiarcondicionado.com/downloads/city-multi-vrf/comercial/... · Air conditioning is an ideal way of controlling the temperature,

AIR CONDITIONING SYSTEMS

HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

http://Global.MitsubishiElectric.com

MEE05K440

MITSUBISHI ELECTRIC MULTIPLE SPLIT TYPE AIR CONDITIONERS Series

The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series 9000 of the International Standard Organization (ISO) based on a review of Quality management for the production of refrigeration and air conditioning equipment.

ISO Authorization SystemThe ISO 9000 series is a plant authorization system relating to quality management as stipulated by the ISO. ISO 9001 certifies quality management based on the "design, development, production, installation and auxiliary services" for products built at an authorized plant.

The Air Conditioning & Refrigeration Systems Works acquired environmental management system standard ISO 14001 certification.

The ISO 14000 series is a set of standards applying to environmental protection set by the International Standard Organization (ISO).

New publication effective Oct 2006Specifications subject to change without notice

http://Global.MitsubishiElectric.com/

FM33568 / ISO 9001;2000

Certificate Number EC97J1227