Page 1: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Low Voltage

Elettra SrlVia Lisbona 28A, int. 5

35127 PadovaTel. +39 0498075544Fax +39 0498077695

E-mail [email protected] www.aegelettra.it

Air Circuit BreakersSeries ME10

Page 2: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without
Page 3: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

3Reference guide - October 2014

Indice

Power Circuit Breakers ME10 Pag. 68Technical data Pag. 69

Basic breakers executed in a fixed mounting pattern Pag. 70Isolators or Non Automatic breakers executed in a fixed mounting pattern Pag. 71 Accessories for Breakers & Isolators in fixed pattern Pag. 72

Isolators or Non Automatic Breakers in a Draw-out pattern Pag. 73 Isolators or Non Automatic Breakers in a Draw-out pattern Pag. 74Cassettes for Draw-out pattern Pag. 75

Electronic trip units Pag. 76

Accessories and spare parts Pag. 79

Page 4: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

4 Reference guide - October 2014

Series ME10

The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without neglecting its AEG’s heritage of more than 50 years in building Air Circuit Breakers.

The ME10 range of Power Circuit breakers encompasses a line of 3 and 4 pole Air Circuit Breakers with Nominal Currents ranging from 400 to 6400Amp in four basic envelopes. (see diagram).

One of the most important user parameters is not the nominal rating of an ‘Air Circuit Breaker’ in free air but its current Rating within a panel or enclosure.Breakers ‘enclosed ratings’ are determined by the heat dissipation produced by the device and its ability to carry current at the temperature within the enclosure.

ME10 Power Circuit breakers have been designed with low Power dissipation values and allow relatively high currents at high ambient temperatures.

The serie ME10 has been designed to offer an uncompromising combination of a fast interruption at high fault levels attaining values of 40 Milliseconds or less whilst maintaining selectivity. The electronic trip unit, already in its basic model, is equipped with protection channels for overload and short-circuit with delay adjustment intervention, in a wide range of bands of timeOptionally a full network measurement device can be installed on the device. Relays can be included to trip the breaker on Voltage Unbalance, Current Unbalance, Power reversal

etc. The device can be equipped with Communication for use with the Modbus or Profibus protocol whilst events as Overload, Short-circuit and Groundfaults can be tracked, the RELT function to protect Service Personnel against the hazards of Short Circuits.

Independent of the number of poles, rated current or interruption rating, each of the two patterns has a common height, depth and cut-out dimension.This strongly simplifying the design of panels and equipment in which these devices are used. The basic breaker width has been optimized to allow for space to connect in- and outgoing bus bars and cables. Both Fixed and Draw-out Power Circuit Breaker types are supplied with rear

connections suitable for Rear Access Horizontal busbar connection.

A large range of internal accessories as Electrical Operators, up to four Shunt Releases, Closing Coils or Undervoltage releases, Interlock Coils, Auxiliary and Alarm contacts, Carriage switches, Coil indication contacts and Breaker status switches are available.

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

Serie T1600AIcu=Ics

R K S N

Serie 12000AIcu=Ics

Serie 36400AIcu=Ics

Serie 24000AIcu=Ics

kA

M G

Page 5: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

5Reference guide - October 2014

Breakers - EN60947-2 standard AT04... AT16

3, 4100012690

TB

Yes400, 630, 800,1000, 1250,

1600

20000125006000

Number of poles Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Rated operational voltage Ue AC (V) DC (V) Envelope Category of use Suitable for use as an isolator Rated current In at 50°C (A)

Ultimate breaking capacity Icu 230/240V - 440V AC (kA) 500V AC (kA) 690V AC (kA) 1000V AC (kA) Service breaking capacity Ics 230/240V - 440V AC (kA) 500V AC (kA) 690V AC (kA) 1000V AC (kA) Short-circuit withstand Icw Icw 1 sec. (kA) Icw 3 sec. (kA) Short-circuit Making current Icm 220-500V AC (kA peak) 690V AC (kA peak) Ultimate breaker capacity Icu 250V DC 1P (kA) = Service breaking capacity Ics 500V DC 2P (kA) DC L/R=15ms (nr. of poles in series) 750V DC 3P (kA) (for DC a special RCD is required) 1000V DC 3P (kA) Single phase breaking capacity IIT 220-500V AC (kA) 690V AC (kA) Mechanical endurance 1 with maintenance without maintenance Electrical endurance at 440V AC without maintenance Electrical endurance at 690V AC without maintenance Electrical endurance at 1000V AC without maintenance

(1) For endurance in DC IEC 60947 (2) 2000A type: 8000 operations (3) 2000A type: 6000 operations

R

505042

505042

423010588,2

K

655042

505042

503010588,2

3024

S 3, 4100012690

1

505040

505040

504210584

200001250010000 2

8000 3

500

AG04... AG20N

3, 4100012690

1B

Yes400, 630, 800,1000, 1250,1600, 2000

656550

656550

6550143105

200001250010000 2

8000 3

500

M 3, 4125012

10001000

1

100100855010010085508550220187655035305050

10000500050005000500

AG25

BYes

2500

N 3, 4100012690

2

656550

656550

6550143105

200001000060005000

M 3, 4125012

10001000

2

100100855010010085508550220187503520305050

10000500050005000500

N 3, 4100012690

2

656550

656550

6550143105

200001000050002500

AG32, AG40M 3,4

125012

10001000

2B

Yes3200, 4000

100100855010010085508550220187655035305050

10000500050002500500

G 3, 4100012690

3

100100100

100100100

10085220220

10000500025001500

AG50M

3, 4100012690

3B

Yes5000

100100100

100100100

10085220220

10000500015001000

AG64M

3, 4100012690

3B

Yes6400

100100100

100100100

10085220220

10000500015001000

Isolator - EN60947-3 standard A704... A716

R 3, 4100012690

T400, 630, 800,1000, 1250,

1600423075

20000125006000

Number of poles Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Rated operational voltage Ue AC (V) DC (V) Envelope Rated current In In at 50°C (A)

Short-circuit withstand Icw Icw 1 sec. (kA) Icw 3 sec. (kA) Short-circuit Making current Icm (kA peak) Mechanical endurance 1 with maintenance without maintenance Electrical endurance at 440V AC without maintenance Electrical endurance at 690V AC without maintenance Electrical endurance at 1000V AC without maintenance

(1) For endurance in DC IEC 60947 (2) 2000A type: 8000 operations (3) 2000A type: 6000 operations

S 3, 4100012690

1

5042

88,2

200001250010000 2

8000 3

AJ(W)04... AJ(W)20N

3, 4100012690

1400, 630, 800,1000, 1250,1600, 2000

6550143

200001250010000 2

8000 3

M 3, 4125012

10001000

2

8550187

10000500050005000500

AJ(W)25

2500

N 3, 4100012690

2

6550105

200001000060005000

M 3, 4125012

10001000

2

8550187

10000500050005000500

N 3, 4100012690

2

6550105

200001000050002500

AJ(W)32, AJ(W)40

3200, 4000

M 3, 4125012

10001000

2

8550187

10000500050002500500

AJ50L

3, 4100012

10007503

5000

10085220

10000500015001000300

AJ64L

3, 41000126907503

6400

10085220

10000500015001000300

Page 6: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

6 Reference guide - October 2014

Basic breakers executed in a fixed mounting pattern In(A)

400630800100012501600

4006308001000125016002000

400630800100012501600

4006308001000125016002000250032004000

40063080010001250160020002500

3200400050006400

Envelope

ME10-TME10-TME10-TME10-TME10-TME10-T

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1

ME10-TME10-TME10-TME10-TME10-TME10-T

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-2ME10-2ME10-2

ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2

ME10-3ME10-3ME10-3ME10-3

Cat. numberAT04R4AT07R4AT08R4AT10R4AT13R4AT16R4

AG04S4AG07S4AG08S4AG10S4AG13S4AG16S4AG20S4

AT04K4AT07K4AT08K4AT10K4AT13K4AT16K4

AG04N4AG07N4AG08N4AG10N4AG13N4AG16N4AG20N4AG25N4AG32N4AG40N4

AG04M4AG07M4AG08M4AG10M4AG13M4AG16M4AG20M4AG25M4

AG32G4AG40G4AG50M4AG64M4

3 PolesRef. number

445230445231445232445233445234445235

445292445296445300445304445308445312445316

445236445237445238445239445240445241

445322445326445330445334445338445342445346445352445356445360

445367445371445375445379445383445387445391445395

445402445406445410445414

Cat. numberAT04R6AT07R6AT08R6AT10R6AT13R6AT16R6

AG04S6AG07S6AG08S6AG10S6AG13S6AG16S6AG20S6

AT04K6AT07K6AT08K6AT10K6AT13K6AT16K6

AG04N6AG07N6AG08N6AG10N6AG13N6AG16N6AG20N6AG25N6AG32N6AG40N6

AG04M6AG07M6AG08M6AG10M6AG13M6AG16M6AG20M6AG25M6

AG32G6AG40G6AG50M6AG64M6

4 PolesRef. number

445245445246445247445248445249445250

445293445297445301445305445309445313445317

445251445252445253445254445255445256

445323445327445331445335445339445343445347445353445357445361

445368445372445376445380445384445388445392445396

445403445407445411445415

R typeIcu = Ics = 50kAIcw = 42kA

S typeIcu = Ics = IcwIcw = 50kA

K typeIcu = Ics = 65kAIcw = 50kA

N typeIcu = Ics = IcwIcw = 65kA

M typeIcu = Ics = 100kAIcw = 85kA

G-M typeIcu = Ics = IcwIcw = 100kA

With Horizontal Rear Connection, Auxiliary contact block equipped with 3NO and 3NC contactsBasic Breaker must be equipped with a Trip UnitFor 1000V applications phase seperators are required

Page 7: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

7Reference guide - October 2014

Isolators or Non Automatic breakers executed in a fixed mounting pattern In(A)

400630800100012501600

4006308001000125016002000

4006308001000125016002000250032004000

4006308001000125016002000250032004000

3200400050006400

Envelope

ME10-TME10-TME10-TME10-TME10-TME10-T

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-2ME10-2ME10-2

ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2 ME10-2ME10-2ME10-2ME10-2

ME10-3ME10-3ME10-3ME10-3

Cat. numberA704R4A707R4A708R4A710R4A713R4A716R4

AJ04S4AJ07S4AJ08S4AJ10S4AJ13S4AJ16S4AJ20S4

AW04N4AW07N4AW08N4AW10N4AW13N4AW16N4AW20N4AJ25N4AJ32N4AJ40N4

AW04M4AW07M4AW08M4AW10M4AW13M4AW16M4AW20M4AW25M4AW32M4AW40M4

AJ32L4AJ40L4AJ50L4AJ64L4

3 PolesRef. number

445275445276445277445278445279445280

445422445426445430445434445438445442445446

445452445456445460445464445468445472445476445482445486445490

445528445532445536445540445544445548445552445497445501445505

445512445516445520445524

Cat. numberA704R6A707R6A708R6A710R6A713R6A716R6

AJ04S6AJ07S6AJ08S6AJ10S6AJ13S6AJ16S6AJ20S6

AW04N6AW07N6AW08N6AW10N6AW13N6AW16N6AW20N6AJ25N6AJ32N6AJ40N6

AW04M6AW07M6AW08M6AW10M6AW13M6AW16M6AW20M6 AW25M6AW32M6AW40M6

AJ32L6AJ40L6AJ50L6AJ64L6

4 PolesRef. number

445281445282445283445284445285445286

445423445427445431445435445439445443445447

445453445457445461445465445469445473445477445483445487445491

445529445533445537445541445545445549445553445498445502445506

445513445517445521445525

R typeIcw = 42kA

S typeIcw = 42kA

N typeIcw = 65kA

M typeIcw = 85kA

L typeIcw = 100kA

With Horizontal Rear Connection, Auxiliary contact block equipped with 3NO and 3NC contactsFor 1000V applications phase seperators are required

Page 8: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

8 Reference guide - October 2014

Accessories for Breakers & Isolators in Fixed pattern In(A)

400-1600

400-16002000

400-32004000

3200-6400

400-1600

400-16002000

400-32004000

Envelope

ME10-T

ME10-1ME10-1

ME10-2ME10-2

ME10-3

ME10-T

ME10-1ME10-1

ME10-2ME10-2

ME10-1/2

Cat. number

GT16H4RVI

G16H4RVIG20H4RVIN

G32M4RVIG40M4RVI

G64L4RVI

GT16H4FFI

G16H4FFIG20H4FFI

G32M4FFIG40M4FFI

GFMTG

3 PolesRef. number

444626

408058408059

408070408072

408073

444625

408060408061

408066408067

408085

Cat. number

GT16H6RVI

G16H6RVIG20H6RVIN

G32M6RVIG40M6RVI

G64L6RVI

GT16H6FFI

G16H6FFIG20H6FFI

G32M6FFIG40M6FFI

GFMTG

4 PolesRef. number

444628

408082408083

408071408074

408075

444627

408062408063

408068408069

408085

Vertical Rear Connection

Front AccessConnections

Wall Mounting Brackets

Page 9: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

9Reference guide - October 2014

Basic breakers in a Draw-out pattern In(A)

400630800100012501600

4006308001000125016002000

400630800100012501600

4006308001000125016002000250032004000

40063080010001250160020002500

3200400050006400

Envelope

ME10-TME10-TME10-TME10-TME10-TME10-T

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1

ME10-TME10-TME10-TME10-TME10-TME10-T

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-2ME10-2ME10-2

ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2

ME10-3ME10-3ME10-3ME10-3

Cat. numberAT04R1AT07R1AT08R1AT10R1AT13R1AT16R1

AG04S1AG07S1AG08S1AG10S1AG13S1AG16S1AG20S1

AT04K1AT07K1AT08K1AT10K1AT13K1AT16K1

AG04N1AG07N1AG08N1AG10N1AG13N1AG16N1AG20N1AG25N1AG32N1AG40N1

AG04M1AG07M1AG08M1AG10M1AG13M1AG16M1AG20M1AG25M1

AG32G1AG40G1AG50M1AG64M1

3 PolesRef. number

445200445201445202445203445204445205

445290445294445298445302445306445310445314

445206445207445208445209445210445211

445320445324445328445332445336445340445344445350445354445358

445365445369445373445377445381445385445389445393

445400445404445408445412

Cat. numberAT04R3AT07R3AT08R3AT10R3AT13R3AT16R3

AG04S3AG07S3AG08S3AG10S3AG13S3AG16S3AG20S3

AT04K3AT07K3AT08K3AT10K3AT13K3AT16K3

AG04N3AG07N3AG08N3AG10N3AG13N3AG16N3AG20N3AG25N3AG32N3AG40N3

AG04M3AG07M3AG08M3AG10M3AG13M3AG16M3AG20M3AG25M3

AG32G3AG40G3AG50M3AG64M3

4 PolesRef. number

445215445216445217445218445219445220

445291445295445299445303445307445311445315

445221445222445223445224445225445226

445321445325445329445333445337445341445345445351445355445359

445366445370445374445378445382445386445390445394

445401445405445409445413

R typeIcu = Ics = 50kAIcw = 50kA

S typeIcu = Ics = IcwIcw = 50kA

K typeIcu = Ics = 65kAIcw = 50kA

N typeIcu = Ics = IcwIcw = 65kA

M typeIcu = Ics = 100kAIcw = 85kA

G-M typeIcu = Ics = IcwIcw = 100kA

With Horizontal Rear Connection, Auxiliary contact block equipped with 3NO and 3NC contactsBasic Breaker must be equipped with a Trip UnitA cassette is neededFor 1000V applications phase seperators are required

Page 10: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

10 Reference guide - October 2014

Isolators or Non Automatic Breakers in a Draw-out pattern In(A)

400630800100012501600

4006308001000125016002000

4006308001000125016002000250032004000

4006308001000125016002000250032004000

3200400050006400

Envelope

ME10-TME10-TME10-TME10-TME10-TME10-T

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1

ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-1ME10-2ME10-2ME10-2

ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2ME10-2

ME10-3ME10-3ME10-3ME10-3

Cat. numberA704R1A707R1A708R1A710R1A713R1A716R1

AJ04S1AJ07S1AJ08S1AJ10S1AJ13S1AJ16S1AJ20S1

AW04N1AW07N1AW08N1AW10N1AW13N1AW16N1AW20N1AJ25N1AJ32N1AJ40N1

AW04M1AW07M1AW08M1AW10M1AW13M1AW16M1AW20M1 AW25M1AW32M1AW40M1

AJ32L1AJ40L1AJ50L1AJ64L1

3 PolesRef. number

445260445261445262445263445264445265

445420445424445428445432445436445440445444

445450445454445458445462445466445470445474445480445484445488

445526445530445534445538445542445546445550 445495445499445503

445510445514445518445522

Cat. numberA704R3A707R3A708R3A710R3A713R3A716R3

AJ04S3AJ07S3AJ08S3AJ10S3AJ13S3AJ16S3AJ20S3

AW04N3AW07N3AW08N3AW10N3AW13N3AW16N3AW20N3AJ25N3AJ32N3AJ40N3

AW04M3AW07M3AW08M3AW10M3AW13M3AW16M3AW20M3 AW25M3AW32M3AW40M3

AJ32L3AJ40L3AJ50L3AJ64L3

4 PolesRef. number

445266445267445268445269445270445271

445421445425445429445433445437445441445445

445451445455445459445463445467445471445475445481445485445489

445527445531445535445539445543445547445551 445496445500445504

445511445515445519445523

R typeIcw = 42kA

S typeIcw = 50kA

N typeIcw = 65kA

M typeIcw = 85kA

L typeIcw = 100kA

With Horizontal Rear Connection, Auxiliary contact block equipped with 3NO and 3NC contactsA cassette is neededFor 1000V applications phase seperators are required

Page 11: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

11Reference guide - October 2014

Cassettes for Draw-out pattern (for use with Breakers & Isolators)In(A)

400-1600

400-16002000

400-2000250032004000 1

3200-6400 2

400-1600

400-16002000

400-2000250032004000

Envelope

ME10-T

ME10-1ME10-1

ME10-2ME10-2ME10-2ME10-2

ME10-3

ME10-T

ME10-1ME10-1

ME10-2ME10-2ME10-2ME10-2

Cat. number

AT16K2UM

AG16S2UMAG20H2UM

AG20M2UMAG25M2UMAG32M2UMAG40M2UM

AG64L2UM

AT16K2FM

AG16S2FMAG20H2FM

AG20M2FMAG25M2FMAG32M2FMAG40M2FM

3 PolesRef. number

445601

445611445615

445619445623445627445631

445634

445600

445610445614

445618445622445626445630

Cat. Number

AT16K5UM

AG16S5UMAG20H5UM

AG20M5UMAG25M5UMAG32M5UMAG40M5UM

AG64L5UM

AT16K5FM

AG16S5FMAG20H5FM

AG20M5FMAG25M5FMAG32M5FMAG40M5FM

4 PolesRef. number

445604

445613445617

445621445625445629445633

445635

445603

445612445616

445620445624445628445632

Type

R, K

SS, N

N, MN, MN, MN, M

G-M

R, K

SS, N

N, MN, MN, MN, M

1) Cassettes for envelope 2 are limited to a current of 3200A when connected in horizontal mode2) The Cassette for envelope 3 is limited to a current of 5000A when connected in horizontal mode

Vertical Rear Connection (can be rotated and used for Vertical or Horizontal connections)

Front Access Connections

Page 12: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

12 Reference guide - October 2014

Electronic Trip Units

LT protection

ST protection

MeasurementDiagnostic

GF protection

GT-Rating Plug

LT protection

ST protection

Canale I

MeasurementDiagnostic

GF protection

I extended protectionModbus

GT-Rating Plug

LT protection

ST protection

I protection

RELTMeasurament 2

Diagnostic

Input/Output

GF protection

I extended protectionZSIModbus

GT-Rating Plug

Description

Overload current setting Ir=0,2… 1InClass C 0,5... 40Neutral protection (50%-63%-100%)Thermal memoryShort-circuit setting 1,5… 12IrTime delay adjustable 30... 940msI2t protection time bands availableCurrent L1, L2, L3Trip reason indicationTrip counterEvent loggerWatchdog

Ground fault setting 0,1… 1InTime delay adjustable 30... 840msI2t protection time bands available

(required for all types)

Overload current setting Ir=0,2… 1InClass C 0,5... 40Neutral protection (50%-63%-100%)Thermal memoryShort-circuit setting 1,5… 12IrTime delay adjustable 30... 940msI2t protection time bands availableIstantaneous short circuit setting 2… 15IeSelective executionFixed istantaneous or HSOC protection

Current L1, L2, L3Trip reason indicationTrip counterEvent loggerWatchdog

Ground fault setting 0,1… 1InTime delay adjustable 30... 840msI2t protection time bands availableIstantaneous short circuit setting 2…30IeModbus communication

(required for all types)

Sovraccarico Ir=0,2…1InClass C 0,5... 40Neutral protection (50%-63%-100%)Thermal memoryShort-circuit setting 1,5… 12IrTime delay adjustable 30... 940msI2t protection time bands availableIstantaneous short circuit setting 2… 15IeSelective executionFixed istantaneous or HSOC protection

Istantaneous 40msCurrent L1, L2, L3Voltage L1, L2, L3Energy (kWh)Real, apparent, reactive, total powerPeak and demand powerFrequencyTrip reason indicationTrip counterEvent loggerWatchdog2 electronic inputs2 general relay outputs

Ground fault setting 0,1… 1InTime delay adjustable 30... 840msI2t protection time bands availableIstantaneous short circuit setting 2… 30IeZone selective interlockModbus communication

(required for all types)

Cataloguenumber

GTG00K1-SF 1

GTG00K2-SR

GTPUNI

GTG00K9-SF 1

GTG00K4-2SR

GTPUNI

GTG00K9-4SF 1

GTG00K4T6SR

GTPUNI

Referencenumber

408800

408802

408860

408803

408809

408860

408813

408819

408860

GT-E

GT-S

GT-N

+

+

+

1) Only factory mounted2) For the measurement package is obligatory an auxiliary power conditioner

Page 13: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

13Reference guide - October 2014

Electronic Trip Units

LT protection

ST protection

I protection

RELT

Measurement 1

Diagnostic

Input/Output

Protezioni con relè

GF protection

ZSI

Modbus

Canale I extended

Profibus

I extended protectionProfibus

GT-Rating Plug

GT Trip Unitwith no protection

Description

Overload current setting Ir=0,2… 1InClass C 0,5... 40Fuse typetime bands availableInverse time current curveNeutral protection (50%-63%-100%)Thermal memory

Short-circuit setting 1,5… 12IrPossibility to SwitchTime delay adjustable 30... 940msI2t protection time bands available

Istantaneous short circuit setting 2… 15IeSelective executionFixed istantaneous or HSOC protection

Istantaneous 40ms

Current L1, L2, L3Voltage L1, L2, L3Energy (kWh)Real, apparent, reactive, total powerPeak and demand powerFrequency

Trip reason indicationTrip info (Magnitude/Phase)Waveform captureTrip counterRelay basedon current levelGood and Bad health indicatorEvent loggerWatchdog

2 electronic inputs2 general relay outputs

Voltage unbalanceUndervoltageOvervoltageCurrent unbalancePower reversal

Available GF-sum or GF-ct (ground return)Ground fault setting 0,1… 1InTime delay adjustable 30... 840msI2t protection time bands available

Zone selective interlock

Modbus communication

Istantaneous short circuit setting 2… 30Ie

Profibus communication (to replace the modbus)

Istantaneous short circuit setting 2… 30IeProfibus communication (to replace the modbus)

(required for all types)

(for Non-automatic types)

Cataloguenumber

GTG00N5T8SR

GTG00N7T8SR

GTG00N5T9SR

GTG00N7T9SR

GTPUNI

G3G00KA-SR

Referencenumber

408849

408851

408853

408855

408860

408796

GT-H

+

+

+

1) For the measurement package is obligatory an auxiliary power conditioner

Page 14: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

14 Reference guide - October 2014

Accessories for Trip UnitDescriziption

Conditioning Power Supply 1 Phase 220-230VConditioning Power Supply 1 Phase 380-400VConditioning Power Supply 1 Phase 240-250 / 277-290 / 415VPower supply - Input 100-240V AC or 100-353V DC - Output 24V DC 0,6A

Trip Unit, sealable transparent front cover

Trip Unit Battery Tester snd Set up unit

Cataloguenumber

GMPU1GMPU2GMPU3GAPU

GTUS

GTUTK20

Referencenumber

408790408791408792408789

408046

407999

1) Obligatory when a fully functioning measurement unit is required

Power Supply 1

Sealable transparent front cover

Batter Tester and Set up unit

Sensors for Trip Units

400A630A800A1000A1250A1600A2000A2500A3200A4000A5000A6400A

400A630A800A1000A1250A1600A2000A2500A3200A4000A5000A6400A

Cat. number

G32LNRCG40LNRCG50LNRCG64LNRC

G32LNCTG40LNCTG50LNCTG64LNCT

Ref. number

408000408001408002408003408004408005408006

408300408301408302408303408304408305408306

Cat. number

G04HNRCG07HNRCG08HNRCG10HNRCG13HNRCG16HNRCG20HNRC

G04HNCTG07HNCTG08HNCTG10HNCTG13HNCTG16HNCTG20HNCT

Ref. number

408186408187408188408189

408331408332408333408334

Cat. number

G04HNRCG07HNRCG08HNRCG10HNRCG13HNRCG16HNRCG20HNRCG25MNRCG32LNRCG40LNRC

G04HNCTG07HNCTG08HNCTG10HNCTG13HNCTG16HNCTG20HNCTG25MNCTG32LNCTG40LNCT

Ref. number

408000408001408002408003408004408005408006408162408186408187

408300408301408302408303408304408305408306408322408331408332

For ME10-T and ME10-1 For ME10-2 For ME10-3

Rogowski Coils 1

Earth leg Current Transformers 2

1) For use with Ground fault Residual (sum) protection2) For use with Ground fault protection, Source Ground Return method

Page 15: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

15Reference guide - October 2014

Closing CoilsRated voltage

24V DC48V AC-DC60V DC110-130V AC-DC220-240V AC-DC277V AC; 250V DC380- 415V AC440V AC

Cat. numberGCCC024DRGCCC048RGCCC060DRGCCC120RGCCC240RGCCC277RGCCC400ARGCCC440AR

Ref. number407835407837407839407841407843407850407851407854

1) Designed to be accessed through the Trip Unit communication option (Modbus or Profibus)

Cat. numberGCCN024DRGCCN048RGCCN060DRGCCN120RGCCN240RGCCN277RGCCN400ARGCCN440AR

Ref. number407860407862407864407866407868407871407876407879

Closing Coil Command Closing Coil 1

Undervoltage Releases and Shunt TripsRated voltage

24V DC48V AC-DC60V DC110-130V AC-DC220-240V AC-DC277V AC; 250V DC380- 415V AC440V AC

Cat. numberGSTR024DRGSTR048RGSTR060DRGSTR120RGSTR240RGSTR277RGSTR400ARGSTR440AR

Ref. number407771407773407775407777407779407781407783407785

Cat. numberGUVT024DRGUVT048RGUVT060DRGUVT120RGUVT240RGUVT277RGUVT400ARGUVT440AR

Ref. number407796407798407800407802407804407806407808407810

Undervoltage Shunt

Motor operatorRated voltage

24-30V DC48V DC60V DC110-130V DC250V DC

48V AC110-130V AC220-240V AC380-415V AC440V AC

Cat. numberGM02024DRGM02048DRGM02060DRGM02110DRGM02250DR

GM02048ARGM02120ARGM02240ARGM02400ARGM02440AR

Ref. number444641444642444643444644444646

444647444648444649444650444651

Cat. numberGMT0024DRGMT0048DRGMT0060DRGMT0110DRGMT0250DR

GMT0048ARGMT0120ARGMT0240ARGMT0400ARGMT0440AR

Ref. number407726407728407730407732407734

407736407738407740407742407744

Cat. numberGM01024DRGM01048DRGM01060DRGM01110DRGM01250DR

GM01048ARGM01120ARGM01240ARGM01400ARGM01440AR

Ref. number407701407703407705407707407709

407711407713407715407717407719

For ME10-T For ME10-1 For ME10-2 and ME10-3

Positive security fail safe electrical interblock 1 (as alternative to mechanical interlock)Rated voltage

110-130V AC-DC220-240V AC-DC

Cat. numberGNTK120GNTK240

Ref. number407753407754

Description Double interlock coil system with positive security fail safe controlDouble interlock coil system with positive security fail safe control

Per ME10-1, ME10-2 e ME10-3

1) Only factory mounted

Time delay module fot undervoltage release Rated voltage

60V DC110-130V DC220-240V DC250V DC

48V AC110-130V AC220-240V AC250-277V AC380- 415V AC440V AC

Cat. number

GTDM060DGTDM120DGTDM240DGTDM250D

GTDM048AGTDM120AGTDM240AGTDM277AGTDM400AGTDM440A

Ref. number

407817407819407821407823

407816407818407820407822407824407825

Description

Adjustable time delay 0... 3 sec.

Page 16: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

16 Reference guide - October 2014

Auxiliary ContactsDescription

3NO+3NC power rated 1

4NO+4NC power rated 8NO+8NC power rated 3NO+3NC power rated + 2NO+2NC signal rated 4NO+4NC power rated + 4NO+4NC signal rated

Cat. numberGAUX3R

GAUX6RGAUX5RGAUX8R

Ref. number407880

407882407881407883

1) Delivered as standard option in all ME10 breakers and isolators

Cat. numberGTAS3RGTAS4R

Ref. number444658444659

For ME10-T For ME10-1, ME10-2 and ME10-3

Bell Alarm ContactDescription

The contact indicates that the Breaker has tripped due to a fault detected by the Trip Unit

Cat. numberGBAT1RGBATS1R

Ref. number407889

Cat. numberGTBAT1RGTBATS1R

Ref. number444672444673

For ME10-T For ME10-1, ME10-2 and ME10-3

Indication ContactsDescription

Release indication contact 1

Ready to close 1NOReady to close 1NC

Ready to close 1NO 2

Ready to close 1NC 2

Cat. number

GRTC2GRTC5

GRTC3GRTC6

Ref. number

407899407912

407894407913

Cat. numberGCSP1R

GRTC1GRTC4

Ref. number407915

407897407911

Power rated Signal rated

1) To indicate is a Shunt or Undervoltage release initiation has resulted OFF or TRIP operation2) Direct connected to the Trip Unit

Position Indication Contacts CassetteDescription

1CO2CO2CO: 1NO+1NC power rated 1NO+1NC signal rated

Cat. numberGCPS1RGCPS2R

Ref. number407924407925

Cat. numberGTCPS1RGTCPS2RGTCPSAR

Ref. number444791444793444795

For ME10-T For ME10-1, ME10-2 and ME10-3

Remote Reset Coil 1 Rated voltage

24V DC110V AC-DC230V AC-DC

Cat. numberGRRC024DGRRC110GRRC230

Ref. number407760407762407764

Description Manual remote Reset OFF the breaker after a tripManual remote Reset OFF the breaker after a tripManual remote Reset OFF the breaker after a trip

For ME10-1, ME10-2 and ME10-3

1) Only factory mounted

Page 17: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

17Reference guide - October 2014

Pre-assembled interlocks for ME10-T 1

Type

A

B

C

D

Cat. numberGTI2WAD

for each breaker

GTI3WB

for each breaker

GTI3WC

for each breaker

GTI2WAD

for breaker 1 and 3

GTI3WDT

for breaker 2

Ref. number444676

444678

444680

444676

444682

1) Interlock is not possible between ME10-T and ME10-1/2/3

Cat. numberGTI2FADfor each breaker

GTI3FBfor each breaker

GTI3FCfor each breaker

GTI2FAD

for breaker 1 and 3

GTI3FDT

for breaker 2

Ref. number444675

444677

444679

444675

444681

Fixed Pattern Draw-outBrk. 1OFFONOFF

OFFONOFFOFF

OFFONOFFOFFONOFFON

OFFONOFFONOFF

Field mountable cables for interlocking of breakers 1

Type

ABCD

CataloguenumberGCB1GCB2GCB3GCB4GCB5GCB6GCB7

Referencenumber407990407991407992407993407994407995407996

1) Breakers 1 and 2 choose 1 cable, breaker 2 choose 2 cables

Lenght

1 m1,5 m2 m2,5 m3 m3,5 m4 m

Brk. 2OFFOFFON

OFFOFFONOFF

OFFOFFOFFONONONOFF

OFFOFFOFFOFFON

Brk. 3

OFFOFFOFFON

OFFOFFONOFFOFFONON

OFFOFFONONOFF

Interlock Scheme

Pre-assembled interlocks for ME10-1, ME10-2 and ME10-3Tipo

A

B

C

D

Cat. numberGI2WADfor each breaker

GI3WBfor each breaker

GI3WCfor each breaker

GI2WADfor breaker

1 and 3

GI3WDTfor breaker 2

Ref. number407901

407903

407905

407901

407907

Cat. numberGI2FADfor each breaker

GI3FBfor each breaker

GI3FCfor each breaker

GI2FADfor breaker 1 and 3

GI3FDTfor breaker 2

Ref. number407900

407902

407904

407900

407906

Fixed pattern Draw-outInt. 1OFFONOFF

OFFONOFFOFF

OFFONOFFOFFONOFFON

OFFONOFFONOFF

Int. 2OFFOFFON

OFFOFFONOFF

OFFOFFOFFONONONOFF

OFFOFFOFFOFFON

Int. 3

OFFOFFOFFON

OFFOFFONOFFOFFONON

OFFOFFONONOFF

Interlock Scheme

Interlock scheme

1 cable for breaker2 cables for breaker2 cables for breakerBreakers 1 and 3: 1 cable for breakerBreakers 2: 2 cables for breaker

Page 18: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

18 Reference guide - October 2014

Locking SystemsDescription

Ronis device allow 1 to 4 locks to be placedCastell device 1Profalux device allow 1 to 4 locks to be placed

Ronis 2 devices for 2 locks are possibleProfalux 2 devices for 2 locks are possible

Ronis 1104 LockCastell FS1 LockProfalux B204Y Lock

Cat. number

GBRONRGBCASRGBPROR

GCRONRGCPROR

GRONGCASGPRO

Ref. number

407968407967407979

407974407981

407985407986407987

1) The locks must be purchased as separate items (see below)

1) The locks must be purchased as separate items (see below)

Wall Mounting Brackets

Cat. numberGFMTG

Ref. number408085

For ME10-1 and ME10-2

OperationDescription

Mis insertion device

Cat. number

GPBD

GCNTW

GREPM

Ref. number

408040

408036

408041

For ME10-1, ME10-2 and ME10-3For ME10-TCat. number

GTBRON

GTBPRO

GTCRONGTCPRO

GRONGCASGPRO

Locking Mechanism mounted on breaker

Locking Mechanism mounted on cassette

Associated Locks

Ref. number

444666

444665

444669444668

407985407986407987

For ME10-1, ME10-2 and ME10-3For ME10-T

Front Facia of Breaker

Operation Indicators

Cassette

Cat. number

GTPBD

GREPM

Ref. number

444667

408041

Page 19: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

19Reference guide - October 2014

Door Flanges and InterlocksDescription

FixedDraw-out

LeftRigh

Cat. number

GDPRFGDPRW

G54DR

GLHDGRHD

Ref. number

408025408026

408038

408039408042

Lifting Breakers

Cat. numberGLTA

Ref. number408049

Phase separators

Cat. numberGJP

Ref. number408057

Description

Set of 9 phase separators for 1000V 1

1) Universal set including 3 pcs for ME10-1 and ME10-2 fixed, 3 pcs for ME10-1 and ME10-2 draw-out and 3 pcs forME10-3

For ME10-1, ME10-2 And ME10-3For ME10-TCat. number

GTPRFGTPRW

G54DR

GTLHDGTRHD

Ref. number

444805444806

408038

444256444257

1) Is a spare, these devices are always supplied with the standard devices

Door Flange 1

Door Escutcheon IP54

Door Interlock

Cat. numberGTJP

Ref. number444255

For ME10-1, ME10-2 and ME10-3For ME10-T

Cat. numberGLTK

Ref. number408045

For ME10-1 and ME10-2 For ME10-3

Breaking Earthing Device for serviceFor Breaker

ME10-1

ME10-2

ME10-3

Cat. numberG16H6EDG20H6ED

G40M6ED

G64M6ED

Ref. number407931407933

407935

407937

Cat. numberG16H4EDG20H4ED

G40M4ED

G64M4ED

Ref. number407930407932

407934

407936

3 Poles 4 PolesDescription

Maximum 1600AMaximum 2000A

Maximum 4000A

Maximum 6400A

CountersDescription

Number of operations

CataloguenumberGMCNR

Referencenumber408033

Page 20: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

20 Reference guide - October 2014

Spare PartsDescription

Kit 1P - R, K typesKit 1P - S, N typesKit 1P - H typeKit 1P - E, N typesKit 1P - H, M typesKit 1P - L type

System with interlock 3P

System with interlock 4P

Front Facia

Set of 4 spare lock, RONIS

In 400-1600AIn 400-1250AIn 1600AIn 2000AIn ≥2000AIn 2500AIn 3200AIn 4000AIn 5000AIn 6400A

Universal Pliers

For Fixed Breaker1 39 pole set

For Fixed Breaker 1 78 pole set

For Draw-out Breaker 1 39 pole set

Cat. num.

G64LCHT

G64LARC

G64L2SSL

G64L5SSL

GRHN

GFA4

GRONCS

G50LCLSG64LCLS

GUNI

GSDFTR1

GSDFT2

GSDWTR

Ref.num.

408102

408104408098

407606

407607

408043

408028

407984

408097408100408103

408047

408052

408029

408054

Cat. num.

G20HCHT

G20NARCG20HARC

G20H2SSL

G20H5SSL

GRHN

GFA4

GRONCS

G13HCLSG16HCLSG20HCLS

GUNI

GSDFTR1

GSDFT2

GSDWTR

Ref.num.

408144

408193

407679

407680

408043

408028

407984

408145408148

408047

408052

408029

408054

Cat. num.

G40MCHT

G40NARCG40MARC

G40M2SSL

G40M5SSL

GRHN

GFA4

GRONCS

G20MCLSG25MCLSG32MCLSG40MCLS

GUNI

GSDFTR1

GSDFT2

GSDWTR

Ref.num.

408131

408172408169

407636

407637

408043

408028

407984

408106408109408117408120

408047

408052

408029

408054

For ME10-1 For ME10-2 For ME10-3For ME10-T

Breaker Arc Chutes

Breaker Fixed Arcing Contacts

Cassettes Shutters

Cassette Racking Handle

Breaker Front Facia Part (the original breaker serial number must be indicated on ordering)

Cassette Cluster Contacts

Breakers and Cassette Spare Auxiliary Disconnect plugs

Cat. num.

GT16KCHT

GT16KARC

GT16N2SSL

GT16N5SSL

GHRN

GTFAL

GT16KCLS

GUNI

GSDFTR1

GSDWTR

Ref.num.

444801

444802

444253

444254

408043

444804

444800

408047

408052

408054

Page 21: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

21Reference guide - October 2014

Note

Page 22: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

Air Circuit Breakers ME10

22 Reference guide - October 2014

Note

Page 23: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without
Page 24: Air Circuit Breakers Series ME10 - elettra.it · Air Circuit Breakers ME10 4 2014 Series ME10 The new serie ME10 has been designed as a Modern ‘Power Circuit Breaker’ without

GR

__M

E10_

14R

1 F

otoc

ompo

sizi

one

Elet

tra S

rl

APPARECCHIATUREELETTRICHEINDUSTRIALI

Via Lisbona, 28A, int. 5 - Z. I. Sud 35127 Padova

Tel. +39 0498075544 - Fax +39 0498077695 E-mail [email protected] www.aegelettra.it

srl