aeration101 r2
TRANSCRIPT
![Page 1: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/1.jpg)
08/31/09 1
AERATION 101
Presented by:Tom FrankelDirector
![Page 2: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/2.jpg)
08/31/09 2
I. HISTORY
![Page 3: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/3.jpg)
08/31/09 3
British Patent No. 22952, Filed 11 October 1913 Subject: Wastewater aeration based on a porous diffuser.
1916 - San Marcos, Texas - l20,000 gpd (approx.) at continuous-flow operation - diffused aeration
![Page 4: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/4.jpg)
08/31/09 4
II. DESIGN & PROCESS OVERVIEW
![Page 5: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/5.jpg)
08/31/09 5
PROCESSES:BNRSBRMBRUASBCONVENTIONALEXTENDED AERATIONFIXED FILM
DESIGN TOOLS:PROCESS SIMULATION(i.e. Biowin)
3d MODELING
MANUFACTURER WEB SITES
![Page 6: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/6.jpg)
08/31/09 6
PROCESS SIMULATION
Model your plant to determine how changes in SRT and Anoxic/aerobic volumes affect your effluent before you make those changes.
![Page 7: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/7.jpg)
08/31/09 7
BLOWER TYPES:MULTISTAGE CENTRIF.SINGLE STAGE CENTR.ROOTS TYPE BLOWERS
CONTROL SYSTEMS: MANUAL
D.O. CONTROL
FEED FORWARD
![Page 8: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/8.jpg)
08/31/09 8
BLOWER CONTROL SYSTEMS
Conventional D.O.control
Feed Forward Off-Gas control
![Page 9: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/9.jpg)
08/31/09 9
INPUT DATA
Aeration system design requires consideration of many factors. BOD, COD, NH3-N, Process Type, Wastewater temperature, Air temperature from blowers and distance from blower room, Altitude at site, Treatment goals, Average to Peak ratios, Industrial influent, target MLSS, Chlorides in the wastewater, Scaling potential of wastewater, Future growth plans for plant and/or growing community, Previous experience with diffusers, elastomers and metals at the plant, Priority for capital cost of energy efficiency (cost of power$$)
To do a proper job of aeration system design, your supplier will need a lot of information from you!
![Page 10: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/10.jpg)
08/31/09 10
III. IN – SITU MONITORING SYSTEMS
![Page 11: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/11.jpg)
08/31/09 11
PRESSURE MONITORING SYSTEM DIFFUSER BACK PRESSURE
![Page 12: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/12.jpg)
08/31/09 12
PILOT GRID INSTALLATION – PERMITS RETRIEVAL AT ANY TIME TO MONITOR DIFFUSER FOULING, SOTEAND BACK PRESSURE WITHOUT DRAINING TANKS
![Page 13: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/13.jpg)
08/31/09 13
IV. OXYGEN TRANSFER TESTING
![Page 14: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/14.jpg)
08/31/09 14
INDEPENDENT NON-STEADY STATE TESTINGSOTE TEST per ASCE STANDARDS IN CLEAN WATER
![Page 15: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/15.jpg)
08/31/09 15
INDEPENDENT STEADY STATE TESTINGIN PROCESS WATER FOR ALPHA DETERMINATION
![Page 16: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/16.jpg)
08/31/09 16
INDEPENDENT NON-STEADY STATE TESTING
![Page 17: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/17.jpg)
08/31/09 17
COMPETITIVE RESULTS
![Page 18: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/18.jpg)
08/31/09 18
NEW VS. OLD MEMBRANE PERFORMANCE
![Page 19: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/19.jpg)
08/31/09 19
V. TYPES OF AERATIONSYSTEMS AND THEIRRELATIVEEFFICIENCIES
![Page 20: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/20.jpg)
08/31/09 20
BUBBLE PATTERNS
Fine Bubble Diffuser Coarse Bubble Diffuser
2% SOTE/FT 1% SOTE/FT
![Page 21: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/21.jpg)
08/31/09 21
TUBE DIFFUSERSTUBE DIFFUSERS
• Consider quantity and location of orifice and seal •Consider method of rubber molding and materials of construction
![Page 22: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/22.jpg)
08/31/09 22
FINE BUBBLE DISC DIFFUSERS – CONNECT TO PIPE WITH SADDLES, GROMMETS OR GLUE-ON BASES
![Page 23: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/23.jpg)
08/31/09 23
COARSE BUBBLE DIFFUSERS
These are often used in digesters, sludge holding tanks, and equalization basins.
![Page 24: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/24.jpg)
08/31/09 24
JET AERATORS
Used only in the smallest SBR’s, due to their high energy consumption. Jets require a pump + a blower, whereas diffusers need only a blower. Useful in Digesters with highly thickened solids.
![Page 25: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/25.jpg)
08/31/09 25
SURFACE AERATORS
Pictured are low and high speed surface aerators Maintenance and freezing are concerns “dead zones” may appear at corners
Useful in Anoxic/Anaerobic zones
![Page 26: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/26.jpg)
08/31/09 26
STATIC AERATORS
Used only in lagoons. Efficiency is similar
to coarse bubble diffusers.
![Page 27: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/27.jpg)
08/31/09 27
FLOATING LATERAL SYSTEMS
Used in earthen lagoons with membrane liners where decanting is not possible, and floor prohibits installation of a fixed grid.
![Page 28: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/28.jpg)
08/31/09 28
RELATIVE EFFICIENCY
AERATOR SAE #O2/HR-HP wire
Membrane 5-9
Ceramic 5-9
Jet 2-3
Static tube 2-3
Coarse bubble 2-3
Low Speed 2.5-3.5
High speed 1.5-2.25
Submerged turbine 2.5-3.5
![Page 29: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/29.jpg)
08/31/09 29
VI. MEMBRANE FOULING
![Page 30: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/30.jpg)
DID YOU KNOW….?DID YOU KNOW….?
08/31/09 30
90% of failures of a membrane diffused aeration system are caused by failed membranes?
![Page 31: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/31.jpg)
08/31/09 31
DID YOU KNOW….?DID YOU KNOW….?
In most cases, the cost of replacing membranes in a tank is higher than the cost of those membranes, when you consider hidden costs?
LABOR & CLEANING OUT OF SERVICE= NO INCOME!!
STEADILY DECLINING PERFORMANCE = ENERGY $$
![Page 32: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/32.jpg)
08/31/09 32
DID YOU KNOW….?DID YOU KNOW….?
EPDM is a very durable material, but it is susceptible to fouling, which may include permanent swelling, shrinking, or crust?
CalciumCarbonate(lime)
CalciumSulfate(gypsum)
Petroleum
Dairy Products Animal Fat
Vegetable OilsAlcohol
![Page 33: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/33.jpg)
08/31/09 33
DID YOU KNOW….?DID YOU KNOW….?
Plastic gas cans are made of polyethylene, which is not recommended for gasoline or diesel service.
Lab bottles that store aggressive solvents are also made of polyethylene, which is not recommended for those solvents.
![Page 34: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/34.jpg)
08/31/09 34
DID YOU KNOW….?DID YOU KNOW….?
The first PTFE coated frying pan was developed in France by TEFAL in 1954?
![Page 35: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/35.jpg)
08/31/09 35
DID YOU KNOW….?DID YOU KNOW….?
Re: PTFE coated EPDM membranes
Those diffusers have a track record in service since late 2004, and have outlasted plain EPDM membranes in aggressive applications by a 10:1 margin.
![Page 36: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/36.jpg)
08/31/09 36
PTFE MEMBRANES – Failure Mode? Not Yet
We observe that a biofilm layer does form on PTFEMembranes, though it takes a long time to form, and when it Does, even in aggressive environments, it can be removed With a fingertip. The scale does not affect performance and Does not enter the slits. See below…
![Page 37: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/37.jpg)
08/31/09 37
Why PTFE??? – Don’t let this happen to you!
![Page 38: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/38.jpg)
08/31/09 38
DID YOU KNOW….?DID YOU KNOW….?
Test report #84395 dated April 30, 2009 proves that SSI’s patent-pending surface fluorination reduces plasticizer loss in an aggressive hot acetone solution compared to standard EPDM membranes by 25%.
Phoenix 91st Ave is retrofitting 2 basins in 2009 with fEPDM from SSI.
Not with fEPDM!!!
New Old Older Fossil
![Page 39: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/39.jpg)
08/31/09 39
DID YOU KNOW….?DID YOU KNOW….?
Not all EPDM is created equal. One manufacturer uses Compression Molding and 700% elongation material. Most others are using injection molding and 500% elongation material, to save cost.
![Page 40: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/40.jpg)
08/31/09 40
VII. QUALITY
![Page 41: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/41.jpg)
08/31/09 41
THE DEVIL IS IN THE DETAILSTHE DEVIL IS IN THE DETAILS
•EPDM compounds are specially formulated for wastewaterapplications providing:
•Even specific gravity, thickness, and tear resistance
• Greater resistance to elongation and tearing (multidirectional tear resistance)
• Resistant to material property changes.
• High modulus for elasticity.
• Proper taper to reduce unit stress.
• High oxygen transfer efficiency.
• Extended service life
![Page 42: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/42.jpg)
08/31/09 42
BURST TEST
![Page 43: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/43.jpg)
08/31/09 43
PLASTIC PARTS SUPPLIER QC MONITORING & PROTOCOL
![Page 44: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/44.jpg)
08/31/09 44
MEMBRANE SUPPLIER QC MONITORING & PROTOCOL
![Page 45: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/45.jpg)
08/31/09 45
LARGE PROJECT – MIL 105E TEST PROTOCOL
![Page 46: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/46.jpg)
08/31/09 46
IN-HOUSE TESTING & REPORTS
![Page 47: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/47.jpg)
08/31/09 47
IN-HOUSE TESTING & REPORTS
![Page 48: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/48.jpg)
08/31/09 48
IN-HOUSE TESTING & REPORTS
![Page 49: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/49.jpg)
08/31/09 49
VIII. PIPING SYSTEM FABRICATION & MATERIALS
![Page 50: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/50.jpg)
08/31/09 50
PLASTIC PIPE FABRICATION
![Page 51: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/51.jpg)
08/31/09 51
SS PIPE FABRICATION
![Page 52: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/52.jpg)
08/31/09 52
IX. DESIGN TOOLS & CALCULATORS
![Page 53: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/53.jpg)
08/31/09 53
WEB (.NET)+ LOCAL CALCULATION SOFTWARE
![Page 54: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/54.jpg)
08/31/09 54
WEB (.NET) BASED DRAFTING SOFTWARE
![Page 55: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/55.jpg)
08/31/09 55
WEB (.NET) BASED DRAFTING SOFTWARE Typical Results
![Page 56: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/56.jpg)
08/31/09 56
X. COMPONENTS & THEIR IMPORTANCE
![Page 57: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/57.jpg)
08/31/09 57
SUPPORTS
![Page 58: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/58.jpg)
08/31/09 58
EXPANSION JOINTS
![Page 59: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/59.jpg)
08/31/09 59
![Page 60: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/60.jpg)
08/31/09 60
REPLACEMENT MEMBRANES
![Page 61: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/61.jpg)
08/31/09 61
XII. TYPICAL SYSTEMS
![Page 62: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/62.jpg)
08/31/09 62
SYSTEMS
![Page 63: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/63.jpg)
08/31/09 63
SYSTEMS
![Page 64: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/64.jpg)
08/31/09 64
SYSTEMS
![Page 65: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/65.jpg)
Replacement Diffusers
08/31/09 65
![Page 66: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/66.jpg)
08/31/09 66
![Page 67: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/67.jpg)
08/31/09 67
The following graph depicts the performance of two tanks in Denmark. Tank 1 has Nopon TM 300 size diffusers. In Tank 2, SSI replaced the Nopon TM membranes with SSI 12” retrofit membranes. The two tanks ran side by side. Notice how the valve to the air supply in the SSI tank is mostly closed, and the valve to the air supply in the Nopon TM tank is mostly open, yet the DO is higher in the SSI tank, in spite of receiving much less air.
![Page 68: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/68.jpg)
08/31/09 68
Hi Tom.Here the first result of changing from Nopon TM 215 to AFD 350/PTFE. Saving ca 16%. But we have to adjust the plant concerning the pressure, so I’ll be back. I would like to end about 25%.
Med venlig hilsen/With best regards Pumpteknik ApS/SSI North Europe Dan Christensen www.pumpteknik.dk Tlf.: ++45 49161676, Fax.: ++45 49161696 Mobil: ++45 31655158 - e-mail mobil: [email protected] Skype member: Pumpteknik
Ad1)
Totalt elforbrug
Elforbrug til beluftning
Procent beluft ud af
total IndløbsflowElforbrug total
pr. m3 vand
Elforbrug beluftning pr. m3
vand
kwh kWh % m3 kWh(total)/m3kWh(beluftning)/m
3maj-07 49958,00 12238,00 24% 201744,00 0,25 0,060661036jan-08 66713,00 12719,00 19% 232016,00 0,29 0,054819495feb-08 58877,00 11429,00 19% 224598,00 0,26 0,050886473
Besparelse 16%
![Page 69: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/69.jpg)
08/31/09 69
XII. OPERATION, MAINTENANCE, AND TROUBLESHOOTING MANUALS
![Page 70: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/70.jpg)
08/31/09 70
XII. DEMONSTRATION/ Q & A SESSION
![Page 71: Aeration101 R2](https://reader034.vdocuments.mx/reader034/viewer/2022052304/55a07c0b1a28abf2578b45d9/html5/thumbnails/71.jpg)
08/31/09 71
THANK YOU!THANK YOU!