Page 1: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

ADT490 TroubleShootingLocating Opens A

Page 2: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

2

Introduction

• Breakdown in Circuit Integrity -> Trouble• Metallic continuity interrupted

• an “open” occurs

• System Trouble LED is lit.

• Open on a conventional Initiating circuit• Yellow Zone LED -> on

Page 3: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

3

Introduction

‣ Open on signal circuit indicate ‣ circuit is Open

‣ “Circuit” or “NAC” yellow LED

‣ System Trouble‣ LED

‣ Buzzer

3

Page 4: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

4

Introduction

‣ Class B Initiating circuit :

4

Page 5: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

5

Typical Input Circuit

‣ Continuous power 24 Vdc≅

‣ EOL Installed after last device‣ Regulates current 5 to 6 mA≅

‣ Current called -> supervisory current‣ Break -> current stops -> 0 mA‣ Sketch – why no supervisory current‣ Insert Multimeter (series) at FACP, set to mA -> 0.0 mA‣ Insert Multimeter (parallel) at FACP, set to V -> 25 Vdc

5

Page 6: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

6

Typical Input Circuit

‣ Break -> ome devices still operate‣ If 1st device is a Manual Station Operated

‣ Places short on circuit prior to break (still powered)‣ Causes Alarm Condition

‣ Remaining three devices electrically disconnected‣ Cannot cause Alarm

‣ Devices panel side of break – function‣ Device on EOL side of break - inoperable

6

Page 7: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

7

Simple Exercise - 1

‣ Example of using senses, logic and DMM to find an open circuit in a simple Class B circuit

‣ Imagine the circuit in Trouble is on Zone 2 on a 4 Zone FACP

‣ In this Apartment Building Zone 2 is the entire Second Floor

7

Page 8: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

8

Simple Exercise - 2

8

Page 9: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

9

Simple Exercise - 3

‣ Wire disconnected somewhere on this circuit.‣ “Disconnected” implies what type of a circuit fault?

____________________________

‣ What will FACP to tell us?

1) _____________________________

2) ____________________________

9

Page 10: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

10

Simple Exercise - 4

Visit 2nd floor. ‣ What will suggest where the open has

occurred?

1)_______________________________________

2)_______________________________________

10

Page 11: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

11

Simple Exercise - 5

The raceway layout might look like this:

11

Page 12: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

12

Simple Exercise - 6

After a visual inspection‣ open location not obvious (hanging device, damage

caused by renovation or repair, etc.), and‣ will probably require some meter work to locate it.‣ Visual inspection suggests problem -> middle to end

of circuit

12

Page 13: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

13

Simple Exercise - 7

What clue(s)?Remember:

“Any device on the panel side of a break in a Class B circuit will continue to work, while any device after the break is inoperable”.

1)____________________________________

2)____________________________________

13

Page 14: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

14

Simple Exercise - 8

Inspection -> both hallway smokes flashing LEDsFirst Manual Station workedLast one did not. Let’s look at the circuit again:

14

Page 15: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

15

Simple Exercise - 9

Open circuit has occurred between the last smoke detector and last Manual Station.

we haven’t to access into any suites.

15

Page 16: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

16

Simple Exercise - 10

‣ Convenient test point is second smoke because:

__________________________________and, because of the way the conduit is run,we can_______________________________

16

Page 17: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

17

Simple Exercise - 11

Remove the second smoke & Check with Meter

17

Page 18: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

18

Simple Exercise - 12

Meter to conductors into octagon-box from the FACP.

What should meter be set for?_______________________________

What reading is expected (app.)?______________________________

18

Page 19: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

19

Simple Exercise - 13

We got what we were looking forLook the other way down the circuit to the EOL.Locate other two wires removed from smoke detector.

19

Page 20: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

20

Simple Exercise - 14Do we leave the meter as previously set?

________________

What setting is going to be helpful?________________

If this part good (pretty sure it isn’t)What read should we expect? (app.)? _______

With circuit open between Test Point and the EOL What reading will you get? _____________________

20

Page 21: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

21

Simple Exercise - 15

Wiring looks like this:

21

Page 22: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

22

Simple Exercise - 16

22

Page 23: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

23

Simple Exercise - 17

Open is between octagon box and the EOL.

23

Page 24: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

24

Simple Exercise - 18

Resistance reading of 4.8 kΩ, seeing EOL.

Open is not between the octagon box and the EOL.

Open has seemingly between the heat detector in suite 203 or the heat detector in suite 204.

24

Page 25: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

25

Simple Exercise - 19Remove remaining Marrettes and short together RED and BLACK going to Suite 204.

Put your DMM (on resistance) across the returning blue and brown wires.

If shorted (0 Ω) -> the wires intact & connected to the detector -> wires to Suite 204 OK

25

Page 26: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

26

Simple Exercise - 20

26

Page 27: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

27

Simple Exercise - 21

Apply same routine and find there is an open-> DMM’s resistance is infinity.

27

Page 28: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

28

Simple Exercise - 22

28

Page 29: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

29

Simple Exercise - 23Access 203Dismount the detector &Blue wire broken off detector’s terminal screw,

-> causes open circuit.

Re-strip &re-connect blue wireRemake the connections in the octagon boxRe-mount the heat detector. Check to see that the FACP is clear.

29

Page 30: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

30

Discussion

How to troubleshoot an open on a Class A circuit?Typically a Class A looks like this:

30

Page 31: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

31

Discussion

1) There are 4 wires associated with the Class A “loop”, 2 leaving the panel and 2 returning.

2) The EOL function is inside the FACP.3) The circuit is actually working like a Class B loop, in

the normal mode.4) The arrows represent 2 “switches” that are “open

state”

31

Page 32: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

32

Discussion

When open occurs relay causes switches to close

Feeds the voltage to the other side of the open

32

Page 33: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

33

DiscussionAn open/break occurred. 1) FACP senses drop in current on loop and closes

the two “switches” (as indicated by the arrows).2) Now we have +24VDC being supplied to the 4th

terminal, and the 0VDC reference being supplied to the 3rd terminal.

3) The FACP is now back feeding the operating voltage and current to the devices beyond the break.

4) ALL DEVICES CONTINUE TO FUNCTION.

33

Page 34: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

34

Discussion

All devices work -> smoke detectors flash LED’s-> location of break more difficult to find

34

Page 35: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System

35

endofpresentation