ADT490 TroubleShootingLocating Opens
![Page 2: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/2.jpg)
2
Power Supply Grounding
‣ Power Supply has circuit -> allows positive & negative outputs to float relative to ground
‣ Green AC input wire -> building Ground‣ Resistance to ground ≤ 10 kΩ
‣ results from abnormal operation‣ Originally, negative was ground
‣ System Fault -> Ground Fault‣ Non specific - one or many‣ Internal or External
![Page 3: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/3.jpg)
3
Bonding
‣ Exterior raceway components bonder to Ground conductor
‣ reduces interference -> EMI, RFI, & ESI
‣ Easirer to test ground during VI
3
![Page 4: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/4.jpg)
4
Bonding
4
![Page 5: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/5.jpg)
5
Ground-to-Ground Short
‣ False Alarm
5
![Page 6: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/6.jpg)
6
Positive Ground
‣ Higher end panels - may show as Positive on LCD
6
![Page 7: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/7.jpg)
7
Ground Fault Processing
‣ Often within 1 second to 90 seconds‣ Lower Priority than Alarms, & Supervisory conditions‣ Return to normals even lower Priority
7
![Page 8: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/8.jpg)
8
Finding Grounds in Small Panels‣ Remove field wiring & install EOLs
‣ Eliminates Panel itself‣ Field
‣ Remove EOL and install field wiring‣ Tag and remove
‣ Find All Circuits with Ground Faults
8
![Page 9: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/9.jpg)
9
Finding Grounds in Large Panels‣ Modules often have 8 circuits‣ CPU Communicates with modules through cables
9
![Page 10: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/10.jpg)
10
Finding Grounds in Large Panels‣ Boolean Search through cables
‣ De-energize panel remove cable
‣ Localize to one module‣ Do small panel search when localized
10
![Page 11: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/11.jpg)
11
Diagnosing Ground Correctly‣ Do not accept LCD info at face value‣ Ground can trigger at 50,000 Ω‣ On positive but can still be detected through
negative wire -> “pass through”
11
![Page 12: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/12.jpg)
12
Diagnosing Ground Correctly
12
![Page 13: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/13.jpg)
13
Measuring Grounds on Positive
13
![Page 14: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/14.jpg)
14
Measuring Grounds on Negative
14
![Page 15: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/15.jpg)
15
Measuring Grounds
‣ Most consistent method - A‣ Positive lead on panel chassis or ground lug‣ Negative Lead on system or circuit common‣ Always gives 0 to 30 V
15
![Page 16: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/16.jpg)
16
Measuring Grounds
16
![Page 17: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/17.jpg)
17
Causes of Grounds
‣ drilled through raceway‣ insulation stripped during insulation‣ wire loose to metal backbox or cover
17
![Page 18: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/18.jpg)
18
Locating Grounds on Class B Ccts
18
‣ Boolean Search
![Page 19: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/19.jpg)
19
Locating Grounds on Class A Ccts‣ Boolean Search
19
![Page 20: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/20.jpg)
20
Boolean Searches for Grounds‣ Same approach as Opens and shorts‣ REMOVE BOTH WIRES
‣ Middle of circuit, remove both wires‣ If ground goes off -> toward EOL‣ f ground stays on -> toward Panel
20
![Page 21: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/21.jpg)
21
Internal Grounds on Small Panels‣ Remove field circuits with EOLs‣ Check Battery connectors‣ Foreign materials near chassis and mounting screws‣ Remove Circuit board -> closely inspect for foreign
materials ‣ If ground remains -> replace Circuit board
21
![Page 22: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/22.jpg)
22
Internal Grounds on Large Panels‣ Boolean search through Card Communication
Ribbons‣ Can sometimes remove card -> Ground clears‣ Replace cards or CPU as appropriate
22
![Page 23: ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56649f155503460f94c2aae4/html5/thumbnails/23.jpg)
23
endofpresentation