addendum number 3 leitchfield water treatment …...a. tube settler system manufacturer shall...

25
ADDENDUM NUMBER 3 Leitchfield Water Treatment Plant Leitchfield utilities Commission Bid Opening Date: November 15, 2018 at 2:00 PM local time Date of Addendum: November 9, 2018 Bidders shall conform to the following changes as same shall become binding upon the Contract to be issued in response to the Invitation to Bid. The Contract Documents shall be revised and/or amended as set forth herein: 1. Revise Specification Section 11230 as follows: 3.03 INSTALLATION SUPERVISION A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision shall be provided for 4 working days (not to exceed 8 hours per day). This time period will be for 2 trips with 2 days per trip. 3.05 EXTRA STOCK/SPARE PARTS A. Spare tube modules - Furnish 2 full size (minimum 10 ft. lengths) spare tube modules to Owner. B. Wastage tube modules - Furnish 2 full size (minimum 10 ft. lengths) modules to contractor as wastage during installation. Any remaining modules (after installation) shall be given to Owner. C. Wastage/Spare Protective Surface Grating – Furnish 8 full size panels to contractor as wastage during installation. If fiberglass grating is being provided, a fiberglass patch and repair kit must be provided as necessary to repair cut fiberglass ends. 2. Cast Iron Valve Boxes are acceptable for buried valves. 3. Blasting shall be permitted. When blasting is required for the removal of rock, every precaution shall be used for the protection of persons and private and public property. The method of blasting will be as determined by the Contractor, subject to the approval of the engineer, prior to construction. The Contractor shall comply with all laws, regulations, and ordinances of the local governmental agencies and the Commonwealth of Kentucky relating to the transportation, storage and use of any and all explosives or blasting agents. Compliance with all of the above stated regulations and submittal of the method of blasting as stated above does not in any way relieve the contractor of responsibility for any damage caused by the blasting. Any damage thus caused shall be promptly and satisfactorily repaired by the Contractor at no additional cost to the owner. Disregard Special Condition #20 and Addendum #2 Item #34 4. The allowance for lab equipment does not include lab cabinets.

Upload: others

Post on 05-Jan-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

ADDENDUM NUMBER 3

Leitchfield Water Treatment Plant Leitchfield utilities Commission

Bid Opening Date: November 15, 2018 at 2:00 PM local time Date of Addendum: November 9, 2018 Bidders shall conform to the following changes as same shall become binding upon the Contract to be issued in response to the Invitation to Bid. The Contract Documents shall be revised and/or amended as set forth herein:

1. Revise Specification Section 11230 as follows: 3.03 INSTALLATION SUPERVISION A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision shall be provided for 4 working days (not to exceed 8 hours per day). This time period will be for 2 trips with 2 days per trip. 3.05 EXTRA STOCK/SPARE PARTS A. Spare tube modules - Furnish 2 full size (minimum 10 ft. lengths) spare tube modules to Owner. B. Wastage tube modules - Furnish 2 full size (minimum 10 ft. lengths) modules to contractor as wastage during installation. Any remaining modules (after installation) shall be given to Owner. C. Wastage/Spare Protective Surface Grating – Furnish 8 full size panels to contractor as wastage during installation. If fiberglass grating is being provided, a fiberglass patch and repair kit must be provided as necessary to repair cut fiberglass ends.

2. Cast Iron Valve Boxes are acceptable for buried valves. 3. Blasting shall be permitted. When blasting is required for the removal of rock,

every precaution shall be used for the protection of persons and private and public property. The method of blasting will be as determined by the Contractor, subject to the approval of the engineer, prior to construction. The Contractor shall comply with all laws, regulations, and ordinances of the local governmental agencies and the Commonwealth of Kentucky relating to the transportation, storage and use of any and all explosives or blasting agents. Compliance with all of the above stated regulations and submittal of the method of blasting as stated above does not in any way relieve the contractor of responsibility for any damage caused by the blasting. Any damage thus caused shall be promptly and satisfactorily repaired by the Contractor at no additional cost to the owner. Disregard Special Condition #20 and Addendum #2 Item #34

4. The allowance for lab equipment does not include lab cabinets.

Page 2: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 3: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 4: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 5: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 6: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 7: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 8: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 9: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 10: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 11: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 12: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 13: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision
Page 14: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Rev:10/5/2018

Panel ID: MCCP

Tag I

D

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESMCC BUILDING INTRUSION DOOR #1 DI X XMCC BUILDING INTRUSION DOOR #2 DI X XMCC BUILDING TEMPERATURE AI DEG F TBA X X

MCC-A POWER STATUS DI-NET TBA X X XMCC-A POWER GENERAL ALARM DI-NET TBA X X XMCC-A PHASE A-B VOLTAGE AI-NET VAC TBA X X XMCC-A PHASE A-C VOLTAGE AI-NET VAC TBA X X XMCC-A PHASE B-C VOLTAGE AI-NET VAC TBA X X XMCC-A CURRENT AI-NET AMPS TBA X X XMCC-A kW AI-NET Kw TBA X X

FLASH MIXER #1 H-O-A IN AUTO DI-NET NA NA X XFLASH MIXER #1 CALL TO RUN DO-NET NA NA XFLASH MIXER #1 RUNNING DI-NET NA NA X X XFLASH MIXER #1 OVER TEMP DI-NET NA NA X XFLASH MIXER #1 FAIL DI-NET NA NA X X

AIR SCOUR BLOWER #1 H-O-A IN AUTO DI-NET NA NA X XAIR SCOUR BLOWER #1 CALL TO RUN DO-NET NA NA XAIR SCOUR BLOWER #1 RUNNING DI-NET NA NA X X XAIR SCOUR BLOWER #1 OVER TEMP DI-NET NA NA X XAIR SCOUR BLOWER #1 FAIL DI-NET NA NA X XAIR SCOUR BLOWER #1 SPEED DEMAND AO-NET % 0-100.0 XAIR SCOUR BLOWER #1 SPEED FEEDBACK AI-NET % 0-100.0 X X

FLOCCULATOR #1 H-O-A IN AUTO DI-NET NA NA X XFLOCCULATOR #1 CALL TO RUN DO-NET NA NA XFLOCCULATOR #1 RUNNING DI-NET NA NA X X XFLOCCULATOR #1 OVER TEMP DI-NET NA NA X XFLOCCULATOR #1 VFD FAIL DI-NET NA NA X XFLOCCULATOR #1 SPEED DEMAND AO-NET % 0-100.0 XFLOCCULATOR #1 SPEED FEEDBACK AI-NET % 0-100.0 X X

FLOCCULATOR #2 H-O-A IN AUTO DI-NET NA NA X XFLOCCULATOR #2 CALL TO RUN DO-NET NA NA XFLOCCULATOR #2 RUNNING DI-NET NA NA X X XFLOCCULATOR #2 OVER TEMP DI-NET NA NA X XFLOCCULATOR #2 VFD FAIL DI-NET NA NA X XFLOCCULATOR #2 SPEED DEMAND AO-NET % 0-100.0 XFLOCCULATOR #2 SPEED FEEDBACK AI-NET % 0-100.0 X X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

Page 1 of 12

Page 15: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Rev:10/5/2018

Panel ID: MCCP

Tag I

D

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTES

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

HIGH SERVICE PUMP #1 H-O-A IN AUTO DI-NET NA NA X XHIGH SERVICE PUMP #1 CALL TO RUN DO-NET NA NA XHIGH SERVICE PUMP #1 RUNNING DI-NET NA NA X X XHIGH SERVICE PUMP #1 OVER TEMP DI-NET NA NA X XHIGH SERVICE PUMP #1 VFD FAIL DI-NET NA NA X XHIGH SERVICE PUMP #1 SPEED DEMAND AO-NET % 0-100.0 XHIGH SERVICE PUMP #1 SPEED FEEDBACK AI-NET % 0-100.0 X X

HIGH SERVICE PUMP #2 H-O-A IN AUTO DI-NET NA NA X XHIGH SERVICE PUMP #2 CALL TO RUN DO-NET NA NA XHIGH SERVICE PUMP #2 RUNNING DI-NET NA NA X X XHIGH SERVICE PUMP #2 OVER TEMP DI-NET NA NA X XHIGH SERVICE PUMP #2 VFD FAIL DI-NET NA NA X XHIGH SERVICE PUMP #2 SPEED DEMAND AO-NET % 0-100.0 XHIGH SERVICE PUMP #2 SPEED FEEDBACK AI-NET % 0-100.0 X X

HIGH SERVICE PUMP #3 H-O-A IN AUTO DI-NET NA NA X XHIGH SERVICE PUMP #3 CALL TO RUN DO-NET NA NA XHIGH SERVICE PUMP #3 RUNNING DI-NET NA NA X X XHIGH SERVICE PUMP #3 OVER TEMP DI-NET NA NA X XHIGH SERVICE PUMP #3 VFD FAIL DI-NET NA NA X XHIGH SERVICE PUMP #3 SPEED DEMAND AO-NET % 0-100.0 XHIGH SERVICE PUMP #3 SPEED FEEDBACK AI-NET % 0-100.0 X X

BACK WASH PUMP #1 H-O-A IN AUTO DI-NET NA NA X XBACK WASH PUMP #1 CALL TO RUN DO-NET NA NA XBACK WASH PUMP #1 RUNNING DI-NET NA NA X X XBACK WASH PUMP #1 OVER TEMP DI-NET NA NA X XBACK WASH PUMP #1 VFD FAIL DI-NET NA NA X XBACK WASH PUMP #1 SPEED DEMAND AO-NET % 0-100.0 XBACK WASH PUMP #1 SPEED FEEDBACK AI-NET % 0-100.0 X X

BACK WASH PUMP #2 H-O-A IN AUTO DI-NET NA NA X XBACK WASH PUMP #2 CALL TO RUN DO-NET NA NA XBACK WASH PUMP #2 RUNNING DI-NET NA NA X X XBACK WASH PUMP #2 OVER TEMP DI-NET NA NA X XBACK WASH PUMP #2 VFD FAIL DI-NET NA NA X XBACK WASH PUMP #2 SPEED DEMAND AO-NET % 0-100.0 XBACK WASH PUMP #2 SPEED FEEDBACK AI-NET % 0-100.0 X X

MCC-B POWER STATUS DI-NET TBA X X XMCC-B POWER GENERAL ALARM DI-NET TBA X X X

Page 2 of 12

Page 16: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Rev:10/5/2018

Panel ID: MCCP

Tag I

D

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTES

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

MCC-B PHASE A-B VOLTAGE AI-NET VAC TBA X X XMCC-B PHASE A-C VOLTAGE AI-NET VAC TBA X X XMCC-B PHASE B-C VOLTAGE AI-NET VAC TBA X X XMCC-B CURRENT AI-NET AMPS TBA X X XMCC-B kW AI-NET Kw TBA X X

GAC PUMP #1 H-O-A IN AUTO DI-NET NA NA X XGAC PUMP #1 CALL TO RUN DO-NET NA NA XGAC PUMP #1 RUNNING DI-NET NA NA X X XGAC PUMP #1 OVER TEMP DI-NET NA NA X XGAC PUMP #1 VFD FAIL DI-NET NA NA X XGAC PUMP #1 SPEED DEMAND AO-NET % 0-100.0 XGAC PUMP #1 SPEED FEEDBACK AI-NET % 0-100.0 X X

GAC PUMP #2 H-O-A IN AUTO DI-NET NA NA X XGAC PUMP #2 CALL TO RUN DO-NET NA NA XGAC PUMP #2 RUNNING DI-NET NA NA X X XGAC PUMP #2 OVER TEMP DI-NET NA NA X XGAC PUMP #2 VFD FAIL DI-NET NA NA X XGAC PUMP #2 SPEED DEMAND AO-NET % 0-100.0 XGAC PUMP #2 SPEED FEEDBACK AI-NET % 0-100.0 X X

Page 3 of 12

Page 17: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Panel ID: FCC-1

Rev:10/4/2018Ta

g ID

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MON

ITOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESAE/AIT-1-1 FILTER #1 TURBIDITY AI NTU 0-2.000 X X X X XLE/LIT-1-1 FILTER #1 LEVEL AI INCHES 0-XX.X X X X X XFE-FIT-1-1 FILTER #1 EFFLUENT FLOW RATE AI GPM 0-XXXX X XFE-FIT-1-1 FILTER #1 EFFLUENT FLOW TOTAL PULSE DI GAL X 1000 X X XPDT-1-1 FILTER #1 LOSS OF HEAD AI INCHES 0-XXX X X X X X

FV-1-1 FILTER #1 INFLUENT VALVE OPEN COMMAND DO NA NA XFV-1-1 FILTER #1 INFLUENT VALVE CLOSE COMMAND DO NA NA XFV-1-1 FILTER #1 INFLUENT VALVE OPEN STATUS DI NA NA XFV-1-1 FILTER #1 INFLUENT VALVE CLOSED STATUS DI NA NA XFV-1-1 FILTER #1 INFLUENT VALVE ACUATOR FAIL DI NA NA X

FV-1-2 FILTER #1 DRAIN VALVE OPEN COMMAND DO NA NA XFV-1-2 FILTER #1 DRAIN VALVE CLOSE COMMAND DO NA NA XFV-1-2 FILTER #1 DRAIN VALVE OPEN STATUS DI NA NA XFV-1-2 FILTER #1 DRAIN VALVE CLOSED STATUS DI NA NA XFV-1-2 FILTER #1 DRAIN VALVE ACTUATOR FAIL DI NA NA X

FV-1-3 FILTER #1 BACKWASH RATE OF FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XFV-1-3 FILTER #1 BACKWASH RATE OF FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XFV-1-3 FILTER #1 BACKWASH EFFLUENT RATE OF FLOW CONTROL VALVE OPEN STATUS DI NA NA XFV-1-3 FILTER #1 BACKWASH EFFLUENT RATE OF FLOW CONTROL VALVE CLOSED STATUS DI NA NA XFV-1-3 FILTER #1 BACKWASH EFFLUENT RATE OF FLOW CONTROL VALVE ACTUATOR FAIL DI NA NA X

FV-1-4 FILTER #1 FILTER TO WASTE FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XFV-1-4 FILTER #1 FILTER TO WASTE FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XFV-1-4 FILTER #1 FILTER TO WASTE VALVE OPEN STATUS DI NA NA XFV-1-4 FILTER #1 FILTER TO WASTE VALVE CLOSED STATUS DI NA NA XFV-1-4 FILTER #1 FILTER TO WASTE VALVE ACTUATOR FAIL DI NA NA X

FV-1-5 FILTER #1 FILTER AIR WASH INLET VALVE OPEN COMMAND DO NA NA XFV-1-5 FILTER #1 FILTER AIR WASH INLET VALVE CLOSE COMMAND DO NA NA XFV-1-5 FILTER #1 FILTER AIR WASH INLET VALVE OPEN STATUS DI NA NA XFV-1-5 FILTER #1 FILTER AIR WASH INLET VALVE CLOSED STATUS DI NA NA XFV-1-5 FILTER #1 FILTER AIR WASH INLET VALVE ACTUATOR FAIL DI NA NA X

FV-1-6 FILTER #1 EFFLUENT RATE OF FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XFV-1-6 FILTER #1 EFFLUENT RATE OF FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XFV-1-6 FILTER #1 EFFLUENT RATE OF FLOW CONTROL VALVE OPEN STATUS DI NA NA XFV-1-6 FILTER #1 EFFLUENT RATE OF FLOW CONTROL VALVE CLOSED STATUS DI NA NA XFV-1-6 FILTER #1 EFFLUENT RATE OF FLOW CONTROL VALVE ACTUATOR FAIL DI NA NA X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

Page 4 of 12

Page 18: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Rev:10/4/2018

Panel ID: FCC-2

Tag I

D

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MON

ITOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESAE/AIT-2-1 FILTER #2 TURBIDITY AI NTU 0-2.000 X X X X XLE/LIT-2-1 FILTER #2 LEVEL AI INCHES 0-XX.X X X X X XFE-FIT-2-1 FILTER #2 EFFLUENT FLOW RATE AI GPM 0-XXXX X XFE-FIT-2-1 FILTER #2 EFFLUENT FLOW TOTAL PULSE DI GAL X 1000 X X XPDT-2-1 FILTER #2 LOSS OF HEAD AI INCHES 0-XXX X X X X X

FV-2-1 FILTER #2 INFLUENT VALVE OPEN COMMAND DO NA NA XFV-2-1 FILTER #2 INFLUENT VALVE CLOSE COMMAND DO NA NA XFV-2-1 FILTER #2 INFLUENT VALVE OPEN STATUS DI NA NA XFV-2-1 FILTER #2 INFLUENT VALVE CLOSED STATUS DI NA NA XFV-2-1 FILTER #2 INFLUENT VALVE ACUATOR FAIL DI NA NA X

FV-2-2 FILTER #2 DRAIN VALVE OPEN COMMAND DO NA NA XFV-2-2 FILTER #2 DRAIN VALVE CLOSE COMMAND DO NA NA XFV-2-2 FILTER #2 DRAIN VALVE OPEN STATUS DI NA NA XFV-2-2 FILTER #2 DRAIN VALVE CLOSED STATUS DI NA NA XFV-2-2 FILTER #2 DRAIN VALVE ACTUATOR FAIL DI NA NA X

FV-2-3 FILTER #2 BACKWASH RATE OF FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XFV-2-3 FILTER #2 BACKWASH RATE OF FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XFV-2-3 FILTER #2 BACKWASH EFFLUENT RATE OF FLOW CONTROL VALVE OPEN STATUS DI NA NA XFV-2-3 FILTER #2 BACKWASH EFFLUENT RATE OF FLOW CONTROL VALVE CLOSED STATUS DI NA NA XFV-2-3 FILTER #2 BACKWASH EFFLUENT RATE OF FLOW CONTROL VALVE ACTUATOR FAIL DI NA NA X

FV-2-4 FILTER #2 FILTER TO WASTE FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XFV-2-4 FILTER #2 FILTER TO WASTE FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XFV-2-4 FILTER #2 FILTER TO WASTE VALVE OPEN STATUS DI NA NA XFV-2-4 FILTER #2 FILTER TO WASTE VALVE CLOSED STATUS DI NA NA XFV-2-4 FILTER #2 FILTER TO WASTE VALVE ACTUATOR FAIL DI NA NA X

FV-2-5 FILTER #2 FILTER AIR WASH INLET VALVE OPEN COMMAND DO NA NA XFV-2-5 FILTER #2 FILTER AIR WASH INLET VALVE CLOSE COMMAND DO NA NA XFV-2-5 FILTER #2 FILTER AIR WASH INLET VALVE OPEN STATUS DI NA NA XFV-2-5 FILTER #2 FILTER AIR WASH INLET VALVE CLOSED STATUS DI NA NA XFV-2-5 FILTER #2 FILTER AIR WASH INLET VALVE ACTUATOR FAIL DI NA NA X

FV-2-6 FILTER #2 EFFLUENT RATE OF FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XFV-2-6 FILTER #2 EFFLUENT RATE OF FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XFV-2-6 FILTER #2 EFFLUENT RATE OF FLOW CONTROL VALVE OPEN STATUS DI NA NA XFV-2-6 FILTER #2 EFFLUENT RATE OF FLOW CONTROL VALVE CLOSED STATUS DI NA NA XFV-2-6 FILTER #2 EFFLUENT RATE OF FLOW CONTROL VALVE ACTUATOR FAIL DI NA NA X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

Page 5 of 12

Page 19: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Panel ID:MCP-1

Rev:10/4/2018Ta

g ID

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MON

ITOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESFE/FIT-100 RAW WATER FLOW RATE AI GPM 0-XXXX X XFE/FIT-100 RAW WATER FLOW TOTAL PULSE DI GAL X 1000 X X XFE/FIT-101 HIGH SERVICE FLOW RATE AI GPM 0-XXXX X XFE/FIT-101 HIGH SERVICE FLOW TOTAL PULSE DI GAL X 1000 X X X

PT-101 HIGH SERVICE DISCHARGE PRESSURE AI PSI 0-300 X X XPSH-101 HIGH SERVICE DISHCHARGE PRESSURE HIGH PRESSURE SWITCH ALARM DI X X XPSL-101 HIGH SERVICE DISHCHARGE PRESSURE LOW PRESSURE SWITCH ALARM DI X X X

FE/FIT-102 BACKWASH FLOW RATE AI GPM 0-XXXX X XFE/FIT-102 BACKWASH FLOW TOTAL PULSE DI GAL X 1000 X X XAE/AIT-103 TOP OF FILTER #1 TURBIDITY AI NTU 0-2.000 X X X XAE/AIT-104 TOP OF FILTER #2 TURBIDITY AI NTU 0-2.000 X X X XAE/AIT-105 COMBINED EFFLUENT TURBIDITY AI NTU 0-2.000 X X X XAE/AIT-106 FINISHED WATER RESIDUAL CHLORINE AI MG/L 0-5.00 X X X XAE/AIT-107 TOP OF FILTER RESIDUAL CHLORINE AI MG/L 0-5.00 X X X X

LT-108 CLEARWELL LEVEL AI FT 0-XX.X X X XLSH-108 CLEARWELL LEVEL HIGH LEVEL DI NA NA X XLSL-108 CLEARWELL LOW HIGH LEVEL DI NA NA X X X

FV-100 RAW WATER RATE OF FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XFV-100 RAW WATER RATE OF FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XFV-100 RAW WATER RATE OF FLOW CONTROL VALVE OPEN STATUS DI NA NA XFV-100 RAW WATER RATE OF FLOW CONTROL VALVE CLOSED STATUS DI NA NA XFV-100 RAW WATER RATE OF FLOW CONTROL VALVE ACTUATOR FAIL DI NA NA X

PT-115 FILTER AIR SCOUR BLOWER #1 PRESSURE AI PSI 0-XXX.X X XPSH-115 FILTER AIR SCOUR BLOWER BLOWER HIGH PRESSURE SWITCH ALARM DI NA NA X X XPSL-115 FILTER AIR SCOUR BLOWER BLOWER LOW PRESSURE SWITCH ALARM DI NA NA X X XFT-115 FILTER AIR SCOUR FLOW RATE AI SCFM 0-XXX.X X XTT-115 FILTER AIR SCOUR BLOWER TEMPERATURE AI DEG F 0-XXX.X X X

TSH-115 FILTER AIR SCOUR BLOWER TEMPERATURE ALARM DI NA NA X X

CV-B1 FILTER AIR SCOUR BLOWER RATE OF FLOW CONTROL VALVE POSITION DEMAND AO % 0-100.0 X XCV-B1 FILTER AIR SCOUR BLOWER RATE OF FLOW CONTROL VALVE POSITION FEEDBACK AI % 0-100.0 X XCV-B1 FILTER AIR SCOUR BLOWER RATE OF FLOW CONTROL VALVE OPEN STATUS DI NA NA XCV-B1 FILTER AIR SCOUR BLOWER RATE OF FLOW CONTROL VALVE CLOSED STATUS DI NA NA XCV-B2 FILTER AIR SCOUR BLOWER RATE OF FLOW CONTROL VALVE ACTUATOR FAIL DI NA NA X

CV-B2 FILTER AIR SCOUR BLOWER VENT VALVE OPEN COMMAND DO NA NA XCV-B2 FILTER AIR SCOUR BLOWER VENT VALVE CLOSE COMMAND DO NA NA XCV-B2 FILTER AIR SCOUR BLOWER VENT VALVE OPEN STATUS DI NA NA XCV-B2 FILTER AIR SCOUR BLOWER VENT VALVE E CLOSED STATUS DI NA NA X

RAPID MIXER #1 H-O-A IN AUTO DI-NET NA NA X XRAPID MIXER #1 CALL TO RUN DO-NET NA NA XRAPID MIXER #1 RUNNING DI-NET NA NA X X XRAPID MIXER #1 OVER TEMP DI-NET NA NA X XRAPID MIXER #1 FAIL DI-NET NA NA X X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUT

Page 6 of 12

Page 20: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Panel ID:CRP-1

Rev:10/4/2018Ta

g ID

DESCRIPTION Prom

inen

t Pan

el

ID

I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESProminet Panel Location

SODIUM PERMANGANATE PUMP #1 H-O-A IN REMOTE CPR-1 DI-NET X XSODIUM PERMANGANATE PUMP #1 CALL CPR-1 DO-NET XSODIUM PERMANGANATE PUMP #1 RUNNING CPR-1 DI-NET XSODIUM PERMANGANATE PUMP #1 FAIL CPR-1 DI-NET X XSODIUM PERMANGANATE PUMP #1 SPEED DEMAND CPR-1 AO-NET % 0-100.0 X XSODIUM PERMANGANATE PUMP #1 SPEED FEEDBACK CPR-1 AI-NET % 0-100.0 X X

ALUM PUMP #1 H-O-A IN REMOTE CPR-1 DI-NET X XALUM PUMP #1 CALL CPR-1 DO-NET XALUM PUMP #1 RUNNING CPR-1 DI-NET XALUM PUMP #1 FAIL CPR-1 DI-NET X XALUM PUMP #1 SPEED DEMAND CPR-1 AO-NET % 0-100.0 X X

POLYMER COAGAULANT PUMP #1 RUNNING CPR-1 DI-NET XPOLYMER COAGAULANT PUMP #1 FAIL CPR-1 DI-NET X XPOLYMER COAGAULANT PUMP #1 SPEED DEMAND CPR-1 AO-NET % 0-100.0 X XPOLYMER COAGAULANT #1 SPEED FEEDBACK CPR-1 AI-NET % 0-100.0 X X

SODIUM HYPOCHLORITE PUMP #1 H-O-A IN REMOTE CPR-1 DI-NET X XSODIUM HYPOCHLORITE PUMP #1 CALL CPR-1 DO-NET XSODIUM HYPOCHLORITE PUMP #1 RUNNING CPR-1 DI-NET XSODIUM HYPOCHLORITE PUMP #1 FAIL CPR-1 DI-NET X XSODIUM HYPOCHLORITE PUMP #1 SPEED DEMAND CPR-1 AO-NET % 0-100.0 X XSODIUM HYPOCHLORITE PUMP #1 SPEEDFEEDBACK CPR-1 AI-NET % 0-100.0 X X

SODIUM HYPOCHLORITE PUMP #2 H-O-A IN REMOTE CPR-1 DI-NET X XSODIUM HYPOCHLORITE PUMP #2 CALL CPR-1 DO-NET XSODIUM HYPOCHLORITE PUMP #2 RUNNING CPR-1 DI-NET XSODIUM HYPOCHLORITE PUMP #2 FAIL CPR-1 DI-NET X XSODIUM HYPOCHLORITE PUMP #2 SPEED DEMAND CPR-1 AO-NET % 0-100.0 X XSODIUM HYPOCHLORITE PUMP #2 SPEEDFEEDBACK CPR-1 AI-NET % 0-100.0 X X

SODIUM HYPOCHLORITE PUMP #3 H-O-A IN REMOTE CPR-1 DI-NET X XSODIUM HYPOCHLORITE PUMP #3 CALL CPR-1 DO-NET XSODIUM HYPOCHLORITE PUMP #3 RUNNING CPR-1 DI-NET XSODIUM HYPOCHLORITE PUMP #3 FAIL CPR-1 DI-NET X XSODIUM HYPOCHLORITE PUMP #3 SPEED DEMAND CPR-1 AO-NET % 0-100.0 X XSODIUM HYPOCHLORITE PUMP #3 SPEEDFEEDBACK CPR-1 AI-NET % 0-100.0 X X

SPARE PUMP #1 H-O-A IN REMOTE CPR-1 DI-NET X XSPARE PUMP #1 CALL CPR-1 DO-NET XSPARE PUMP #1 RUNNING CPR-1 DI-NET XSPARE PUMP #1 FAIL CPR-1 DI-NET X XSPARE PUMP #1 SPEED DEMAND CPR-1 AO-NET % 0-100.0 X XSPARE PUMP #1 SPEED FEEDBACK CPR-1 AI-NET % 0-100.0 X X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

Page 7 of 12

Page 21: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Panel ID:CRP-1

Rev:10/4/2018Ta

g ID

DESCRIPTION Prom

inen

t Pan

el

ID

I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTES

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

SODIUM PERMANGANATE DAY TANK #1 WEIGHT CPR-1 AI-NET LBS TBA X X X XALUM DAY TANK WEIGHT CPR-1 AI-NET LBS TBA X X X XPOLYMER COAGAULAN DAY TANK WEIGHT CPR-1 AI-NET LBS TBA X X X XSODIUM HYPOCHLORITE DAY TANK WEIGHT CPR-1 AI-NET LBS TBA X X X X

SODIUM PERMANGANATE PUMP #2 H-O-A IN REMOTE CPR-1-I DI-NET X XSODIUM PERMANGANATE PUMP #2 CALL CPR-1-I DO-NET XSODIUM PERMANGANATE PUMP #2 RUNNING CPR-1-I DI-NET XSODIUM PERMANGANATE PUMP #2 FAIL CPR-1-I DI-NET X XSODIUM PERMANGANATE PUMP #2 SPEED DEMAND CPR-1-I AO-NET % 0-100.0 X XSODIUM PERMANGANATE PUMP #2 SPEEDFEEDBACK CPR-1-I AI-NET % 0-100.0 X X

SODIUM BISULFITE PUMP #1 H-O-A IN REMOTE CPR-1-I DI-NET X XSODIUM BISULFITE PUMP #1 CALL CPR-1-I DO-NET XSODIUM BISULFITE PUMP #1 RUNNING CPR-1-I DI-NET XSODIUM BISULFITE PUMP #1 FAIL CPR-1-I DI-NET X XSODIUM BISULFITE PUMP #1 SPEED DEMAND CPR-1-I AO-NET % 0-100.0 X XSODIUM BISULFITE PUMP #1 SPEEDFEEDBACK CPR-1-I AI-NET % 0-100.0 X X

SODIUM PERMANGANATE DAY TANK #2 WEIGHT CPR-1-I AI-NET LBS TBA X X X XSODIUM BISULFITE DAY TANK WEIGHT CPR-1-I AI-NET LBS TBA X X X X

Page 8 of 12

Page 22: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Panel ID:GAC

Rev:10/4/2018Ta

g ID

DESCRIPTION Pane

l ID

I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESGAC BUILDING INTRUSION DOOR #1 DI X XGAC BUILDING INTRUSION DOOR #2 DI X XGAC BUILDING TEMPERATURE AI DEG F TBA X X

FE/FIT-201 GAC BYPASS FLOW RATE AI GPM 0-XXXX X X XFE/FIT-201 GAC BYPASS FLOW TOTAL PULSE DI GAL X 1000 X X XFE/FIT-201 U.V. SYSTEM #1 FLOW RATE AI GPM 0-XXXX X X XFE/FIT-201 U.V. SYSTEM #1 FLOW TOTAL PULSE DI GAL X 1000 X X XFE/FIT-202 U.V. SYSTEM #2 FLOW RATE AI GPM 0-XXXX X X XFE/FIT-202 U.V. SYSTEM #2 FLOW TOTAL PULSE DI GAL X 1000 X X X

GAC U.V. SYSTEM #1 ON DI X XGAC U.V. SYSTEM #1 FAULT ALARM DI X X UP TO 4 ALAMS RESERVED FOR GAC SYSTEMGAC U.V. SYSTEM #1 FAULT ALARM DI X XGAC U.V. SYSTEM #1 FAULT ALARM DI X XGAC U.V. SYSTEM #1 FAULT ALARM DI X X

GAC U.V. SYSTEM #2 ON DI X XGAC U.V. SYSTEM #2 FAULT ALARM DI X X UP TO 4 ALAMS RESERVED FOR GAC SYSTEMGAC U.V. SYSTEM #2 FAULT ALARM DI X XGAC U.V. SYSTEM #2 FAULT ALARM DI X XGAC U.V. SYSTEM #2 FAULT ALARM DI X X

LT-208 GAC WET WELL LEVEL AI FT 0-XX.X X X XLSH-108 GAC WET WELL HIGH LEVEL DI NA NA X XLS1-108 GAC WET WELL LEVEL-EAD PUMP CALL DI NA NA X XLS2-108 GAC WET WELL LEVEL-LAG PUMP CALL DI NA NA X XLSL-108 GAC WET WELL LOW-LOW LEVEL-INTIATE BACK UP CONTROL MODE DI NA NA X X X

SODIUM HYDROXIDE PUMP #1 H-O-A IN REMOTE CPR-GAC DI-NET X XSODIUM HYDROXIDE PUMP #1 CALL CPR-GAC DO-NET XSODIUM HYDROXIDE PUMP #1 RUNNING CPR-GAC DI-NET XSODIUM HYDROXIDE PUMP #1 FAIL CPR-GAC DI-NET X XSODIUM HYDROXIDE PUMP #1 SPEED DEMAND CPR-GAC AO-NET % 0-100.0 X XSODIUM HYDROXIDE PUMP #1 SPEED FEEDBACK CPR-GAC AI-NET % 0-100.0 X X

PHOSPHATE PUMP #1 H-O-A IN REMOTE CPR-GAC DI-NET X XPHOSPHATE PUMP #1 CALL CPR-GAC DO-NET XPHOSPHATE PUMP #1 RUNNING CPR-GAC DI-NET XPHOSPHATE PUMP #1 FAIL CPR-GAC DI-NET X XPHOSPHATE PUMP #1 SPEED DEMAND CPR-GAC AO-NET % 0-100.0 X XPHOSPHATE PUMP #1 SPEED FEEDBACK CPR-GAC AI-NET % 0-100.0 X X

SODIUM HYPOCHLORITE PUMP #1 H-O-A IN REMOTE CPR-GAC DI-NET X XSODIUM HYPOCHLORITE PUMP #1 CALL CPR-GAC DO-NET XSODIUM HYPOCHLORITE PUMP #1 RUNNING CPR-GAC DI-NET XSODIUM HYPOCHLORITE PUMP #1 FAIL CPR-GAC DI-NET X X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

Page 9 of 12

Page 23: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Panel ID:GAC

Rev:10/4/2018Ta

g ID

DESCRIPTION Pane

l ID

I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTES

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

SODIUM HYPOCHLORITE PUMP #1 SPEED DEMAND CPR-GAC AO-NET % 0-100.0 X XSODIUM HYPOCHLORITE PUMP #1 SPEED FEEDBACK CPR-GAC AI-NET % 0-100.0 X X

FLUORIDE PUMP #1 H-O-A IN REMOTE CPR-GAC DI-NET X XFLUORIDE PUMP #1 CALL CPR-GAC DO-NET XFLUORIDE PUMP #1 RUNNING CPR-GAC DI-NET XFLUORIDE PUMP #1 FAIL CPR-GAC DI-NET X XFLUORIDE PUMP #1 SPEED DEMAND CPR-GAC AO-NET % 0-100.0 X XFLUORIDE PUMP #1 SPEED FEEDBACK CPR-GAC AI-NET % 0-100.0 X X

SODIUM HYDROXIDE DAY TANK WEIGHT CPR-1-I AI-NET LBS TBA X X X XPHOSPHATE DAY TANK WEIGHT CPR-1-I AI-NET LBS TBA X X X XSODIUM HYPOCHLORITE DAY TANK WEIGHT CPR-1-I AI-NET LBS TBA X X X XFLUORIDE DAY TANK WEIGHT CPR-1-I AI-NET LBS TBA X X X X

Page 10 of 12

Page 24: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

Panel ID:DFP-1DRY FEEDER REMOTE I/O PANEL

Rev:10/4/2018Ta

g ID

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESCARBON FEEDER RUNNING DI X XCARBON FEEDER GENERAL TROUBLE ALARM DI X XCARBON FEEDER LOW POWDER ALARM DI X XCARBON FEEDER CALL TO RUN DO XCARBON FEEDER SPEED DEMAND AO % 0-100.0 X XLIME FEEDER RUNNING DI X XLIME FEEDER GENERAL TROUBLE ALARM DI X XLIME FEEDER LOW POWDER ALARM DI X XLIME FEEDER CALL TO RUN DO XLIME FEEDER SPEED DEMAND AO % 0-100.0 X XALUM FEEDER RUNNING DI X XALUM FEEDER GENERAL TROUBLE ALARM DI X XALUM FEEDER CALL TO RUN DO XALUM FEEDER SPEED DEMAND AO % 0-100.0 X X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

Page 11 of 12

Page 25: ADDENDUM NUMBER 3 Leitchfield Water Treatment …...A. Tube settler system manufacturer shall provide the services of a qualified field installation supervisor. Installation supervision

Project: Leitchfield, KY Water Treatment Plant

PLC Panel I/O List

GENERATOR AREA REMOTE I/O PANEL

Panel ID:GENP-1

Rev:10/4/2018Ta

g ID

DESCRIPTION I/O TY

PE

UNIT

SCAL

ED R

ANGE

MONI

TOR

CONT

ROL

TREN

D

TOTA

LIZE

ALAR

M

REPO

RT

NOTESGENERATOR AREA CONTROL PANEL INTRUSION SWITCH DI X XGENERATOR RUNNING DI XGENERATOR TROUBLE ALARM #1 DI X XGENERATOR TROUBLE ALARM #2 DI X XATS IN NORMAL POSITION DI XATS IN EMERGENCY POSITION DI X X

ABBREVIATIONS:DI: DISCRETE INPUTDO: DISCRETE OUTPUTAI:ANALOG INPUTAO: ANALOG OUTPUTNET: NETWORK

Page 12 of 12