activo transformador

40
NORMATIVIDAD EN LA GESTION DEL ACTIVO TRANSFORMADOR SEMINARIO INTERNACIONAL DE GESTION DE ACTIVOS DE TRANSFORMADORES SIGAT - CIER 2010 I.E. M.Sc. HERNAN DARIO RODRIGUEZ S.

Upload: johnheltahs

Post on 18-Apr-2015

109 views

Category:

Documents


8 download

DESCRIPTION

Activo Transformador

TRANSCRIPT

Page 1: Activo Transformador

NORMATIVIDAD EN LA GESTION DEL ACTIVO TRANSFORMADOR

SEMINARIO INTERNACIONAL DE GESTION DEACTIVOS DE TRANSFORMADORES SIGAT - CIER 2010

I.E. M.Sc. HERNAN DARIO RODRIGUEZ S.

Page 2: Activo Transformador

INTRODUCCION

“Large power transformers are the most significant p ortion of the T&D assets, and a major concern to every electric utility” .

Life Cycle Management of Utility Transformer AssetsWilliam H. Bartley P.E. Hartford Steam Boiler Inspection & Insurance Co.

October 10–11, 2002 Salt Lake City, Utah

Deregulation and an increasing competition in elect ricity markets urge energy suppliers to optimize the utilization of their equipment, foc using on technical and cost-effective aspects. As a respond to these requirements utiliti es introduce methods formerly used by aspects. As a respond to these requirements utiliti es introduce methods formerly used by investment managers or insurance companies.

Asset management techniques.Schneider, J. y otros.

International Journal of Electrical Power & Energy Systems,

Volume 28, Issue 9, November 2006.

It is therefore imperative to manage power transfor mers to attain optimum utilization and thereby maximizing the return on investment without lowering their production and availabilility levels ”.

Power Transformer Life Management. L.M.Geldenhuis

18th International Conference on Electricity Distribution –CIRED 2005-

Turin, 6 -9 June 2005

2

Page 3: Activo Transformador

ENTORNO DE LAS EMPRESAS ELECTRICAS

EMPRESAS

Usuarios

Empleados y sindicatos

Financiadores

Accionistas

Contratistas yconsultores

3

ELECTRICAS Empleados y sindicatos

Entes reguladores ymarcos regulatoriosde la industria

Proveedores

Accionistas

Normatividadtécnica nacionale internacional

Page 4: Activo Transformador

Regulaciones o los estándares mundiales:

ISO 9001:2000 – Sistemas de Gestión de Calidad

ISO 14000:2004 – Sistemas de Gestión Ambiental (basada en la BS 7750, sólo la 14001-Requisitos con orientación para su uso- es certificable)

ENTORNO DE LAS EMPRESAS ELECTRICAS

certificable)

OHSAS 18000:2007 -Sistemas de Gestión de Seguridad y Salud Ocupacional ( basada en la BS 8800) (OHSAS = Occupational Health and SafetyAssessment Series)

ISO 26000:2010 - Guía sobre Responsabilidad Social (no certificable y voluntaria)

PAS 55:2008 – Gestión de Activos(PAS = Publicly Available Specification)

4

Page 5: Activo Transformador

A diferencia de las demás, la PAS 55 se estandarizó como una especificacióny está dirigida a:

“Mejorar y garantizar un desarrollo sostenible de los activos (físicos, humanos, financieros, información y social) de forma optimizada a niveles realmente

ENTORNO DE LAS EMPRESAS ELECTRICAS

financieros, información y social) de forma optimizada a niveles realmente requeridos”

Objeto : demostrar a los reguladores y/o accionistas un manejo de sus activos de forma responsable y sustenible en el tiempo. Todo esto planteado en un plan real a lo largo del ciclo de vida de sus activos, sin hipotecarlos a mediano y largo plazos.

Fuente:

Asset Management PAS 55 para una gestión optimizada de los activos certificada

Sojo, Luis. The Woodhouse Partnership Ltd, England

5

Page 6: Activo Transformador

La especificación PAS 55 fue desarrollada por el Institute of Asset Management –AMI- en colaboracióncon el British Standards Institute –BSI- y un grannúmero de organizaciones y personas.

ORIGEN DE LA PAS 55

Está dividida en dos partes, así:

� Part 1 – Specification for the optimized management of physical infrastructure assets

� Part 2 – Guidelines for the application of Part 1

6

Page 7: Activo Transformador

DEFINICION DE LA GESTIÓN DE ACTIVOS

“Actividades y prácticas coordinadas y sistemáticas a través de las cuales una organización maneja óptima y sostenible sus activos, su desempeño, riesgos y gastos

PAS 55

ACTIVOS: Planta, maquinaria, propiedades, edificios, vehículos y otros ítems dede valor importante para una organización empresarial

7

sostenible sus activos, su desempeño, riesgos y gastos asociados a lo largo de sus ciclos de vida con el propósito de lograr su plan estratégico organizacional”.

Page 8: Activo Transformador

ACTIVOS DE INFORMACION

NEGOCIO

Condición, desempeño, actividades, costos, oportunidades

Contexto Vital: Objetivos, políticas, regulación, requerimientos de desempeño, gestión de riesgos

8

ACTIVOS ACTIVOS FISICOS

ACTIVOS FINANCIEROS

RECURSOS HUMANOS

ACTIVOS INTANGIBLES

Ciclos de vida, criterios de inversión, costos de capital, valor de activos.

oportunidadesMotivación, comunicación, responsabilidades, conocimiento, experiencia

Reputación, imagen, restricciones, impacto social

Page 9: Activo Transformador

� Cualquier negocio intensivo en activos que tenga gastos importantes, recursos y dependencia del desempeño y los riesgos asociados con el ciclo de vida de los activos.

ALCANCE DE LA GESTION DE ACTIVOS

PAS 55

� Cualquier organización que tenga la intención de invertir en un portafolio importante de activos o su desempeño es vital para la entrega del servicio o producto u otros objetivos del negocio.

� Organizaciones con el requerimiento de responsabilidad pública y que deba demostrar la mejor gestión para el suministro de servicios (p.e.salud, educación, etc.).

9

Page 10: Activo Transformador

- Uso y cuidado de los activos- Desempeño a corto y largo plazo- Inversiones de Capital- Costos Operacionales- Riesgos

ALCANCE DE LA GESTIÓN DE ACTIVOS

VIDA UTIL

PAS 55

10

DIMENSIONESDE LA GESTION DE ACTIVOS

- Holística- Sistemática- Sistémica- Basada en el riesgo- Óptima- Sostenible- Integrada

Page 11: Activo Transformador

- Estructura organizacional que facilite su implementación con adecuada dirección y liderazgo.

- Conciencia, competencias y Actividades

PAS 55

- Conciencia, competencias y compromiso del personal .

- Información y conocimientos adecuados del aseguramiento de la condición, desempeño, riesgos y costos de los activos y su interrelación.

11

Actividades de los Elementos Habilitadores

Page 12: Activo Transformador

Crear/adquirir

ACTIVIDADES DEL CICLO DE VIDA DE LOS ACTIVOS

Renovar/disponerMantenerUtilizar

PAS 55

12

OPTIMIZACION DEL CICLO DE VIDA DE LOS ACTIVOS

SISTEMAS DE GESTION DE ACTIVOS

Page 13: Activo Transformador

Actividades de la Gestión del Activo Transformador

ACTIVIDADES

REMPLAZO/ DISPOSICION FINALVIDA UTIL

DEFINICIONES Y ESPECIFICACIONES

FABRICACION Y PRUEBAS

TRANSPORTE, MONTAJE Y PUESTA EN SERVICIO

MONITOREO, ASEGURAMIENTO DE CONDICION, MANTENIMIENTO

Y USO DE VIDA UTIL

FINAL

13

VIDA UTIL

Page 14: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

¿Para qué son las especificaciones?

Desde el punto de vista del Cliente : para comunicar formal y claramente lo que desea que el fabricante le entr egue.

Desde el punto de vista del fabricante : para ser capaz de ofrecer servicios y productos que entreguen una sol ución satisfactoria (técnica/comercial) al Cliente que le permita mantener la rentabilidad de su negocio.

Desde ambos lados : evitar malentendidos que pueden resultar costosos.

14

Las especificaciones son el campo de entendimiento entre el Cliente y el fabricante

Page 15: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

Entorno operativo

Tipo de transformador y aplicación, niveles de tensión, con o sin aceite, siliconados o encapsulados (SF6), lugar donde va a ser usado (al aire libre o confinado), temperatura ambiente, sismicidad, condiciones de servicio, altitud sobre el nivel del mar, proyecciones de demanda, ceraunicidad, etc.ceraunicidad, etc.

15

IEEE Std C57.12.80 IEEE Standard Terminology for Power and Distribution Transformers

IEC 60076-1 Power transformers –Part 1:General

IEEE Std C57.12.00 IEEE Standard for Standard General Requirements for Liquid-ImmersedDistribution, Power, and Regulating Transformers

IEEE Std C57.12.01, IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers, Including Those with Solid-Cast and/or Resin Encapsulated Windings

DIN VDE 0532, DIN 42 500-523-524

Page 16: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

� Guías para especificaciones

Nuestra experiencia y conocimiento.

Información y consultas a los fabricantes.

Estándares Internacionales (IEEE, ANSI, BSI, VDE, DIN EN, ISO, NEC, NEMA, ASTM, NFPA y otras normas dependiendo del país de origen y destino con las respectivas equivalencias).

� Otras fuentes de ayuda

CIGRE Working Group 12.15., “Guide for Customers Specifications for Transformers 100MVA and 123kV and above”, Technical Brochure 156, April 2000

ABB, “Transformer Handbook”, ABB Power Technologies Management Ltd, 2010.

16

Page 17: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

� Evaluación de ofertas

La evaluación de las ofertas deberá incluir todos los aspectos de cumplimiento de la normatividad solicitada. Para la valoración de las diferencias de eficiencias deberá tenerse en cuenta la norma:

IEEE Std C57.120 IEEE Loss Evaluation Guide for Power Transformersand Reactors

� Aspectos a tener en cuenta:

Variación de precios de la energía en el tiempo, tasas de interés paraevaluación, ciclos de carga en el tiempo del transformador.

Presencia de armónicos, costos de mantenimiento, instalaciones, niveles de polución, etc.

17

Page 18: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

Pruebas en fábrica

Objetivo: verificar, asegurar y documentar que el t ransformador cumplió con los requerimientos de las especificaciones

IEEE Std C57.12.00 IEEE Std C57.12.00 IEEE Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers

ANSI/IEEE C57.12.90 IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers

IEC 60076 Power transformers - Part 1: General

18

Page 19: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

Pruebas en fábrica

� Pruebas de calentamiento : IEC 60076 Power transformers - Part 2: Temperature rise.

� Pruebas de impulso : IEC 60076 Part 4: Guide to the lightning impulse and � Pruebas de impulso : IEC 60076 Part 4: Guide to the lightning impulse and switching impulse testing - Power transformers and reactors.ANSI/IEEE Std C57.98 Guide forTransformer Impulse Test

Pruebas dieléctricas : IEC 60076 Power transformers - Part 3: Insulation levels, dielectric tests and external clearances in air

� Pruebas de pédidas : IEEE C57.123 IEEE Guide for Transformer Loss Measurement

� Otras pruebas en fábrica : ANSI/IEEE C57.12.90 IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers

19

Page 20: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

Pruebas en fábrica

Medida de la relación de voltaje y chequeo de la po laridad y el grupo de conexión (measurement of voltage ratio and check of grupo de conexión (measurement of voltage ratio and check of polarity and vector group)

� Resistencia y Factor de potencia del aislamiento

� Medida de la resistencia de los devanados y núcleo (measurementof winding/core resistance)

20

Page 21: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

Pruebas en fábrica

� Dieléctricas: Prueba de impulso de onda recortada o completa, alta tensión (hi-pot), descargas parciales, voltaje inducido, suicheo, etc.

� Medida de las pérdidas sin carga y corriente de exc itación (measurement of no-load losses and no-load current losses)(measurement of no-load losses and no-load current losses)

� La prueba de calentamiento a ventilación natural o elevación de temperatura (Heat-run test at natural cooling)

� Medida de las pérdidas con carga (measurement of load loss)� Medida del voltaje de la impedancia (measurement of impedance

voltage)� Secuencia cero y otros parámetros� Prueba de cortocircuito (short circuit test)

21

Page 22: Activo Transformador

Actividades de la Gestión del Activo Transformador

DEFINICIONES Y ESPECIFICACIONES

Definición de protecciones eléctricas, mecánicas y seguridad física y del personal

� IEEE Std C37.91 IEEE Guide for Protecting Power Transformers� ANSI/IEEE Std-242 IEEE Recommended Practice for Protection and

Coordination of Industrial and Commercial Power Systems-BuffBookCoordination of Industrial and Commercial Power Systems-BuffBook� IEEE Std 142 IEEE Recommended Practice for Grounding of Industrial

and Commercial Power Systems- Green Book� IEEE Std C57.109 -IEEE guide for liquid-immersed transformer through-

fault-current duration� IEEE Std C57.131 IEEE Standard Requirements for Load Tap Changers� IEEE Std C57.19.01 IEEE Standard Performance Characteristics and

Dimensions for Outdoor Apparatus Bushings� NFPA 70 (NEC) y NFPA 70E (Standard for Electrical Safety in the

Workplace)� IEEE 979-1994. IEEE Guide for Substation Fire Protection. � NEMA Standards Publication 250, IEC/EN 60529 (tableros de control)

22

Page 23: Activo Transformador

Actividades de la Gestión del Activo TransformadorNormas IEC Normas ANSI/IEEE

60076-1, 2000 Power Transformers Part 1, GeneralC57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code

60076-2, 1993 Power Transformers Part 2, Temperature RiseC57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code

60076-3, 2000Power Transformers Part 3, Insulation levels, dielectric tests and external clearances in air

C57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code

60076-4, 2002

Power transformers Part 4:Guide to the lightning impulse andswitching impulse testing –Power transformers and reactors C57.98-1993 Impulse Test Guide

60076-5, 2006Power transformers - Part 5: Ability to withstand short circuit

C57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code

60076-6, 1997 ReactorsC57.16, C57.21, IEEE 1277, C57.32 Various

Power transformers - Part 7: Loading guide for oil-

23

Fuente:H. Jin Sim;TF Chairman IEEE/IEC Cross Reference - Transformers Committee Oct. 2008

60076-7, 2005Power transformers - Part 7: Loading guide for oil-immersed power transformers C57.91-1995 Loading Guide

60076-8, 1997 Power transformers - Part 8: Application guide C57.105-1978 Application Guide

60076-10, 2005Power transformers - Part 10: Determination of sound levels C57.12.90-2006 Test Code

60076-10-1, 2005Power transformers - Part 10-1: Determination of sound levels - Application guide

60076-13, 2006Power transformers - Part 13: Self-protected liquid-filled transformers

60076-14, 2004

Power transformers - Part 14: Design and application of liquid-immersed power transformers using high-temperature insulation materials IEEE Std 1276-1997

Guide for the Application of High-Temperature Insulation Materials in Liquid-Immersed Power Transformers

60214-1, 2003Tap-changers - Part 1: Performance requirements and test methods C57.131-1995 IEEE Standard Requirements for Load Tap Changers

60214-2, 2004 Tap-changers - Part 2: Application guide

60296, 2003Fluids for electrotechnical applications - Unused mineral insulating oils for transformers and switchgear C57.106-2006 Oil Guide

60616, 1978 Terminal and tapping markings for power transformers C57.12.70-2000IEEE Standard Terminal Markings and Connections for Distribution and Power Transformers

60599, 1999? Gas Guide C57.104-1991 Gas Guide60076-2, Annex D (CD now) Gas Guide during Factory Thermal Tests PC57.130 Gas Guide during Factory Thermal Tests

Page 24: Activo Transformador

TRANSPORTE

Actividades de la Gestión del Activo Transformador

24

Fuente:Betancourt, E; Hernández, C. PowerTransformer Manufacturer´s Experience withTransportation Mishandling. WeidmannDiagnostic Solutions 7th AnnualConference. New Orleans, L.A. Sept. 15-17 2008

Page 25: Activo Transformador

TRANSPORTE

Actividades de la Gestión del Activo Transformador

Referencias

ANSI/IEEE PC 57.150. Guide for the Transportation of Transformers and Reactors Rated 10.000 kVA and Larger.

T.Lundquist, E.Schweiger, M.Silvestre, W.Hoffman. Transportation

25

T.Lundquist, E.Schweiger, M.Silvestre, W.Hoffman. TransportationIssues of Power Transformers , IEEE TC Meeting, San Diego, CA, 2004.

Transformer Logistics Monitoring Key to Customer Satisfaction. http://www.masplantiz.com

Normas de transporte fluvial, aéreo y vial en cada país.

Regímenes aduaneros nacionales

Normas INCOTERMS (International Commercial Terms) - 2010

Page 26: Activo Transformador

TRANSPORTE

Actividades de la Gestión del Activo Transformador

Proveedor Cliente

26

Page 27: Activo Transformador

TRANSPORTE

Actividades de la Gestión del Activo Transformador

Durante el transporte si un transformador experimenta choques mecánicos, y más que los sugeridos niveles “g” los siguientes daños pueden ocurrir:

� Deformación/desplazamiento de los devanados/núcleo

27

� Deformación/desplazamiento de los devanados/núcleo

� Desgaste del aislamiento por fricción que causaráfallas en funcionamiento

� Vibraciones mecánicas que desajustan las sujecionesmecánicas que llevan a colapsar el devanado durantefallas eléctricas

� Compromiso de los espacios entre las partes activas y eltanque

.

Page 28: Activo Transformador

TRANSPORTE

Actividades de la Gestión del Activo Transformador

Casos de impactos por tipo de transporte :

1. Durante los procesos de carga, descarga y amarre . De baja ocurrenciapero con alto potencial de impacto (fallas en mecanismos de alce, caída), Los eventos de choque estarán entre 2.5g y 10g en la banda de 2-20 Hz.

28

Los eventos de choque estarán entre 2.5g y 10g en la banda de 2-20 Hz.

2. A bordo del transporte terrestre . Impactos longitudinales (frenados) y verticales debido al esatdo de la carretera. La aceleración estará entre 1.0g y 1.0 g en la banda de 3-350 Hz.

3. A bordo un barco . Rodamiento, lanzamiento. Vibraciones de frecuencia bajas que repiten en períodos regulares. La aceleración es de 0.3 a 0.8 g en la banda de 2-30 Hz.

4. A bordo de un tren . Los transformadores están sujetos a impactos en el eje longitudinal por de cambio de carril y vertical debido a las uniones de los rieles. La aceleración de 0.5 a 1.0 g en la banda de 2-500 Hz pero durante maniobras de la aceleración de operación hasta 4.0g en la banda de 2-20 Hz.

Page 29: Activo Transformador

TRANSPORTE

Actividades de la Gestión del Activo Transformador

PREPARACION PARA ENVIO PREPARACION PARA RECIBO

• Realizar prueba FRA • Verificar registradores de Impacto

Preparación para envío y recibo

29

• Desensamble del transformador • Prueba de contenido de humedad (Dew Point)

• Presurización del transformador (aire seco, nitrógeno)

• Inspección de daños físicos

• Instalación registradores de Impacto (A/D) • Medidas de aislamiento

• Empacar las partes para envío • Prueba de respuesta en frecuencia

Page 30: Activo Transformador

Actividades para la Gestión del Activo Transformado r

ESTRATEGIAS DEL MANTENIMIENTO

RCMMantenimiento Basado en Confiablidad�Lista de prioridades

CBMMantenimiento basado en

condición

Con

side

rado

30

Con

dici

ón

TBMMantenimiento Basado en Tiempo

�Inspecciones y mantenimiento a intervalos de tiempo fijos

CMMantenimiento Correctivo

�No hay inspección ni mantenimiento hasta que el equipo falle

�Lista de prioridades�Conexión entre condición y efecto de la falla�Gestión de riesgos

condición�Monitoreo continuo u ocasional�Mantenimiento cuando sea necesarioC

onsi

dera

doN

o C

onsi

dera

do

Importancia

No Considerada Considerada

Page 31: Activo Transformador

Actividades para la Gestión del Activo Transformado r

31

Monitoreo y Aseguramiento de Condición

Desarrollo de planes de mantenimiento

Envejecimiento, estado y final de vida útil

Page 32: Activo Transformador

Actividades de la Gestión del Activo Transformador

Monitoreo de Condición y Aseguramiento de Condición

Tiene que ver con la aplicación y desarrollo de métodos y equipos que están involucrados en el monitoreo de una condición de un parámetro en un transformador. Se concentra más en la detección de fallas incipientes.

Puede ser dividido en seis categorías principales:

- Monitoreo de los puntos calientes. IEEE Std C57.134, C57.115, IEEE Std 1538- Monitoreo de la vibración de paredes y devanados. IEEE Std C57.131, CIGRE

SC 12 WG 12.05- Monitoreo de gases disueltos y furanos. IEEE Std C57.104, IEC 60599- Monitoreo de descargas parciales. IEEE Std C57.113- Monitoreo de movimiento y deformaciones de los dev anados . IEEE PC57.149

A Guide to Frequency Response Analysis in Oil-immersed Transformers- Niveles de ruido. IEEE Std C57.136

32

Page 33: Activo Transformador

Actividades de la Gestión del Activo Transformador

Deformaciones y Niveles de Descargas Vibración de cuba Gases disueltos Monitoreo de

Parámetros de Monitoreo de Condición

33

Análisis térmico

Análisis de Vibraciones

Análisis de gases disueltos

Análisis de Descargas parciales

Análisis de respuesta en frecuencia (FRA)

Aseguramiento de Condición

Fuente: Abu-Elanien; Salama. Asset Management Techniques forTransformers. Electric Power Systems Research. 2010.

Ultrasonido

Deformaciones y movimiento de devanados

Niveles de ruido

Descargas parciales

Vibración de cuba y devanados

Gases disueltos en el aceite

Monitoreo de puntos calientes

Page 34: Activo Transformador

Actividades de la Gestión del Activo Transformador

34Importancia de los métodos de diagnóstico

Fuente:Zhang, X; Gockenbach, EAsset-Management of TransformersBased on Condition Monitoring andStandard DiagnosisIEEE Electrical Insulation Magazine July/August 2008 — Vol. 24, No.4

Page 35: Activo Transformador

Actividades de la Gestión del Activo Transformador

Técnicas más usadas en el análisis de gases disueltos

� Triángulo de Duval� IEEE C57.104, Limites, tasas y TDCG� Método de los gases claves

35

� Método de los gases claves� Razones de Dörnenburg� Razones de Roger� IEC 60599 Razones y Límites� Análisis de tendencias� Huella digital (Fingerprints)� Análisis por sistemas expertos� DGA Bujes (IEC 61464)

Discusión de los distintos métodos:N.A. Muhamad, B.T. Phung, T.R. Blackburn, K.X Lai. Comparative Study and Analysis of DGA Methods for Transformer Mineral Oil . PowerTech 2007

Page 36: Activo Transformador

Actividades de la Gestión del Activo Transformador

COMPONENTEMÉTODO DE

DIAGNÓSTICOEN LÍNEA

FUERA DE LÍNEA

LABORATORIO OBSERVACIONES

Envejecimiento aceite X Rutinaria

DGA X Rutinaria

Medida de resistencia XDespués de

indicación (DGA)

XDespués de

Estrategia de diagnóstico

36

Partes activas

Medida Impedancia XDespués de

indicación (DGA)

Descargas Parciales XDespués de Cortocircuito

FRA XDespués de Cortocircuito

Análisis furanos XAseguramiento

condiciónGrado de

PolimerizaciónX

Aseguramiento condición

Bujes

Tang δ/ Capacitancia X Rutinaria

DGA XAseguramiento

condición

Descargas Parciales XAseguramiento

condición

Cambiador de tomasInspección suiche X Rutinaria

Medida torque XAseguramiento

condición

Asset managementtechniques. Schneider, J. y otros. International Journal of ElectricalPower & EnergySystems, Volume28, Issue 9, November 2006.

Page 37: Activo Transformador

ENSAYOS BÁSICOS

• Rigidez dieléctrica ASTM D 1816• Tensión interfacial ASTM D 2285• Número de neutralización (acidez orgánica) ASTM D 974• Contenido de inhibidor de oxidación (para aceites inhibidos) IEC 60666• Contaminación con agua ASTM D 1533

Existe gran número de ensayos para los aceites dieléctricos pero con los siguientes se considera suficiente para determinar su estado y comportamiento futuro:

37

• Contaminación con agua ASTM D 1533• Gases disueltos IEC 60567 / 60599

ENSAYOS COMPLEMENTARIOS

• Color, aspecto ASTM D 1500 / VDE 0370• Sustancias polares ASTM D 1902• Punto de inflamación ASTM D 3• Punto de escurrimiento ASTM D 97• Lodos IEC 60422• Densidad ASTM D 1298• Viscosidad. ASTM D 445• Tangente delta, factor de disipación dieléctrica ASTM D 927• Contaminantes sólidos ISO 4406• Residuo carbonoso ASTM D 189• Cenizas ASTM D 482

Fuente: Lantos, E. Mantenimiento Proactivo en transformadores. Reliability World 2006-Sudamérica

Page 38: Activo Transformador

EXTENSIÓN DE LA VIDA ÚTIL

Métodos de extensión de la vida útil:

� Tratamiento/cambio del aceite� Remplazo de los bujes� Cambio de los contactos del cambiador de tomas� Secado de partes activas� Reparación después de falla

38

Los procedimientos de reparación en sitio requieren de una inspección exacta, identificando la falla y que sea accesible y mediante métodos ya probados y riesgos calculados; de lo contrario es mejor llevar a la fábrica o al proveedor del servicio.

IEEE Std. C57.140 IEEE Guide for the Evaluation and Reconditioning of Liquid Immersed Power Transformers.ANSI/IEEE C57-125 IEEE Guide for Failure Investigation Documentation and Analysis for PowerTransformers and Shunt ReactorsAn Analysis of Transformer Failures, Part 1-2 — Caus es, Prevention and Maximum Service Life By William H. Bartley, P.E. Hartford Steam Boiler CIGRE-WG 12-05: An international survey on failures in large power transformers in service , Electra No.88 1983

Page 39: Activo Transformador

FINAL DE LA VIDA ÚTIL

Un transformador llega al final de su vida útil por dos razones básicas:

� Decisión de reemplazo � Falla definitiva� Falla catastrófica (incendio)

39

GESTIÓN DE RESIDUOS PELIGROSOS

� Manejo y disposición final de PCB´s (C12H10-nCln, n>2) (ANSI/IEEE 799 -IEEE Guide for Handling and Disposal of Transformer Grade Insulating Liquids Containing PCBs

� Disposición de residuos de los mantenimientos� Disposición final de transformadores remplazados� Disposición final de transformadores fallados� Reciclaje

Page 40: Activo Transformador

¿PREGUNTAS?

40

GRACIAS POR SU ATENCION

I.E. M.Sc. HERNAN DARIO RODRIGUEZ [email protected]

S