Rondo PANTHER ® Acoustic and Fire-Tested Wall & Ceiling Access Panels REVISED: OCTOBER 2008

Upload: phungnhan

Post on 18-May-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

Rondo pantheR®

Acoustic and Fire-Tested Wall & Ceiling Access Panels

revised: oCTober 2008

Page 2: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

introductionThe Rondo PanTheR® range of acoustic and Fire rated access Panel Systems have been designed to perform to the new requirements of the Building Codes of australia and new Zealand for both Domestic and Commercial installations.Rondo Panther access Panel Systems are designed for internal installation only in both stud and masonry walls and suspended ceiling systems as required.The prime purpose is to provide access to concealed services such as the adjustment of mechanical equipment, electrical installations and data cabling.

note 1access panels are not intended for persons to access plenum areas unless the surrounding area has been designed for that purpose.Ref AS 1657 – 1992 Fixed Walkways, Stairways Design, Construction and Installation.

note 2The Rondo PanTheR® range of access Panel Systems are for internal use only. For access panels that are for use externally consult a Rondo Technical Representative.

safety• Testreportsareavailable

for all Rondo Panther Sound Rated and Fire Rated access Panels. Standard non rated panels are warranted against faulty workmanship.

• TwohingesarefittedtoallRondo Panther access Panels.

• Safetychainsfittedtoallpanelsexceeding 450mm square.

• Safetyinstructionsfittedtothe inside of Rondo Panther access Panel doors.

• Installationdetailsforacousticandfireratedpanelsattachedto the rear of the panel door.

• access panels over 530mm x 530mm should be independently supported as the ceiling grid furring channels will have to be cut and the plasterboard will not support the self-weight of the access panel.

design considerations

2

features & benefits

feature benefit

Standard panel design tested to meet the requirements of the Building Code of Australia Sound Isolation performance ratings of Rw+Ctr 28 or Rw 30

One standard panel design can be used in rated or non-rated sound installations reducing the risk of the incorrect panel being installed.

Five standard sizes. Designedtofitbetweenstandarddrywall stud spacing and suspended ceiling furring spacing reducing installation times.

Low profile 55mm deep. Idealforwhenplenumspaceislimited.

Custom manufactured systems. High profile 76mm deep.

Panels can be easily tailor made to suit wall or ceiling design requirements up to 1200mm wide.

High moisture resistance panel doors.

Manufactured from 16mm (hMR-MDF board) with a 0.4mm galvanised steel plate laminated to the back and painted with white primer, eliminating buckling and twisting.

Strong robust steel frame. Manufactured from 0.90bmt Z275 galvabond

® steel with mitred and welded corners to eliminate distortion and deflection.

Selection of surround finishes. Design flexibility is provided with aSetBeadfinishprovidingaflush-concealed surround, whilst the white FeatheredEdgesurroundprofilerequires no setting.

Three standard lock options. Flexibility and safety are offered with the choice of a Square Key Budget Lock, numbered Key Cam – Lock or a Concealed Touch Lock.

Concealed hinges on all panels. added security for keyed panels.

aesthetically more pleasing.

State of the art manufacturing and assembly plant.

Consistently assured quality of all panels.

Individually packed in product identifiable cartons.

ensures panels are delivered undamaged with panel type clearly identified.

Panels available through over 400 Rondo Stockists across Australia and New Zealand, and throughout Asia.

easy availability for the customer.

Page 3: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

3

standards• TheLowProfileRondo

PanTheR® acoustic access Panel Systems have been tested as an insertion loss and certifiedtoAS1191–2002byPKa acoustic Consultants, Project test number 204083 May 2004. (Australian Standard AS1191–2002 is based on and conforms closely to the essential principles of the International Standard ISO: 1140 Part 1 and Part 3.)

• FiretestsconductedtoaS1530.4 1990 by BRanZ on behalf of Fyreguard Qld Pty Ltd. ASTME2075–00 (Without Hose Steam) BS476: Part 22

and will perform to those standards when installed by an approvedfixertothestandard’srequirements.

contents

©2008 Rondo Building Services. panther® and Rondo® are registered trademarks of

Rondo Building Services Pty Ltd. aBn 69 000 289 207. The contents of this manual are covered by copyright laws. Reproduction of all or any part without the owners permission is prohibited. all illustrations are subject to change. Whilst every care has been taken in the preparation of this product guide, Rondo Building Services Pty Ltd expressly disclaims all and any liability to any person whether a purchaser of any product details of which are set out in this product manual, or otherwise in respect of anything done or omitted to be done and the consequences of anything done or omitted to be done, by any such person in reliance, whether in whole or in part upon the whole or part of the within information.

Lloyd’s register Quality assurance (LrQa) has certified rondo building services Pty Ltd’s Quality Management system as complying with iso9001 in new south Wales, Queensland, Victoria, south australia & Western australia.

Page nO

Low Profile sound Loss insulation access Panels — sraP30 4

fire rated ceiling and Wall Panels – fraP 1H 6

fire rated ceiling and Wall Panels – fraP 2H 8

Metal faced budget access Panel — MfaP 10

other rondo PantHer® access Panels: – tile access Panel system 11 – HP51 High Performance access Panel 12 – Lift Motor room Hatch Panel 14

access Panel Hardware 15

installation details – ceilings 16

installation details – Walls 17

architectural specifications 18

additional rondo Products 19

Page 4: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

Rondo PanTheR® sound loss insulation access panels have been designed and tested to meet the requirements of the BCa when installed to the manufacturers recommendations to provide access to services in a sound rated wall or ceiling. Precision manufacturing processes ensure each panel when installed correctly assists in minimising any possible sound flanking.Pre-formed holes in all four sides of the frame are positioned to match wall and ceiling metal structures for securescrewfixingofthepanelto the structures.

note To avoid cutting furring channels or studs installed at 450 or 600mm centres, use 400 x 400mm or 530 x 530mm sized panels.

For installation details, refer Pages 12–13

LoW ProfiLe sound Loss insuLation access PaneLs

4

SRAP 30

Page 5: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

PaneL descriPtion:

SRAP30 – lOW PROFIlE ACOuSTIC PAnEl

Application Ceilings and Walls

Acoustic Rating Rw + Ctr28 or Rw30. Tested by PKa acoustic Consultants

Profile LowProfile55mmdeep

Panel Frame Precision manufactured from 0.90bmt galvabond® steel with a corrosion

resistant zinc coating of Z275

Panel Door 16mm MDF high Moisture Resistant panel with a 0.40mm galvanised steel plate laminated to the rear of the door. Door face is painted with two coatsofhighqualityoil-basedprimer.Finalpaintfinishbyothers.

Trim •FeatheredEdge •SetBead

Locks Square Key Budget Lock Keyed alike numbered key (can be keyed to differ) Touch Lock (standard panels only)

Hinges 110° Concealed hinges with safety screws through hinge arms to prevent separation

Safety Features SafetychainsfittedtoallTouchLatchpanelsandallpanelsexceeding 450 x 450mm in size Identificationandsafetylabelsattachedtotheinsideofthepaneldoor

Standard Sizes 300 x 300mm 400 x 400mm 450 x 450mm 530 x 530mm

Pack Size One per carton

ACCESS PAnEl PROFIlES

5

Page 6: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

PaneL descriPtion:PaneL descriPtion:noteTo avoid cutting furring channels or studs installed at 450 or 600mm centres, use 400 x 400mm or 530 x 530mm sized panels.

Forfireratedaccesspanelsthatrequire an acoustic rating, these can be supplied upon request as a‘special’panel.PleaseconsultaRondo Technical Representative for further advice.

fire rated ceiLing and WaLL PaneLs

6

SET BEAD AnD FEATHER EDgE DETAIl

FRAP 1H

Application Ceilings and Walls

Fire Rating FRL 60/60/60

Tested by BRanZ (reports available)

Profile 110mm deep zincalume® 1.1mm thick metal frame

Panel Door Promatect based core faced with a 4.75mm MDF board laminated to the face,witha30mmwidegrafitexintumescentheat-activatedseallocatedalong all four edges. Primed and painted by others.

Trim •FeatheredEdge •SetBead

Locks Square Key Budget Lock

Hinges Concealed

Safety Features Identificationandsafetylabelsattachedtotheinsideofthepaneldoorwith installation details

Standard Sizes 300 x 300mm; 400 x 400mm; 450 x 450mm; 530 x 530mm; 600 x 600mm

Pack Size One per carton

ACCESS PAnEl PROFIlES

RONDO BUILDING SERVICES

PH: 1300 367 663

lIgHTWEIgHT WAll FIxIng DETAIl

Page 7: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

7

ceiLing HatcH (Refer Figure 1)

1. Mark and cut out opening in ceiling to match dimensions of hatch (eg 530 x 530).

2. Cut and place 51mm steel stud trimmers on all four sides 16mm back from edge of opening. Position 16mm fire-ratedplasterboardfacingstrips on the face of all four studsandscrew-fix.

3. Fit the access panel into the opening, ensuring it is positioned square and the profiledtrimishardagainstthe plasterboard surface. Fix through the pre-formed holes located on all four sides of the frame into the stud supports using a minimum of two 45mm x 8 self-fastening screws per side.

4. Seal around hatch surrounds andfire-ratedplasterboardwith Promaseal Mastic.

5. Connect safety chain and lock hatch door.

LigHtWeigHt WaLL (Refer Figure 2)1. Frame opening with steel

stud on all four sides and trimwith16mmfire-ratedplasterboard to required opening size.

2. Match hatch to wall opening.3. Fit the access panel into

the opening, ensuring it is positioned square and the profiledtrimishardagainstthe plasterboard surface. Fix through the pre-formed holes located on all four sides of the frame into the stud supports using a minimum of two 45mm x 8 self-fastening screws per side.

4. Seal around hatch surround andfire-ratedplasterboardwith Promaseal Mastic.

5. Shut hatch and engage lock.

Masonry WaLL (Refer Figure 3)1. Match hatch to wall opening.2. Fit the access panel into the

opening provided, ensuring it is positioned square and the profiledtrimishardagainstthe masonry surface. Secure frame to masonry wall using a minimum of two 60mm x 8mm masonry anchors to all four sides.

3. Seal around hatch frame surround and masonry with Promaseal Mastic.

4. Shut hatch and engage lock.

notes • All penetrations and joint

sealing shall be done in accordance with AS4072.1 2005.

• Maintenance shall be done in accordance with AS1905.1 2005.

INSTALLATIoN DeTAILS

FIguRE 1: InSTAllATIOn OF CEIlIng HATCH

FIguRE 2: InSTAllATIOn In lIgHTWEIgHT WAll

FIguRE 3: InSTAllATIOn In MASOnRy WAll

Page 8: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

PaneL descriPtion:notes To avoid cutting furring channels or studs installed at 450 or 600mm centres, use 450x450mm or 530x530mm sized panels.All penetrations and joint sealing shall be done in accordance with AS4072.1 2005.Maintenance shall be done in accordance with AS1905.1 2005.

Forfireratedaccesspanelsthatrequire an acoustic rating, these can be supplied upon request as a‘special’panel.PleaseconsultaRondo Technical Representative for further advice.

fire rated ceiLing and WaLL PaneLs

8

FRAP 2H

Application Ceilings and Walls

Fire Rating FRL 120/120/120

Tested by BRanZ (reports available)

Profile 64mm deep zincalume® 1.5mm thick metal frame

Panel Door Promatect based panel with a 4.75mm MDF board laminated to the face, witha30mmwidegrafitexintumescentheat-activatedseallocatedalongall four edges

Trim •FeatheredEdge •SetBead

Locks None.Screwfixed

Hinges None.Screwfixed

Safety Features Identificationandsafetylabelsattachedtotheinsideofthepanelwithinstallation details

Standard Sizes 300 x 300mm; 450 x 450mm; 530 x 530mm; 600 x 600mm; 1200 x 600mm

Pack Size One per carton

RONDO BUILDING SERVICES

PH: 1300 367 663

FRAP 2H ACCESS PAnEl PROFIlES

Page 9: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

9

FIguRE 4: InSTAllATIOn

FIguRE 5: SHAFTWAll DETAIl

INSTALLATIoN DeTAILS

FIguRE 6: STEEl STuD WAll DETAIl

30mm heat-activated intumescent seal

Min. 50x 50x1mm galv. steel angle frame

IBS gasket 50x10 65mm CSK screwsM4 steel

self-tapping screws at 300mm max. centres

Steel Stud

FIguRE 7: MASOnRy WAll DETAIl

Min. 50x 50x1mm galv. steel angle frame M4 steel steel expanding anchors at 300mm max. centres IBS gasket 50x10

65mm CSK screws

Page 10: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

PaneL descriPtion:

MetaL faced budget access PaneL

REAR vIEW OF MFAP

10

Mfap

Application Ceilings and Walls

Acoustic Rating none

Profile 30mm deep zinc plated, primed for painting. 1.5mm thick metal frame

Panel Door 1mm zinc plated pressed door, primed for painting

Trim •FeatheredEdge •SetBead

Locks Square Key Budget lock Touch Lock (set bead only)

Hinges Concealed

Safety Features Safety chain on panels 600 x 600mm and over

Standard Sizes 300 x 300mm; 450 x 450mm; 550 x 550mm; 600 x 600mm

Pack Size Four panels per carton

a budget-priced all-steel acccess panel for use in isolated areas whereacousticsorfireratingsarenotrequired.Itshouldnotbe used in areas where moisture or dampness may be of concern, use only in dry, protected areas. Panels must be painted for extra protection.

note To avoid cutting furring channels or studs installed at 450 or 600mm centres, use panel sizes that are in between them.

MFAP ACCESS PAnEl PROFIlES

MFAP SHOWIng SET BEAD

Page 11: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

otHer rondo PantHer® access PaneLs

PaneL descriPtion:

11

tile access panel systeM (rptp)

an access panel designed for a ceramic tiled or panelled wall where access maybe required to service plumbing works in the event of leaks, etc. or other concealed services.

Application Walls only, 6mm or 10mm deep tile

Profile StandardProfile76mmdeep(thispanelcanalsobemanufacturedwith a frame depth of 21mm – Budget Lock only)

Panel Frame Precision manufactured from 1mm galvanised steel

Panel Door 9mm CFC with a 0.40mm galvanized backing sheet

Locks Touch Lock only (Touch Lock cannot exceed 6002)

Safety Features Identification,safetychainsandsafetylabelsattachedtotheinsideof the door

Standard Sizes There are no standard sizes in this panel. all Tile Panels are made to order.

54mm

120mm minimum clearance

6-10mm tileby customer

Handshake hinge always at bottom of door once installed

Acoustic seal

9mm fibre cement door

Nominal

Touch Latches

TIlE ACCESS PAnEl SySTEM

FIguRE 8: InSTAllATIOn DETAIl

iMportant inforMation

Hinge arrangement is always placed at bottom of penetration, not at side. (i.e. 450H x 600W 10mm tile panel will have the hinge on the 600 dimension.) this prevents the panel from falling out of the wall, due to the fact that the locks are at the top of the panel and hinges are always at the bottom of the panel.

When nominating a panel for tiling:1. If a panel 3002 is

nominated, this is overall frame size, therefore tile must be trimmed.

2. If a 3002 tile is not to be cut, then an overall panel of 3072 is required. This allows the tile to fit within the steel trim, but the overall panel will be in line with outside of grout lines.

Page 12: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

The high performance hP-51 access panel provides the effective acoustic control now required by the BCa in situations within multi-storey buildings where floor and ceiling cavities, ducts and risers containing pipe-work for soil, waste and water supply pass through both habitable and non habitable areas and the provision of service access hatches would potentially give rise to noise issues.The hP-51 meets and exceeds the BCa standard with an Rw Rating of 51 and an Rw + Ctr rating of 41. The unit features a flanged steel outerframewithascrewfixedouter door, a lead blanketed lockable inner door, and acoustic seals where appropriate. Figure 9 shows how the panel can be installed in both plasterboard-lined steel stud walls and also masonry walls. When installing, ensure that the opening for the panel is cut no more than 10mm overall greater than your panel size (that is 5mm all around) and that the frame is sealed, as shown, to the substrate with suitable acoustic compound. This panel is necessarily heavy and is therefore only recommended for insertion into walls or into the vertical face of a properly constructed bulkhead.The Panther hP-51 access Panel can be made to order in various sizes however lead times may apply.

Application Strictly wall applications only

Profile Flange only, 100mm deep frame including primary and secondary acoustic seals

Panel Frame Precision manufactured from 1mm zincanneal steel

Primary Panel Door hD3 18mm thick MDF

Secondary Panel Door 8kg M2 Wave Bar between 1mm and 1.6mm steel

Locks Slotted coin lock (no key required)or keyed cam locks

Safety Features Identificationandsafetylabelsattachedtodoor

Standard Sizes all hP-51 panels are custom made (no standard sizes)

100mm

otHer rondo PantHer® access PaneLs

Hp-51 HigH-perforMance access panel

PaneL descriPtion:

12

HP51 CROSS-SECTIOn & PROFIlE

(COnTInuED)

Page 13: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

13

Acoustic sealant

Acoustic sealant

Acoustic sealant

Acoustic sealant

Typical Installation inplasterboard-lined steel stud wall

Typical Installation inmasonry wall and plasterboard-lined masonrywall

FIguRE 9: InSTAllATIOn In PlASTERBOARD-lInED STEEl STuD WAll OR MASOnRy WAll

Page 14: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

otHer rondo PantHer® access PaneLs

lift Motor rooM HatcH panel (lMrH2H)

For further information on lead times and other specially designed panels please contact aRondostateofficeandasktospeak to one of our technical representatives.

other Panels not detailed:• security panels• slim line panels 21mm Deep• shadow Bead profile panels

Application Floor

Fire Rating FRL 120/120/120

Tested by BRanZ (reports available)

Profile Standard depth 125mm

Panel Door Top Doors precision manufactured from 5mm chequer plate.FireDoorconstructedofatwo-hourfireratedcorewitha50x2mmintumescent heat activated stripSafety barricade between outer doors constructed from 24 x 25 x 1.6ShShinged safety mesh panels from 25 x 25 x 4mm galvanized steel

Hinges heavy duty broad butt/steel tube hinges to top door

Safety Features Safety Mesh panels comply with aS1755.2 1993Installationandsafetyinstructionsattachedtoeachframe

Standard Sizes There are no standard sizes in this panel. all Lift Motor Room hatches are manufactured to order.

PaneL descriPtion:

14

(COnTInuED)

Page 15: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

access PaneL HardWare

budget Lock

• Sealedkeyholelockbackforacoustic performance

• Onekeyperpanel

caM Lock

• Twokeysperpanel• Locksarekeyedalike

(can be keyed to differ)

conceaLed Hinge

• Twoperpanel• Safetyscrewsarefixed

directly through hinge into panel to prevent separation

toucH LatcH

• Twoperpanel• Safetyscrewsarefixed

directly through hinge into panel to prevent separation

15

Page 16: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

16

instaLLation detaiLs

steP oneSelection of the correct sized access panel and its location is most important – standard spacings for furring channels in ceilings are 450 or 600mm centres. To eliminate the need to cut these sections and install additional support framing, it is recommended that 400 x 400mm sized panels be used in 450mm spacing and 530 x 530mm sized panels in 600mm spacing. Ifforlogisticalreasonsfurringchannels or studs have to be cut, see Figures 10–13 for correct installation details

steP tWoSuRFAcEPENETRATION– SuSPENDEDcEILINgS For an access panel being installedinafinishedceilingwhere the furring channel does not have to be cut, the opening in the building board should be cut 5mm larger than the access panel size (i.e. a 530 x 530mm access panel requires an opening of 535 x 535mm) allowing the access panel to be adjusted for square, both vertically and horizontally. Trim around the opening using 64mm stud, screw-fixedtotheplasterboard.(Refer Figure 9, Detail 1A.)Before installing the frame, a thick layer of acoustic sealant should be placed inside and on to the front edge of the plasterboard opening.The frame should then be installed into the opening, ensuring that the acoustic sealant squeezes out around the flanges of the panel and the plasterboard.

Check that the panel is square and parallel on all four sides in the opening before securing the panel to the framing members on all four sides with a minimum twofixingspersidethroughtheholes provided.Ifpossible,squeezearunofacoustic sealant along the back of the plasterboard opening and on all four sides of the frame to ensure a complete seal is obtained.Clean away any squeezed-out acoustic sealant around the flanges, at the same time checking to ensure no gaps have been left.

note: An acoustic sealant is not required if a sound loss insulation performance is not required.

steP tHreeWhere an access panel is being installed in a plasterboard suspended ceiling and is over 530 x 530mm in size or when the furring channel has to be cut to allow installation it should be independently supported from the ceiling suspension system. (See Figures 10 & 11.)

RoNDo PANTHeR® SouND LoSS INSuLATIoN ACCeSS PANeLS — CeILINgS

FIguRE 9 – SECTIOn THROugH ACCESS PAnEl DETAIl 1A – ASSEMBly DETAIl

FIguRE 10 – ACCESS PAnEl lAyOuT

FIguRE 11 – SuSPEnDED CEIlIng lOW PROFIlE ASSEMBly DETAIl

FIguRE 12 – lOW PROFIlE ACCESS PAnEl DETAIl

Setbeadprofile

Accesspanelfixedto64mmstud on four sides through preformd holes

Page 17: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

17

steP oneSelecting the right size access paneltofitbetweenthestudspacing is most important and can save in having to cut installed studs and having to install additional framing sec-tions. generally studs are spaced at 450mm or 600mm centres with the ideal access panel sizes to use being a 400 x 400mm or a 530 x 530mm.

steP tWoWhen installing an access panel intoafinishedwallwherethestuds do not have to be cut a penetration into the build-ing board 5mm larger than the access panel and central between the studs if possible should be cut. a nogging should befittedtopandbottomtotheinside of the opening and screw fixedtotheplasterboard. Before installing the frame, a thick layer of acoustic sealant should be placed inside and on the front edge of the plaster-board opening.

The frame should then be installed into the opening, ensur-ing that the acoustic sealant squeezes out around the flanges of the panel and the plaster-board. Check that the panel is square and parallel on all four sides in the opening before securing the panel to the framing members on all four sides with a minimum twofixingspersidethroughtheholes provided.Ifpossible,squeezearunofacoustic sealant along the back of the plasterboard opening and on all four sides of the frame to ensure a complete seal is obtained.Clean away any squeezed-out acoustic sealant around the flanges, at the same time checking to ensure no gaps have been left.

note: An acoustic sealant is not required if a sound loss insulation performance is not required.Slimline access panels should always be installed with the hinges at the bottom of the penetration (walls only).

steP tHreeIfwheninstallinganaccesspanel requiring a stud to be cut, noggingtracksshouldbefittedat the top and bottom of the opening and connected to the uncut studs on either side as well as the cut stud to provide stabilityandafixingframeforthe access panel (see Figure 14).The plasterboard should be fixedtothenoggingtracksand studs as normal. The panel should then be installed as per the details in Step Two.

RoNDo PANTHeR® sounD loss insulation access panels — Walls

FIguRE 13 – STuD WAll InSTAllATIOn

FIguRE 14 – STuD WAll InSTAllATIOn DETAIl

Accesspanelframescrew-fixedtonoggin track. Minimum 2 screws per side using pre-formed holes

Page 18: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

scoPeThe contractor is to furnish all materials, labour and equipment for the installation of a Rondo PanTheR® access panel, where so indicated on the architectural drawings.

MateriaL all materials supplied by Rondo Building Services meet the relevant australian and new Zealand Standards.

instaLLation The penetration in the wall/ceiling (accurately levelled) is to be 5mm larger than the access panel. For access panels under 530 x 530mm square, the penetration is to be framed out as detailed prior to the access panel being installed. For access panels over 530 x 530mm square, the access panel is to be independently suspended from the ceiling system.

iMPortant Rondo PanTheR® access panels can be installed into virtually any wall/ceiling application. even though the access panel is a very strong product, it is still part of a system. The access panel is not designed to be used as a lever to pull through into the ceiling space.

adVisory serVice Individualprojectsmayrequirespecial detailing and development. Technical assistance is available from our engineering staff, such as detailed drawings and custom access panels (specials).

note as new technology is introduced, or industry standards are altered, Rondo reserves the right to alter existingspecificationswithoutnotice.

guarantee Rondo Building Services Pty Ltd supplies both acoustic (Rw30 Rw+Ctr28) and Fire (1 & 2-hour firerated)accesspanelswhicharewarranted to be free from defects in material and workmanship, and will replace and/or repair any product found to be defective, if installed in accordance with our technical literature and standard guarantee details.This warranty is in addition to any rights the customer may have at law. all of Rondo BuildingServices’productsaredesigned to satisfy australian and new Zealand conditions.

arcHitecturaL sPecifications

18

Page 19: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

19

additionaL rondo Products

cEILINgSYSTEMS

•Rondokey–lock® Concealed Suspended Ceiling Systems.

•Rondoduo® exposed Suspended Ceiling Systems.

•Rondotag–lock™ aluminium exposed Suspended Ceiling Systems.

•Rondowalk–about™TrafficableceilingSystems.

•RondoMetalceilingBattenSystemsforResidentialconstruction.

DRYwALLSTEELSTuDwALLFRAMINgSYSTEMS

•RondoDrywallSteelStudPartitionSystems

(fire-rated,loadbearing/non-loadbearing,internalpartitionandcurtainwallframing

systems).

•RondoShaftwallFramingSystems.

•Rondoquiet stud®DrywallSoundInsulationSystems.

SOuNDISOLATIONASSEMBLIESFORwALLS&cEILINgS

•RondoAcousticIsolationAssembliesforsound-ratedwall&ceilingsystems.

wALL&cEILINgAccESSPANELSYSTEMS

•Rondopanther®AccessPanels(acoustic&fire-ratedsystems).

FINIShINgSEcTIONS

•Rondoexangle® Drywall Finishing Sections.

•Rondoexangle® rt Render and Texture Finishing Sections.

EzY-DRIvE

•Rondoezy-drive® Roadside guide Posts.

•Rondoezy-drive® Utility Markers & Poly-Flex Safety Products.

•Rondoezy-drive® Roadside accessories.

•Rondoezy-drive® steel-flex™ Flexible Steel guide Posts.

OThERSERvIcES

•RondocustomRollFormingServices.

•RondoTechnicalDesignandResearch&DevelopmentServices.

•RondoFreight&LogisticsServices.

Page 20: Acoustic and Fire-Tested Wall & Ceiling Access Panels · Acoustic and Fire-Tested Wall & Ceiling Access Panels ... • Installation details for acoustic ... InSTAllATIOn In MASOnRy

1300–36–rondo (1300–36–7663) FORcALLSwIThINAuSTRALIAwww.rondo.com.au

0800–0800–rondo (0800–0800–76) FORcALLSwIThINNEwzEALANDwww.rondo.co.nz

rondo buiLding serVices Pty LtdcuSTOMERSERvIcEhOTLINE: 1300–36–ROnDO (1300–36–7663)

neW soutH WaLes3–33 glossop Street St Marys nSW 2760 (PO Box 324 St Marys nSW 1790)Phone:61–2–99127300Fax:61–2–99127310

Victoria12–14DunlopRoadMulgravevIc3170Phone:61–3–85612222Fax:61–3–85612266

QueensLandLot512BinaryStreetYatalaQLD4207Phone:61–7–32874944Fax:61–7–32871881

soutH austraLia39 george Street greenfields Sa 5107Phone:61–8–82834065Fax:61–8–82834320

Western austraLia5 hazelhurst Street Kewdale Wa 6105Phone:61–8–93532944Fax:61–8–93532955

Head office PO Box 324 St Marys nSW 1790Phone:61–2–99127303Fax:61–2–99127313

exPortPhone:61–438–427–479Fax:61–7–3287–1881

Rondo Offices

austraLia

rondo buiLding serVices Pty Ltd117a Captain Springs Road Onehunga aucklandPhone:64–9–6365110 Fax:64–9–6365111FREEcALL: 0800–0800–ROnDO (0800–0800–76)

neW zeaLand

rondo MetaL Products sdn bHdLot 606, off Jalan SS 13/1K, Subang Jaya, Selangor Phone:60–3–56292000 Fax:60–3–56292117

MaLaysia

panther® and rondo® are registered trademarks of Rondo Building Services Pty Ltd. aBn 69 000 289 207. Revised:OCTOBeR 2008.