abt meter reading with cmri procedure

19
ABT METER READING WITH CMRI PROCEDURE (At on site) A.Press Power/Resume button for CMRI power ON. B.Select option “1” for “SEMS” for ABT Meter reading. C.Then CMRI display showing following options. 1.Read Meter Data. 2.Dump Data. 3.Read Energy. 4.Calibration. 5.Terminals. 6.Space. 7.Meter –Summator. 8.Identification No. 9.Load Survey Days. R.Read Direct Meter. F. Configure IID. D.Select “9” for “Load survey days”. E.Type load survey days. F.CMRI display again point 5. G.Select “1” for Read meter data. H.After successful meter reading by CMRI again display as point 5. I.Press “6” for check space and nos of meters read. J.If CMRI do not read the data from meter and show the COMMINICATION FAIL then wait for 5 min and again repeat from point E to I

Upload: amitvi

Post on 19-Dec-2015

73 views

Category:

Documents


14 download

DESCRIPTION

yes

TRANSCRIPT

Page 1: Abt Meter Reading With Cmri Procedure

ABT METER READING WITH CMRI PROCEDURE (At on site)

A.Press Power/Resume button for CMRI power ON.

B.Select option “1” for “SEMS” for ABT Meter reading.

C.Then CMRI display showing following options.

1.Read Meter Data.2.Dump Data. 3.Read Energy.4.Calibration.5.Terminals.6.Space.7.Meter –Summator.8.Identification No.9.Load Survey Days.R.Read Direct Meter.F. Configure IID.

D.Select “9” for “Load survey days”.

E.Type load survey days.

F.CMRI display again point 5.

G.Select “1” for Read meter data.

H.After successful meter reading by CMRI again display as point 5.

I.Press “6” for check space and nos of meters read.

J.If CMRI do not read the data from meter and show the COMMINICATION FAIL then wait for 5 min and again repeat from point E to I

DATA DUMP BY CMRI WITH PC PROCEDURE

Page 2: Abt Meter Reading With Cmri Procedure

a.Collect CMRI from meter reader & check MRI space & no of meters which read.

b.Charge CMRI & ready to be dumping in computer.

c.Open Smart2000 & type username “SUPERVISOR” & password “superpower”.

d.Process of MRI data uploading is as follows:

i.Connect the MRI to COM port of PC having SMART 2000 with a serial cable.

Figure 1

ii. Select MRI>MRI Communication from the main menu of SMART

2000.

Page 3: Abt Meter Reading With Cmri Procedure

Figure 2

iii.Select different options as follows:

1.From “MRI Type” select type of MRI which is to be read i.e. “Analogic MRI”.

2.From “Protocol Type” select protocol to be used for communicating with MRI. i.e. “SMART Protocol”.

3.From “COM Port” select the COM port where MRI is connected.

iv. Click Read MRI.

Page 4: Abt Meter Reading With Cmri Procedure

Figure 3

v.Click on “Cancel” for data saving in default folder.

Page 5: Abt Meter Reading With Cmri Procedure

Figure 4

vi.Put the CMRI in Dump mode by press the button “2” by CMRI.vii.Click on “yes” on PC as per above figure show.

Page 6: Abt Meter Reading With Cmri Procedure

Figure 5

viii.Data dumping process start as per above figure.

Page 7: Abt Meter Reading With Cmri Procedure

Figure 6

ix.After successfully read the MRI the above screen shown and click on “OK”.

Precaution: Make sure that the MRI is connected on the right COM port and is in Dump mode.

Page 8: Abt Meter Reading With Cmri Procedure

CMRI PREPARE WITH PC PROCEDURE

1.Connect the MRI to COM port of PC having SMART 2000 with a serial data cable.

2.Select MRI > MRI Communication from the main menu of SMART 2000.

Figure 7

1.From “MRI Type” select type of MRI which is to be read i.e. “Analogic MRI”.2.From “Protocol Type” select protocol to be used for communicating with

MRI. i.e. “SMART Protocol”.

3.From “COM Port” select the COM port where MRI is connected. Click Prepare MRI.

Page 9: Abt Meter Reading With Cmri Procedure

Figure 8

1. Select meter Schedule file name from schedule folder AND Select CLEAR MRI.SDL & OPEN.

Click on this tab.

Page 10: Abt Meter Reading With Cmri Procedure

Figure 9

VII. Then showing following window clicks OK.

Figure 10

Page 11: Abt Meter Reading With Cmri Procedure

VIII. Then showing following window click yes. MRI will be preparing.

Figure 11

PRECOSION:

During MRI read operation the PC must not running any other program loaded in the memory which captures the serial port or which can take away CPU time such as memory resident program.

Unnecessary key pressing should be avoided while data transfer is taking place.

 

Page 12: Abt Meter Reading With Cmri Procedure

LOAD SURVEY (METER DATA) IN CSV FILE

1. Select Meter no. In Smart 2k as following screen.

Figure 12

b. Double Click on MRD file as showing following screen.

Page 13: Abt Meter Reading With Cmri Procedure

Figure 13

c. Select Load Survey Menu as showing following screen.

Page 14: Abt Meter Reading With Cmri Procedure

Figure 14

d. Click on Print Load Survey in Tabular format Tab.

After that shown fallowing window.

Click On this point

Page 15: Abt Meter Reading With Cmri Procedure

e. Then click on the tab and shown fallowing window. Select Your like Redio button Demand or Energy choice. E.g. Active (E) and Active (I).

This massage appears.

Page 16: Abt Meter Reading With Cmri Procedure

f. After that click on convert button to make CSV file.Then popup fallowing window screen on converted file successfully.as fallowed.

Page 17: Abt Meter Reading With Cmri Procedure

Figure 15

g. Now go to My Computer - C drive – Program file – Entity – Smart2000 – CSV folder open & check same meter no. folder.

Page 18: Abt Meter Reading With Cmri Procedure