Technical Site Selection ReportABB, Faridabad AG2 Location
-
8/22/2019 ABB Faridabad
2/37
-
8/22/2019 ABB Faridabad
3/37
ABB AG2 site, 5 nearest possible Industrial/commercial plot/properties identified by Infotel team
are recommended for further commercial/technical evaluation after field survey by site selectionteam. The details of these recommended sites are as given below.
Location Co-ordinates
Site NameABB FARIDABAD AG2
Location as per Design - 2827' 22.732" N 7718' 25.849" E
Sl.
No.Site Address
Location Distance
from Design
Location
Remarks
Latitude Longitude
1
Plot No. 1523, A Block
Market, Green Field,
Faridabad.
2827' 53.4" N 7718' 3.42" E1126 m
Site suitable for AG2
2
Plot No. 1529, A Block
Market, Green Field,
Faridabad.
2827' 53.34" N 7718' 1.62" E
1152 mSite suitable for AG2
3
Plot No. 644, B Block
Market, Green Field,
Faridabad. 121003
2827' 42.96" N7717' 43.02" E
1320 mSite suitable for AG2
4
SCO 63, Huda market
Sec 31, Adjoining Pristine
Mall, Faridabad-121001
2826'41.3"N 7718'58.6"E
1558 mSite suitable for AG2
5
Plot 181, double story
Sec 31. Adjoining Pristinemall, Faridabad -121001
2826'45.6"N 7718'57.4"E
1432 m Site suitable for AG2
-
8/22/2019 ABB Faridabad
4/37
Plot No -1523 Green Field Market Faridabad
-
8/22/2019 ABB Faridabad
5/37
10.00 Ft Road
63.30 ft30.00 Ft Road
28.50 Ft
30 Ft Road
-
8/22/2019 ABB Faridabad
6/37
Front View Left View
Right View Road View
-
8/22/2019 ABB Faridabad
7/37
Term sheet/Checklist for AG2 facilitiesSl.
No.
Description / Requirement
1 Location of Facility
Complete Postal Address
with Pin Code
Plot No. 1523, A Block Market, Green Field,
Faridabad.
Location Coordinates
Longitude 7718' 3.42" E
Latitude 2827' 53.4" N
Contact Person S.N. Arora
Phone/Mobile No. of
Contact person
9810183093
2 Does the Property belong to
Reliance?
No
if Yes Is property Owned by
Reliance?
No
Is property taken on
Lease by Reliance?
No Lease Period From..
To ..
if No Is property available on
Sale?
Yes
Is property available on
Lease?
No Lease Period (required
for 20 years)
From..
To ..
3 Space Available for Infotel Facilities
Does available
property have
Open space ?
Yes
-
8/22/2019 ABB Faridabad
8/37
Minimum Requirement for
Open Space
a) If Covered/Built-up Area
not available
i. 1600 sq ft , minimum 25 ft
wide
b) If Covered/Built-up Area is
also available
i. 400 sq ft - for Manhole,
earth pits, DGs and
transformer if emergency
power (DG) is not available.
ii. 250 sq ft - for Manholes,
earth pits plus if DG power is
available.
if yes
1804.05 Sqft
(28.5 x63.3)
The site is
available on sale.
Corner Plot
having area 1800
Sqft Space for
MH, EP, GBM
and DG are
available. Plot
requires Approx
2 m filling. The
site is 1.1 Km
from designed
coordinates.
Does available
property have
covered/built-up
space?
No
Minimum Requirement for
Covered/Built-up space
400 sq ft, minimum 10 ft
width
if yes
4 Is Covered space air
conditioned?
No
Minimum Requirement
8 ton cooling capacity.
Only Precision AC is
acceptable
Controlled Temperature
(maximum) 25 deg C
if yes NA
5 Power Requirement
Minimum Requirement
a) If non AC covered/built-in
space or only open space
available
Normal Power (grid) : 3-
Ph, 415 V
Power
Availab
le
No
If yes Normal Power(grid), kW
Emergency Power (DG), KW NA
-
8/22/2019 ABB Faridabad
9/37
Connected Load : 64
kW
Operating Load : 50
kW
Redundant Emergency
Power (DG): 3-Ph, 415V, 13
kW
b) If covered/built up space
available is also having
precision air conditioning
Normal Power (grid) : 3-
Ph, 415 V
Connected Load : 38
kW
Operating Load : 38
kW
Redundant EmergencyPower (DG): 3-Ph, 415 V, 1
kW
6 Other Requirements
Access for
Personnel
24x7 accesses available? Yes
Independent Entry
Possible?
Yes
Access for
Equipment
Vehicular access available
(min 3m road)?
Yes
Independent Entry for
Infotel Possible?
Yes
Access to
Fiber and
Electrical
cables
Space for cable routing to
Infotel facility available
(required for 20 fiber
cables each in 40 mm
duct and three phase
power supply)?
Yes
Security
for
facilities
Facility has 24x7
securities? No
Can it be extended to
Infotel?No
Potable
Water
Will 250 let potable water
be available for use by
No
-
8/22/2019 ABB Faridabad
10/37
Infotel personnel?
Toilet
Facilities
Are toilet facilities
available for use by
Infotel personnel?
No
Earthling
Facilities
Is it possible to share
existing earthling system
with Infotel (for Lightning,
electrical/equipment, DC
(for electronic
equipment), DG neutral
etc.) if available?
No
-
8/22/2019 ABB Faridabad
11/37
Plot No. 1529, A Block Market, Green Field,
Faridabad.
-
8/22/2019 ABB Faridabad
12/37
10.00 Ft Road
63.30
28.50 Ft
-
8/22/2019 ABB Faridabad
13/37
Main view inside view
-
8/22/2019 ABB Faridabad
14/37
Term sheet/Checklist for AG2 facilitiesSl.
No.
Description / Requirement
1 Location of Facility
Complete Postal
Address with Pin
Code
Plot No. 1529, A Block Market, Green
Field, Faridabad.
Location Coordinates
Longitude 7718' 1.62" E
Latitude 2827' 53.34" N
Contact Person S.N. Arora
Phone/Mobile No. of
Contact person
9810183093
2 Does the Property
belong to Reliance?
No
if Yes Is property Owned by
Reliance?
No
Is property taken on
Lease by Reliance?
No Lease Period From..
To ..
if No Is property available
on Sale?
Yes
Is property available
on Lease?
No Lease Period
(required for 20years)
From..
To ..
3 Space Available for Infotel Facilities
Does available
property have Open
space?
Yes
Minimum Requirement for
Open Space
a) If Covered/Built-up Area
not available
i. 1600 sq ft , minimum 25
ft wide
b) If Covered/Built-up Area
is also available
i. 400 sq ft - for Manhole,
earth pits, DGs and
if yes
1804.05 Sqft
(28.5 x63.3)
The site is available
on sale. Plot area
1800 Sqft Space for
MH, EP, GBM and
DG is available.
Plot requires
Approx 2 m filling.
The site is 1.1 Km
from designed
coordinates.
-
8/22/2019 ABB Faridabad
15/37
transformer if emergency
power (DG) is not available.
ii. 250 sq ft - for Manholes,
earth pits plus if DG power
is available.
Does available
property have
covered/built-up
space?
No
Minimum Requirement for
Covered/Built-up space
400 sq ft, minimum 10 ft
width
if yes
4 Is Covered space air
conditioned?
No
Minimum Requirement
8 ton cooling capacity.
Only Precision AC is
acceptableControlled Temperature
(maximum) 25 deg C
if yes NA
5 Power Requirement
Minimum Requirement
a) If non AC covered/built-in space
or only open space available
Normal Power (grid) : 3-Ph, 415 V
Connected Load : 64 kW
Operating Load : 50 kW
Redundant Emergency Power
(DG): 3-Ph, 415V, 13 kW
b) If covered/built up space
available is also having precision air
conditioning
Normal Power (grid) : 3-Ph, 415 V
Connected Load : 38 kW
Power
Available
N0
If yes Normal Power(grid), kW
Emergency Power (DG), kW NA
-
8/22/2019 ABB Faridabad
16/37
Operating Load : 38 kW
Redundent Emergency Power
(DG): 3-Ph, 415 V, 1 kW
6 Other RequirementsAccess for Personnel 24x7 access available? Yes
Independent Entry
Possible?
Yes
Access for Equipment Vehicular access
available (min 3m
road)?
Yes
Independent Entry for
Infotel Possible?
Yes
Access to Fiber and
Electrical cables
Space for cable routing
to Infotel facility
available (required for
20 fiber cables each in
40 mm duct and three
phase power supply)?
Yes
Security for facilities Facility has 24x7
securities?
No
Can it be extended to
Infotel?
No
Potable Water Will 250 lt potablewater be available for
use by Infotel
personnel?
No
Toilet Facilities Are toilet facilities
available for use by
Infotel personnel?
No
Earthing Facilities Is it possible to share
existing earthing
system with Infotel(for Lightning,
electrical/equipment,
DC (for electronic
equipment), DG
neutral etc.) if
available?
No
-
8/22/2019 ABB Faridabad
17/37
Plot N0-644 B Block Mkt Green Field Faridabad-
121003
-
8/22/2019 ABB Faridabad
18/37
-
8/22/2019 ABB Faridabad
19/37
60.00 ft
24.00 Ft
30 Ft Road
-
8/22/2019 ABB Faridabad
20/37
Front View Left view
Right View
Term sheet/Checklist for AG2 facilitiesSl.
No.
Description / Requirement
1 Location of Facility
Complete Postal
Address with Pin
Code
Plot No-644 B Block Mkt Green Field
faridabad-121003
Location Coordinates
Longitude 7717' 43.02" E
Latitude 2827' 42.96" N
Contact Person Rajveer Yadav
Phone/Mobile No. of
Contact person
9811424208
-
8/22/2019 ABB Faridabad
21/37
2 Does the Property
belong to Reliance?
No
if Yes Is property Owned by
Reliance?
No
Is property taken on
Lease by Reliance?
No Lease Period From..
To ..
if No Is property available
on Sale?
Yes
Is property available
on Lease?
No Lease Period
(required for 20
years)
From..
To ..
3 Space Available for Infotel Facilities
Does available
property haveOpen space?
Yes
Minimum Requirement for Open
Space
a) If Covered/Built-up Area not
available
i. 1600 sq ft, minimum 25 ft wide
b) If Covered/Built-up Area is also
available
i. 400 sq ft - for Manhole, earth
pits, DGs and transformer if
emergency power (DG) is not
available.
ii. 250 sq ft - for Manholes, earth
pits plus if DG power is available.
if yes
1440 Sqft
(24 x 60)
The site is
available on sale.
Plot area 1440
Sqft Space for MH,
EP, GBM and DG is
available. Plot
requires Approx 1
m filling. The site
is 1.3 Km from
designed
coordinates.
Does available
property have
covered/built-
up space?
No
Minimum Requirement for
Covered/Built-up space400 sq ft, minimum 10 ft width
if yes
4 Is Covered space air
conditioned?
No
-
8/22/2019 ABB Faridabad
22/37
Minimum Requirement
8 ton cooling capacity.
Only Precision AC is acceptable
Controlled Temperature
(maximum) 25 deg C
if yes NA
5 Power Requirement
Minimum Requirement
a) If non AC covered/built-in
space or only open space
available
Normal Power (grid) : 3-Ph,
415 V
Connected Load : 64 kW
Operating Load : 50 kW
Redundant Emergency Power(DG): 3-Ph, 415V, 13 kW
b) If covered/built up space
available is also having precision
air conditioning
Normal Power (grid) : 3-Ph,
415 V
Connected Load : 38 kW
Operating Load : 38 kW
Redundant Emergency Power
(DG): 3-Ph, 415 V, 1 kW
Power
Available
No
If yes Normal Power(grid), kW
Emergency Power (DG), kW NA
6 Other Requirements
Access for Personnel 24x7access available? Yes
Independent Entry Possible? Yes
Access for Equipment Vehicular access available (min
3m road)?
Yes
Independent Entry for Infotel
Possible?
Yes
Access to Fiber and
Electrical cables
Space for cable routing to Infotel
facility available (required for 20
fiber cables each in 40 mm duct
and three phase power supply)?
Yes
Security for facilities Facility have 24x7 security? No
Can it be extended to Infotel? No
-
8/22/2019 ABB Faridabad
23/37
Potable Water Will 250 lt potable water be
available for use by Infotel
personnel?
No
Toilet Facilities Are toilet facilities available for
use by Infotel personnel?
No
Earthing Facilities Is it possible to share existing
earthing system with Infotel (for
Lightning, electrical/equipment,
DC (for electronic equipment),
DG neutral etc.) if available?
No
Sco-63 Huda Market Sec-31 Faridabad
-
8/22/2019 ABB Faridabad
24/37
-
8/22/2019 ABB Faridabad
25/37
38
17.5
Front View Right View
-
8/22/2019 ABB Faridabad
26/37
Left View Right View
Term sheet/Checklist for AG2 facilities
Sl.
No.
Description / Requirement
1 Location of Facility
Complete Postal Address
with Pin Code
SCO 63, Huda Market Sec 31, Adjoining Pristine
Mall, Faridabad-121001
Location Coordinates
Longitude 7718'58.6"E
Latitude 2826'41.3"N
Contact Person Mr. Manchanda
Phone/Mobile No. of
Contact person
9350646304
-
8/22/2019 ABB Faridabad
27/37
2 Does the Property belong to
Reliance?
Yes
if Yes Is property Owned by
Reliance?
RIL Recommended Vendor
Is property taken on Lease
by Reliance?
No Lease Period From.. To
..
if No Is property available on
Sale?
No
Is property available on
Lease?
Yes Lease Period (required
for 20 years)
From.. To
..
(Available on
lease)
3
Space Available for Infotel FacilitiesDoes
available
property
have
Open
space?
Yes
Minimum Requirement for
Open Space
a) If Covered/Built-up Area
not available
i. 1600 sq ft , minimum 25 ft
wide
b) If Covered/Built-up Area
is also available
i. 400 sq ft - for Manhole,
earth pits, DGs and
transformer if emergency
power (DG) is not available.
ii. 250 sq ft - for Manholes,earth pits plus if DG power is
available.
if yes
162 Sq Ft.
(12.5x13)
Open space for DG
162 Sqft available on
back side.
Does
available
property
have
covered/
built-up
space?
Yes
-
8/22/2019 ABB Faridabad
28/37
Minimum Requirement for
Covered/Built-up space
400 sq ft, minimum 10 ft
width
if yes
665 Sqft
17.5x38
The site is available
on Lease. Total
Covered area725 Sqft
suitable for AG2.
Space for MH, EP
available. Open space
for DG 162 Sqft
available on back
side. The site is 1.56
Km from designed
coordinates.
4 Is
Covered
space air
conditioned?
No
Minimum Requirement
8 ton cooling capacity.
Only Precision AC is
acceptable
Controlled Temperature
(maximum) 25 deg C
if yes Cooling Capacity available, tons NA
5 Power Requirement
Minimum Requirement
a) If non AC covered/built-in
space or only open space
available
Normal Power (grid) : 3-
Ph, 415 V
Connected Load : 64
kW
Operating Load : 50
kW
Redundent EmergencyPower (DG): 3-Ph, 415V, 13
kW
b) If covered/built up space
available is also having
precision air conditioning
Normal Power (grid) : 3-
Ph, 415 V
Connected Load : 38
PowerAvailable
Yes CommercialPower
available
If yes Normal Power(grid), kW 50 Kw
Emergency Power (DG), KW NA
-
8/22/2019 ABB Faridabad
29/37
kW
Operating Load : 38
kW
Redundent Emergency
Power (DG): 3-Ph, 415 V, 1
kW
6 Other Requirements
Access for
Personnel
24x7 access available? Yes
Independent Entry Possible? Yes
Access for
Equipment
Vehicular access available (min
3m road)?
Yes
Independent Entry for InfotelPossible? Yes
Access to
Fiber and
Electrical
cables
Space for cable routing to Infotel
facility available (required for 20
fiber cables each in 40 mm duct
and three phase power supply)?
Yes
Security for
facilities
Facility have 24x7 security? No
Can it be extended to Infotel? NA
Potable
Water
Will 250 lt potable water be
available for use by Infotel
personnel?
Yes
Toilet
Facilities
Are toilet facilities available for
use by Infotel personnel?
Yes
Earthing
Facilities
Is it possible to share existing
earthing system with Infotel (for
Lightning, electrical/equipment,
DC (for electronic equipment),
DG neutral etc.) if available?
No
-
8/22/2019 ABB Faridabad
30/37
Plot No -181 Double Story Sec -31 Faridabad
-
8/22/2019 ABB Faridabad
31/37
-
8/22/2019 ABB Faridabad
32/37
46'
19'
-
8/22/2019 ABB Faridabad
33/37
Front View Right View
Inside View Left View
-
8/22/2019 ABB Faridabad
34/37
Term sheet/Checklist for AG2 facilities
Sl.
No.
Description / Requirement
1 Location of Facility
Complete Postal
Address with Pin Code
Plot 181, double story sec 31. adjoining pristine mall,
Faridabad -121001
Location Coordinates
Longitu
de
7718'57.4"E
Latitude
2826'45.6"N
Contact Person Mr. Manchanda
Phone/Mobile No. of
Contact person
9350646304
2 Does the Property belong to
Reliance?
Yes
if Yes Is property Owned by
Reliance?
RIL Recommended Vendor
Is property taken on
Lease by Reliance?
No Lease Period From.. To
..
if No Is property available on
Sale?
Yes
Is property available on
Lease?
No Lease Period
(required for 20
years)
From.. To
..
(Available on lease)
3 Space Available for Infotel Facilities
Does available property have
Open space ?
Yes
-
8/22/2019 ABB Faridabad
35/37
Minimum
Requirement for
Open Space
a) If Covered/Built-
up Area not
available
i. 1600 sq ft ,
minimum 25 ft
wide
b) If Covered/Built-
up Area is also
available
i. 400 sq ft - for
Manhole,
earthpits, DGs andtransformer if
emergency power
(DG) is not
available.
ii. 250 sq ft - for
Manholes,
earthpits plus if DG
power is available.
if yes874 Sqft
(46x 19)
The site is
available onsale. Total plot
area 900 Sqft .
As per FAR
(19'*35') can be
constructed on
G. floor. We
can construct as
per our
requirement.
Space for MH,
EP, DG is
available. Thesite is 1.56 Km
from designed
coordinates.
Does available property have
covered/built-up space?
No
Minimum
Requirement for
Covered/Built-up
space
400 sq ft,
minimum 10 ft
width
if yes Built-up Area
Available, Sq ft
NA
4 Is Covered
space air
conditioned?
No
Minimum
Requirement
8 ton cooling
capacity.
Only Precision
AC is acceptable
Controlled
Temperature
if yes Cooling Capacity available,
tons
NA
-
8/22/2019 ABB Faridabad
36/37
(maximum) 25
deg C
5 Power
RequirementMinimum
Requirement
a) If non AC
covered/built-in
space or only
open spaceavailable
Normal Power
(grid) : 3-Ph, 415
V
Connected Load :
64 kW
Operating Load :
50 kW
Redundent
Emergency Power
(DG): 3-Ph, 415V,
13 kW
b) If
covered/built up
space available is
also having
precision air
conditioning
Normal Power
(grid) : 3-Ph, 415V
Connected Load :
38 kW
Operating Load :
38 kW
Redundent
Power Available No
If yes Normal Power(grid), kW NA
Emergency Power (DG), kW NA
-
8/22/2019 ABB Faridabad
37/37
Emergency Power
(DG): 3-Ph, 415 V,
1 kW
6 Other Requirements
Access for
Personnel
24x7 access available? Yes
Independent Entry
Possible?
Yes
Access for
Equipment
Vehicular access
available (min 3m
road)?
Yes
Independent Entry for
Infotel Possible?
Yes
Access to Fiber
and Electrical
cables
Space for cable routing
to Infotel facility avialble
(required for 20 fiber
cables each in 40 mm
duct and three phase
power supply)?
Yes
Security for
facilities
Facility has 24x7
security?
No
Can it be extended to
Infotel?
NA
Potable Water Will 250 lt potable water
be available for use by
Infotel personnel?
No
Toilet Facilities Are toilet facilities
available for use by
Infotel personnel?
No
Earthing
Facilities
Is it possible to share
existing earthing systemwith Infotel (for
Lightning,
electrical/equipment,
DC (for electronic
equipment), DG neutral
etc.) if available?
No