ABB Components USA
Seismic Considerations &Power Bushings
Using IEEE Standards
ABB Components USA
![Page 2: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/2.jpg)
ABB Components USA
IEEE 693 - 1997
IEEE Recommended Practice for Seismic Design of Substations
![Page 3: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/3.jpg)
djr 2/00 ABB Components USA
IEEE Std 693 - 1997
Electrical Equipment for Sub Stations Based on IEEE 693-1984
Very major revision Basically a new standard
Three Qualification Levels Low, Moderate & High
User determines Qualification Levels
![Page 4: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/4.jpg)
ABB Components USA
European Standards
IEC Technical Report 1463
![Page 5: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/5.jpg)
djr 2/00 ABB Components USA
IEC Technical Report 1463
Covers seismic qualification of power bushings
Based on static coefficient calculations Based on cantilever withstand of bushing Not widely accepted in North America
![Page 6: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/6.jpg)
djr 2/00 ABB Components USA
IEEE 693-1997
Performance Levels Selection of performance Level Requirements for bushings Test Methods Qualification of bushings < 161 kV Qualification of bushings 161 kV
![Page 7: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/7.jpg)
djr 2/00 ABB Components USA
Performance Levels (ground acceleration)
Low = 0.1 g, horizontal acceleration peak
Moderate = 0.5 g, horizontal acceleration peak
High = 1.0 g, horizontal acceleration peak
Vertical acceleration = 0.8 x horizontal
![Page 8: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/8.jpg)
djr 2/00 ABB Components USA
Selection of Performance Level
By User of equipment Expected ground acceleration by
earthquake hazard method or … … by seismic exposure maps and site
conditions Select Performance Level to match the
expected ground acceleration
![Page 9: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/9.jpg)
djr 2/00 ABB Components USA
General Requirements for Bushings
Bushings as components of larger equipment
Annex D of IEEE 693 - Transformers
Requirements depend on system voltage
![Page 10: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/10.jpg)
djr 2/00 ABB Components USA
Testing for Seismic Performance Levels
Low: 0.1g, horizontal Equipment testing not required
Moderate: 0.5 g, horizontal Testing required (when practical with equipment size)
High: 1.0 g, horizontal Testing required (when practical with equipment size)
![Page 11: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/11.jpg)
djr 2/00 ABB Components USA
Qualification of Bushings
Less than 161 kV Static Pull Test Force = 2 x weight Applied horizontally at top of bushing Duration = 2 seconds
161 kV and Higher Shake Table test Time history method Test by design family Test most seismically
vulnerable family member
Pass = no damage & no leakingPass = no damage & no leaking
![Page 12: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/12.jpg)
djr 2/00 ABB Components USA
Bushing Seismic Considerations
Bushing is not at ground level Bushing acceleration is amplified by
transformer structure Bushing acceleration = 2x ground acceleration Transformer tank:
Amplification factor = 2, or Super Elevation factor (IEC) = 1.5
![Page 13: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/13.jpg)
djr 2/00 ABB Components USA
Transformer Tank Amplification Factor = 2
1.0 g
2.0 g
![Page 14: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/14.jpg)
djr 2/00 ABB Components USA
Shake Table Testing of Bushings
Method 1 Test at 1/2 level and Calculate to demonstrate a 2x safety factor
Method 2 Test at full level
![Page 15: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/15.jpg)
djr 2/00 ABB Components USA
Shake Table Testing of Bushings
1/2 Test + Calculation Method Only practical method for some large equipment Good when structure behaves in linear fashion and
is predictable Not good for bushings because of the non-linearity
of the bushing’s mechanical system, ie, gasket + porcelain + spring clamps
![Page 16: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/16.jpg)
djr 2/00 ABB Components USA
Shake Table Testing of BushingsUsing 1/2 Level Test Method
For large equipment where not practical to test at full level.
Must demonstrate by calculation that equipment can withstand forces 2 times as great as test values
![Page 17: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/17.jpg)
djr 2/00 ABB Components USA
Example of 1/2 Test Method(Power Transformer)
Purpose of test: demonstrate that transformer is qualified for the High Performance Level where ground acceleration = 1.0 g
Shake Table set-up at 1/2 value = 0.5 g
Use calculations to show that the test results at 0.5 g can be extended to 1.0 g
![Page 18: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/18.jpg)
djr 2/00 ABB Components USA
Example of 1/2 Test Method(Transformer Bushings)
Purpose of test: demonstrate qualification at High Performance Level ground acceleration = 1.0 g
Bushing acceleration is 2 times ground acceleration because of tank effect
Bushing must withstand 2 x 1.0 g = 2.0 g Shake Table set-up at 1/2 value = 1.0 g Use calculations to show that the test results at 1.0
g can be extended to 2.0 g
![Page 19: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/19.jpg)
djr 2/00 ABB Components USA
Shake Table Testing of BushingsUsing Full Test Method (Full Performance Level Test)
Purpose of test: demonstrate qualification at High Performance Level ground acceleration = 1.0 g
Bushing acceleration is 2 times ground acceleration because of tank effect
Bushing must withstand 2 x 1.0 g = 2.0 g Shake Table set-up at full value = 2.0 g Bushing directly qualified by Test Calculations not required
![Page 20: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/20.jpg)
djr 2/00 ABB Components USA
Shake Table Testing of BushingsUsing Full Test Method (Full Performance Level Test)
Moderate Level (0.5 g) Bushing tested at 1.0 g
High Level (1.0 g) Bushing tested at 2.0 g
![Page 21: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/21.jpg)
djr 2/00 ABB Components USA
2 g
Bushing Qualification @High Level by Direct Testing
![Page 22: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/22.jpg)
djr 2/00 ABB Components USA
1 g
Bushing Qualification @ Moderate Level by Direct Testing
![Page 23: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/23.jpg)
djr 2/00 ABB Components USA
Shake TableTest Set-up
![Page 24: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/24.jpg)
djr 2/00 ABB Components USA
ABB Components USA
Qualify bushings based on IEEE 693-1997 Actual shake table test used for higher
voltage bushings ABB full line of ANSI/IEEE bushings has
been tested and qualified according to IEEE 693-1997
![Page 25: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/25.jpg)
djr 2/00 ABB Components USA
ABB Bushing Qualification Summary
Qualified @ High - Static Pull Test Bushings 25 kV through 138 kV
Qualified @ High - Shake Table Bushings 161 kV through 196 kV
full test of seismically worse bushing in family
Qualified @ Moderate - Shake Table Bushings 362 kV
full test of seismically worse bushing in family
![Page 26: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/26.jpg)
djr 2/00 ABB Components USA
ABB Bushing Qualification Summary
500 kV bushing not qualified at moderate passed 0.45 g at flange equivalent to 0.22 g, ground acceleration
(with tank amplification factor = 2) failure mode (@ 0.50 g at flange)
slight leak at flange during shake test re-sealed after test no worse after second test
![Page 27: ABB Components USA Seismic Considerations & Power Bushings Using IEEE Standards ABB Components USA](https://reader030.vdocuments.mx/reader030/viewer/2022020111/56649ca85503460f9496ac13/html5/thumbnails/27.jpg)
djr 2/00 ABB Components USA
ABBComponents USA