a.a.g. stucchi light management app user manual
TRANSCRIPT
A.A.G. StucchiLight Management App User Manual
Eng
Rev. 0
TABLE OF CONTENTS
PRESENTATION1.1 TECHNICAL CHARACTERISTICS OF A DALI CIRCUIT1.2 THE DALI SIGNAL1.3 TYPICAL INSTALLATION:1.4 CONNECTIVITY WITH THE ONETRACK PROGRAMMING SYSTEM1.5 ELECTRICAL CHARACTERISTICS1.6 CASAMBI MODULE USER AND INSTALLATION MANUAL
ANDROID APP2.1 INSTALL THE APPLICATION WITH THE “APK” FILE2.2 USING THE ANDROID ONETRACK PROGRAMMER APP2.3 MAIN SCREEN
DALI LAMP BRIGHTNESS CONTROL 3.1 CHANGING THE BRIGHTNESS CONTROL ADDRESS3.2 GROUP MODE BRIGHTNESS CONTROL
DALI LAMP CONFIGURATION PAGE4.1 SEARCH LAMPS4.2 SEARCH UNADDRESSED LAMPS4.3 CLEAR LAMP4.4 CLEAR LIST LAMPS4.5 MODIFY LAMPS ADDRESS 4.5.1 Aborting the new address assignment procedure4.6 TEST ON/OFF LIGHT4.7 CONFIGURE GROUP LAMPS 4.7.1 Clear Lamp Into Group 4.7.2 Test Lamps On Group (1..2..3..4) 4.7.3 Assigning a lamp to a group4.8 LAMP PROPERTIES 4.9 BOOTLOADER SERVICE 4.9.1 Checking the OneTrack module update
pag. 3pag. 3pag. 4pag. 5pag. 6pag. 6pag. 6
pag. 7pag. 7pag. 7pag. 7
pag. 11pag. 11pag. 13
pag. 14pag. 16pag. 17pag. 19pag. 20pag. 21pag. 23pag. 24pag. 25pag. 27pag. 27pag. 27pag. 29pag. 30pag. 32
1
2
3
4
1 PRESENTATION
This manual describes the operation of the DALI protocol compatible programmer for managing, installing and servicing networks controlled by the Casambi module and other objects capable of connecting to a bus of this type.
Modern lighting system cannot be limited to simply turning lights on and off. Lighting systems today are an integral element of the comfort of a location and its power management, a consideration which has given rise to the DALI (digital addressable lighting interface) control standard.
DALI is the outcome of a collaboration within the lighting industry and establishes a shared standard for the industry as a whole. DALI is thus not a system, but rather defines an interface for digital communications between a control module and the various electronic power supplies. It has therefore been included in EN 60929 for electronic power supplies as Annex E4, thus ensuring interchangeability between electronic PSU's made by different manufacturers.
A.A.G. Stucchi has developed a tool for configuring the Dali network during installation of the lighting equipment, called the ONETRACK Programmer.The programming tool, intended for System Integrators, scans the devices connected to the bus and handles or re-addresses them. This programming tool includes Android and iOS apps which guide the user in his use of the system.
9.5 V - 22.5 V, typically 16 V
Max. 250 mA (depending on the installed DALI supply power)
Data bitrate 1200 baud
L17L27L3/N = Three-phase power 16A/440VD+/D- 2x1A/50V FELV AC (DALI)
1.1 TECHNICAL CHARACTERISTICS OF A DALI CIRCUIT
3www.aagstucchi.it
DALI Voltage
DALI system current
A.A.G. Stucchi Light Management App User Manual
4www.aagstucchi.it
1.2 THE DALI SIGNAL
IDLE IDLE
MSB
833us 416us
Start LSB Stop Stop
1 1 1 1 10 0 0 0
The data is transmitted on the bus over the wires marked “D+” and “D-“.The “Idle” (standby) voltage is described in the above table.When data is sent over the bus, connected DALI systems receive a pulse train similar to the following:
This information contains the address to which the data is being sent.
The electrical signal is generated by the programmer and generates the data by shorting the 2 signals: “D+” and “D-“.
Interfacesaddess01011011
Interfacesinfo
00111011
DALIsignal
DALIcable
DALIinterfaces
DALIcontrollers
A.A.G. Stucchi Light Management App User Manual
5www.aagstucchi.it
1.3 TYPICAL INSTALLATION
We show a typical installation below.
PROGRAMMING OF UPTO 64 LIGHTING FIXTURES
ProgrammingApp
Tablet
Tablet
Tablet
Smartphone
PATENT PENDING
MANAGEMENT
PROGRAMMING
Casambi App
ManagementApp
Smartphone
Smartphone
Sync via cloud
A.A.G. Stucchi Light Management App User Manual
6www.aagstucchi.it
1.4 CONNECTIVITY WITH THE ONETRACK PROGRAMMING SYSTEM
1.5 ELECTRICAL CHARACTERISTICS
The ONETRACK programmer has been developed to support the Android and iOs platforms.
1.6 CASAMBI MODULE USER AND INSTALLATION MANUAL
Nominal input Voltage
Input voltage Range
Frequency
Power
Current
Ambient operating temperature
Max Output power
Output Channel
Output Voltage
Output current in short circuit
V AC
V AC
Hz
W
A
100-240
90-264
50/60
W
0.025 – 0.06
0 to +40°C
5 - 7 Watt
1
18 - 18.5 V DC
250 mA
Dedicatdhardware
DALI system current
ELECTRICAL CHARACTERISTICS
To configure the app - download the manual from: www.aagstucchi.it
A.A.G. Stucchi Light Management App User Manual
7www.aagstucchi.it
2.1 INSTALL THE APPLICATION WITH “APK” FILE
Download the .apk file from www.aagstucchi.it.Now open the Download folder into which the you downloaded thw APK file.Select the file and follow the prompts to install the app by pressing Avanti (Next), Installa (Install) and Fine (End)in sequence.
2.2 USING THE ANDROID ONETRACK PROGRAMMER APP
When you have installed the Light Management app, you will find the following icon on your device's screen:.
2.3 MAIN SCREEN
This section presents the main screen and its functions
Select About in the menu to display information about the app:
Launch the application. We will now review its functions and how to use them.
2 ANDROID APP
A.A.G. Stucchi Light Management App User Manual
8www.aagstucchi.it
Select BootLoader Service to enable the firmware update function, which allows us to reprogram the ONETRACK module (we will cover this later).
Select Connect, or tap the Connect icon to scan for installed modules, which are displayed in a table.
A.A.G. Stucchi Light Management App User Manual
9www.aagstucchi.it
Select the module you wish to connect by tapping on it; this launches the connection between your smart device and the ONETRACK module.
Once the connection has been established, the following displays will appear:
If the module does not have a factory password, the following screen will prompt for a user password.
A.A.G. Stucchi Light Management App User Manual
10www.aagstucchi.it
The following main page functions are available:
Disconnects from ONETRACK(you can also tap on the icon to do so)
Enters the DALI Setup page(you can also tap on the image to do so)
Disconnect controller
Setup DALI controller
Dimming Light
Check Firmware UpDate
Diagnostic DALI Bus
Change Password
About
Enters the Dimmer page(you can also tap on the image to do so)
This function interrogates the ONETRACK module and warns you if its firmware needs updating.
This function opens a session which displays the voltage of the DALI bus and the current draw of the connected DALI modules in real time.
This functions a session in which you can change the module's name and programming password.
We obtain information about the app
A.A.G. Stucchi Light Management App User Manual
11www.aagstucchi.it
You can now use the functions to control the DALI devices.
3 DALI LAMP BRIGHTNESS CONTROL PAGE
This section explains how to set the brightness of the lamps in broadcast or single point mode, using the 64 addresses available with the DALI protocol.
Let's review the touch screen functions:
Tap the icon
The lamp whose address is shown above the icon switches to maximum
brightness; if you tap on it again,the lamp turns off.
Indirizzo Lampada 3
Drag the cursor
The lamp whose address is shownabove the icon changes brightness.
Drag the cursor
All the lamps connected to theDALI bus change brightness.
3.1 CHANGING THE BRIGHTNESS CONTROL ADDRESS
A DALI address can be assigned to each individual control so that the brightness of all lamps on the bus can be controlled.Up to 64 lamps can be controlled, per the DALI protocol specification.To do this, we select the menu options:
Set Address A
Set Address B
Set Address C
Set Address D
Dimming Group Lamp
Return to MainPage
A.A.G. Stucchi Light Management App User Manual
12www.aagstucchi.it
Each option corresponds to a single control; select the option to open the page for changing the control's address:
Use “+” to increment and ”-“ to decrement the value of the address.
The address management keys are disabled when the controls are being used.
A.A.G. Stucchi Light Management App User Manual
13www.aagstucchi.it
Select the option Dimming Group Lamp to enable brightness control by groups.The ONETRACK system can handle up to 4 separate groups of lamps.
As above, you can control the brightness of each group by tapping on the 4 bulb icons, or withthe slider control.
3.2 GROUP MODE BRIGHTNESS CONTROL
In this section we will see how to set the brightness of the lamps in broadcast and group mode.
To return to the previous session and control the lamps individually, select Dimmer Single Lamp; to return to the main page, select Return To Main Page.i
A.A.G. Stucchi Light Management App User Manual
14www.aagstucchi.it
4 DALI LAMP CONFIGURATION PAGE
This section explains how to configure and manage the DALI bus and the connected lamps.
As explained in the main section, to enter the configuration section, simply tap on the icon:
The following interface displays:
Here we can manage the installation of a DALI lamp system, test the on/off controls, and configure logical and group addresses.
A.A.G. Stucchi Light Management App User Manual
DALI Bus
1
2
21
40 54 63
15www.aagstucchi.it
To return to the main page, select Return To Main Page.
Let's take a closer look at these functions.
The menu is structured as follows:
Lamps Property
Locate Lamps
Return to Main Page
Modify Lamps Address
Test On/Off Light
Configure Group Lamps
Search Unandressed Lamps
Search Lamps
Clear Lamp
CleaList Lamp
Queries the status and configuration of the lamp.
The system searches for lamps which have a logical address - which are therefore already configured.
This option deletes the selected lamp from the bus.
This option deletes all lamps on the bus.
This option replaces the logical address assigned during the scan.
This option visually locates the lamp.
This search is slower since it scans randomly to obtain a response from the devices.The system now assigns addresses to the devices in increasing order from 0 to 63.
The system searches for lamps which have not been installed and configured on the DALI bus.
This DALI function groups a set of logical addresses into a single group address.
Lamp group configuration service.
Lamp location service - turns all lamps on the bus on and off automatically.
A.A.G. Stucchi Light Management App User Manual
16www.aagstucchi.it
The DALI protocol has 64 logical addresses (“0” to “63”), so that up to 64 lamps can be installed(per the Dali specification).
4.1 SEARCH LAMPS
When this option is selected, the application will search for all previously addressed and configured lamps on the bus.
This search only scans previously assigned addresses.
Select Stop Searching Lamps to stop the scan.
A.A.G. Stucchi Light Management App User Manual
17www.aagstucchi.it
4.2 SEARCH UNADDRESSED LAMPS
When this option is selected, the application will search for any lamps on the bus which have NOT been addressedand configured.
An unconfigured DALI device responds to the dimming command in broadcast mode only; no access requests are considered since the device does not have a logical address.This scan is slower than the previous one; the system first scans for devices on the bus to check for active logical addresses, and then scans for unaddressed devices.When the application finds a new device, it assigns it a free logical address in increasing order.
The service displays as follows:
A.A.G. Stucchi Light Management App User Manual
18www.aagstucchi.it
When the scan terminates, the following message displays:
For each new logical address it assigns, the system flashes the lamp for one second.To return to the main page, select Return To Main Page.
A.A.G. Stucchi Light Management App User Manual
19www.aagstucchi.it
4.3 CLEAR LAMP
When this option is selected, the application sends the delete command over the bus and the selected lamp's logical address is cancelled.You must first select the lamp to delete its logical address.
The application will prompt you to confirm the deletion option.
If you then want to re-install the lamp, use the Search Unaddressed Lamps option
Press No to abort the operation.Press Yes to delete the lamp.
A.A.G. Stucchi Light Management App User Manual
20www.aagstucchi.it
If you then want to re-install the lamp, use the Search Unaddressed Lamps option
4.4 CLEAR LIST LAMP
This option deletes the addresses of all scanned lamps, and sends the delete command for all listed lamps overthe bus.
Select Clear List Lamps
The application will prompt you to confirm the deletion option.
Press No to abort the operation.Press Yes to delete the lamp.
A.A.G. Stucchi Light Management App User Manual
21www.aagstucchi.it
4.5 MODIFY LAMPS ADDRESS
This option allows you to modify the logical addresses assigned to the listed lamps during the scan.
Select Modify Lamps Address to display a new list of lamps in the positions assigned during the scan.
The menu changes, and Modify Lamps Address is replaced by List Lamps Address.
To edit an address, select a lamp and follow the instructions:
A.A.G. Stucchi Light Management App User Manual
22www.aagstucchi.it
Now choose a free address (free addresses are marked “n Free”, where “n” is the unassigned address).
The lamp is now displayed in the new position with its new address.
Select No to quit the procedure, and Yes to update the list with the address change code “<*>” assigned to the selected lamp, as shown below.
A.A.G. Stucchi Light Management App User Manual
23www.aagstucchi.it
4.5.1 Aborting the new address assignment procedure
If you have selected the wrong lamp, simply select it again and follow the prompts:
Select List Lamps Address to return to the list of individual lamps.
A.A.G. Stucchi Light Management App User Manual
24www.aagstucchi.it
4.6 TEST ON/OFF LIGHT
This option allows to you identify which lamps have been addressed and their locations, by turning them on at maximum brightness.
Select Test On/Off Light to display a new list of lamps in the positions assigned during the scan.
Select a lamp to display the on/off test option.
Items which display (n) Free are unassigned addresses.
A.A.G. Stucchi Light Management App User Manual
25www.aagstucchi.it
4.7 CONFIGURE GROUP LAMPS
This option enables you to group sets of lamps on the Dali bus together, so that they can be controlled using a single group address.The DALI protocol provides for up to 16 groups of lamps, but the application is limited to 4 groups.A group can be represented graphically as follows:
Select Configure Group Lamps to run a service which reads the configuration of the DALI network.
A.A.G. Stucchi Light Management App User Manual
Addr1 2 3 4 5 6
Addr
Addr23 24 30 33 41 45
12 14 15 16 17 18Group 0
Group 1
Group 2
Scans for lamps in existing groups.Search Lamps Into Group
Clear Lamp Into Group
Test Lamps on Group 0
Test Lamps on Group 1
Test Lamps on Group 2
Test Lamps on Group 3
Return To Main Page
Turns a group of lamps on and off
Deletes a lamp from a group
4.7.1 Clear lamp into group
This option displays:
As shown in the picture to delete a lamp from a a group simpy press the lamp itself for a few seconds.
26www.aagstucchi.it
Once the configuration has been scanned, the following options are available:
A.A.G. Stucchi Light Management App User Manual
27www.aagstucchi.it
4.7.2 Test lamps on group (1..2..3..4)
Select an option to run the guided procedure for turning the group of lamps on and off.
4.7.3 Assigning a lamp to a group
Proceed as follows:
To return to the main page, select Return To Main Page.
Select the lamp as shown in the figure by pressing it for a few seconds.
The lamp is now marked with “<*>”.
Now select the menu option Memo Lamp into Group (1..2..3..4).
A.A.G. Stucchi Light Management App User Manual
28www.aagstucchi.it
To abort the procedure, simply select Abort Assign Group Procedure or touch the lamp marked “<*>” again.
A.A.G. Stucchi Light Management App User Manual
29www.aagstucchi.it
4.8 LAMP PROPERTIES
This option displays the lamp's factory settings.Simply select the option, select a lamp and wait for the system read its properties.
A.A.G. Stucchi Light Management App User Manual
30www.aagstucchi.it
4.9 BOOTLOADER SERVICE
AAG Stucchi products are continually evolving, and our firmware and software can be updated to ensure that they are compa-tible with the full range of commercial products.
This option allows you to update the firmware of the A.A.G. ONETRACK module.
When you launch the app, as described in par. 2.3 the following menu will display, which provides access to the module update page.
To update the module, press Connect Controller.
A.A.G. Stucchi Light Management App User Manual
31www.aagstucchi.it
Now press Download to start the update.Wait for the update to terminate.Press OK to return to the main page.
You will be prompted to turn the ONETRACK module off and back on again, since the update service only initiates during the first 5 seconds after power on, after which the programming app executes.Shut off power to the programmer, and wait 10 seconds to ensure that it has turned off completely.After 10 seconds, press OK on the app and power the ONETRACK module back on again.
The application will automatically connect to the update routine and display the following interface:
A.A.G. Stucchi Light Management App User Manual
32www.aagstucchi.it
The following message will display:
The update procedure is now complete.
4.9.1 Checking the ONETRACK module update
To make sure the update was successful, connect to the ONETRACK module and select Check Update.
Always check that the ONETRACK module's firmware is up to date when you install a new version of the app.
A.A.G. Stucchi Light Management App User Manual
A.A.G. STUCCHI s.r.l. u.s.Via IV Novembre 30/32, 23854 Olginate (LC) - ITALYPh. +39-0341-653111Fax [email protected]
A.A.G. STUCCHI NORTH AMERICA, INC.3400 Peachtree Road NE, Ste 945 Atlanta, GA 30326 - USAPh. +1-404-806-5399Fax [email protected]
A.A.G. STUCCHI ASIA PACIFIC LTD.Regional officeRoom 01, 11/fl., New Treasure Centre N° 10 Ng Fong Street, Kowloon - HONG KONGPh. +852-2578-8988Fax [email protected]
A.A.G. STUCCHI SHANGHAI LTD. Rm 3007, №738, Chang Yang Rd YangPu area, 200082 - SHANGHAIPh. +86-21-52389291Fax [email protected]