Page 1: A1 sk300 (electric)
Page 2: A1 sk300 (electric)

SK300Electrical Steam Humidifier

Page 3: A1 sk300 (electric)

• Permanent S/S evaporation chamber

• Patented water level control sensors

• Tubular heating elements with high coefficient of thermal expansion

• Electric compartment separate from boiling compartment

• Allows easy access for servicing and wiring

• Easy maintenance

Neptronic® SK300 a Unique Design

Approved with 2 year warranty

Page 4: A1 sk300 (electric)

SK300Electrical Steam Humidifier

Electronic and display

Boiling Compartment

Steam Supply

Page 5: A1 sk300 (electric)

Neptronic® SK300 a Unique Design

Power supply connector

Unique fill/drain connector

Drain pump

Easy to removeS/S permanent evaporation

chamber

2 fill valves for integrated drain

cooler

Boiling Compartment

Foam sensor

Page 6: A1 sk300 (electric)

Neptronic® SK300 a Unique Design

Water level sensor(mass and temperature)

EPDM gasket

Foam sensor

Evaporation Chamber

Heating Element

Page 7: A1 sk300 (electric)

SK300 Major Benefit

• Stainless steel, Teflon coated mass sensing probe

• Water mass is independent of water quality

The unique AFEC® system designed for:

1. maximizing energy efficiency of humidifiers

2. reducing maintenance time and cost

3. Ability to operate with any type of water: 1. Tap water: soft or hard2. DI (de-ionized water), 3. RO (Reverse Osmosis)

AFEC ® (Anti-Foaming Energy Conservation System)

Page 8: A1 sk300 (electric)

SK300 – Control Panel and Menu

POWERUnit is connected to power source

CHECKUnit indicates an abnormal condition of operation(i.e. blocked water supply )Or when flashing service is required

FILLWater supply valve is open

STEAMHumidifier is on and there is a

humidity demand

DRAINUnit is in drain cycle

AUTO Automatic operation

DRAIN Unit is in manual drain mode

OFF Unit is off

Page 9: A1 sk300 (electric)

Model Capacitylb/hr

PowerkW

Amperage Nb of

outletsDia. of outlets240V

/1ph208V/1ph

208V/3ph

480V/1ph

480V/3ph

600V/1ph

600V/3ph

SK302 6 2 8.5 10 - 4.5 - 3.5 - 1 1-3/8”

SK304 12 4 17 19 11.5 8.5 5 7 4 1 1-3/8”

SK306 18 6 26 30 16.5 13 7.2 10.5 6 1 1-3/8”

SK310 30 10 - - 28 - 12 - 10 1 1-3/8”

SK314 40 13.5 - - 38 - 16.5 - 13.5 1 1-3/8”

SK320 60 20 - - 57 - 25 - 20 2 1-3/8”

SK330 90 30 - - - - 36 - 30 2 1-3/8”

SK340 120 40 - - 120 - 50 - 40 2 2-1/8”

SK360 180 60 - - - - 72 - 60 3 2-1/8”

Master & slave configuration : up to 540 lb/hr (3 X 180 lb/hr)

SK300 – CharacteristicsSK300 – Characteristics

Page 10: A1 sk300 (electric)

SK300 Product Line ExtensionLarger Capacities

Model Capacitylb/hr

TotalkW Voltage Amp

SK370 210 lb/hr 70 kW480 Vac 84 A

600 Vac 70 A

SK380 240 lb/hr 80 kW480 Vac 96 A

600 Vac 80 A

SK390 270 lb/hr 90 kW480 Vac 109 A

600 Vac 90 A

Page 11: A1 sk300 (electric)

SK300 New Design

Page 12: A1 sk300 (electric)

SK300 – Controls Features• ON/OFF or modulating control functions

• Jumper Selectable• 0-10 VDC, 2-10 VDC, 4-20 mA

• BACnet compatible

• Holding temperature (70 ºC) for close RH % control• + /- 1% RH accuracy output

Page 13: A1 sk300 (electric)

SK300 - OptionsSteam Distribution

S.A.M. Steam Absorption Manifold

Multi SteamShort Absorption Manifold

SDU Space Distribution Unit

Page 14: A1 sk300 (electric)

Roof Mounted outdoor unit• Fully insulated cabinet• In program low temperature protection• Connection on side or through pipe chase• Optional electrical comparment cooler

for hot & dry climate region

SK300 - Options