A UK evacuation case study usingPathfinder questions the

suitability of fire safety guidanceStewart Brown BSc (Hons) Dip Stat FIFireE

University of South Wales, UK

[email protected]

Page 3: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

UK Guidance for staircases

Playback isn't supported on this device.

stopwatch

0:00 / 2:40

Page 4: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Sizing staircasesFlow rate and

capacity to hold

people taken into

account when

sizing staircases

Page 5: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Time to safetyWhen the last

person enters the

staircase people

are safe

Page 6: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

The starting point

Page 7: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Guidance

Page 8: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

GuidanceADB says maximum of

350 people

BS 9999 says maximum of

427 people

Page 9: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

The observed evacuationdrill

Page 10: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

One staircase discounted

Page 11: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Model

Page 12: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Times for each floor to evacuate

Page 13: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Safe?Building not considered safe

Remedial works were undertaken

Page 14: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Remaining QuestionIf the building had been code compliant

what would the evacuation times have been?

Page 15: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Pathfinder

Evacuation reproduced in Pathfinder

Page 16: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Model adjustments

Priorities and speeds adjusted to closely match observed

evacuation times.

Page 17: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Typical run

Playback isn't supported on this device.

BS9999 compliant building

0:00 / 1:31

Page 18: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Evacuation timesPopulation reduced to

be code compliant

(BS 9999)

Page 19: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Is there a problem?There appears to be a problem as people are unlikely

to survive on a fire floor for over 6 minutes.

And yet we have no history of deaths in office buildings

Page 20: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

BS 9999This is new code

It is less onerous than ADB

It has not stood the test of time as ADB has

Page 21: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

ADB compliant building

Population reduced to ADB max. and model run again

Page 22: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

Methodology

Playback isn't supported on this device.

BS9999 compliant two stairs fire on 6th

0:00 / 4:35

Page 23: A UK evacuation case study using Pathfinder questions the ... · A UK evacuation case study using Pathfinder questions the suitability of fire safety guidance Stewart Brown BSc (Hons)

SummaryPathfinder modeling shows that the assumed 2 and a half minutes

is unachievable when populations at maximum, under current

assumptions

But there is no history of fire deaths

New guidance (BS 9999) produces worse results than traditional

approach (ADB)

But ADB results were not great

Maybe we are too pessimistic about the performance of staircases

As use of BS 9999 continues to grow time may reveal the answer