92-24161-150-03 SUPERSEDES 92-24161-150-02 INSTALLATION INSTRUCTIONS HYDRONIC AIR HANDLER RWIT/RWIP DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY QUALIFIED SERVICE PERSONNEL. ISO 9001:2008

Upload: others

Post on 07-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

92-24161-150-03SUPERSEDES 92-24161-150-02

INSTALLATION INSTRUCTIONSHYDRONIC AIR HANDLERRWIT/RWIP

DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEPIN A SAFE PLACE FOR FUTURE REFERENCE BY QUALIFIED SERVICE PERSONNEL.

ISO 9001:2008

Page 2: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

2

IMPROPER INSTALLATION, ORINSTALLATION NOT MADE INACCORDANCE WITH THEUNDERWRITERS LABORATORY(UL) CERTIFICATION OR THESEINSTRUCTIONS, CAN RESULT INUNSATISFACTORY OPERATIONAND/OR DANGEROUS CONDI-TIONS AND ARE NOT COVEREDBY THE UNIT WARRANTY.

DUCT LEAKS CAN CREATE ANUNBALANCED SYSTEM ANDDRAW POLLUTANTS SUCH ASDIRT, DUST, FUMES AND ODORSINTO THE HOME CAUSINGPROPERTY DAMAGE. FUMESAND ODORS FROM TOXIC,VOLATILE OR FLAMMABLECHEM I CALS, AS WELL AS AUTO-MOBILE EXHAUST AND CARBONMONOXIDE (CO), CAN BE DRAWNINTO THE LIVING SPACETHROUGH LEAKING DUCTS ANDUNBALANCED DUCT SYSTEMSCAUSING PERSONAL INJURY ORDEATH (SEE FIGURE 2). • IF AIR-MOVING EQUIPMENT ORDUCTWORK IS LOCATED INGARAGES OR OFF-GARAGESTORAGE AREAS - ALL JOINTS,SEAMS, AND OPENINGS IN THEEQUIPMENT AND DUCT MUSTBE SEALED TO LIMIT THEMIGRATION OF TOXIC FUMESAND ODORS INCLUDING CAR -BON MONOXIDE FROMMIGRATING INTO THE LIVINGSPACE.

• IF AIR-MOVING EQUIPMENT ORDUCTWORK IS LOCATED INSPACES CONTAINING FUELBURNING APPLIANCES SUCHAS WATER HEATERS ORBOILERS - ALL JOINTS, SEAMS,AND OPENINGS IN THE EQUIP -MENT AND DUCT MUST ALSOBE SEALED TO PREVENTDEPRESSURIZATION OF THESPACE AND POSSIBLEMIGRATION OF COMBUSTIONBYPRODUCTS INCLUDINGCARBON MONOXIDE INTO THELIVING SPACE.

IN COMPLIANCE WITHRECOGNIZED CODES, IT ISRECOMMENDED THAT ANAUXILIARY DRAIN PAN BEINSTALLED UNDER ALLEVAPORATOR COILS AND UNITSCONTAINING EVAPORATORCOILS AND AIR HANDLERS USEDWITH EVAPORATOR COILS THATARE LOCATED IN ANY AREA OF ASTRUCTURE WHERE DAMAGE TOTHE BUILDING OR BUILDINGCONTENTS MAY OCCUR AS ARESULT OF AN OVERFLOW OFTHE COIL DRAIN PAN, ASTOPPAGE IN THE PRIMARYCONDENSATE DRAIN PIPING ORANY WATER LEAK POTENTIALFROM THE AIR HANDLER.

! WARNING

NOTICE

APPLICATION OF THIS HYDRONICAIR HANDLER SHOULD BEINDOORS. SPECIAL ATTENTIONSHOULD BE GIVEN TO UNITSIZING AND PIPING, FILLING, ANDPURGING.

NOTICE

FAILURE TO FOLLOW THISCAUTION MAY RESULT INPERSONAL INJURY. SHEETMETAL PARTS MAY HAVESHARP EDGES OR BURRS. USECARE AND WEAR APPROPRIATEPROTECTIVE CLOTHING.

CAUTION

NOTICE

SAFETY INFORMATION

WHEN AN AIR HANDLER ISINSTALLED SO THAT SUPPLYDUCTS CARRY AIR CIRCULATEDBY THE AIR HANDLER TO AREASOUTSIDE THE SPACECONTAINING THE AIR HANDLER,THE RETURN AIR SHALL ALSOBE HANDLED BY DUCT(S)SEALED TO THE AIR HANDLERCASING AND TERMINATINGOUTSIDE THE SPACECONTAINING THE AIR HANDLER.

INSTALLATION MUST COMPLYWITH ALL INSTALLATIONINSTRUCTIONS INCLUDING:• AIR HANDLER OPERATINGUNDER THERMOSTATICCONTROL;

• RETURN AIR DUCT SEALED TOTHE AIR HANDLER;

• AIR FILTERS IN PLACE;• RETURN AIR TEMPERATUREMAINTAINED BETWEEN 55°F(13°C) AND 80°F (27°C); AND

• CLEAN AIR HANDLER, DUCTWORK AND COMPONENTSUPON SUBSTANTIALCOMPLETION OF THECONSTRUCTION PROCESS,AND VERIFY AIR HANDLEROPERATING CONDITIONSINCLUDING FLOW RATE ANDTEMPERATURE RISE,ACCORDING TO THEINSTRUCTIONS.

! WARNING

! WARNING

HORIZONTAL UNITS MUST BECONFIGURED FOR RIGHT HANDAIR SUPPLY OR LEFT HAND AIRSUPPLY. HORIZONTAL DRAINPAN MUST BE LOCATED UNDERINDOOR COIL. FAILURE TO USETHE DRAIN PAN CAN RESULT INPROPERTY DAMAGE.

! CAUTION

WHEN USED IN COOLINGAPPLICATIONS, EXCESSIVESWEATING MAY OCCUR WHENUNIT IS INSTALLED IN ANUNCONDITIONED SPACE. THISCAN RESULT IN PROPERTYDAMAGE.

! CAUTION

CODES AND STANDARDS:IT IS THE RESPONSIBILITY OFTHE INSTALLER TO FOLLOW ALLNATIONAL CODES, STANDARDSAND LOCAL ORDINANCES, INADDITION TO INSTRUCTIONSLAID OUT IN THIS MANUAL. THEINSTALLATION MUST COMPLYWITH REGULATIONS OF THELOCAL BUILDING, HEATING,PLUMBING, AND OTHER CODES.WHERE LOCAL CODES ARE NOTAPPLICABLE, THE INSTALLATIONMUST COMPLY WITH THENATIONAL CODES AND ANY ANDALL AUTHORITIES HAVINGJURISDICTION.

! NOTICE

! WARNINGDO NOT OPERATE THE SYSTEMWITHOUT FILTERS. A PORTIONOF THE DUST ENTRAINED IN THEAIR MAY TEMPORARILY LODGEIN THE DUCT RUNS AND AT THESUPPLY REGISTERS. THISRESIDUE COULD SOIL CEILINGS,WALLS, DRAPES, CARPETS ANDOTHER ARTICLES IN THE HOUSE.SOOT DAMAGE MAY OCCURWITH FILTERS IN PLACE, WHENCERTAIN TYPES OF CANDLES,OIL LAMPS OR STANDING PILOTSARE BURNED.

Page 3: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

3

IMPORTANT: TO ENSURE PROPER INSTALLATION AND OPERATION OFTHIS PRODUCT, COMPLETELY READ ALL INSTRUCTIONS PRIOR TOATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, MAINTAIN OR REPAIRTHIS PRODUCT. UPON UNPACKING OF THE AIR HANDLER, INSPECT ALLPARTS FOR DAMAGE PRIOR TO INSTALLATION AND START-UP.

PROHIBITED APPLICATIONSRWI(-) HYDRONIC AIR HANDLERS ARE EQUIPPED STANDARD WITHSTAINLESS STEEL PUMPS AND COMPLY WITH CALIFORNIA PER AB1953AND VERMONT PER SB152 FOR USE IN AIR HANDLER AND IN AN OPENSYSTEM WITH POTABLE WATER.

CONTENTS

Safety Precautions ...................................................................................................1

Safety Information ....................................................................................................2

General Information..................................................................................................4

Location Requirements and Considerations ............................................................6

Selection Procedure .................................................................................................8

Ducting ...................................................................................................................10

Installation ..............................................................................................................12

Plumbing.................................................................................................................13

Electrical Wiring......................................................................................................16

Accessories ............................................................................................................16

Sequence of Operation ..........................................................................................20

Maintenance...........................................................................................................22

Troubleshooting......................................................................................................24

Wiring Diagrams................................................................................................25-26

IMPORTANT: All manufacturerproducts meet current Federal OSHAGuidelines for safety. CaliforniaProposition 65 warnings are requiredfor certain products, which are notcovered by the OSHA standards.

California's Proposition 65 requireswarnings for products sold in Californiathat contain, or produce, any of over600 listed chemicals known to the Stateof California to cause cancer or birthdefects such as fiberglass insulation,lead in brass, and combustion productsfrom natural gas.

All “new equipment” shipped for sale inCalifornia will have labels stating thatthe product contains and/or producesProposition 65 chemicals. Although wehave not changed our processes,having the same label on all ourproducts facilitates manufacturing andshipping. We cannot always know“when, or if” products will be sold in theCalifornia market.

You may receive inquiries fromcustomers about chemicals found in, orproduced by, some of our heating andair-conditioning equipment, or found innatural gas used with some of ourproducts. Listed below are thosechemicals and substances commonlyassociated with similar equipment inour industry and other manufacturers.

• Glass Wool (Fiberglass) Insulation• Carbon Monoxide (CO)• Formaldehyde• Benzene

More details are available at theWebsites for OSHA (OccupationalSafety and Health Administration), atwww.osha.gov and the State ofCalifornia's OEHHA (Office ofEnvironmental Health HazardAssessment), at www.oehha.org.Consumer education is important sincethe chemicals and substances on thelist are found in our daily lives. Mostconsumers are aware that productspresent safety and health risks, whenimproperly used, handled andmaintained.

! WARNING

Page 4: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

GENERAL INFORMATION

FIGURE 1THE RWI(-) SERIES HYDRONIC AIR HANDLERS ARE DESIGN-CERTIFIED BY UL

1. DOOR SWITCH2. JUNCTION BOX3. TRANSFORMERS4. CAPACITORS5. LOW VOLTAGE (THERMOSTAT) TERMINAL6. BLOWER

7. PUMP (IF REQUIRED)8. WATER INLET (OUTLET FOR 14” HAH)9. WATER OUTLET (INLET FOR 14” HAH)10. BLOWER MOTOR11. HYDRONIC COIL ASSEMBLY

S

11

8

9

10

6

4

7

5

1

2

3

4

ST-A1242-01-X1

Page 5: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

Association, Inc., BatterymarchPark, Quincy, MA 02269.” Thesepublications are:

• ANSI/NFPA No. 70-(Latest Edition)National Electrical Code.

• NFPA90A Installation of AirConditioning and VentilatingSystems.

• NFPA90B Installation of Warm AirHeating and Air ConditioningSystems.

• The equipment has beenevaluated in accordance with theCode of Federal Regulations,Chapter XX, Part 3280.

IMPORTANTINFORMATION ABOUTEFFICIENCY AND INDOORAIR QUALITYCentral cooling and heatingequipment is only as efficient as theduct system that carries the cooled orheated air. To maintain efficiency,comfort and good indoor air quality, itis important to have the properbalance between the air beingsupplied to each room and the airreturning to the cooling and heatingequipment. Proper balance and sealing of theduct system improves the efficiencyof the heating and air conditioningsystem and improves the indoor airquality of the home by reducing theamount of airborne pollutants thatenter homes from spaces where theductwork and/or equipment islocated. The manufacturer and theU.S. Environmental ProtectionAgency’s ENERGY STAR Programrecommend that central duct systemsbe checked by a qualified contractorfor proper balance and sealing.

DUCT LEAKS CAN CREATE ANUNBALANCED SYSTEM ANDDRAW POLLUTANTS SUCH ASDIRT, DUST, FUMES AND ODORSINTO THE HOME CAUSINGPROPERTY DAMAGE. FUMESAND ODORS FROM TOXIC,VOLATILE OR FLAMMABLECHEMICALS, AS WELL ASAUTOMOBILE EXHAUST ANDCARBON MONOXIDE (CO), CANBE DRAWN INTO THE LIVINGSPACE THROUGH LEAKINGDUCTS AND UNBALANCED DUCTSYSTEMS CAUSING PERSONALINJURY OR DEATH (SEE FIGURE2). • IF AIR-MOVING EQUIPMENT ORDUCTWORK IS LOCATED INGARAGES OR OFF-GARAGESTORAGE AREAS - ALL JOINTS,SEAMS, AND OPENINGS IN THEEQUIPMENT AND DUCT MUSTBE SEALED TO LIMIT THEMIGRATION OF TOXIC FUMESAND ODORS INCLUDINGCARBON MONOXIDE FROMMIGRATING INTO THE LIVINGSPACE.

• IF AIR-MOVING EQUIPMENT ORDUCTWORK IS LOCATED INSPACES CONTAINING FUELBURNING APPLIANCES SUCHAS WATER HEATERS ORBOILERS - ALL JOINTS, SEAMS,AND OPENINGS IN THEEQUIPMENT AND DUCT MUSTALSO BE SEALED TO PREVENTDEPRESSURIZATION OF THESPACE AND POSSIBLEMIGRATION OF COMBUSTIONBYPRODUCTS INCLUDINGCARBON MONOXIDE INTO THELIVING SPACE.

IMPROPER INSTALLATION, ORINSTALLATION NOT MADE INACCORDANCE WITH THE ULCERTIFICATION OR THESEINSTRUCTIONS, CAN RESULT INUNSATISFACTORY OPERATIONAND/OR DANGEROUS CONDI-TIONS AND ARE NOT COVERED BYTHE UNIT WARRANTY.

IN COMPLIANCE WITHRECOGNIZED CODES, IT ISRECOMMENDED THAT ANAUXILIARY DRAIN PAN BEINSTALLED UNDER ALLEVAPORATOR COILS OR UNITSCONTAINING EVAPORATOR COILSOR AIR HANDLERS USED WITHEVAPORATOR COILS THAT ARELOCATED IN ANY AREA OF ASTRUCTURE DAMAGE TO THEBUILDING OR BUILDING CONTENTSMAY OCCUR AS A RESULT OF ANOVERFLOW OF THE COIL DRAINPAN OR A STOPPAGE IN THEPRIMARY CONDENSATE DRAINPIPING.

required for the job specification. • Read the entire instructions beforestarting the installation.

• Some building codes require extracabinet insulation and gasketingwhen unit is installed in atticapplications.

• If installed in an unconditionedspace, apply caulking around thepower wires, control wires,refrigerant tubing and condensateline where they enter the cabinet.Seal the power wires on the insidewhere they exit conduit opening.Caulking is required to prevent airleakage into and condensate fromforming inside the unit, control box,and on electrical controls.

• Install the unit in such a way as toallow necessary access to thecoil/pump and blower/controlcompartment.

• Install the unit in a level position toensure proper condensatedrainage. Make sure unit is level inboth directions within 1/8”.

• Install the unit in accordance withany local code which may applyand the national codes. Latesteditions are available from:“National Fire Protection

RECEIVINGImmediately upon receipt, all cartonsand contents should be inspected fortransit damage. Units with damagedcartons should be openedimmediately. If damage is found, itshould be noted on the deliverypapers, and a damage claim filedwith the last carrier. • After unit has been delivered to jobsite, remove carton, taking carenot to damage unit.

• Check the unit rating plate for unitsize, voltage, phase, etc. to besure equipment matches what is

NOTICE

NOTICE

! WARNING

FIGURE 2MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES

5

Page 6: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

6

GENERAL INFORMATION1. IMPORTANT: If installing the unit

over a finished ceiling or livingarea, be certain to install anauxiliary condensate drain panunder the entire unit. Thisauxiliary drain pan should extendunder any evaporator coilinstalled with the air handler andthe open portion of thecondensate drain assembly.

2. IMPORTANT: If using a coolingevaporator coil with this airhandler:

Be sure the air passes over thecoil/pump before passing overthe cooling coil.

IMPORTANT: Support this unitwhen installed. Since this airhandler is suitable for attic orcrawl space installations, it maybe installed on combustible woodflooring or by using supportbrackets. See Figure 5.

5. IMPORTANT: If installing in autility room, be sure the dooris wide enough to:

a. allow the largest part of the airhandler to pass; or

b. allow any other appliance(such as a water heater)to pass.

6. IMPORTANT: This air handler isnot approved or recommendedfor installation on its back, withaccess doors facing upwards(see Figure 3).

CLEARANCE -ACCESSIBILITYThe design of air handlers with inputratings as listed in the tables underFigure 4 are certified by UL for theclearances to combustible materialsshown in inches.

See name/rating plate and clearancelabel for specific model number andclearance information.

Service clearance of at least 24” isrecommended in front ofall air handlers.

NOTE: Use recommended 24”clearance if accessibility clearancesare greater than fire protectionclearances.

Air handlers are shipped with abottom closure panel installed.When bottom return air is used,remove the panel by removing thetwo screws attaching the panel tothe front base angle.

SITE SELECTION1. Select a site in the building near

the center of the proposed, orexisting, duct system.

2. Locate the air handler to maintainproper clearance to combustiblesas shown in the following tables.

LOCATION REQUIREMENTS AND CONSIDERATIONS

FRONT

BACK

THE AIR INLET IS NOT ALLOWED TO BE AT THE FRONT OR BACK OF THE AIR HANDLER.

DO NOT POSITION THE AIR HANDLER ON ITS BACK OR WITH IT FACE DOWN. DO NOT CUT SIDES OF HORIZONTAL APPLICATION.

PROHIBITED INSTALLATIONSNOTE: MULTIPLE AIR HANDLERS CONFIGURED FOR INSTALLATION WITH A SINGLE TANKLESS WATER IS PROHIBITED.

ST-A1242-02-X0

FIGURE 3

ST-A1242-02-X0

Page 7: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

FIGURE 4CLEARANCE TO COMBUSTIBLES, UPFLOW, HORIZONTAL LEFT OR RIGHT, DOWNFLOW

RE

TUR

N A

IRS

UP

PLY

AIR

TOP

BOTTOM

LEFT

RIGHT

FRONT

OP

TIO

NA

L R

ETU

RN

AIR

CU

TOU

T (E

ITH

ER

SID

E)

OP

TIO

NA

L R

ETU

RN

AIR

CU

TOU

T (E

ITH

ER

SID

E)

A I R F L O W

ABC

REF

DE

F

G H

7

ST-A1242-03-X0

Mod

elA

BC

DE

F

RW

1*04

A241

414

1313

1613⁄16

1933⁄8

RW

1*06

A361

717

1 ⁄216

1 ⁄216

1 ⁄216

13⁄16

1945⁄8

RW

1*08

A482

121

2020

1613⁄16

1947⁄16

RW

1*10

A602

424

1 ⁄223

1 ⁄223

1 ⁄217

7 ⁄16

195 ⁄8

57⁄16

Note: Service clearance of 2

4” is re

commended in front o

f air handler.

Page 8: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

8

SELECTION PROCEDURE(WITH EXAMPLE)I. Define hot water load for the totalrequired domestic hot waterusage.

As an example, let’s assume that theselected Tankless Water Heater for yourwhole house solution is the RTG-74 andyour calculated heat gain and heat lossvalues are as stated in section II.

II. Determine cooling and heatingrequirements at design conditions:

The ACCA’s Manual J Residential LoadCalculation method is the establishedtrade standard, approved by ANSI, forthe correct siziing and selection ofHeating, Ventilation, Air-Conditioningand Refrigeration (HVACR) equipment inresidential homes. The most recentrevision is the eight edition, an all-inclusive new approach to ensuring thatIndoor Air Quality (IAQ) systems are asefficient, safe, and healthy as possible.Refer to the Air Conditioning Contractorsof America website at:http://www.acca.org/tech/manualj/ or aqualified HVACR contractor for furtherassistance.

Assumptions:

Required Cooling Capacity . 48,000 BTU/HR(Total Capacity)

Required Heating Capacity . 60,000 BTU/HR

Evaporator Air Quantity. . . . . . . . . 1600 CFM

External Static Pressure . . . . . . . 0.2 in. W.C.

Electrical Characteristics . . . . . . . . . 115-1-60

III. Determine total external staticpressure (ESP) at designconditions:

Before using the Airflow PerformanceTable calculate the total static pressurerequired. From the given example, notethe Wet Coil Pressure Drop (selectedfrom the field supplied EvaporativeCased Coil Installation Instructions), andthe Filter Pressure Drop. Determine bothstatic pressures at 1600 CFM:

Wet Coil Pressure Drop . . . .0.3 in. W.C.(From Coil Manufacturer’s Installation Instructions)

External Static Pressure . . . 0.2 in. W.C.(Ductwork, etc.)

Filter Pressure Drop . . . .08 in. W.C.(.08 inches if the included filter is used; refer tothe filter’s manufacturer’s instructions if another

filter is used.)

Total Static Pressure. . . 0.58 in. W.C.

IV. Select unit based on requiredcooling capacity airflow:

For an initial selection, choose a unitsize that will provide the requiredairflow. Refer to Airflow PerformanceTable. Note that at 0.6 ESP (externalstatic pressure) theRW1T06A3617NAA unit will deliver1560 CFM when configured for HIGHspeed.

V. Select heating capacity of unitto provide the requisite designcondition:

From the Hydronic Air Handler/Tankless Water Heater, note that theunit RW1T06A3617NAA, (as selectedabove) when matched with the RTG-95 Tankless Water Heater, willprovide 59.2 MBH (59,200 BTU/HR)at an input water temperature (to AirHandler) of 150°F.

3

2

Model Number Nomenclature 3 08 K A 5

M

RW 1 T 04 A 24 14 N A A ***TRADE BRANDR = RHEEM

PRODUCT CATEGORYW = HYDRONIC AIR HANDLER

STAGE OF AIR FLOW1 = SINGLE2 = TWO STAGEM = MODULATING

MOTOR TYPET = CONSTANT TORQUEV = VARIABLE SPEEDP = PSC

NOMINAL CAPACITY04 = 40,000 BTU/H06 = 60,000 BTU/H08 = 80,000 BTU/H10 = 100,000 BTU/H

MAJOR SERIESA = FIRST

OPTION CODEBLANK = NONE415 = WITHOUT PUMP

WIDTH14 = 14”17 = 17.5”21 = 21”24 = 24.5”

MAX COOLING AIRFLOW TONNAGE24 = UP TO 2 TON36 = UP TO 3 TON48 = 2.5 TO 4 TON60 = 3 TO 5 TON

VOLTAGEA = 115/1/60

CONTROLSC = COMMUNICATINGN = NON-COMMUNICATING

MINOR SERIESA = FIRST

Page 9: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

9

HYDRONIC AIR HANDLER ELECTRICAL PHYSICAL SPECIFICATIONS - ECO-TECH™ MODELSModel Numbers

Nominal Heating Capacity BTU/hr [kw] 40000 [11.7] 60000 [17.6] 80000 [23.4] 100000 [29.3]Air Side Temperature Rise* °F [°C] 32-53 [17.6-29.2] 24-43 [13.2-23.7] 25-49 [13.8-27.0] 25-46 [13.8-25.3]

Rated Heating CFM [L/s] 800 [378] 1200 [566] 1625 [767] 1800 [850]Cooling Range CFM [L/s] 600-800 [283-556] 800-1200 [283-612] 1000-1625 [472-775] 1200-1800 [612-804]Power Supply (V - HZ - PH) 115 - 60 - 1

Minimum Circuit Ampacity - Amps 8 10 12.9 12.9Max Rating of Over Current Protective Device - Amps 11.7 18 23.2 23.2

Maximum Fuse or Circuit Breaker Size - Amps 10 15 20 20Motor HP [W] 1/3 [248] 1/2 [373] 3/4 [559] 3/4 [559]

Blower (D x W) in [mm] 10 x 6 [254 x 152] 10 x 8 [254 x 203] 10 x 10 [254 x 254] 11 x 11 [279 x 279]Blower Motor Type EcoTech / ECM Type

Pump Type Wet RotorPump Power Supply (V - HZ - PH) 115 - 60 - 1Pump Motor RLA/LRA - Amps 1.8

Pump HP [W] 1/8 [.86]Pump Maximum Working Pressure psi [kPa] 125 [861]

Max Working Temperature °F [°C] 160 [71]Water Connection Type Copper Studs

Inlet Water Connection Diameter in [mm] 3/4 [19]Out Water Connection Diameter in [mm] 3/4 [19]

Shipping Weight LBS [kg] 91 [41] 100 [45] 122 [55] 129 [58]

RW1T04A2414NAA RW1T06A3617NAA RW1T08A4821NAA RW1T10A6024NAA

Model Numbers

Nominal Heating Capacity BTU/hr [kw] 40000 [11.7] 60000 [17.6] 80000 [23.4] 100000 [29.3]Air Side Temperature Rise* °F [°C] 32-53 [17.6-29.2] 24-43 [13.2-23.7] 25-49 [13.8-27.0] 25-46 [13.8-25.3]

Rated Heating CFM [L/s] 800 [378] 1200 [566] 1625 [767] 1800 [850]Cooling Range CFM [L/s] 600-800 [283-556] 800-1200 [283-612] 900-1625 [424-641] 1050-1850 [472-873]Power Supply (V - HZ - PH) 115 - 60 - 1

Minimum Circuit Ampacity - Amps 5 10 11 11Max Rating of Over Current Protective Device - Amps 7.0 15.3 17.6 18.2

Maximum Fuse or Circuit Breaker Size - Amps 15 15 15 15Motor HP [W] 1/5 [93] 1/2 [373] 3/4 [559] 3/4 [559]

Blower (D x W) in [mm] 10 x 6 [254 x 152] 10 x 8 [254 x 203] 10 x 10 [254 x 254] 11 x 11 [279 x 279]Blower Motor Type PSC

Pump Type Wet RotorPump Power Supply (V - HZ - PH) 115 - 60 - 1Pump Motor RLA/LRA - Amps 1.8

Pump HP [W] 1/8 [.86]Pump Maximum Working Pressure psi [kPa] 125 [861]

Max Working Temperature °F [°C] 160 [71]Water Connection Type Copper Studs

Inlet Water Connection Diameter in [mm] 3/4 [19]Out Water Connection Diameter in [mm] 3/4 [19]

Shipping Weight LBS [kg] 91 [41] 100 [45] 122 [55] 129 [58]

RW1P04A2414NAA RW1P06A3617NAA RW1P08A4821NAA RW1P10A6024NAA

Page 10: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

10

DUCTINGProper air flow is required for thecorrect operation of this air handler.Too little air flow can cause erraticoperation and can damage the heatexchanger. The duct system mustcarry the correct amount of air forheating and cooling if summer airconditioning is used. Size the ducts according toacceptable industry standards andmethods. The total static pressuredrop of the air distribution systemshould not exceed 0.8" w.c.

NOTE: Return air grilles and warm airregisters must not be obstructed

IMPORTANT: Some high efficiencyfilters have a greater than normalresistance to air flow. This canadversely affect air handler operation.BE SURE TO CHECK AIR FLOW.IMPORTANT: When using outsideair, design and adjust the system tomaintain a return air temperatureABOVE 50° F during the heatingseason.

FIGURE 5CUTOUT AND DRILL INFORMATIONUPFLOW ONLY

CUT OUT USING EMBOSSED ANGLES AS A GUIDE FOR THE

PROPER SIZE.

JACKET

*Solid metal bottom required if side duct penetration is used.

ST-A1242-04-X0

HYDRONIC AIR HANDLER HEATING PERFORMANCE

!"#$%&'()*&%"#$

+()*$%&,-$$.

/0#$%1"(&2#"#34&

-%$225%$63%&'()*

7$"#&8"-"43#9

:1($# ;5#($# <$(#" :1($# ;5#($# <$(#"

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

63%&7"1.($%&=).$(

>?@=A >%-BA >31C&*C4CA >8D=A

1234 #&% !+## (+&##

!"#$%&E$B-$%"#5%$ 63%&E$B-$%"#5%$

>FDA >FDA

(+&##1234 #&%$ !"##

(+&##!("%#&%1234

>+#5GH%A

(+&##1234 #&%* +##

*NOTE: Capacities are based on a constant inlet water temperature supplied by a tankless water heater and do not apply to storage tank applications.

Page 11: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

11

FIGURE 6POSITION ORIENTATION

ST-A1242-05-X0

UPFLOW UNITS1. Position the unit to minimize long

runs of duct or runs of duct withmany turns and elbows.

2. Open the return air compartment.

a. Cut an opening in the side.The opening should be cut the full width of theknockouts on the unit. SeeFigure 5.

NOTE: Where the maximum air flowis 1800 CFM or more, both sides orthe bottom must be used for returnair.

3. Connect the return duct or returnair cabinet to the unit. Make theconnection air tight to prevententraining combustion gasesfrom an adjacent fuel-burningappliance.

4. Be sure to have adequatespace for the unit filter.

NOTE: DO NOT take return airfrom bathrooms, kitchens, airhandler rooms, garages, utility orlaundry rooms, or cold areas.

NOTE: DO NOT use a rear airreturn.

5. If summer air conditioning (heatpump) is desired, position theindoor coil on the top of the unit.Insure that no air can bypass thiscoil.

6. Connect the supply air plenum tothe air handler plenum opening.

HORIZONTAL UNIT1. Position the unit to minimize long

runs or runs with many turns andelbows.

2. If summer air conditioning or heatpump is desired, position theindoor coil on the supply air endof the unit. Insure that no air canbypass this coil.

3. Connect the air handler to thesupply air plenum.

4. Connect the return air ducting tothe return air opening of the unit.Make the connection air tight toprevent pulling combustion gasesfrom an adjacent fuel-burningappliance.

5. Be sure to have adequatespace for the unit filter.

NOTE: DO NOT take return airfrom bathrooms, kitchens, airhandler rooms, garages, utility orlaundry rooms, or cold areas.

DOWNFLOW UNITS1. Position the unit to minimize long

runs of duct or runs of duct withmany turns and elbows.

2. If summer air conditioning isdesired, position the indoor coilon the supply air side of the unit.Insure that no air can bypass thiscoil.

3. Connect the furnace to thesupply air plenum.

4. Connect the return air ducting tothe return air opening at the topof the unit. Make the connectionair tight to prevent entrainingcombustion gases from anadjacent fuel-burning appliance.

5. Be sure to have adequate spacefor the unit filter.NOTE: DO NOT take return airfrom bathrooms, kitchens,furnace rooms, garages, utility orlaundry rooms, or cold areas.

Page 12: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

12

SUSPENDED CABINETINSTALLATIONIf the cabinet cannot be supported on aframe or supported from the wall, it maybe suspended.

Use metal strapping or threaded rod withangle iron supports under cabinet forsupport. These supports MUST runparallel with the length of the cabinet.

Ensure that there is adequate room toremove service and access panels afterinstalling supporting brackets.

If an auxiliary drain pan is required, thesupport is to be placed under a drainpan.

IT IS THE INSTALLER’SRESPONSIBILITY TO USE ANAPPROPRIATE HANGING METHODCAPABLE OF SUPPORTING THEUNIT’S WEIGHT. REFER TO THESPECIFICATION SECTION OF THISDOCUMENT FOR THE RESPECTIVEUNIT’S INSTALLED WEIGHTS.

FOR SEISMIC HANGINGREQUIREMENTS, REFER TO LOCALCODES.

Attachment Methods Using Straps

Method 1

Use (4) #8 x 3/4 sheet metal screwsfor each strap. The straps should bevertical against the air handler sidesand not pull away from the air handlersides.

Method 2

Fold all straps under the air handlerand secure with (4) #8 x 3/4 sheetmetal screws (2 screws at the sideand 2 screws at the bottom. (Caremust be taken not to drive the screwthrough the coil.)

INSTALLATION

! WARNING

NOTICE

FIGURE 7HORIZONTAL UNIT SUSPENSION

Refer to the specification section of this d

T

DOORASSEMBLY

8” MIN FORDOOR REMOVAL

(2) HEX NUTS, (2) WASHERS & (2)LOCK WASHERS REQ. PER ROD

USE 1” SQUARE, 1-1/4 x 1-1/4 x 1/4ANGLE IRON OR EQUIVALENT

SECURE ANGLEIRON TO BOTTOMOF AIR HANDLERWITH 3 #8 x 3/4”SCREWS TYPCIALFOR 2 SUPPORTS

1/4” THREADED ROD(4 REQUIRED)

F

U

F

FIGURE 8HORIZONTAL UNIT SUSPENSION WITH STRAPS

DOORS

1 INCH x 22 GAUGEGALVANIZED STRAPSTYPICAL FOR 4 STRAPS

RETURN AIROPENING

SUPPLY AIR OPENING

BACK

Page 13: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

13

PLUMBING Codes: The RW1T air handler is used in potablewater systems. Therefore, it is importantto observe all local sanitary codes wheninstalling water lines. The water supplymating connection to the Hydronic AirHandler is made via the two 3/4 in. dia.copper stubs labeled “WATER IN” and“WATER OUT” (see Figure 1).

All associated hydronic piping MUSTcomply with ICC, UPC and any otherlocal codes or ordinances havingjurisdiction. USE POTABLE GRADECOPPER PIPING AND BRASSAPPURTENANCES ONLY.

Soldering Copper Tubing: The common method of joining coppertubing in hydronic heating systems issoft soldering. Plumbing codes do notallow solders containing lead to be usedfor domestic water service. USE ONLY95/5 tin/antimony solder for all pipingsystems that incorporate a domesticwater supply.

NOTE: Precautions must be takenduring soldering to avoid debris orsolder from lodging in piping system.

Water Storage Tank: When connecting directly to a waterstorage tank it is necessary to ensurethe water flow rate does not becomeexcessive. Excessive water flow canresult in increased system noise andpotential system damage. In order toregulate the flow it is required that anadjustable valve be placed between theair handler outlet and the storage tankRheem Accessory HC. Furthermore, twopressure taps will need to be installed,the first located between the air handleroutlet and the adjustable valve as nearas possible to the outlet, and the secondon the inlet water attached as near aspossible to the inlet. While the waterpump is engaged the adjustable valvewill be closed until the pressuredifference between the outlet and theinlet is greater than 13.5 PSID.

Tubing Insulation:Any tube-conveying fluid at atemperature greater than that of thesurrounding air releases heat.

Insulate all accessible hot water linesand associated valves with material,such as expanded neoprene orpolyurethane 3/8-in. to 1⁄2-in. thick.

Match the pipe sleeve’s inside diameterto the pipe’s outside diameter for a snugfit. Place the pipe sleeve so the seamwill be face down on the pipe. Tape,wire, or clamp insulation every foot ortwo to secure it to the pipe. If taping isdesired, use acrylic tape instead of ducttape.

Copper Tubing Support: Copper tubing must be properlysupported to prevent sagging orbuckling. On horizontal runs with hardtemper tubing, the following maximumsupport spacing is suggested:

• 1/2 in. to 3/4 in. tube: 5 feet maximumspacing

• 1 in. to 1-1/4 in. tube: 6 feet maximumspacing

The above suggested spacing does notaccount for extra weight of pipingcomponents such as an expansion tank,etc. When such components arepresent, the piping should be supportedimmediately adjacent to the component.

On vertical runs, copper tubing shouldbe supported at each floor level or at amaximum of every 10 feet.

Thermal Expansion of Piping: In all hydronic systems, pipingundergoes temperature swings as thesystem operates. This causes changesin the length of the piping due to thermalexpansion.

If the piping is rigidly mounted, thisexpansion can cause annoying poppingor squeaking sounds and, in extremecases, the piping can even buckle.

To counter expansion movement,design piping circuits with sufficientelbows, tees or expansion loops (onlyused in large systems) or pipingsupports that allow the tubing to expandand contract freely.

Another alternative is to install anexpansion compensator fitting capableof absorbing the movement.

Hydronic Resistance ofFittings, Valves, and OtherDevices: Before the total hydronic resistanceof a piping circuit can be found, theindividual hydronic resistances of allfittings, valves, or other suchcomponents must be determined.One approach is to consider eachfitting, valve, or other device as anequivalent length of copper tube ofthe same pipe size (see Table 1).

By using the equivalent length ofpiping for all components in thecircuit, the circuit can be treated as ifit were a single piece of pipe havinga length equal to the sum of theactual pipe length, the totalequivalent lengths of all fittings,valves, or other devices. Refer toFigure 9 and the calculation ofequivalent lengths.

Pipe Sizing Considerations: When selecting a pipe size for agiven flow rate, the resulting averageflow velocity should be between 2and 4 feet per second.

At water flow velocities ofapproximately 2 feet per second,flowing water will carry air bubblesalong a vertical pipe. Average flowvelocities of 2 feet per second orhigher can draw along air bubbles ina downward flow. At the abovestated velocities air bubbles shall berouted to an air separator where theycan be collected and discharged fromthe system. Use Taco 4900 series airseparator, Model 49-075, orequivalent (field supplied).

Average flow velocities higher than 4feet per second could cause flownoise and should be avoided.

Expansion Tank: All liquids used in hydronic heatingsystems expand when heated. Forall practical purposes, liquids areincompressible. Any containercompletely filled with a liquid andsealed from the atmosphere willexperience a rapid increase inpressure as the liquid is heated.

To prevent this from occurring, allclosed-loop hydronic systems MUSTbe equipped with an expansion tank.Refer to expansion tank man u fac -turer’s instructions for proper sizingand installation.

Water circulation:The hydronic air handler has a strictin press cycle which will circulate thewater in the coil for 6 minutes per dayto prevent water stagnation.

Page 14: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

14

PROCEDURE FORCALCULATING THE TOTALEQUIVALENT LENGTH OF PIPE

Given piping assembly as shown inFigure 9 below, what is the totalequivalent length of the system?

First determine the total straight pipelengths; next refer to Table 1 todetermine the equivalent straight pipelength for each fitting shown. Addtogether the equivalent lengths of pipingand fittings.

(3/4”) Tubing 24 ft.

7 (3/4”) 90 deg. Elbows 7 (1.9) = 13.3 ft.

5 (3/4”) Side Port Tees 5 (3.8) = 19.0 ft.

1 (3/4”) Taco air separator = .3 ft. 2 (3/4”) Ball Valve 2 (.2) = .4 ft.

Total Equivalent Length . . . . . = 57 ft.

WHERE POSSIBLE THE LENGTH OFPIPE SHOULD NOT EXCEED 100FEET TOTAL EQUIVALENT LENGTH.

ANY PIPING RUNNING THROUGHUNCONDITIONED SPACE MUST BEINSULATED TO PREVENT HEATLOSS, AND POSSIBLE FREEZING OFTHE LINE.

STICKERS INDICATING DIRECTIONOF FLOW (WATER IN AND WATEROUT) ARE LABELED ON THEOUTSIDE OF THE CABINET. DO NOTREVERSE THESE LINES, AS THISWILL CAUSE THE UNIT TOMALFUNCTION.

Piping Configuration When employing a Tankless WaterHeater in a hydronic system, thesystem is considered an open-loopsystem when configured tosimultaneously deliver both domestichot water and space heating. Bydefinition, if the circuit is sealed offfrom the atmosphere at all locations(as is true for most modern hydronicsystems), it is called a closed-loopsystem. If the circuit is open to theatmosphere at any point, it is calledan open-loop system.

NOTICE

FIGURE 9EQUIVALENT LENGTH CALCULATION

COLDHOTT3T1

1-1/2 FT

BV1

1 FT

T4

EV2

COLDWATERSUPPLY

T2

T5

EL7

2 FT1-1/2 FT

TEMPEREDWATER

AS

EL5

1 FT

EL6 2 FT

1 FT

4 FTEL4

4 FT

3 FT

EL3

IN

1/2 FT

EL2

EL1

1 FT

OUT

AIRHANDLER

Flow control Valve(Storage tank and pumplessapplications only)

Pumpless only

WATER HEATER

Table 1 – Equivalent Length of Straight Pipe for Valves and Fittings (ft)

Diameter (in.)

0.375 0.5 0.75 1 1.25 1.5

Globe Valve 14.1 18.8 28.1 37.5 46.9 56.3

Angle Valve 6.3 8.3 12.5 16.7 20.8 25.0

Gate Valve 0.5 0.7 1.1 1.4 1.8 2.1

Ball Valve (BV) 0.1 0.1 0.2 0.3 0.3 0.4

90 Degree Standard Elbow 0.9 1.3 1.9 2.5 3.1 3.8

45 Degree Standard Elbow 0.5 0.7 1.0 1.3 1.7 2.0

Standard Tee with flow through run 0.6 0.8 1.3 1.7 2.1 2.5

Standard Tee with flow through branch 1.9 2.5 3.8 5.0 6.3 7.5

ST-A1242-09-00

*Optional for pump only and storage tank water heaters.

Page 15: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

15

FIGURE 10TYPICAL PIPING ARRANGEMENT FOR DIRECT SPACE HEATING AND DOMESTIC WATER SUPPLY WITH TANKLESS

Open-Loop System If piping is done in accordance with therecommended schematic diagramshown in Figure 10, the following purgeand priming procedure applies.

PURGING AND PRIMING THESYSTEM: The following procedure describes howthe system may be piped to eliminatethe need for a “purge cart” to fill thesystem and remove entrapped airbubbles.

STEP 1: CLOSE the air separatorventing valve.

STEP 2: CLOSE ball valve 3 (BV3);

STEP 3: OPEN drain valve 3 (DV3) towhich a hose MUST be connected anddraining to a sink, drain or outdoors.

STEP 4: CLOSE drain valves 1 & 2(DV1 and DV2) and OPEN ball valve 2(BV2).

STEP 5: OPEN cold water supply mainvalve (ball valve 1 - BV1). The systemwill begin the prime/purge process usingthe street pressure. Entrapped airbubbles being pushed out of the systemwill be evident by a slight vibration of thedischarge hose connected to drain valve3 (DV3). The hose will stop vibratingwhen laminar flow is achieved.

STEP 6: CLOSE drain valve 3 (DV3);

STEP 7: OPEN ball valve 3 (BV3).The system is now purged, primedand ready to go.

STEP 8: OPEN the air separatorventing valve.

NOTE: For an open-loop system, useexpansion tank approved for potablewater use only.

Pumpless only

ST-A1242-08-00

Page 16: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

16

jurisdiction. USE COPPER WIREONLY. Provide separate branch electriccircuit with field supplied disconnectswitch.Location of disconnect switch to be inclear site, accessible and in closeproximity to the unit.Correct polarity MUST be maintained for115 V wiring. If polarity is incorrect, unitwill NOT operate.Use a separate fused branch electricalcircuit containing a properly sized fuseor circuit breaker. Run this circuit directlyfrom the main switch box to an electricaldisconnect that is readily accessible andlocated near the air handler. Connectfrom the electrical disconnect to thejunction box on the left side of the airhandler, inside the blower compartment.For the proper connection, refer to theappropriate wiring diagram located onthe inside cover of the air handlercontrol box and in these instructions.The electrical junction box may bemoved to the right side if necessary. Aknockout is provided. Seal the oppositehole with plug provided.Make all electrical connections inaccordance with the latest edition of theNational Electrical Code, ANSI/NFPA70and local codes having jurisdiction.These may be obtained from:National Fire ProtectionAssociation, Inc.

Batterymarch ParkQuincy, MA 02269

CSA - International178 Rexdale Blvd.Etobicoke (Toronto), OntarioCanada M9W, 1R3

ELECTRICAL WIRING

TURN OFF ELECTRIC POWER ATFUSE BOX OR SERVICE PANELBEFORE MAKING ANYELECTRICAL CONNECTIONS.FAILURE TO DO SO CAN CAUSEELECTRICAL SHOCK RESULTINGIN PERSONAL INJURY OR DEATH.

THE CABINET MUST HAVE ANUNINTERRUPTED GROUNDACCORDING TO THE LATESTEDITION OF THE NATIONALELECTRICAL CODE (NEC), ANSI/NFPA70- OR IN CANADA, THECANADIAN ELECTRICAL CODE,CSA-C221 OR LOCAL CODESTHAT APPLY. DO NOT USE GASPIPING AS AN ELECTRICALGROUND. A GROUND SCREW ISPROVIDED IN THE JUNCTIONBOX. FAILURE TO DO SO CANCAUSE ELECTRICAL SHOCK,RESULTING IN PERSONALINJURY OR DEATH.

THIS AIR HANDLER IS EQUIPPEDWITH A BLOWER DOOR SAFETYSWITCH. DO NOT DISABLE THISSWITCH. FAILURE TO FOLLOWTHIS WARNING CAN RESULT INELECTRICAL SHOCK, PERSONALINJURY OR DEATH.IMPORTANT: The air handler mustbe installed so that the electricalcomponents are protected from water(condensate).Before proceeding with the electricalconnections, be certain that thevoltage, frequency and phasecorresponds to that specified on theair handler rating plate. For single airhandler application, maximum over-current protection is 15 amperes.

IF A DISCONNECT SWITCH IS TOBE MOUNTED ON THE UNIT,SELECT A LOCATION WHERE ADRILL OR FASTENER WILL NOTCONTACT ELECTRICAL ORHYDRONIC COMPONENTS.ELECTRICAL SHOCK CAN CAUSEPERSONAL INJURY OR DEATH.NOTE: Prior to making any electricalconnections, ensure that supplyvoltage, frequency, and phase are asspecified on unit rating plate.Check to ensure that the existingelectrical service is adequate tohandle the additional load imposed bythe Hydronic Air Handler. Refer tounit wiring diagram for properelectrical connections.All electrical connections MUSTcomply with NEC and any other localcodes or ordinances having

! WARNING

! WARNING

! WARNING

! CAUTION

THERMOSTATThe room thermostat must be com-patible with the integrated air handlercontrol on the air handler. Generally,all thermostats that are not of the“current robbing” type are compatiblewith the integrated air handler control.The low voltage wiring should besized as shown (see Figures 12 and13).NOTE: Do not use 24 volt controlwiring smaller than No. 18 AWG.Install the room thermostat inaccordance with the instruction sheetpacked in the box with the thermostat.Run the thermostat lead wires insidethe blower compartment and connectto low voltage terminals as shown onthe wiring diagram. Never install thethermostat on an outside wall orwhere it will be influenced by drafts,concealed hot or cold water pipes orducts, lighting fixtures, radiation fromfireplace, sun rays, lamps, televisions,radios or air streams from registers.Refer to instructions packed with thethermostat for “heater” selection oradjustment.

ACCESSORIESFIELD-INSTALLEDOPTION ACCESSORIESELECTRONIC AIR CLEANERLine voltage power can be suppliedfrom the screw terminal “EAC” and aline voltage neutral screw terminal onthe control board. This will power theelectronic air cleaner whenever thecirculating air blower is in operation.

Expansion Tank: Expansion tank for closed systemsair separator – TACO Model 49-075.

Page 17: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

*Requires Fossil Fuel KitRefer to Kit for further wiring instructions.

17

FIGURE 11FIELD WIRING DIAGRAM

W G R C Y1

Y1

Y2

W

G

B

R

CP3

FS

BLK

WHT

AIR HANDLER

Flow Sensor(Packaged with Unit)

5 Wire

3 Wire Heating Only

Single StageThermostat

24 Volt FS / WH Connector

24 Volt Terminal Block

Control Box

PCB

Condensing Unit

Field 115, 208 / 230 Volt Wiring

Field 24 Volt Wiring

Factory 24 Volt Wiring

Factory 115 Volt Wiring

Junction Box

L1

L2

FIGURE 12THERMOSTAT WIRING DIAGRAMSSINGLE STAGE AIR HANDLER W/SINGLE STAGE A/C

FIRST STAGE HEAT/COOL

AUX HEATING

FAN

24VAC HOT

24 VAC COMMON

SINGLE STAGEAIR-HANDLER

SINGLE SPEEDCONDENSING

UNIT

HEAT/COOL & COOL ONLYTHERMOSTATS

Y1

W

G

R

C

Y1

Y2

W

G

B

R

C

Y1

C

FIGURE 13THERMOSTAT WIRING DIAGRAMSSINGLE STAGE AIR HANDLER W/SINGLE STAGE HEAT PUMP*

FIRST STAGE HEAT/COOL

AUX HEATING

FAN

RVS HEATING

24VAC HOT

24 VAC COMMON

HEAT PUMP THERMOSTATS SINGLE STAGEAIR-HANDLER

SINGLE STAGEHEAT PUMP

Y1

W

G

B

R

C

Y1

W

G

B

R

C

Y1

B

R

C

Y2

F

Page 18: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

18

TABLE 2

System Low Voltage WiringDiagramsNOTE: Local codes may requirethermostat wiring to be routed throughconduit or raceways. In such instancessplices can be made inside the HydronicAir Handler. All wiring must be NEC ClassI and must be separated from incomingpower leads.

Provide field-supplied disconnect formaximum fuse or circuit breaker sizes, asrequired by code.

Transformer is factory wired for 115Voperation.

The secondary circuit of the transformeris protected by a 3-amp fuse mounted onthe printed circuit board.

FIGURE 14HYDRONIC AIR-HANDLER CONTROL BOARD

NOTES:1. For proper operation of an open loop system (refer to Figures 11 and 17), the jumper (shunt) position on PCB point “P7” should be in

the FS position.2. When changing shunt position ensure that unit power is turned off.

Wire Gauge Maximum Distance (feet)

18 gauge 60

16 gauge 100

14 gauge 160

12 gauge 250

Dip Switch Options:

Refer to the appropriate diagram for theproper dip switch setting to be used withthe designed application (Figure 17).

THERMOSTAT INSTALLATION:

Thermostat should be mounted:

• approximately 5 ft. (1.5 m) from floor

• close to or in a frequently usedroom, preferably on an inside,partitioning wall

• on a section of wall without pipesor duct work.

Thermostat should NOT be mounted:

• close to a window, on an outsidewall, or next to a door leading tothe outside.

Page 19: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

19

• exposed to direct light and heat froma lamp, sun, fireplace, or other heat-radiating object which may cause afalse reading.

• close to or in direct airflow fromsupply registers and return-air grilles

• In areas with poor air circulation,such as behind a door or in an alcove

Refer to thermostat wiring diagram andthermostat installation instructions forfurther details.

START-UP PROCEDURE(HEATING ONLY): The following conditions must be metprior to unit start-up.

Debris from soldering and/or otherinstallation activities can causeequipment failure. Ensure that allassociated lines and appurtenancesare free of debris.

Check to ensure that unit is secure.

Check that blower wheel rotates freelywithin the scroll housing.

Check all wiring to ensure thatconnections are tight.

Check all ductwork and pipeconnections to ensure proper seal.

Check to ensure that all packagingwraps are removed from equipment.

Ensure that front access doors areproperly installed.

Check to ensure proper connection(s)to the appropriate blower speed tap(Heat /Cool – High and Low). Refer toDry Air Delivery Table and/or theappropriate wiring diagram(s) in thismanual.

Perform all safety and start-up checksfor Tankless Water Heater as permanufacturer’s instructions.

Having verified all preceding checks,the Air Handler’s Start-Up Procedure isas follows:

STEP 1: Purge and fill system; followappropriate purging procedure as laidout in this manual in section titled“Purging and Priming the System”.

STEP 2: Turn on power supply to airhandler. Caution: blower and/orcirculator may start to operate ifthermostat is on and a call is present.

STEP 3: Turn thermostat ON andswitch system to the heating mode.The thermostat shall be set higher thanthe actual room temperature; this willcause the circulator to energize andinitiate the heating cycle. (If the pumpdoes not start, or the Air Handler is notproducing heat, refer to theTroubleshooting Section, in thismanual).

STEP 4: Program room thermostat asdesired by homeowner.

START-UP PROCEDURE(COOLING SYSTEM) Refer to field-supplied evaporator coiland outdoor unit manufacturer’sInstallation Instructions for systemhook-up, start-up instructions andrefrigerant-charging method details.

TROUBLESHOOTING BLOWERAND/OR PUMP MOTOR ANDCONTROLS If blower and/or pump motor doesnot run:

Turn OFF power and check thefollowing:

1. Check that door switch is in theCLOSED position.

2. Check 3 amp fuse on PrintedCircuit Board (PCB).

3. Check for 24 VAC between COMand 24 VAC on IAC. If no voltageis present, check transformer.

4. Check all connections for kinkswhich could cause looseconnections. Ensure connectionsare secure.

5. Verify that approximately 120VAC is present across L1 and L2.

LED FAULT CODES ONCONTROL BOARDThe control board of the air handlerhas an LED light that flashes in anumber sequence for a given faultcondition. Below is a summary ofwhat the flashes mean.

1 - Fault displayed when supplysensor open or shorted

2 - Fault displayed when returnsensor open or shorted

3 - Fault displayed when heat modeactive

4 - Displayed when in five minutedelay

FIGURE 15DIP SWITCH POSITIONS

30 SECONDS OFFDELAY (DEFAULT)

60 SECONDS OFFDELAY

1 ON234 1 O

N234

90 SECONDS OFFDELAY

120 SECONDS OFFDELAY

1 ON234 1 O

N234

1 ON

Key:

Switch is in the ON position.

Switch does not affect this setting.

1 ONSwitch is in the OFF position.

TWO-STAGE A/CCONFIGURATION

TWO-STAGE HPCONFIGURATION

1 ON234 1 O

N234

Page 20: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

20

blower tap (COOL_HI).

• When the thermostat ends the call forcooling (Y), there is a 30 secondcooling off delay then the control de-energizes the high blower tap(COOL_HI).

• When the thermostat calls foremergency heat (W), the hydronicheating mode is activated.

BLOWER TIME DELAY (HEATINGOR COOLING)All models are equipped with a blowertime delay (BTD) in lieu of a blower relay(BR) (see Figure 19). The blower will runfor 30 seconds after the blower timedelay (BTD) is de-energized.

DEFROST (DEFROST HEATCONTROL)• For sequence of operation of defrostcontrols, see outdoor heat pumpinstallation instructions.

• Supplemental heat during defrost canbe provided by connecting the purple(PU) pigtail in the outdoor unit to theW on the thermostat. This willcomplete the circuit between R and Wthrough a set of contacts in the defrostrelay (DR) when the outdoor heatpump is in defrost. This circuit, ifconnected, will help prevent cold airfrom being discharged from the indoorunit during defrost.

• For most economical operation, if coldair is not of concern during defrost, thepurple wire can be left disconnected.Supplemental heat will then come ononly when called for by second stageroom thermostat.

EMERGENCY HEAT (HEATINGHEAT PUMP)• If selector switch on thermostat is setto the emergency heat positioin, theheat pump will be locked out of theheating circuit, and all heating will behydronic heat. Jumper should beplaced between W and E on thethermostat sub-base so that theelectric heat control will transfer to thefirst stage heat on the thermostat. Thiswill allow the indoor blower to cycle onand off with the electric heat when thefan switch is in the auto position.

SEQUENCE OF OPERATIONCOOLINGSingle Stage Cooling• When the thermostat calls for cooling(Y), there is a 1 second delay thenthe control energizes the high blowertap (COOL_HI).

• When the thermostat ends the call forcooling (Y), there is a 30 secondcooling off delay then the control de-energizes the high blower tap(COOL_HI).

• A call for cooling has priority overcontinuous fan.

HEATING (HYDRONIC)• On a call for heating the pump willstart.

• After a sixty second delay the controlwill look at the FS jumper if this isjumpered the control will go intowater heating mode and ignore thetemperature sensors.

• If the air supply temperature isgreater than 85°F the control willenergize the indoor blower. If the airtemperature is less than 85°F thecontrol will turn off the pump and gointo a 5 minute delay.

• If the supply temperature is adequatethe main blower will then beenergized and run for 30 seconds.

• After the 30 second delay the controlwill monitor the supply temperature. Ifthis drops the control will turn off thepump and go into a 5 minute delay. Ifthe temperature is greater than theshut off temperature the control shallremain in heating mode.

• There must be a minimum delta of10°F to remain in the heating mode.

• When the W call ends the pump shallde-energize the blower shall turn offafter a blower off delay.

The FS input shall be used to allow away to bypass the system to allow it torun. If this is jumpered the control willignore the temperature and go into aheating cycle.

HEATING (Heat pump is theprimary source of heat)Single Stage Heating

• The thermostat calls for heating (Y,R, and B), there is a 1 second delaythen the control energizes the high

ROOM THERMOSTAT(ANTICIPATOR SETTING)See instructions with outdoor section,condensing unit or heat pump forrecommended room thermostats.

• The thermostat should be mounted4 to 5 feet above the floor on aninside wall of the living room or ahallway that has a good aircirculation from the other roomsbeing controlled by the thermostat.It is essential that there be free aircirculation at the location of thesame average temperature as otherrooms being controlled. Movementof air should not be obstructed byfurniture, doors, draperies, etc. Thethermostat should not be mountedwhere it will be affected by drafts,hot or cold water pipes or air ductsin walls, radiant heat fromfireplaces, lamps, the sun, T.V. oran outside wall. See instructionssheet packaged with thermostat formounting and installationinstructions.

Page 21: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

21

!"# $"!%& !"% $"!'& !"( $"!)& !"* $"#!& !"' $"#%& !"+ $"#'& !") $"#)& !", $"#-& !"- $"%%./0 +,+ $(%*& +(* $%--& ',% $%)'& '(! $%'!&

12345/0 )%( $(*#& +,, $(%'& +#) $%-#& '+) $%+,& '#% $%*%& *'- $%#)&123 )*, $('(& +-) $(%-& +*, $(!+& '-) $%,%& '*, $%'-& *-# $%(%& **' $%#!&

12346786 -%% $*('& ,,' $*#,& ,*- $*!#& ,## $(,(& ))' $(++& )(( $(*+& +-' $(%,& +** $(!*& +*' $(!*&9786 -*! $***& -#) $*((& ,)' $*#(& ,(, $(-'& )-- $())& )+! $('-& )#+ $((,& +)( $(#,& +%, $%-+&./0 +*+ $(!'& ',% $%)'& '#) $%**& *(+ $%!+&

12345/0 -,* $*+*& -() $**%& ,-* $*%%& ,*+ $(--& )-, $())& )') $(')& )#! $(('&123 #!() $*,-& --' $*)!& -'( $*'!& -#! $*%-& ,+, $*#!& ,%# $(,)& ),# $(+-& )() $(*,&

12346786 ##+# $'*,& #!%! $*,#& #!), $'!-& #!*! $*-#& --- $*)#& -+( $*'*& -%! $*(*& ,)( $*#%& )'( $(''&9786 #(-) $+'-& #('* $+(-& #(%# $+%(& #%)- $+!*& #%(, $',*& ##-( $'+(& ##') $'*+& #!+, $'!*& -'+ $*'#&./0 ,#' $(,'& )+' $(+#& )#' $(()& ++' $(#*& +#* $%-!& '', $%+(& '#* $%*(&

12345/0 #%,* $+!+& #%(( $',%& ##), $''+& ##%- $'((& #!)! $'!'& --- $*)#& -%) $*()& ,)+ $*#(& ,%( $(,,&123 #*#- $+)!& #()( $+*,& #(%( $+%*& #%,% $+!'& #%%, $',!& ##,! $'')& ##%- $'((& #!'* $*-)& -,# $*+(&

12346786 #*,' $)!#& #*'% $+,'& #*#, $++-& #(,+ $+'*& #(*+ $+('& #(#( $+%!& #%)% $+!!& #%%% $'))& ##-' $'+*&9786 #)*' $,%*& #)%% $,#(& #+-% $)--& #++* $),'& #+(! $)+-& #'-- $)''& #'++ $)(-& #'!* $)#!& #('+ $+*!&./0 #!** $*-(& -'( $*'!& ,+) $*!-& )+) $(+%& ++) $(#'& ')- $%)(& '!# $%(+&

12345/0 #!#! $*))& -)! $*',& -(+ $**%& -!% $*%+& ,+) $*!-& ,(% $(-(& )-, $())& )++ $(+%& )%' $(*%&123 #%*) $',-& ##,( $'',& ##%# $'%-& #!+* $'!%& --- $*)#& -(( $**!& ,+* $*!,& )-) $()+& )(' $(*)&

12346786 #,(* $,++& #)+, $,(*& #+-) $,!#& #+(- $))*& #',' $)*,& #'(- $)%+& #*), $+-,& #*%) $+)(& #()! $+*)&9786 %!!, $-*,& #-'+ $-%(& #-!' $,--& #,** $,)!& #,!% $,'!& #)'! $,%+& #+-, $,!#& #+'' $),#& #+!* $)')&

:5/02;<=2;>/;?@A2<B2@CD;23<07E6/DE<>75E2;<7?<=5@A2

4 44

FG#H#!I+!%*JII##<K<##<<<<<<<<<<<<

$%)-<K<%)-&(L*<<$''-&

4 4

FG#H!,I*,%#JII#!<K<#!<<<<<<<<<<<<<

$%'*<K<%'*&(L*<<$''-&

4 4

FG#H!+I(+#)JII#!<K<,<<<<<<<<<<

$%'*<K<%!(&#L%<<$()(&

4 4 4

4 44 4 4

4 4

4

4 4

FG#H!*I%*#*JII#!<K<+<<<<<<<<<<<<

$%'*<K<#'%&#L(<$%*,&

4 4

!"#$%&'()*'$)!*&#+,$)*'$)-+%.)/,$-%$0*&(,)1),(!%)2,(!)0%#,+3

1/325:5/02;<M7N2<7?<<

$BB&1/E/;<9O<<$G@EE&

:5/02;<M=223(-0)4+567)*89)#:;8<:9=)),>?:9@A;)3?A?8B)/9:66C9:)'@BD:6).A?:9)(E;CF@)4G/A7

DIRECT DRIVEINSTRUCTIONS FORCHANGING BLOWERSPEED

DISCONNECT THE ELECTRICALSUPPLY TO THE AIR HANDLERBEFORE ATTEMPTING TOCHANGE THE BLOWER SPEED.FAILURE TO DO SO CAN CAUSEELECTRICAL SHOCK RESULTINGIN PERSONAL INJURY OR DEATH.

The blower motor must be wired forblower speeds required for normaloperation.

If additional blower speed taps areavailable (leads connected to “M1” and“M2” on the electronic control), speedsmay be changed if necessary to fitrequirements of the particularinstallation. Reconnect the unusedmotor leads to “M1” or “M2.” Checkmotor lead color for speed designation.

! WARNING

TABLE 3

Heating speeds should not bereduced where it could cause the airhandler air temperature rise toexceed the maximum outlet airtemperature specified for the unit.

IMPORTANT: Always check airtemperature rise after changing theheating speed for any reason.

HYDRONIC AIR HANDLER AIR FLOW PERFORMANCE -PSC MODELS

Model Blower Sizein [mm]

Motor HP[Watt] Blower Speed

RW1P04A2414NAA 10 X 6[254 X 152] 1/5 [93]

RW1P06A3617NAA 10 X 8[254 X 203] 1/2 [373]

RW1P08A4821NAA 10 X 10[254 X 254] 1/2 [373]

RW1P10A4821NAA 11 X 11[279 X 279] 3/4 [559]

0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.17] 0.9 [.22]CFM [L/s] Air Delivery External Static Pressure Inches Water Column [kPa]

Low 642 [339] 612 [322] 591 [311] 524 [273] — — — — —

Med-low 711 [377] 684 [362 655 [346] 624 [329] 578 [303] 526 [274] — — —

Med-high 890 [477] 853 [456] 821 [438] 786 [419] 744 [396] 694 [368] 633 [334] 549 [287] —

High 950 [510] 917 [492] 880 [471] 843 [451] 803 [428] 752 [400] 689 [365] 690 [366] 604 [318]

Low 900 [482] 882 [472] 865 [463] 843 [451] 806 [430] 759 [404] 687 [364] 617 [325] —

Med-low 1135 [613] 1101 [594] 1073 [578] 1050 [566] 1012 [544] 960 [516] 889 [476] 801 [427] 700 [371]

Med-high 1260 [682] 1231 [666] 1199 [648] 1154 [623] 1113 [601] 1060 [571] 978 [526] 895 [479] 767 [408]

High 1397 [758] 1363 [739] 1314 [712] 1268 [687] 1209 [654] 1148 [620] 1077 [581] 980 [527] 829 [443]

Low 947 [508] 943 [506] 940 [504] 926 [497] 897 [481] 857 [458] 784 [418] 711 [377] —

Med-low 1200 [649] 1193 [645] 1183 [639] 1163 [628] 1137 [614] 1084 [584] 1025 [552] 917 [492] 769 [409]

Med-high 1493 [812] 1481 [805] 1452 [789] 1411 [766] 1365 [741] 1220 [660] 1124 [607] 957 [514] —

High 1865 [1018] 1810 [988] 1737 [947] 1671 [911] 1608 [876] 1533 [834] 1457 [792] 1292 [700] 1135 [613]

Low 904 [484] 875 [468] 845 [452] 798 [426] 735 [391] 688 [364] 643 [339] 593 [312] 539 [282]

Med-low 1189 [643] 1165 [629] 1114 [601] 1092 [589] 1057 [569] 1005 [541] 947 [508] 879 [471] 821 [438]

Med-high 1326 [719] 1304 [707] 1286 [697] 1266 [686] 1244 [673] 1217 [658] 1189 [643] 1140 [616] 1060 [571]

High 1970 [1077] 1951 [1066] 1937 [1058] 1926 [1052] 1895 [1035] 1865 [1018] 1759 [959] 1673 [912] 1624 [884]

Blower performance measured without filter in place.

Page 22: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

22

THESE INSTRUCTIONS AREINTENDED AS AN AID TOQUALIFIED SERVICEPERSONNEL FOR PROPERINSTALLATION, ADJUSTMENTAND OPERATION OF THIS UNIT.READ THESE INSTRUCTIONSTHOROUGHLY BEFOREATTEMPTING INSTALLATIONOR OPERATION. FAILURE TOFOLLOW THESE INSTRUCTIONSMAY RESULT IN IMPROPERINSTALLATION, ADJUSTMENT,SERVICE OR MAINTENANCE,POSSIBLY RESULTING IN FIRE,ELECTRICAL SHOCK, CARBONMONOXIDE POISONING,EXPLOSION, PROPERTYDAMAGE, PERSONAL INJURYOR DEATH.

DISCONNECT MAIN ELECTRICALPOWER TO THE UNIT BEFOREATTEMPTING ANY MAINTE-NANCE. FAILURE TO DO SO CANCAUSE ELECTRICAL SHOCKRESULTING IN PERSONALINJURY OR DEATH.

! WARNINGDO NOT OPERATE THE SYSTEMFOR EXTENDED PERIODSWITHOUT FILTERS.A PORTION OF THE DUSTENTRAINED IN THE AIR MAYTEMPORARILY LODGE IN THE AIRDUCT RUNS AND AT THE SUPPLYREGISTERS. THIS RESIDUE CANSOIL CEILINGS, WALLS, DRAPES,CARPETS AND OTHERHOUSEHOLD ARTICLES.

MAINTENANCE

FIGURE 16

JACKET ASSEMBLY

SOLID BOTTOM

SCREWS (2) REQ’D

REMOVE FROM SHIPPED LOCATION

RELOCATE TO

SIDE RETURN

ALWAYS

BOTTOM FOR

! CAUTION

ST-A1242-06-X0

NOTE: DISCARD BLOCK OFF PLATEIF SIDE RETURN IS NOT REQUIRED.

Page 23: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

23

FIGURE 17FILTER LOCATIONS

CUT OUT USING EMBOSSED ANGLES AS A GUIDE FOR THE

PROPER SIZE.

JACKET

the flue passageways, the ventsystem and the main burners forcontinued safe operation. Payparticular attention to deteriorationfrom corrosion or other sources.

• IMPORTANT: It is recommendedthat at the beginning and atapproximately half way through theheating season, a visual inspectionbe made of the main burner flamesfor the desired flame appearance bya qualified installer, service agencyor the gas supplier. If the flames aredistorted and/or there is evidence ofback pressure, check the vent andinlet air system for blockage. If thereis carbon and scale in the heatexchanger tubes, the heatexchanger assembly should bereplaced.

REPLACEMENT PARTSSee sheet enclosed with air handlerfor replacement part information.

TROUBLESHOOTINGRefer to Figure 18 for determiningcause of unit problems.

WIRING DIAGRAMSFigures 19 through 22 are completewiring diagrams for the air handlerand power sources.

LUBRICATIONIMPORTANT: DO NOT attempt tolubricate the bearings on the blowermotor or the induced draft blowermotor. Addition of lubricants canreduce the motor life and void thewarranty.

The blower motor and induced draftblower motor are permanentlylubricated by the manufacturer and donot require further attention.

The blower motor and induced draftblower motor must be cleanedperiodically by a qualified installer,service agency, or the gas supplier toprevent the possibility of overheatingdue to an accumulation of dust anddirt on the windings or on the motorexterior. And, as suggestedelsewhere in these instructions, theair filters should be kept clean. Dirtyfilters can restrict airflow. The motordepends upon sufficient air flowingacross and through it to keep fromoverheating.

SYSTEM OPERATIONINFORMATIONAdvise The Customer

1. Keep the air filters clean. Theheating system will operatebetter, more efficiently and moreeconomically.

2. Arrange the furniture and drapesso that the supply air registersand the return air grilles areunobstructed.

3. Close doors and windows. Thiswill reduce the heating load onthe system.

4. Avoid excessive use of kitchenexhaust fans.

5. Do not permit the heat generatedby television, lamps or radios toinfluence the thermostatoperation.

6. Except for the mounting platform,keep all combustible articles 3feet from the air handler and ventsystem.

7. IMPORTANT: Replace all blowerdoors and compartment coversafter servicing the air handler. Donot operate the unit without allpanels and doors securely inplace.

8. Explain proper operation of thesystem with constant aircirculation.

ANNUAL INSPECTION• The air handler should operate formany years without excessive scalebuild-up in the flue passageways.However, it is recommended that aqualified installer, service agency, orthe gas supplier annually inspect

ST-A1242-04-X0 ST-A1242-07-X0

Page 24: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

24

FIGURE 18GENERAL TROUBLESHOOTING CHART

ydemeResuaC elbissoPmotpmyS

lortnoc ta egatlov tcerroc rof kcehCnoitcennoc lacirtcele ensool ro ffo rewoPlortnoc ta egatlov tcerroc rof kcehChgih oot tes - noitarbilac fo tuo tatsomrehT

Call for domes�c hot water - air handler disabled un�l call ends. Unit is opera�ng as designed. Unit is opera�ng as designed

rekaerb teser / sesuf ecalpeRrekaerb deppirt / sesuf nwolBremrofsnart ecalperg–niriw kcehCevitcefed remrofsnarT

daol etaluclaceRretaeh retaw ro reldnah ria dezis ylreporpmIgnittes pat deeps rotom kcehCwolf ria roodni reporpmI

Call for domes�c hot water–air handler disabled un�l call ends. Unit is opera�ng as designed. Unit is opera�ng as designed

Check line voltage at pumpCheck wires and connectorsCheck pump capacitor

Call for domes�c hot water - air handler disabled un�l call ends. Unit is opera�ng as designed. Unit is opera�ng as designed

Check line voltage at blower motorCheck wires and connectorsCheck blower motor capacitor

General Trouble Shoo�ng Chart

Power off or loosen electrical connec�onPump does not run

Power off or loosen electrical connec�onBlower does not run

Warning: Disconnect all power to unit before servicing. Failure to shut off power can cause electrical shock resul�ng in personal injury or death.

Unit will not run

Insufficient hea�ng

Water does not flow Water lines are air locked Purge air from lines

General Troubleshooting Chart

Page 25: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

25

FIGURE 19ELECTRICAL WIRING DIAGRAM – ECO TECH™ MODELS (RWIT)

NO

TE

SC

OM

PO

NE

NT

CO

DE

S

WIR

E C

OL

OR

CO

DE

BK......BLA

CK

BR......BROWN

BL.......BLU

E

G........G

REEN

GY......GRAY

O........O

RANGE

PR......PURPLE

R........R

ED

W.......W

HITE

Y........YELL

OW

WIR

ING

INFO

RM

AT

ION

WAR

NING

-CAB

INET

MUST

BE

PERM

ANEN

TLY

GRO

UNDED

AND C

ONFO

RM T

O I.E.C.,

N.E.C.,

C.E.C.,

NAT

IONAL

WIRING R

EGULA

TIONS, A

ND L

OCAL

CODES

AS

APPL

ICAB

LE.

REP

LACEM

ENT

WIRE

-MUST

BE

THE

SAME

SIZE

AND T

YPE

OF

INSU

LATION A

S ORIGINAL

(105

C. MIN.)

-FIELD

INST

ALLE

D-FAC

TORY

STAN

DAR

DLO

W VO

LTAG

E

-FIELD

INST

ALLE

D-FAC

TORY

OPT

ION

-FAC

TORY

STAN

DAR

DLINE

VOLT

AGE

ORIG

INAL

RELE

ASE

NO.:

ELE

CTR

ICAL

WIRING D

IAGRAM

MODELE

DBY:

CHECKED:

APPROVED:

REV:

PART

NO.:

DATE

:

90-103

346-05

6-26-15

H-1025S012

JHB

00

Page 26: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

26

FIGURE 20ELECTRICAL WIRING DIAGRAM – PSC MOTORS (RWIP)

Page 27: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

27

FIGURE 21ELECTRICAL WIRING DIAGRAM

NO

TE

SC

OM

PO

NE

NT

CO

DE

S

WIR

E C

OL

OR

CO

DE

BK

......

BLA

CK

BR

......

BR

OW

NB

L....

...B

LUE

G...

.....G

RE

EN

GY.

.....G

RA

YO

......

..OR

AN

GE

PR

......

PU

RP

LER

......

..RE

DW

......

.WH

ITE

Y....

....Y

ELL

OW

WIR

ING

INFO

RM

AT

ION

WAR

NIN

G-C

ABIN

ET

MU

ST

BE P

ERM

ANE

NTL

Y G

ROUN

DED

AND

CON

FORM

TO

I.E

.C.,

N.E

.C.,

C.E

.C.,

NAT

IONA

L W

IRIN

G R

EGU

LATI

ON

S, A

ND

LO

CAL

COD

ES A

S AP

PLIC

ABLE

.

REP

LAC

EM

ENT

WIR

E-M

UST

BE

THE

SAM

E SI

ZE A

ND

TYP

EO

F IN

SUL

ATIO

N A

S O

RIG

INA

L (1

05C

. MIN

.)

-FIE

LD I

NS

TALL

ED

-FAC

TOR

Y S

TAN

DAR

DLO

W

VO

LTA

GE

-FIE

LD I

NS

TALL

ED

-FAC

TOR

Y O

PTIO

N-F

ACTO

RY

STA

ND

ARD

LIN

E V

OLT

AG

E

OR

IGIN

AL

RE

LEA

SE

NO

.:

ELE

CTR

ICA

L W

IRIN

G D

IAG

RA

M

MO

DE

LED

BY

:

CH

EC

KE

D:

AP

PR

OV

ED

:

RE

V:

PAR

T N

O.:

DA

TE:

90-1

0334

6-06

11

-23

-15

H-1

025

S0

24

MB

A

00

FLOW

SWITCH

BR

R

Page 28: 92-24161-150 Rev 3 - MyRheem.compts.myrheem.com/.../RW1/92-24161-150_Rev_3.pdfand local ordinances, in addition to instructions laid out in this manual. the installation must comply

28 CM 0116

FIGURE 22ELECTRICAL WIRING DIAGRAM

FLO

WSW

ITCH

BR

NO

TE

SC

OM

PO

NE

NT

CO

DE

S

WIR

E C

OL

OR

CO

DE

BK

......

BLA

CK

BR

......

BR

OW

NB

L....

...B

LUE

G...

.....G

RE

EN

GY.

.....G

RA

YO

......

..OR

AN

GE

PR

......

PU

RP

LER

......

..RE

DW

......

.WH

ITE

Y....

....Y

ELL

OW

WIR

ING

INFO

RM

AT

ION

WAR

NIN

G-C

ABIN

ET

MU

ST

BE P

ERM

ANE

NTL

Y G

ROUN

DED

AND

CON

FORM

TO

I.E

.C.,

N.E

.C.,

C.E

.C.,

NAT

IONA

L W

IRIN

G R

EGU

LATI

ON

S, A

ND

LO

CAL

COD

ES A

S AP

PLIC

ABLE

.

REP

LAC

EM

ENT

WIR

E-M

UST

BE

THE

SAM

E SI

ZE A

ND

TYP

EO

F IN

SUL

ATIO

N A

S O

RIG

INA

L (1

05C

. MIN

.)

-FIE

LD I

NS

TALL

ED

-FAC

TOR

Y S

TAN

DAR

DLO

W

VO

LTA

GE

-FIE

LD I

NS

TALL

ED

-FAC

TOR

Y O

PTIO

N-F

ACTO

RY

STA

ND

ARD

LIN

E V

OLT

AG

E

OR

IGIN

AL

RE

LEA

SE

NO

.:

ELE

CTR

ICA

L W

IRIN

G D

IAG

RA

M

MO

DE

LED

BY

:

CH

EC

KE

D:

AP

PR

OV

ED

:

RE

V:

PAR

T N

O.:

DA

TE:

MBA

11-2

4-15

90-1

0334

6-07

00

H-1

025S

024

R

PSC

MO

TOR

NO

PU

MP