02/2007 1
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Power Transmission and DistributionCommunication in Substations with IEC 61850Commissioning & DiagnosticsMarkus Spangler, Siemens AG, PTD EA 13
05/2007 2
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Recommended Commissioning and Diagnostic Tools
1.) Networkview to visualize all participants in the network
2.) WEB Monitor to have access to commissioning aids supportedby SIPROTEC-devices
3.) IEC Browser to communicate, based on MMS communication, between client and server
4.) TFTP to get or load the configuration file of the switch
5.) EN100 homepage shows commisioning data, error data and statisticdata as well
6.) module infodisplay shows module parameter
7.) SNMP8) Ethereal9.) Kema Analyzer/Observer10.) PING11.) Firmware update
05/2007 3
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
1.) Networkview www.networkview.com
Start\Programs\networkview
The program identifies all IP-addressesConfigurations can be saved and printed outDirect access to all participants with right mouse-click via telnet or http
05/2007 4
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
1.) Networkview www.networkview.com
License:
The program can be run without any license (old version V 2.03)
There will be some hints that you are using an unregistered version
If you have a registered license, the key must be copied in installation-roote.g. C:\program files\networkview\
05/2007 5
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
1.) Networkview www.networkview.com
Creating a new file
File => NewSelection of the IP-address range
Remove the hooks forquick processing
05/2007 6
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
The Online Mode
Edit => Monitor Nodes ( adjust the scanning cycle for the polling of all devices)
The recommended polling cycle (10 s ) depends on the no. of devices. Theshorter the polling time the higher the network data flow, i.e. if you have200 devices you should set the polling time to 60-120 seconds. The default timeout shouldn‘t be changed
05/2007 7
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
The Online Mode
05/2007 8
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
The Online Mode / Recommendation for a fast switchdiagnosis
05/2007 9
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Expanding an existing Configuration
This can be done only in offline mode:
Edit => Add node ( insert address or range of addresses for the new devices)
05/2007 10
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
2.) Web Monitor of SIPROTEC (directly or withnetworkview)
05/2007 11
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
3.) IEC Browser
Start => Programs => IEC_Browser => IEC_Browser.exe
Files => Fault Records
Description of the switchgear with 5 logical devices:CTRL ControlDR Disturbance RecorderEXT extendedMEAS MeasurementPROT Protection
05/2007 12
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
3.) IEC Browser
GGIO = user defined indicationsLLN0 = common indication of logical nodeLPHD = common indication of logical node
physical deviceCILO = Control interlockingsCSWI = Control SwitchesXCBR = class switching devices X; CBR=Q0
05/2007 13
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
3.) IEC Browser
CF = Configuration CO = ControlDC = DescriptionEX = Extended definitionRP = Unbuffered reportST = Status information
FC=FunctionalConstraint
05/2007 14
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
3.) IEC Browser (Feedback DPI of Q1)
01 = OFF
05/2007 15
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
3.) IEC Browser (Actualizing the information)
Attention:Please check the correct time stamp of all indications.Only that information is valid and actual whichis allocated in DIGSI to system interface IEC61850
05/2007 16
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
3.) IEC Browser (Get fault records)
05/2007 17
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
4.) TFTP Trivial File Transfer Program
to get the configuration file of the switch
To get the file:tftp 192.168.1.21 get config.csv c:\temp\config.csv
IP-Address Destination Folder
Editing the config.csvwe recommend Excel or notepad
For diagnosis (syslog.txt and crashlog.txt):i.e. tftp 192.168.1.21 get syslog.txt c:\temp\syslog.txt
IP-Address Destination Folder
05/2007 18
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
4.) TFTP Trivial File Transfer Program
to load the configuration file to the switch
Attention:In the switch (IP Services) the tftp-access must beEnabled
To load the file:tftp 192.168.1.21 put c:\temp\config.csv config.csv
IP-Address Source Folder
Editing the config.csvwe recommend thenotepad-program
For diagnosis (syslog.txt and crashlog.txt):i.e. tftp 192.168.1.21 get syslog.txt c:\temp\syslog.txt
IP-Address Destination Folder
05/2007 19
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
5.) EN100 module homepage
e.g. 192.168.1.99/home
05/2007 20
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
module-homepage – Error Buffer
05/2007 21
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
EN100-Homepage – FEC-Statistics
05/2007 22
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
FEC-Statistics
RSTP-Role Chan1/2 = Alternate/RootIf theSIPROTEC 4 devices are arranged in a ring, and the ring is closed
and connected to the external switches which are also on, one device on the FEC side must always display the above text. If none of the devices in the ring does, the ring is physically broken.FilterSymErrCntChan1/2 = 0/2753
If these two counters are incremented during stable operation of thedevice, and with neither of the two adjacent devices turned off, there is a poor FO connection. This can be due to an excessive attenuation by thecoupling devices, or to a defective cable.FNS queue overflow = 0If this display is not equal zero, this suggests that there are circulatingbroadcast telegrams.Frames Loss = 0A value that is not zero indicates circulating multicast telegrams.
05/2007 23
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Module-Homepage – Dump
05/2007 24
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Modul-Homepage – Print Buffer
05/2007 25
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Modul-Homepage – Print Buffer
All shown pages can be saved with the used Internet Browser as a HTMLfile (e.g. for troubleshooting in case of failures)
05/2007 26
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
6. Diagnostic – module informationpage
Menu ->Test/Diagnostic -> moduleinfos -> Port B
line 1 to 7 (network configuration)same for EN100 optical and electric7 Phy1 100 MBit Full-Duplex (electr. EN100)
Zeilen 8-10 (status of interface)Zeilen 12 bis 21 (Parameter optical interface)
see EN100 manual chapter 7.3 foradditional information
05/2007 27
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
7. SNMP
possible with FW >= 3
SNMP:Simple Network Management Protocol
for displaying use a mib browser,e.g. iReasoning(www.ireasoning.com)
necessary file: SipEthernet.mibMIB, ManagementInformation Basedownload under www.siprotec.com
RSTP
link Status
IP-address
05/2007 28
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
8. Ethereal
Read the Ethernetframes on the bus
for investigating detailed ethernet knowledge is necessary
Ethereal with GOOSE-Filter available
Freeware
05/2007 29
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
8. Ethereal
05/2007 30
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
8. Ethereal
12
6
4
5
7
8
3
9
10
05/2007 31
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
2
1
3
45 6
7
sending device
10
05/2007 32
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
receiving device
1
9
3
4
8
6 7
1
10
05/2007 33
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
System configurator – „properties“
45
05/2007 34
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
9.) KEMA Observer/Analyzer
Read the Ethernetframes on the bus
A frame will be viewed in one line (Observer)
the captured file can be investigated with the analyzer by ourdevelopment
The Observer ist Freeware, the Analyzer costs more than 4.000,- EUR.
05/2007 35
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
KEMA UNICA Observer
05/2007 36
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
KEMA UNICA Analyzer
05/2007 37
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
10.) PING
multiple transmission of ICPM Echo Requests
05/2007 38
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Firmware update – EN100 module
1.) download the firmware of the relevant device under www.siprotec.com.2.) the update will be done via Siprotec Firmware-update tool3.) if updating an existing optical EN100 module with FW <= 3.04, an update of theBootfirmware to V01.02.04 has to be done first
05/2007 39
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Firmware update – Ruggedcom switches
1.) download updatetool and firmware under www.ruggedcom.com2.) insert the IP-addresses of the relevant switches or import from an existing table3.) insert Admin-Passwort4.) choose the firmware-file (.bin), start upload (if uploading a config-file (.csv), just one IP-address possible)
05/2007 40
Power Transmission and Distribution
Power AutomationProgress. It‘s that simple.
Backup the configuration – Ruggedcom switches
1.) in section „Download“ tag thedata for backup2.) select the destination folder
background: