74132089 victoria tech manual
TRANSCRIPT
-
7/22/2019 74132089 Victoria Tech Manual
1/56
Wall-Hung On-Demand
VICTORIA20/20FCombination Water Heater
Radiant Heating Technologies, Inc.PO Box 13217,Burton, WA 98013
253-238-1706 / 866-682-3078 / fax 253-238-0650
www.radiantheattech.com
-
7/22/2019 74132089 Victoria Tech Manual
2/56
Victoria wall-hung boilersHeating training centres
Table of contents
Table of contentsNomenclature and servicesOverall viewOverall dimensionsPre-plumbing jig and Wall Spacing FrameHydraulic testInstallation recommendationsStart-up recommendations (I)Start-up recommendations (II)Start-up recommendations (III)Start-up recommendations (IV)Automatic air vent KitPressures of gasElectronic PCBElectrical wiringRoom thermostat connectionFuse change
Connection of Victoria 20 + V3V kitMain components (l)Main components (ll)Control panelOverall view of HydroblockHydroblock componentsHydroblock operationHydroblock and pumpWater loopCentral Heating mode operation
DHW mode operationOutlines hydraulic Victoria 20 (Heating)3-Way ValveOutlines hydraulic Victoria 20/20 (Heating)Outlines hydraulic Victoria 20/20 (Sanitary)
Outlines hydraulic Victoria 20/20 F (Heating)Outlines hydraulic Victoria 20/20 F (Sanitary)Outlines hydraulic Victoria 20/20 T (Heating)Outlines hydraulic Victoria 20/20 T (Sanitary)Stored DHW serviceOverheat thermostatFlame safeguard rectification system (l)Flame safeguard rectification system (ll)Chimney pull safety :20/20Chimney pull safety :20/20F and TBurnerCombustion chamberKit valve G20 and G25Cross-section of gas valveGas changeover KitComponents of the boilers F and TFlue duct kit (l)
Flue duct kit (ll)Flue duct kit (III)Flue duct kit (IV)Flue duct kit (V)Flue duct kit (VI)Flue duct kit (VII)Timer connectionsProgramming instructions (l)Programming instructions (ll)Programming instructions (lll)
Control DIP switchesMaintenaceFactory settingsFault codes
1 2 3 4 5 6 7 8 91011121314151617
18192021222324252627
2829303132
3334353637383940414243444546474849
50515253545556575859
60616263
1
-
7/22/2019 74132089 Victoria Tech Manual
3/56
Victoria wall-hung waterheaters
CE marked. These waterheaterscomply with the requirements of the Electromagnetic Compatibility Directive 89/336/EEC,the Gas Appliance Directive 90/396/EEC, the Low Voltage Directive 73/23/EEC, and the Efficiency Directive 92/42/EEC .
Victoria 20/20 F
Overall view
2Heating training centres
CSA CERTIFIED FOR USA and CANADA.
-
7/22/2019 74132089 Victoria Tech Manual
4/56
Victoria wall-hung waterheaters
8.4" / 213mm
12.6
"/320mm
26.8
"/680mm
17.7" / 450mm13.2" / 335mm
3.9" / 100mm
Victoria 20/20 F
42" / 1066mm
3Heating training centres
Overall dimensions
-
7/22/2019 74132089 Victoria Tech Manual
5/56
Victoria wall-hung waterheaters
Pre-plumbing jig and wall Spacing Frame
Wall-mounting bracket, suppliedwith the pre-plumbing jig
Distance from the wall: 5.5" / 140 mm
Gap between connections: 2.36" / 60mm
PMI with no cocks PMI with cocks PMCA with cocks Wall Spacing Frame (1.38"/35 mm)
4Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
6/56
Victoria wall-hung waterheaters
Hydraulic test
The PMCA is supplied with the 3/4 cap nut.The PMI could do without the pump; in thiscase, the mains pressure and connectionshould be used for filling the system.Monitor the operation through the necessarycontrols: Pressure gauge and safety valve.
5
Mains water
Pump
3/4 cap nut
Pump
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
7/56
Victoria wall-hung waterheaters
Installation recommendations
Observe current regulations and minimum distance from flammable materials.
Please refer to the Instructions delivered with the waterheater
6Heating training centres
15.7" /
59" /
-
7/22/2019 74132089 Victoria Tech Manual
8/56
Victoria wall-hung waterheaters
Start-up recommendations (l)
Please refer to the instructions which are delivered with the waterheater.Power supply 230V Live/Neutral. (Do not reverse polarity).Room thermostat connection.
Work on the pump motor shaft to unlock it if it were jammed.Manually vent the boiler.Fill the primary loop (if no DHW cylinder has been installed) slowly until the pressure reaches14.5 - 29 PSI / 1-2 bar. (If a DHW cylinder has been installed, then fill the secondary loop first).Open the DHW circuit for it to fill up and ventWith the gas inlet cock still closed, program the Heating mode. The boiler will perform a lightingcycle and will then lock out under code 60-70-90.Leave it like that for five minutes so that the pump, which is still running, can help vent the circuit.
Next, check the pressure level and top up if it has dropped to 14.5 PSI / 1 bar.Open the gas inlet cock, reset the system (code 60-70-90) and the boiler will start operating.Allow the waterheaterto operate in the Heating mode for ten minutes, during whichcheck that allradiators warm up. Should one radiator fail to warm up, bleed the air in it. But if it still does notwarm up, then the flow rates in all radiators should be balanced, always optimizing the pumpperformance curve (flow rate/pressure) through its speed selector control.Open the DHW tap with the highest flow rate in the house. The waterheaterwill operate for ten minutescontinuously at full output (79,366 Btu / 20,000 kcal/h). If the flue spillage detection thermostat does
not trip, that means that the removal of flue gases is correct.If a gas meter is available, check the gas input rate, as indicated in the waterheater Instructions
7Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
9/56
Victoria wall-hung waterheaters
Where a water column is available, connect it to the gas valve pressure test point and check theworking pressure with the waterheateroperating at full output (79,366 Btu / 20,000 kcal/h).Program the Heating mode again.
Program the DHW mode again. For a higher level of comfort, particular ly where substantialpressure variations in the water supply occur, set the program close to the draw-off temperature.Remove the water column, replace the plug and washer, start the system, and using soapy watercheck the whole circuit for gas tightness.Ensure that the waterheaterroom has a proper ventilation and air renewal system.
Instruct the user on the following points:Recommend him/her to read the Users Instructions.
Instruct him/her on how to program the Heating and DHW temperature and the roomthermostat (if any).Instruct him/her on how to fill and/or top up the Heating system.Demonstrate how the fault codes work for insufficient gas (60-70-90 and 40-80-90) and how toreset (R) after opening the gas inlet cock or changing the gas cylinder.Recommend him/her to turn the selector switch to the R position whenever a red fault lamp lights up.If the red light appears two or three consecutive times, tell the user to write down the number of thetemperature LEDs which light up and then to notify the nearest Service Centeror Installer.
Train him/her on the various safety devices, recommendations and maintenance operations specifiedin the waterheaterInstructions.
8Heating training centres
Start-up recommendations (lI)
-
7/22/2019 74132089 Victoria Tech Manual
10/56
Victoria wall-hung waterheaters
It should be ON
It should be between 14.5 and 29 PSI / 1 and 2 bar
Fill and/or top up if pressure is less than 14.5 PSI / 1 bar
9Heating training centres
Start-up recommendations (lII)
-
7/22/2019 74132089 Victoria Tech Manual
11/56
Victoria wall-hung waterheaters
Set the minimum speed possible
to reduce system rumbling as muchas possible. See the pump performancegraph (flow rate/pressure).
Bleed air and/or drain
Turn
10Heating training centres
Start-up recommendations (lV)
-
7/22/2019 74132089 Victoria Tech Manual
12/56
Victoria wall-hung waterheaters
Automatic air vent Kit
11Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
13/56
Victoria wall-hung waterheaters
Pressures of gas
Gas Inlet Pressure:G20(GN): 20 mbarG30(GB): 28 30 mbarG31(GP): 37 mbar
12Heating training centres
Gas input rates and pressures with Natural Gas (G20) are for3
a L.H.O. = 9,200kcal/m , density = 0.62, 15 C and 1,013mbar.
(*) measured under standard conditions (15C and 1013mbar)(**) burner setting pressure
2.39
1.460.87
85
3614
0.83
0.570.31
1.03
0.710.38
270
140 47
341
158 52
Heat Output79,366 Btu/20,000 Kcal/h
47,620 Btu/12,000 Kcal/h27,778 But/7,000 Kcal/h
3Gas Input Rate(m /h)(*)
G20 G30 G31Pressure (mmwg) (**)
G20 G30 G31
-
7/22/2019 74132089 Victoria Tech Manual
14/56
Victoria wall-hung waterheaters
Electronic PCB
RH electrodeLH electrode
TimerTransformer(230V/12V)
Azul
Azul
Azul
Azul
Azul
Azul
Marrn
Marrn
Gris
Gris
Naranja
Rojo
220Vca Blanco
Gris
Tierraamarillo
GrisNaranja
Rojo
FlowSwitch
To the mains
Ignition transformer(18,000V)
Earthconn.(tochassis)
Room Stat(option) Low Voltage Wiring
Conexin relojprogramador, en laplaca electrnica
5 Vcc
Clixon Cortatiros: 5 VccClixon intercambiador: 12V
Sondas: 5Presostato: 5
12 Vcc220 Vca
220VcaV Amarillo
Marrn
Azul
220Vca
Flame rod
230Vca
Fuse3.15 A
Neutral
LiveEarthconn.(to mains)
Pump and Fan Wiring
Timer connection onthe electronic PCB
5Vcc
Flue Spillage Limit Thermostat: 5VdcOverheat Thermostat: 12V
Sensors: 5VdcPressure switch: 5Vdc
12Vcc230Vca
230Vca
230Vca
13Heating training centres
Blue
Yellow
Brown
White
Blue
Blue
Brown
Grey
Brown
Grey
Orange
Blue
Red
BlueGreyOrange
Red
Bluel
Earth-yellow
Blue
Grey
20Thso
lenoidvalve
Kitpowersupply
3-wayvalve
Neutral-Fan(F/T)
Neutral-Pump
Live-Pump
Live-Fa
n(F/T)
Common-SolenoidV
12Thso
lenoidvalve
Safetys
olenoidvalve
DHWse
nsor
Overhea
tthermostat
CHsensor
Fluespill.detect.th.Or
PressureswitchinF&T
Overhea
tthermostat
Earth
co
nnection
Po
wersupply
Ea
rth
Signal
Green
7Thsolenoidvalve
-
7/22/2019 74132089 Victoria Tech Manual
15/56
Victoria wall-hung waterheaters
Electrical wiring
Low Voltage Wiring
15.79" / 400 mm
Earth connection to chassis
Solenoid valves connector
Indicator lights, sensors,and pressure switch connector
21.65" / 550 mm
4.72"/120 mm
5.9"/150 mm
9" / 230 mm
7 Th Solenoid valve 12 Th 20 Th Safety
Flue spillage detectionthermostat or pressureswitch (F and T) DHW sensor
Overheatthermostat
CH Sensor
Note:The exhaust fan, the pump and the
flow switch are fed by other connectors(see Electronic PCB sections)
3.94" / 100 mm
7.09"/180 mm
7.09"/180 mm
3.15"/80 mm
14Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
16/56
Victoria wall-hung waterheaters
Room thermostat connection
Thermostat with anticipatory resistor Thermostat without anticipatory resistor
15
Fuse Fuse
Main powersupply
Neutral (N)Room thermostat withanticipatory resistor
Remove jumper
N T1 T2 T1 T2
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
17/56
Victoria wall-hung waterheaters
Fuse change
Room thermostatconnection
Mains powersupply
Neutral
Live
Earth connection
(to the mains)
Earth connection(to chassis)
Thermostat jumper isobligatory when no roomthermostat has been fitted(it is supplied with it)
Fuse of 3.15 AmpsRoca genuine spare only.
The only fuse in the boiler.It can be accessed after removing the lower LH coverin the waterheaterand then pulling out the cover holding it.
16Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
18/56
3-way valve
Supplied
Supplied
Cables to besupplied by others
R 33kW
Magnetic detector
DHWSensor
Connection of Victoria 20 + V3V kit
c
2
B1
A3
87
7
62
B2
B3
B4
A
1
1
230V
Victoria 20
1
2
3
4
5
6
7
8
9
10111213
1415
1 2 3 4 5 6
Victoria wall-hung waterheaters
V3V
17Heating training centres
N F
Stored
-
7/22/2019 74132089 Victoria Tech Manual
19/56
Victoria wall-hung waterheaters
Compact casingTop fixing: Locating pinsBottom fixing: ScrewsRemovable decor. lidSpring-effect flanges
Color of casingWHITE - RAL 9016Stages of Output:27,778 Btu / 7,000 kcal/h47,620 Btu / 12,000 kcal/h79,366 Btu / 20,000 kcal/hAdjustable for Heating
Net efficiency: 91.7% , as per Efficiency Directive 92/42/CEE
Main components (I)
18Heating training centres
CSA CERTIFIED EFFICIENCY: 87%
-
7/22/2019 74132089 Victoria Tech Manual
20/56
Victoria wall-hung waterheaters
Expansion VesselFill pressure: 10.88 PSI / 0.75 bar Butyl diaphragm and nitrogen chargeTotal/useful capacity: 2.1 gal/1.2 gal - 8 litres/4.5 litres
Draught DiverterFlue socket collar 5" / 127 IDFlue duct 4.9" / 125 OD
BurnerStainless steel. 13 becks Clover-like flame on theends for interlighting
Ignition electrodes and flame rodBurner CentredControl panelDirect access to the boiler wiring and fuse (3.15A).Fault codes in Heating temperature leds.Ignition transformer on electronic board (18,000V)
Flue Spillage Limit ThermostatSet at: 149F / 65C
Heat ExchangerBithermal. 6 steps in DHW and Heating. Made ofcopper and high-temperature aluminium paint
Combustion ChamberCompact. Side fixing rods
Main components(II)
19Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
21/56
Victoria wall-hung waterheaters
DHW Temp. SelectorTemperature range: 104F/40C 140F/60C
CH Temp. SelectorTemperature range: 104F/40 C 194F/90 C
Service Changeover SelectorHeating and DHW / DHW only / Reset / Off
TimerPlanned position in thesupplied kit. Digital
Access cover forexternal connectionSupply Voltage: 230VInput fuse: 3.15 AmpsRoom Thermostat Power
Supply (optional): 230V
Casing Fixing ScrewsBottom only.Top - locating pins
Access Cover to Internal WiringAll boilers internal wiring
Indicator leds for:Service, Voltage,Faults
Pump
3-speed type2.6F, 450VCapacitor
CentralHeatingTemp. LedsFault codes
Pump SpeedSelector(I, II and III)
MechanicalPressure GaugeRecommended
Fill Pressure: 21.8 PSI/1.5 bar
Pressure Relief ValveSet at 43.5 PSI/3 bar. Removable
Control panel
20Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
22/56
Victoria wall-hung waterheaters
Overall view of Hydroblock
21
Set in the Hydroblokserviceable if captivepin is removed
Flow Regulator
MainsWater Inlet FilterUse Allen 4 keyor Screwdriver to open
By -pass
Mains WaterInlet
MainsWaterInlet (3/4)
CH Return (3/4)
Pressure Relief
Valve Discharge (1/2).Route to a drain
2 Chassis FixingScrewsAllen 4
Outlet to the HeatExchanger
Connection
to the pump
Pressure ReliefValveSet at 3 bar
Serviceable and rotary
Magnetic Detector
By - pass, Ventand Drain CockTight: Fixed by - pass
Loose: Air vent or drain
Fill Point Valve
Limitation: 3.7gal/14 l/min.
4
Mains water
By - pass pipe
Inlet
60 mm
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
23/56
Victoria wall-hung waterheaters
Hydroblock components
22
Magnetic Detector
M4 x 12
8 ID x 1.9
23 ID x 3.6
Fill Point Valve Pin 2 x 16 mm long
Fill Point ValveO-rings
Mains Water Inlet FilterUse Allen 4 key to open
Water Filter O-ring13 ID x 2
7.2 ID x 1.9 and 2.6 ID x 1.9
Mains Water Inlet
Magnetic FloatMagnet material: Nd powder
Maximum Temperature: 302F/150CMin. DHW Collection: 2.9 PSI/0.2 barand 0.79gal/3 litres/min.
Flow RegulatorLimitation: 3.7gal/14 l/min
By-pass O-ring. 4.2 ID x 1.9
Anti-friction Washerfor Pressure Relief Valve25,5 ID x 28,6 OD x 1
Pressure Relief ValveSet at 3 barServiceable and rotary
Pressure ReliefSet Pin 3 x 16 mm long
Detector O-ring
By - pass, Vent and Drain Cock
Allen 4 Bolts
Pump O-ring
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
24/56
Victoria wall-hung waterheaters
Magnetic Detector CH ReturnTo pump volute andheat exchanger
CH Circuit Fill Point
Mains Water Inlet
By - pass Circuit Inlet
Discharge to a drain
Drain and Vent
To the DHW
Heat Exchanger
Hydroblock operation
23Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
25/56
Hydroblock and pump
160014.0012.001100800600
Victoria wall-hung waterheaters24
0,40,2
6
5
4
3
2
1
Pressure Gauge Connectionto Pump Volute
O-ring for fixing the PressureGauge. 9.52 ID x 1.78
Mechanical PressureGauge Fixing
To Heat Exchanger
Fixing the body to thevolute Allen 5 M6 x 20
Fixing the Pump to the Hydroblok
O-ring 23 ID x 3.6
Return toradiators
MainsWater Inlet
MechanicalPressure Gauge
Unblocks of the
pump
PRIMARY HEAD
0,6 0,8 1,0 1,2 1,4 1,63
V (m /h)
H (m.w.g.)
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
26/56
Victoria wall-hung waterheaters
Water loop
Expansion VesselFill pressure: 10.88PSI/0.75 barButyl diaphragm and nitrogen charge
Total/useful Capacity: 2.11gal/1.2 gal - 8 litres/4.5 litres
Heat Exchanger6 steps in Heating:3 for flow and 3for returnPrimary capacity: 0.08 gal/300 cmSecondary capacity: 0.71 gal/270 cm
Domestic Cold Water Inlet PipeOD 0.55"/14 mmDHW SensorContact-type.DHW Outlet PipeOD 0.55"/14 mm
Hydroblok
Air vent Kit
CH SensorContact-typeOverheat ThermostatManual reset.Set at 221F/105C
CH Return PipeOD 0.71"/18 mm
CH Flow PipeOD 0.71"/18 mm
Mechanical PressureGauge
Pump3-speed type.
25Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
27/56
Victoria wall-hung waterheaters
Expansion VesselFill pressure: 10.88PSI/0.75 barButyl diaphragm and nitrogen charge
Total/useful Capacity: 2.11gal/1.2 gal - 8 litres/4.5 litres
Heat Exchanger6 steps in Heating:3 for flow and 3for returnPrimary capacity: 0.08 gal/300 cmSecondary capacity: 0.71 gal/270 cm
Air vent Kit
CH Sensor
CH Flow Pipe OD 0.71"/18 mm
To radiatorsMaximum Operating Pressure: 43.5 PSI/3 bar
Central Heating mode operation
26
Temp. Res. k104F/40C 5.330122F/50C 3.605140F/60C 2.490158F/70C 1.753176F/80C 1.256194F/90C 0.915
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
28/56
DHW mode operation
Heat Exchanger6 Steps in DHWPrimary capacity: 0.08 gal/300 cmSecondary capacity: 0.71 gal/270 cm
Expansion VesselFill pressure: 10.88PSI/0.75 barButyl diaphragm and nitrogen chargeTotal/useful Capacity: 2.11gal/1.2 gal - 8 litres/4.5 litres
Temp. Res. k104F/40C 5.330122F/50C 3.605140F/60C 2.490
DHW Sensor
Mains Water Inlet PipeOD 0.55"/14 mm
Outlet to draw-off pointsOD 0.55"/14 mm
Mains Water Inlet
Maximum operating pressure: 7 bar
Victoria wall-hung waterheaters27Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
29/56
3-way valve
Victoria wall-hung waterheaters
Sanitaryway
Heating training centres
HeatingWay
28
-
7/22/2019 74132089 Victoria Tech Manual
30/56
Outlines hydraulic Victoria 20/20 F
Victoria wall-hung waterheaters
Stoppedway
29Heating training centres
HeatingWay
-
7/22/2019 74132089 Victoria Tech Manual
31/56
Outlines hydraulic Victoria 20/20 F
Victoria wall-hung waterheaters
Sanitaryway
30Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
32/56
-
7/22/2019 74132089 Victoria Tech Manual
33/56
Overheat Thermostat
Open during service Open before light-up
Display of fault code50, 60, 70, 90,
and red Led
Display of faultcode 50, 60, 90,
and red Led
Gas supply cuts off Gas supply cuts offLockout
Faultcorrected
Faultcorrected
Thermostat Reset Thermostat Reset
Boiler Reset
Press red reset button Press red reset button
Control knob in R position
Yes Yes
No No
Operation of the Overheat Thermostat
Service restored
Victoria wall-hung waterheaters32Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
34/56
Flame safeguard rectification system (I)
Yes
Yes
Yes
No
No No
No
Light-up
Boiler Reset
Lockout
End of spark ignition Service available
Control knob inR position
End of spark ignition Safety solenoid
valve closes Display of fault code 60, 70, 90, and red Led
Call for service (Light-up)
Spark ignitionIgnitionelectrodes
Sadety solenoidvalve opens(gas inlet)
1st solenoidvalve opens(7 Th)
2nd solenoid
valve opens(12 Th)
Attempt tolight up
Light upin less than
4 secs
Light upin less than
1 sec
Faultcorrected
Lights up
in less than2 secs.
Service now restored
1st solenoidvalve opens (7 Th)
Yes
Victoria wall-hung waterheaters33Heating training centres
I t ti f i Note: If fault code 40-80-90 lights up for any of the
-
7/22/2019 74132089 Victoria Tech Manual
35/56
Yes
Yes
Yes
No
No No
No
Light-up
Boiler Reset
End of spark ignition Service available
Control knob inR position
End of spark ignition Safety solenoid
valve closes Display of fault code 40, 80, 90 and red Led
Interruption of service
Spark ignitionIgnition
electrodes
Safety solenoidvalve opens(gas inlet)
1st solenoidvalve opens
(7 Th)
2nd solenoidvalve opnes(12 Th)
Light-upprocess
Lights upin less than
4 secs
Lights upin less than
1 secFault
corrected
Light upin less than
2 secs.
Service now restored
1st solenoidvalve opens (7 Th)
Yes
Note: If fault code 40-80-90 lights up for any of thefollowing reasons:
Sensor lead splits Sensor rubbing against earth connection Bad earth connection contact
Then the process would be as follows:The flame does not blow out. Sparking begins for
7 seconds.
Boiler operation switches from 20 Th to 12Th and 7 Thuntil it goes into complete lockout.
Victoria wall-hung waterheaters
Lockout
34
Flame safeguard rectification system (II)
Attempt to relight
Heating training centres
Interruption offlue gas removal
Pressure influe pipe lower
(1) 12 mbar in VICTORIA 20/20 T
-
7/22/2019 74132089 Victoria Tech Manual
36/56
Chimney pull safety 20/20 F
Victoria wall-hung waterheaters
Si
Yes
No
No
Lockout
Light-up
Stop
Display of fault code40,50,80,90and red Led
Service now restored
Waiting for service call
flue gas removal(insufficient
chimney pull)
flue pipe lowerthan (1)
Automatic pressureswitch resetting
Pressure in fluepipe is higher than (2)
Faultcorrected
in less than3 minutes
Call service
Si
Si
Yes
Yes
Yes
No
No
Pressureswitchclosed
Pressureswitch open
Faultcorrected
Si
Si
Locked out againPre-purge
Exhaust fan starts
Display of fault code60, 80, 90
and red Led
Exhaust fanwill run for30 seconds
Boiler DIP switchchecking whether the
pressure switch is closed(pressure in flue pipe > (2)
No
Boiler DIP switch checkingwhether the pressure switch
is open (pressure in flue pipe < (1)
Exhaust fan stops for1 second
35Heating training centres
(1) 12 mbar in VICTORIA 20/20 T 17 mbar in VICTORIA 20/20 F(2) 15 mbar in VICTORIA 20/20 T 19,5 mbar in VICTORIA 20/20F
Ignition Sequence:2 seconds at 7 Th.
-
7/22/2019 74132089 Victoria Tech Manual
37/56
Burner
seco ds a4 seconds at 12 Th.1 seconds at 7 Th
Burner Fixing to theGas Valve. Allen 4 x 15
Ignition ElectrodesCentered on the middle burner 5mm higher anda 4mm electrode gap
Gas Valve PressureTest Point Bracket
Baffle plate
Flame Sensing RodAverage current: Mn: 3A, Med: 3,6 A, Mx: 4,1A13 becks
Material: Stainless Steel
Victoria wall-hung waterheaters36Heating training centres
Do not start the waterheateruntil the insulation panels have been properly assembled.
-
7/22/2019 74132089 Victoria Tech Manual
38/56
Combustion chamber
For optimum operation it is essential that these insulation panels be in good condition.
Victoria wall-hung waterheaters37
Side Insulation Panels. Material: Ceramic Fibre
CompactCombustion Chamber
Threaded Rods for Chassis Fixing8.58"/218 mm long x 0.24"/6mm
M5 Set NutsFor fixing the burner baffle plate
Front Insulation Panels.Material: Ceramic Fibre
Side Tabs. Fold them after fittingSide Insulation Panels
Heating training centres
Al i P fil f B
-
7/22/2019 74132089 Victoria Tech Manual
39/56
Kit valve G20 and G25
Victoria wall-hung waterheaters38
Chassis FixingBracket.
27,778 Btu/7,000 kcal/h
Solenoid Valve.
47,620 Btu/12,000 kcal/h
Solenoid Valve.
27,778 Btu/20,000 kcal/h
Solenoid Valve.
Safety SolenoidValve.
Aluminum Profile for BurnerInjector HolderSolenoid ValveAssembly
Gas GovernorNatural Gas only
Control Range: 0.25 0.36 PSI / 17 25 mbar
Burner SettingPressure Device
Gas Supply Pressure Test PointG20(GN): 0.29 PSI/20 mbar. G30(GB): 0.41 0.44PSI/28 30 mbar. G31(GP): 0.54PSI/37 mbar
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
40/56
Cross-section of gas valve
Victoria wall-hung waterheaters39
Stages of Output Bore Size
27,778 Btu/7,000 kcal/hSolenoid Valve.
47,620 Btu/12,000 kcal/h
Solenoid Valve.
79,366 Btu/20,000 kcal/h
Solenoid Valve.
Aluminum Profile for BurnerInjector Holder
Burner Fixing.
To PressureTest Point
Valve GasketMaterial: Cork + Nitrile
Gas Valve BodyMaterial: Aluminium
Solenoid Assembly GasketMaterial: Cork + Nitrile
Solenoid Valve Assembly
Heating training centres
A dj t t d/ tti t b i d t b lifi d t h i i
-
7/22/2019 74132089 Victoria Tech Manual
41/56
Gas changeover kit
Any adjustments and/or settings must be carried out by a qualified technician
Victoria wall-hung waterheaters
Kit G30 / G31Kit G20 / G25
40
Natural Gas Kit(To convert a Propane/ButaneGas waterheaterinto Natural Gas)
Propane/Butane Gas Kit(To convert a Natural Gas waterheater
into Propane/Butane Gas)
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
42/56
Components of the waterheatersF
Victoria wall-hung waterheaters41
Pressure SwitchSetting Range for VICTORIA 20/20F:17 19.5 mm.w.g.
Socket for connectionto specific flue ductOutlet 2.36"/60mm
Pressure SwitchConnecting PipesExhaust Fan
r.p.m.: 2720Average current: 0.41A
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
43/56
42
Kit 140040030-03 for F waterheaters(supplied as standard)
Flue duct kit (I)
Victoria wall-hung waterheatersHeating training centres
Victoria 20/20 F (C - 12)
-
7/22/2019 74132089 Victoria Tech Manual
44/56
Flue duct kit(II)
Victoria wall-hung waterheaters43
Configuration C12:Room-sealed waterheater. Horizontal concentric flue pipe.Flue gases discharged directly into the atmosphere. Exhaust fan locatedabove the combustion chamber.
Heating training centres
Victoria 20/20 F (C - 12)
L
4.9
2"/125
L 19.69ft/6 m
3.94"/100mm
10
0mm
L
M
L + M
9.84ft/
3 m
Victoria 20/20 F (C - 42)
-
7/22/2019 74132089 Victoria Tech Manual
45/56
Flue duct kit(III)
Victoria wall-hung waterheaters44
Configuration C42:Room-sealed waterheater. Horizontal concentric flue pipe connected to a twincommon shunt or stack. Exhaust fan located above the combustion chamber.
140040030-03Configurations C12 / C42: Directional, concentric horizontal flue pipe kit with 60/100damper. Quick connect coupling. 1m horizontal flue length. SUPPLIED AS STANDARD.
140040061-01Configurations C12 / C42: Directional, concentric horizontal flue pipe kit with 60/100damper. Quick connect coupling. 1m horizontal flue length and 0.2m vertical flue length.
140040084-00Configurations C12 / C42: Directional, concentric horizontal flue pipe kit with 80/125damper. Quick connect coupling. 1m horizontal flue length.
Heating training centres
Victoria 20/20 F (C - 42)
7.87"/0.2 m < L 9.84ft/3 m
3.9
4"/100mm
L
Victoria 20/20 F (C - 82)
-
7/22/2019 74132089 Victoria Tech Manual
46/56
Flue duct kit(IV)
Victoria wall-hung waterheaters45
Configuration C82: Room-sealed waterheater. Single, horizontal flue pipes. Fresh air intake.Flue gas outlet to a standard common shunt. Exhaust fan located above the combustion chamber.
140040039-02Configuration C82. Directional, twin-pipe horizontal flue kit with 80 damper.Quick connect coupling. 1m horizontal flue length for both runs.
Heating training centres
Victoria 20/20 F (C 82)
With no diaphragm: 13.12 ft/4 m< L + P 32.8 ft/10 m
With diaphragm 1.8"/46 mm: L + P 13.12 ft/4 m
3.1
5"/80
L P
3.1
5"/80
Diaphragm 1.8"/46 mm
Victoria 20/20 F (C - 32)
-
7/22/2019 74132089 Victoria Tech Manual
47/56
Flue duct kit(V)
Victoria wall-hung waterheaters46
Configuration C32: Room-sealed waterheater. Vertical concentric flue pipe. Flue gases dischargeddirectly into the atmosphere. Exhaust fan located above the combustion chamber.
140040034-03Configuration C32. Directional, concentric vertical flue pipe kit with 60/100 damper.Quick connect coupling. 1m vertical flue length.
140040059-00Optional vertical concentric accessory in the C32 configuration for vertical outlet to the roof.
Heating training centres
With no diaphragm: 7.87ft/2.4 m < L 36.1"/11 m
With diaphragm 1.77"/45 mm: 1.4 m < L 7.87ft/2.4 m
3.94"/100mm
4.9" /125mmL
3.94"/100mm
4.65" /118mmL
4.6ft/1.4 m < L 23ft/7 m
Victoria 20/20 F (C 32)
Diaphragm 1.77" / 45 mm
-
7/22/2019 74132089 Victoria Tech Manual
48/56
Flue duct kit(VII)
Victoria wall-hung waterheaters47Heating training centres
Each 90 concentric elbow 100 reducesallowed length2.3ft/0.7mEach single 90 elbow 80 reduces allowed length 1.64ft/0.5mThe first waterheateroutlet elbow should not be taken into account.No reduction is necessary when using 45 elbows.
M
3.94"/100mm / 4.9"/125mm
3.94"/100mm/ 4.9"/125mm
M
L
L
PP
Location of the timer connection on the electronic PCB.
-
7/22/2019 74132089 Victoria Tech Manual
49/56
Timer connections
Victoria wall-hung waterheaters48
Timer connection
(Earth)
Black (Signal)
Green
(Power)
Red
Heating training centres
Start-up
-
7/22/2019 74132089 Victoria Tech Manual
50/56
Programming instructions (I)
1 2 3 4 5 6 7
1 2 3 4 5 6 7
1 2 4 5 6 731 2 3 4 5 6 7
Day h m
Prog.
Programmed
operatinginformation
Day & time
Programmode
Set day
RES1hTo switch fromsummer to wintertime
Weekdays Time and minutes
Denotes boiler
operating orstopped
Set Time
Set minutes
Manual mode
Reset
Start upFirst of all, delete all stored data.To do that, press the RES keyfor 3 seconds. Release key andthe following display will appear:
The days of theweek are flashing
Finally, releasethe key.The colon willbe flashing.
Setting the time
1h 1h
Victoria wall-hung waterheaters49Heating training centres
Possible Day Combinations are:
1 2 3 4 5 6 7= Mo, Tu, We, Th, Fr, Sa, Su
-
7/22/2019 74132089 Victoria Tech Manual
51/56
Finally, after entering the last switchingstatus required, close the programming mode by
pressing the key.The standard screen in theoperating mode will besimilar to the one shown here.Manual OperationPress the key. The screen will be similar tothe one shown in this figure.
1 2 3 4 5 6 7
1 2 3 4 5 6 7
Press thekey and the followingscreen will be displayed.
Enter the status of the daysfirst command by pressing
and taking into accountthat this symbol indicatesthat the Waterheateris operating.With no centre black dot, it means
that the waterheateris OFF.
Enter the days first switching command.To do that, press the keys.
1 2 3 4 5 6 7
1 2 3 4 5 6 7 1 2 3 4 5 6 7
Enter the required switching day(s)by pressing the key.
See Possible Day Combinations table.The screen displayed will besimilar to the one in this figure.
To continue programming, press thekey and repeat steps 2to 4as many times asnecessary to complete the whole week.
Victoria wall-hung waterheaters
Or each individual day of the week.
1 2 3 4 5 6 71 2 3 4 5 61 2 3 4 5 6 7
Mo, Tu, We, Th, Fr, Sa, Su = Mo, Tu, We, Th, Fr, Sa, = Mo, Tu, We, Th, Fr,= Sa, Su
50
Programming instructions(II)
Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
52/56
In the manual mode, stored data will not be altered.In addition, there are specific functions to thisoperating mode, which are as follows:
Switching Times DisplayPress the key repeatedly.The stored switching times willbe displayed in sequence.
To exit the display mode,press the key.
Once all programmed status havebeen displayed, the followingscreen will appear again.
Changing:Press the key several times until reaching theprogram to be changed. Alter the settings by following
steps 2 to 6 in the Programming section.Deleting:Press the key several times until reaching theprogram to be deleted. Press the keys untilthe -- symbol is displayed on the screen.Keep the key pressed for 3 seconds. This willdelete all stored data. Press the key to exit thedeleting mode.
1 2 3 4 5 6 7
1 2 3 4 5 6 7
Victoria wall-hung waterheaters
The following switching output status are possible:After the last occupied memory block, the number offree memory blocks are displayed on the screenFr 00 = indicates that all memory blocks are occupied.
Above two manually altered switching commands will becancelled by the next automatic switching time.
= Advance OFF (if current switching status is=ON
=OFF
=Permanently OFF
=Permanently ON
Return automatic mode is only possible by pressingthe key.
= Advance ON(if current switching status is
51
Programming instructions(III)
Heating training centres
The factory-set configuration is shown in red.
-
7/22/2019 74132089 Victoria Tech Manual
53/56
Control DIP switches
Access to DIP SwitchesRemove the control panel fascia
Location of DIP switches on the electronic board.
DIP SWITCHES 1 & 2: Central Heating Output Adjustment
DIP SWITCH 3: CH pump operationDIP SWITCH 4: Time-delay between ON and OFFDIP SWITCHES 5 & 6: Hysteresis Selection
Output Adjustment SW1 SW2
47,620 Btu/12.000 kcal/h ON OFF27,778 Btu/7,000 kcal/h OFF OFF
79,366 Btu/20,000 kcal/h ON ON
Hysteresis SW5 SW671.6F/22C OFF OFF
53.6F/12C ON OFF46.4F/8C ON ON
62.6F/17C OFF ON
Circulating Pump Operation SW3Continuous operation OFF30 seconds after Room Thermostat stops ONTime-delay SW4Enabled (6 minutes running) OFFDisabled ON
Victoria wall-hung waterheaters52Heating training centres
-
7/22/2019 74132089 Victoria Tech Manual
54/56
Maintenance
Carry out the following maintenance operations at least once a year, and preferably at the beginningof the Heating season:DHW
Clean the cold water filterCheck the DHW temperatureHeatingCheck the system pressureCheck the waterheaterwater temperatureCheck the pump operationBleed the air in the radiators and boilerCheck the room thermostat
Check the safety valveGasCheck the burner setting pressureCheck the input rateCheck the circuit for gas tightnessClean the burner VenturisCombustion and VentilationCheck the flue duct tightness
Check the effectiveness of ventilation and air renewal system. Ensure there are no obstructions.Conduct a flue gas analysis.
Victoria wall-hung waterheaters53Heating training centres
The following parameters are factory-set as shown:
-
7/22/2019 74132089 Victoria Tech Manual
55/56
Factory settings
Output to Central Heating
Victoria 20/20 FFeature
(*) It is governed by the Room Thermostat. If no Room Thermostat has been installed,it will operate continuously.
Victoria wall-hung waterheaters54Heating training centres
79,366 Btu/20,000 kcal/hSW1 (ON) SW2 (ON)
79,366 Btu/20,000 kcal/h
2
30 secs following stoppage of Room StatSW3 (ON)
De-energizedSW4 (ON)
62.6F/17C
SW5 (OFF) SW6 (ON)
Output toDomestic Hot Water System
Pump Speed Position
Pump Operation Time (*)
6-minute Time Delay
CH Hysteresis
-
7/22/2019 74132089 Victoria Tech Manual
56/56