ComfortNet™ CTK04 Communicating Thermostat With wireless accessories System Installation Guide Modulating control for up to 4 Heat/2 Cool communicating heat pump systems or up to 3 Heat/2 Cool communicating gas heat, electric cooling systems for residential and commercial applications. Installation guide for: Quick start guide ComfortNet CTK04 Communicating Thermostat Portable Comfort Control Wireless Outdoor Sensor Wireless Indoor Sensor RedLINK Internet Gateway Entry/Exit Remote Vent Boost Remote 1 Install thermostat .......................................................... page 4 2 Power optional accessories ................................................... 7 3 Setup thermostat ................................................................... 8 4 Link optional accessories ...................................................... 9 5 Mount optional accessories ................................................. 11 6 Installer options ................................................................... 12 ComfortNet™ User Menu .................................................... 13 Device replacement and specifications .......................... 21-23 DISCONNECT POWER BEFORE INSTALLATION. Can cause electrical shock or equipment damage. MERCURY NOTICE: If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact the Thermostat Recycling Corporation at www.thermostat-recycle.org or 800-238-8192 for information on how and where to properly and safely dispose of your old thermostat. Must be installed by a trained, experienced technician. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition. I/O-CHTSTAT03 69-2688-07

Upload: others

Post on 04-Aug-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

ComfortNet™ CTK04 Communicating Thermostat

With wireless accessories

SystemInstallation Guide

Modulating control for up to 4 Heat/2 Cool communicating heat pump systems or up to 3 Heat/2 Cool communicating gas heat, electric cooling systems for residential and commercial applications.

Installation guide for:

Quick start guide

• ComfortNetCTK04 CommunicatingThermostat

• PortableComfortControl

• WirelessOutdoorSensor

• WirelessIndoorSensor

• RedLINK™InternetGateway

• Entry/ExitRemote

• VentBoostRemote

1 Installthermostat ..........................................................page 42 Poweroptionalaccessories ...................................................73 Setupthermostat ...................................................................84 Linkoptionalaccessories ......................................................95 Mount optional accessories .................................................116 Installeroptions ...................................................................12

ComfortNet™UserMenu ....................................................13

Device replacement and specifications ..........................21-23

DISCONNECT POWER BEFORE INSTALLATION. Can cause electrical shock or equipment damage.

MERCURY NOTICE: If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact the Thermostat Recycling Corporation at www.thermostat-recycle.org or 800-238-8192 for information on how and where to properly and safely dispose of your old thermostat.

Must be installed by a trained, experienced technician. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.

I/O-CHTSTAT03

69-2688-07

Page 2: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

269-2688—07 I/O-CHTSTAT03

The ComfortNet advantage

ThepremiumHoneywellComfortNet™controlsystemiseasytouse,energy-efficient,reliableandensuresthesystemissetupproperly.Advancedoperatingalgorithmsbuiltintothecontroldeliversefficientequipmentoperationwhileprovidingoptimalcomfort.TheHoneywellComfortNetCommunicatingthermostatisdesignedtoregulateandcommunicatewiththecentralheatingandcoolingequipmentandhastheabilitytoshareinformationsotheuserwillenjoyefficient,economicalcomfortthroughout the home.

RedLINK™ CompatibleRedLINKaccessoriesincludetheWirelessOutdoorSensor,PortableComfortControl(PCC),RedLINKInternetGateway,WirelessIndoorSensor,TrueSTEAM™humidifierwithWirelessAdapter,VentBoostRemoteandEntry/ExitRemote.

Customizable Service RemindersSetupto10servicereminders.Choosefrompre-setoptionsorcustomizeyourown.Pre-setreminderoptionsincludefilterreplacement,humidifiermaintenance,dehu-midifierfilter,ventilatorfilter,UVbulbreplacement,annualservice,springservice,fallserviceandwarrantyexpiringsoon.Remindersbasedonthedateoroutdoortemperaturewillbedisplayedonthethermostat'smainscreenalongwithpre-setorcustom instructions.

User Interactions LogTheinteractionlogstoreshistoryofthermostatsettingchangesincludingtempera-ture,systemandinstallersetup.Youcanusetheinteractionlogtosavetimebydetermining if the issue is a system error or an accidental user error.

Configurable for Residential and Light Commercial ApplicationsOnethermostatdoesitalltomeettheneedsofResidentialandLightCommercialapplications.SimplyselectResidentialorCommercialduringtheinstallersetup.IfCommercialisselected,thethermostatwillusecommerciallanguage,meetbuildingcodes and offer 365 day holiday scheduling.

USB PortVisithttp://thermostatsetup.honeywell.comtoenteryourdealerinformationandsavetoaUSBstick.Thenloadyourdealerinformationandlogotomultiplethermostats.

Aftersettingupathermostat,saveInstallerSetup,Holiday/EventSchedulerandCustomReminderstoaUSBstick.Thenloadthisinformationtomultiplethermostats.

TousetheUSBport,insertaUSBstickinthebottomofthethermostat.Thenselecttheitemyouwouldliketoloadorsave.

Selectable SensorsWhenpairedwithaWirelessIndoorSensor(s)youhavetheabilitytochoosewhichsensor(s)tousefortemperature,humidificationanddehumidification.Theycanbeusedincombinationfortemperatureaveraging—orindividually—toconditionhumiditylevels in separate spaces.

Page 3: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

3 I/O-CHTSTAT03 69-2688—07

Installation

Thisbookletcontainsinstallationinstructionsandinformationonthethermostatandwirelessaccessories.SeparateinstallationinstructionsforthefurnaceorairhandlerandoutdoorACcondensingunitorheatpumpareprovidedwiththeappropriateequipment.ThisthermostatisdesignedexclusivelyforusewiththeComfortNetcom-municating system.

Valid System Configurations

Thiscontrolmayonlybeusedwithcertainsystemconfigurations.Validsystemcon-figurationsforwhichthiscontrolcanbeusedare:• AcommunicatingairhandlermatchedwithacommunicatingoutdoorAC

condensing unit.• Acommunicatingairhandlermatchedwithacommunicatingoutdoorheatpump

unit.• AcommunicatingfurnacematchedwithacommunicatingoutdoorACcondensing

unit.• Acommunicatingfurnacematchedwithacommunicatingoutdoorheatpumpunit.• Acommunicatingfurnacematchedwithanon-communicatingsinglestageAC

condensing unit.

Installing Thermostat

1. RemoveandinventoryallComfortNetcomponents.TheCTK04containstheComfortNetcommu-nicatingthermostat,lithiumcoincellbattery,wallmountingscrewsandanchors,systeminstalla-tionguide,operatingmanual,transformerandawiringsetthatincludestwoterminalblocks,twosheetmetalscrewsandwires.

2. Carefullyseparatethethermostatbodyfromthethermostatbase.3. Placebaseatinstallationlocationandmarkmountingholelocationsonwallusingbaseasa

template.SeeThermostatMountingsectiononnextpageforoptimalmountinglocation.4. Drillmountingholes.Drill3/16"holesfordrywalland7/32"holesforplaster.5. Attachbasefirmlytowallusingtwomountingscrews.Levelingisforappearanceonlyandwill

not affect thermostat operation.6. Connectwirestoterminalblockonbase.7. 18AWGsolidwireisrecommended.8. Pushexcesswireintowallandplugholewithafireresistantmaterial(suchasfiberglassinsula-

tion)topreventdraftsfromaffectingthermostatoperation.9. Insertcoincellbatteryinthebackofthethermostat.10. Carefullylineupthethermostatwiththebaseandsnapintoplace.

HIGHVOLTAGE

TRANSFORMER LOWVOLTAGE CONNECTEDTO R AND CTERMINALS

CONNECT 2-WIRES TO INDOOR UNIT

REMOVE AND INVENTORY ALLCOMFORTNET™ COMPONENTS

REMOVE OUTDOOR UNITCOVER AND 7-PIN CONNECTOR

NOTE: THE CTK04 CONTAINS THE THERMOSTAT, LITHIUM COIN CELL BATTERY, WALL MOUNTING SCREWS AND ANCHORS, SYSTEM INSTALLATION GUIDE, OPERATING MANUAL, TRANSFORMER AND A WIRING SET THAT INCLUDES TWO TERMINAL BLOCKS AND WIRES.

P/N F0430675005

INSTALL HVAC COMPONENTS

GASFURNACE

AIRHANDLER

TERMINALS 1 & 2 ARECOMMUNICATIONS WIRES. THEY SHOULD NEVER BE CONNECTEDTO THE 24 VAC R&C POWER SUPPLYTERMINALS.

CONNECT 4-WIRES FROM STAT AND 2 WIRES FROM OUTDOOR UNIT

P/N F0430679005

P/N F0430673005

CONNECT TO THE OUTDOOR UNIT 2-WIRE/TRANSFORMER CONNECTION

CONNECT HIGH VOLTAGE TRANSFORMER LEADS TO L1 AND L2 MALE SPADE TERMINALS ON CIRCUIT BOARD. DO NOT CONNECT R AND C BETWEEN THE INDOOR UNIT AND OUTDOOR UNIT. SEE PAGE 5.

INSTALL THERMOSTAT ON INTERIOR WALL

NOTE: THERMOSTAT WILL AUTOMATICALLY CONFIGURE TO THE SYSTEM ONCE HIGHVOLTAGE POWER IS APPLIED TO THE INDOOR AND OUTDOOR EQUIPMENT.

M33487B

1 REMOVE 9-PIN CONNECTORFROM FURNACE OR AIR HANDLER CONTROL

2 3

4

5 6

AIR CONDITIONEROR HEAT PUMP

AIR CONDITIONEROR HEAT PUMP

TRANSFORMER

ADDITIONAL TRANSFORMERIS NOT REQUIRED FORINVERTER/VARIABLE SPEED OUTDOOR COMMUNICATINGUNITS. ADDITIONAL TRANSFORMERIS REQUIRED FOR 2-STAGEOUTDOOR COMMUNICATINGUNITS.

LOW (24 VAC)VOLTAGE

Page 4: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

469-2688—07 I/O-CHTSTAT03

Install thermostat1

Thermostat MountingMountthethermostatapproximately5feetfromtheflooronaninteriorwallusingtheincludedscrewsandanchors.Drill3/16"holesfordrywalland7/32"holesforplaster.Donotinstallthethermostatwhereitcanbeaffectedby:• Draftsordeadspotsbehinddoorsandincorners.• Hotorcoldairfromducts.• Radiantheatfromsunorappliances.• Concealedpipesandchimneys.• Unheated(uncooled)areassuchasanoutsidewall.

Terminal Functions:1 - Data 12 - Data 2R-24voltpowerC - 24 volt common

Wire Gauge:18gaugewireisrecommended.MaximumwiredistancebetweentheComfortNetthermostatandtheIFCshouldnotexceed100feetusing18gaugewire.

MCR29241

MCR33170

12RC

MCR33171

12RC

Page 5: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

5 I/O-CHTSTAT03 69-2688—07

Install thermostat1

Wiring Thermostat, Indoor Unit and Outdoor Unit

Wire Thermostat to Indoor Unit

Connect1,2,RandCfromthethermostatto1,2,RandCattheIndoorUnit.

Wire Outdoor Unit

Connectwires1and2fromtheIndoorUnitto1and2attheOutdoorUnit.InstallthetransformerprovidedandconnecttoRandCattheOutdoorUnit.(NOTE:installingtheadditionaltransformerisNOTrequiredforinverter/variablespeedoutdoorcom-municatingunits.AdditionaltransformerISrequiredfor2-stageoutdoorcommunicat-ingunits.)DoNOTconnectRandCbetweentheIndoorUnitandOutdoorUnit.Seebelow.

CTK04

INDOORBOARD TERMINAL

CONNECTIONS

R

C

1

2

24VAC (HOT)

24VAC(COMMON)

DATA 1

DATA 2

L1

L2

24VAC 240V

OUTDOORBOARD TERMINAL

CONNECTIONS

OUTDOORTRANSFORMER

INSTALLING THE ADDITIONAL TRANSFORMER IS NOT REQUIRED FOR INVERTER/VARIABLE SPEED OUTDOOR COMMUNICATING UNITS. ADDITIONAL TRANSFORMER IS REQUIRED FOR 2-STAGE OUTDOOR COMMUNICATING UNITS.

R

C

1

2

R

C

1

2

M33168C

1

1

Page 6: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

669-2688—07 I/O-CHTSTAT03

M32940

[If no wireless accessories are used, skip to Section 3.]

Portable Comfort Control

Install 2 fresh AAA alkaline batteries Install 3 fresh AA alkaline batteries

Outdoor air sensor Indoor air sensor

Install 2 fresh AA lithium batteries

Power optional accessories2

TheHoneywellRedLINKInternetGatewaygivesyourcustomersremoteaccesstohomeclimate-controlsystemsfromanylocationwithInternetaccess.

UsingaWebbrowser,userscanreviewandadjustindoortemperature, systemmodeandothersettings.TheGatewaycanalsosendalertstoasmanyas6emailaddressesifaproblemoccurs.

RedLINK™ Internet Gateway

Connect power cord to an electrical outlet not controlled by a wall switch

Connect RedLINK Gateway to a router or modem with Ethernet cable (RJ45).

MCR32937 MCR32938 MCR32939

Page 7: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

7 I/O-CHTSTAT03 69-2688—07

Power optional accessories2

TrueSTEAM

ConnecttheABCDterminalsbetweenTrueSTEAMandtheTHM4000WirelessAdapter.

AdjusttheDIPSwitchesonTrueSTEAMasfollowswhenusingtheWirelessAdapter:DIP3:UPDIP4:UPDIP5:DOWN

THM4000R1000

TrueSTEAM

MCR31476

65432

ON

OFF

1

Entry/Exit Remote or Vent Boost Remote1 Removethecover.2 InserttheCR2450coincellbattery(included)intotheslotatthebottomoftheremote.Seepolaritymarkingontheremote.

3 TheLEDwillbrieflyflashgreen.Ifitflashesred,batteryisnotgood.

MCR33269

Page 8: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

869-2688—07 I/O-CHTSTAT03

Setup thermostat3

Initial Power Up1 TurnonACpowertothesystem.

2 SelectLanguage.PressNext.

3 SelectApplication(ResidentialorCommercial).PressNext.

Thethermostatwillautomaticallyiden-tifytheComfortNetcommunicatingequipmentinstalledandthenyouwillbepromptedtoaddRedLINKaccessories(page9)andsetuptheInstallerOptions(page12).

4 EnteraDeviceName.PressNext.

Page 9: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

9 I/O-CHTSTAT03 69-2688—07

MCR32935MCR32934

WhiletheAddDevicescreenisdisplayedon the thermostat, press and release the CONNECTbuttononeachwirelessdevice,asdescribedbelow.Accessoriesneedtobeatleast2feetawayfromthethermostatduringthelinkingprocess.

Ifyouneedtoreturntothe"AddDevice"screentoadddeviceslater,pressMENU andscrolldowntopressINSTALLER OPTIONS.Enterthedatecode(password)whenprompted.Thedatecodeisprintedonthebackofthethermostat;orpressMENU > EQUIPMENT STATUStofindthedatecode.Afteryouenterthepassword,scrolldowntopress WIRELESS DEVICE MANAGER and then select ADD DEVICE.

MCR28847A

Link optional accessories to wireless network4

Wireless outdoor sensor

Wireless indoor sensor

Press and release CONNECT. After a short delay the thermostat will display "Wireless Outdoor Sensor added" on the Add Device screen.

Press and release CONNECT. After a short delay, the status light will glow green for 15 seconds.

If the status light turns red, the sensor did not link with the thermostat.

Battery level indicators (when batteries are inserted)Good: Status light flashes green for 5 seconds.Low: Status light flashes red for 5 seconds. Use fresh batteries.

Battery level indicators (during use)Good: Status light remains off.Low: Battery power will be depleted in about 2 months. Thermostat displays Low

Battery warning. Status light remains off.Critical: Battery power will be depleted in about 2–3 weeks. Status light flashes red.

Press DONE after all devices have been linked

When power is interrupted, the equipment and the RedLINK accessories will automatically restore communication after power resumes.

If you have both a wired and wireless outdoor sensor installed, the thermostat displays the reading from the wireless outdoor sensor.

The thermostat can use up to 6 optional wireless sensors.

Page 10: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

1069-2688—07 I/O-CHTSTAT03

Entry/Exit Remote or Vent Boost RemotePress and release CONNECT button.

TrueSTEAMPress and release the CONNECT button on the THM4000 Wireless Adapter. After a short delay, the CONNECTED status light will glow steady green..

Link optional accessories to wireless network4

MCR32943

RedLINK Internet GatewayPress and release the button on the bottom of the Internet Gateway. After a short delay, the RedLINK status light will glow steady green.

The Internet Gateway must be registered online before use at www.mytotalconnectcomfort.com. Enter the MAC ID and MAC CRC numbers located on the bottom of the Internet Gateway. For additional information, see instructions provided with the device.

MCR32942

CONNECT

WIRELESS SETUP

Portable Comfort Control

The linking procedure will time out if there is no keypress for 30 minutes. To begin again, press and hold in the lower right corner of the screen until the display changes (about 3 seconds).

Press CONNECT on the Portable Comfort Control display screen. Press DONE when the screen displays "Connected." Press NO at the next screen to save and exit. (Or press YES to link another thermostat.)

Error messages:E1 29 Incompatible device cannot be connected.E1 34 Low RF signal. Move device to a different location and try

again.E1 38 Make sure the thermostat is in Wireless Setup mode,

and the Portable Comfort Control is at least 2 feet away.

MCR33096

After a short delay, the status light will glow green for 15 seconds. If the status light turns red, the remote did not link with the thermostat for the connection process.

Page 11: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

11 I/O-CHTSTAT03 69-2688—07

Mount optional accessories

1 Mountthesensoronaverticalexteriorwall,atleast6inchesbelowanyoverhang. Choose a location protected from direct sunlight.

2 Placesensorsecurelyinbracket,facingawayfromwall.

5

M28491

M28849A

[If no sensors are used, skip to Section 6.]

To install outdoor air sensor

To install indoor air sensor

To install Entry/Exit Remote or Vent Boost Remote

1 Removethewallplateandmountit4to6feetabovetheflooronaninteriorwall.Drill3/16-inchholesfordrywall,7/32-inch for plaster.

2 Attachsensorsecurelytowallplateasshown.

Mounting the remote is optional.

1 Removethefrontcoverfromtheremote.

2 Useprovidedscrewsandwallanchorstofastentheremotetothewall.Drill3/16-inchholesfordrywall,7/32-inchfor plaster.

3 Replacethecoverontheremote.

M32936B

M33095

Do not install the indoor air sensor where it can be affected by:• Drafts or dead spots behind doors and in corners.• Hot or cold air from ducts.• Radiant heat from sun or appliances.• Concealed pipes and chimneys.• Unheated (uncooled) areas such as an outside wall

Page 12: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

1269-2688—07 I/O-CHTSTAT03

Installer options (ISU)6

Create Setup: Press CREATE SETUP to set all system settings one by one.

View/Edit Current Setup: Press VIEW/EDIT CURRENT SETUP to select a specific function and make quick changes.

Installer Test: Press INSTALLER TEST to quickly determine if the heat, cool, fan and thermostat are operating properly. Minimum off timers are ignored during the test.

Data Logs: Press DATA LOGS to view the Alerts Log and User Interactions Log.

Wireless Device Manager: Press WIRELESS DEVICE MANAGER to add or remove wireless accessories.

Advanced Options: Press ADVANCED OPTIONS to setup the thermostat using a USB device or to restore the thermostat to the factory default settings. See page 2 for more information on the USB port.

TIP: You can use the thermostat USB port to download all system configuration and installer options, including your company name and contact information. You can upload this data to each thermostat you install, to save time.

Tosetupthethermostat,pressMENUandscrolldowntopressINSTALLER OPTIONS. Enterthedatecode(password)whenprompted.Thedatecodeisprintedonthebackofthethermostat;orpressMENU > EQUIPMENT STATUS to find the date code. Afteryouenterthepassword,pressCREATE SETUP to setup the thermostat.

Abriefsummaryofinstalleroptionsfollows.Youcandownloadacompletelistofalloptionsathttp://customer.honeywell.com.

1000 Language B1010 Residential/Commercial B1030 Device Name B1030 Device Name on Home Screen C1040 Programmable/Non-programmable B1050 Fahrenheit/Celsius B1060 Outdoor Air Sensor B2000 Heating System Type B2010 Heating Equipment Type B2070 Heat Stages B2070 Cool/Compressor Stages B2070 Backup Heat Stages B2180 Backup Heat Type B2190 System Zoning - Backup Heat Control B3000 Manual/Auto Changeover B3000 Auto Changeover Deadband B3010 Temperature Control Options B3020 Finish With High Cool Stage B3021 Finish With High Heat Stage B3030 Staging Control - Cool Differentials B3050-3060 Staging Control - Heat Differentials B3090 Staging Control - Backup Heat Differentials B3110 Backup Heat Upstage Timer B3120 Outdoor Compressor Lockout B3120 Outdoor Backup Heat Lockout B3140 Cool/Compressor Cycles Per Hour B

3150 Heat Cycles Per Hour B3160 Backup Heat Cycles Per Hour B3170-3190 Cooling Derivative, Integral, Throttling range C3200-3220 Heating Derivative, Integral, Throttling range C3240 Minimum Compressor Off Time B3260 Extended Fan Run Time in Cool B3260 Extended Fan Run Time in Heat B4000 Number of Schedule Periods B4010 Pre-occupancy Purge Duration C4020 Override: Standard or Initiate Occupancy C4030 Override Duration C4050 Minimum Recovery Settings - Heat C4060 Maximum Recovery Settings - Heat C4070 Minimum Recovery Settings - Cool C4080 Maximum Recovery Settings - Cool C4090 Adaptive Intelligent Recovery R4100 Minimum Cool Setpoint B4100 Maximum Heat Setpoint B4110 Keypad Lockout B4120 Entry/Exit Remote -

Home/Occupied Cool Setpoint B4120 Entry/Exit Remote -

Home/Occupied Heat Setpoint B4130 Entry/Exit Remote -

Away/Unoccupied Cool Setpoint B

ISU Function ISU Function

R: Residential C: Commercial B: Both

Page 13: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

13 I/O-CHTSTAT03 69-2688—07

ComfortNet User Menu PressMENU > COMFORTNET USER MENU

AdditionalequipmentinformationisfoundintheComfortNetUserMenu.PressMENU andscrolldowntopressCOMFORTNET USER MENU.Enterthedatecode(password)whenprompted.Thedatecodeisprintedonthebackofthethermostat;orpressMENU > EQUIPMENT STATUS to find the date code.

Afteryouenterthepassword,selecttheequipmenttype(furnace,airhandler,airconditioner,heatpump)toviewthespecifications.

Eachequipmenttypeisdividedintocategorieswhichmayinclude:(Notallmenuoptionslistedheremaybeavailable.Additionalmenuoptionsmaybedisplayedonthethermostat.)

4130 Entry/Exit Remote - Away/Unoccupied Heat Setpoint B

4140 Entry/Exit Remote - Vacation/Holiday Cool Setpoint B

4140 Entry/Exit Remote - Vacation/Holiday Heat Setpoint B

5040 Indoor Sensors Used for Temperature Control B7000 Filter Type B7020 Number of Air Filters B7110 Air Filter Replacement Reminder B7110 Air Filter 2 Replacement Reminder B7120 EAC Cell Cleaning Reminder B7120 EAC Pre-Filter Cleaning Reminder B7120 EAC Post-Filter Replacement Reminder B8000 Humidifier Type B8010 Indoor Sensor Used for Humidification Control B8050 Humidification - Window Protection B8060 System Modes Allowing Humidification B8070 Humidification Control B8100 Clean Tank / Water Filter Replacement Reminder B8100 Humidifier Pad Replacement Reminder B9000 Dehumidification Equipment B9010 Indoor Sensor Used for Dehumidification Control B9020 Humidity Sensor Displayed on the Home Screen B9070 Dehumidification - Overcooling Limit R9080 Dehumidification Control C9090 Dehumidification Minimum On Time C

9100 High Humidity Comfort Reset Setting C9180 Dehumidification Away Mode B9190 Dehumidification Away Mode - Fan Control B9200 Dehumidification Away Mode -

Low Limit Temperature B9200 Dehumidification Away Mode -

Temperature Setting B9200 Dehumidification Away Mode -

Dehumidification Setting B9210 Dehumidifier Filter Replacement Reminder B10000 Ventilation Type B10050 Ventilation Control Method B10090 Number of Bedrooms R10090 Size of House R10100 Enter Equipment Ventilation Rate R10120 Ventilation Percent On Time B10170 Ventilator Filter Cleaning Reminder B11000 Number of UV Devices B11050 UV Bulb Replacement Reminder B11050 UV Bulb 2 Replacement Reminder B12000 Installer Custom Reminders B14000 Clock Format B14010 Daylight Saving Time B14020 Indoor Temperature Display Offset B14020 Indoor Humidity Display Offset B15000-15020 Dealer name, phone, email, website, message B

Installer options (ISU)6

ISU Function ISU Function

• Configuration: Provides information regarding the setup of the equipment. An example of configuration data is the number of cooling stages for an AC condensing unit.

• Diagnostics: Provides a fault history of the equipment and allows the installer to clear the fault history.• Identification: Provides the model and serial number of the equipment and software revision information.• Sensors: Provides the sensor data of the equipment. In some instances, it may allow the installer to setup or turn off a

sensor.• Setup: Allows the installer to change the settings of the equipment.• Status: Provides the current status of the equipment.

Seeequipmentinstallermanualforspecificsubmenuoptionsavailablewithineachcategory.Bothindoor(AirHandlerandFurnace)andoutdoor(AirConditionerandHeatPump)unitswillhavedifferentsetsofsubmenus.

Page 14: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

1469-2688—07 I/O-CHTSTAT03

Wiring humidifier to the IFC

Wiring TrueEASE to IFC

Wiring TrueSTEAM to IFC

To change installer setup (ISU) information, see pages 12-13.

IFC

1

2

R

C

THERMOSTAT

12RC

HUM

HUM

1. WIRE THERMOSTAT AND TrueSTEAM AS SHOWN.2. SET THERMOSTAT ISU 8000 TO “STEAM”.3. SET TrueSTEAM DIP SWITCHES AS SHOWN (3 DOWN, 4 UP, 5 DOWN).

NOTEFAN INTERLOCK IS HANDLED BY THE COMFORTNET COMMUNICATION.

TrueSTEAM DIP SWITCHES

TRUESTEAM

MCR33172

24 V

24 V

HUM

HUM

C

GT

R

RT

GF

EXT

65432

ON

OFF

1

AFS MONITOR RECOMMENDED

IFC

1

2

R

C

THERMOSTAT

1

2

R

C

HUM

HUM

1. WIRE THERMOSTAT AND TrueEASE AS SHOWN.2. SET THERMOSTAT ISU 8000 TO “BYPASS OR FAN POWERED”.3. SET TrueEASE DIP SWITCHES AS SHOWN : • TOP DIP SWITCH – SET TO THE RIGHT • BOTTOM DIP SWITCH – SET TO THE LEFT

NOTEFAN INTERLOCK IS HANDLED BY THE COMFORTNET COMMUNICATION.

MCR33173

TrueEASE DIP SWITCHES

BYPASS

HUM

CONTROL

FANPOWERED

TrueEASE

Page 15: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

15 I/O-CHTSTAT03 69-2688—07

Heat pump with outdoor temperature lockouts

Outdoortemperaturelockoutsareoptional.SeeInstallerSetup options(ISU3120).

Heat pump only

Heatpumpwithbackupheatasneeded*

Backupheatonly

Heat pump only

Heatpumporbackupheatoperates*

Backupheatonly

Ou

tdo

or

tem

per

atu

reO

utd

oo

r te

mp

erat

ure

Backup heat lockout

Backup heat lockout

Compressor lockout

Compressor lockout

* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat Upstage Timer expires. Heat pump stays ON when backup heat turns on.

* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat Upstage Timer expires. Heat pump turns OFF when backup heat turns on.

Electric - Backup heat allowed to run with heat pump

Fossil Fuel - Backup heat NOT allowed to run with heat pump

Page 16: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

1669-2688—07 I/O-CHTSTAT03

Backup heat differential and upstage timer

Basic and Advanced Temperature Control Options (ISU 3010)

Abackupheatdifferentialandbackupheatupstagetimercanbesetonheatpumpsystemswithbackupheat.Seeinstallersetupoptions(ISU3090-3110).

Normal operationWhentheBackup Heat DifferentialissettoComfort,thethermostatusesbackupheatasneededtokeeptheindoortemperaturewithin1°F(0.5°C)ofthesetpoint.

WhentheBackup Heat Differentialissetto2°Forhigher,backupheatisnotusedunless the indoor temperature drops to the Backup Heat Differential setting or the Backup Heat Upstage Timerexpires,whicheveroccursfirst.Theupstagetimerstartswhenthehigheststageofthepreviousequipmenttypeturnson.

Manual temperature changeWhentheBackup Heat DifferentialissettoComfort,thethermostatusesbackupheatasneededtokeeptheindoortemperaturewithin1°F(0.5°C)ofthesetpoint.

WhentheBackup Heat Differentialissetto2°Forhigher,iftheheatpumpismak-ingprogressasexpected,backupheatwillnotbeusedtoreachthenewsetpoint.Settoahighernumbertouselessbackupheat(agreaterdifferencebetweenthecurrentindoortemperatureandthenewsetpointisrequiredtoturnonbackupheat).Seenotesbelow.

Programmed recoveryIftheheatpumpismakingprogressasexpected,backupheatwillnotbeusedtoreachthesetpointofthenextprogramperiod.Backupheatisalways restricted dur-ingaprogrammedrecoverywhentheAdaptiveIntelligentRecoveryfeatureisused.Seenotebelow.

Basic Options:TheInstallerSetupdisplaysbasictemperaturecontroloptionswhichincludeBackupHeatDifferential,BackupHeatUpstageTimerandOutdoorTemperatureLockouts.Note:OutdoorTemperatureLockoutsonlyapplytoHeatPumpapplications.

Advanced Options:TheInstallerSetupdisplaysbothBasicandAdvancedOptions.AdvancedtemperaturecontroloptionsincludeFinishWithHighCoolStage,FinishWithHighHeatStage,TemperatureDifferentialsettingsbetweenallstagesandCycleRatesettingsperstage.

During a programmed recovery (or when the temperature setpoint is changed by the user), the thermostat waits to turn on the backup heat depending on system performance, load conditions and how many degrees the temperature setpoint is changed. Backup heat will be used ONLY when the temperature is not rising quickly enough to reach the setpoint in a reasonable time.

If the backup heat was used in the last 2 hours because the heat pump was not able to maintain the setpoint, the thermostat may turn on the backup heat earlier when the user raises the setpoint.

Finish With High Heat or Cool Stage - When a multi-stage heating or cooling system is used, this feature keeps the high stage of the heating or cooling equipment running until the desired setpoint is reached.

Page 17: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

17 I/O-CHTSTAT03 69-2688—07

Humidification

Thethermostatreadstheindoorhumiditylevelandallowstheusertosetahumidifi-cationsettingwithorwithoutwindowprotection.

Window ProtectionWindowProtectionlimitstheamountofhumiditytopreventfrostorcondensationonwindows.WindowProtection(ISU8050)requiresanoutdoorsensor.

Themaximumhumiditylevelthatisallowed("WindowLimit")isdisplayedontheHumidificationSettingsscreen.ThethermostatpreventsfrostorcondensationonwindowsbynotallowingthehumiditytogoabovetheWindowLimitwhenitiscon-trollingthehumidifier.Thishelpsinformtheuserastowhytheirhumiditysettingmightnotbereachedattimes.TheWindowLimitisbasedonthecurrentoutdoortempera-tureandtheuser'swindowprotectionsetting.

IfWindowProtectionisturnedOff,thether-mostatcontrolsthehumidityleveltotheuser'sdesiredhumiditysetting.Frostorcondensationmayappearonwindows.

Dehumidification - Residential

Thethermostatreadstheindoorhumiditylevelandallowstheusertosetadehu-midification setting.

Whensetupfordehumidificationusingthecoolingsystem,anovercoolinglimitcanbesetfrom0Fto3F(ISU9070).Thethermostatusesthecoolingsystemtoreducehumiditybyloweringthetemperatureupto3Fbelowthecurrentcoolsetpointuntilthe desired humidity level is reached.

To see all dehumidification options, press MENU > INSTALLER OPTIONS > VIEW/EDIT CURRENT SETUP > DEHUMIDIFICATION.

To see all humidification options, press MENU > INSTALLER OPTIONS > VIEW/EDIT CURRENT SETUP > HUMIDIFICATION.

Page 18: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

1869-2688—07 I/O-CHTSTAT03

Dehumidification - Commercial

Thethermostatreadstheindoorhumiditylevelandallowstheusertosetadehumidification setting.

Dehumidificationusingthecoolingsystemhasthefollowingmethodsofdehumidificationcontrol(ISU9080):

Basic:Thisoptionusesthecoolingsystemtoreachthedesiredhumiditylevel.MinimumOnTimeandHighHumidityComfortResetarenotusedwiththismethod.Thisoptionshouldonlybeusediftheequipmentcanlowerthefanspeedinacallfordehumidification.

Minimum on Time (ISU 9090):Thisoptionensuresthatthecompressorrunslongenoughtoeffectivelyreducehumiditywhenthecoolingequipmentiscycledon.Thecompressorwillrunfortheminimum"ontime"yousetuntilthedesiredhumiditylevelis reached.

High Humidity Comfort Reset (ISU 9100):Thisoptionusesthecoolingsystemtolowerthetemperatureupto5Fbelowthecurrentcoolsetpointuntilthedesiredhumidityisreached.Thehighhumiditycomfortrangeisfrom1to5F.

High Humidity Comfort Reset with Minimum On Time (ISU 9090 and ISU 9100):Thismethodusesbothoptionsabovetoreducehumiditywhilemaintainingacomfortabletemperature.

To see all dehumidification options, press MENU > INSTALLER OPTIONS > VIEW/EDIT CURRENT SETUP > DEHUMIDIFICATION.

Page 19: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

19 I/O-CHTSTAT03 69-2688—07

Dehumidification Away Mode

DehumidificationAwayModeprotectsthehomewhenunoccupiedforlongperiodsoftimeduringhotandhumidweatherbymaintainingthedesiredhumidityandtemperature settings.

TostartDehumidificationAwayMode,pressMenu,thenpressDehumidificationAwayMode.Thethermostatautomaticallyfollowssettingsthataresetbythedealerduringinstallersetup.

PressCanceltoendDehumidificationAwayMode.

Southern Dehumidification Away Mode Options: (ISU 9180 to 9200)• Fan:Auto,OnorCirculate• LowLimitTemperatureSetting:ThethermostatallowsthecoolingsystemtolowertheindoorairtotheLowLimitTemperatureSettingtocontrolhumidity.

• TemperatureSetting:ThetemperaturemaintainedwhileDehumidificationAwayMode is active and the desired humidity level is satisfied.

• DehumidificationSetting:ThedesiredhumiditylevelwhileDehumidificationAwayModeisactive.

Ventilation

Ventilation Control Method (ISU 10050)

ThethermostatcancontrolthefantomeeteitherASHRAEorPercentOnTimesettings.IftherequiredventilationhasnotbeenachievedforASHRAEorPercentOnTimeduringcallsforheatandcool,thethermostatwillforcethefanon.• ASHRAE:ThethermostatoperatesthefantomeettheASHRAE62.2ventilationstandardbasedonCFM,numberofbedrooms,andsquarefootageofthehouse.ASHRAE62.2canonlybemetifthefanisrunning.Ifthefanisoffforanyreason(setuptoturnOffduringSleepperiod,turnedoffbyuseretc.),ASHRAE62.2isnotmetduringthosetimes.

• Percent On Time:Thethermostatoperatesthefanbasedonapercentageenteredintheinstallersetup(ISU10120).Forexample,ifPercentOnTimeissetto50%,thefanwillrunatrandomtimesduringa1hourperioduntilitreachesa50%runtime(approximately30minutes).Options10%to100%.

To see all ventilation options, press MENU > INSTALLER OPTIONS > VIEW/EDIT CURRENT SETUP > VENTILATION.

Page 20: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

2069-2688—07 I/O-CHTSTAT03

Indoor sensor operation

Temperature control

Thethermostatcanbesettorespondtoitsinternal temperature sensor, or to an optional remoteindoorsensor.Ifmultiplesensorsareused,thethermostatwillrespondtoanaver-age of temperatures detected at each sensor.

Humidification control

Ifoptionalremoteindoorsensorsareinstalled,youcanchoosewhichsensoryouwanttousefor humidification control. You can use a differ-ent sensor for dehumidification.

Dehumidification control

Ifoptionalremoteindoorsensorsareinstalled,youcanchoosewhichsensoryouwanttousefordehumidificationcontrol.Forexample,youcan use one sensor for humidification control, and another for dehumidification.

Page 21: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

21 I/O-CHTSTAT03 69-2688—07

Alerts Log

MENU > INSTALLER OPTIONS > DATA LOGS > ALERTS LOG

Thethermostatsavesthemostrecent25alerts.Itrecordsthedate,time,alertstatus(snoozed,dismissed,recovered),anddiagnosticinformationtohelpyouidentifyandcorrectproblems.

User Interactions Log

MENU > INSTALLER OPTIONS > DATA LOGS > USER INTERACTIONS LOG

Checkthislogtofindoutifaproblemwascausedbyanaccidentalusererror.Thelogshowsmostchangesmadetothermostatsettings,bytimeanddate,anddescribeswhatchangewasmade.

Thethermostatrecordsthemostrecent250changes.Youcanquicklysearchthembydateandtime,orbyfunction.Thisfeaturecanbeturnedoffifnecessary,sothatno user interactions are recorded.

Examples:

* [date, time] Heattemperaturesetto80°F

* [date, time] SystemmodesettoOff

* [date, time] Installersetupchanged—heatingequipmenttype

Replacing system components

FollowstepsbelowtodisconnectthethermostatandRedLINKaccessories.

To replace a thermostat

AtthePortableComfortControl

1 Pressandholdtheblankspace(orarrowifpresent)inthelowerrighthandcornerofthescreenuntilthedisplay changes.

2 PressREMOVE, then YES to disconnect from the old thermostat.

AttheIndoorSensor,Entry/ExitRemote,VentBoostRemote,RedLINKInternetGatewayorTrueSTEAMWirelessAdapter

1 PressandholdtheCONNECTbuttonontheRedLINKaccessoryuntilthestatuslightglowsamber(holdforabout10seconds).Thiswilldisconnectthedevicefrom the old thermostat.

Re-connectRedLINKaccessories

1 Followthestepsin“Linkoptionalaccessoriestowirelessnetwork”onpage9.

MCR32958

Press and hold in lower right corner of screen

Page 22: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

System Installation Guide

2269-2688—07 I/O-CHTSTAT03

Replacing system components

To remove accessories from a thermostat

Atthethermostat

1 PressMENUandscrolldowntopressINSTALLER OPTIONS.Enterthedatecode(password)whenprompted.Thedatecodeisprintedonthebackofthethermostat;orpressMENU > EQUIPMENT STATUS to find the date code.

2 Afteryouenterthepassword,scrolldowntoselectWIRELESS DEVICE MANAGER.

3 PressREMOVE DEVICE,thenselectthedeviceyouwanttoremove.

Specifications & replacement parts

Operating Ambient Temperature Thermostat:32to120°F(0to48.9°C) Portable Comfort Control: 32to120°F(0to48.9°C) Wireless Outdoor Sensor:-40to140°F(-40to60°C) Wireless Indoor Sensor:0to120°F(-17.8to48.9°C)

– ForOptimalBatteryLife:35to114°F(1.7to45.6°C) RedLINK Internet Gateway:32to120°F(0to48.9°C)

Operating Relative Humidity Thermostat:5%to90%(non-condensing) Portable Comfort Control: 5%to90%(non-condensing) Wireless Outdoor Sensor:0%to100%(condensing)

Wireless Indoor Sensor:5%to90%(non-condensing) RedLINK Internet Gateway:5%to95%(non-condensing)

Physical Dimensions(height,width,depth) Thermostat: 3-7/8x6-13/16x1-7/16inches(99x173mmx36mm)

Wireless Outdoor Sensor:5x3-1/2x1-11/16inches(127x89x43mm) Wireless Indoor Sensor:2-7/8x1-7/8x15/16inches(74x48x24mm) Portable Comfort Control: 6-1/4x3-1/8x1-5/8inches(158x80x38mm)

RedLINK Internet Gateway:6x4-7/8x2-1/2inches(152x124x64mm)

Electrical Ratings 18to30VAC

Accessories & Replacement PartsItem Honeywell Part NumberRedLINKInternetGateway THM6000R1002Entry/ExitRemote REM1000R1003VentBoostRemote HVC20A1000PortableComfortControl REM5000R1001WirelessOutdoorSensor C7089R1013WirelessIndoorSensor C7189R1004CoverPlate(coversmarksleftbyoldthermostats) 50028399-001BatteryPack(Fordemouseonly) THP1000A1007

Page 23: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

CTK04 ComfortNet™ Communicating Thermostat

23 I/O-CHTSTAT03 69-2688—07

Regulatory information

FCC Compliance Statement (Part 15.19) (USA only) This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

1 This device may not cause harmful interference, and2 This device must accept any interference received, including interference that may cause undesired operation.

FCC Warning (Part 15.21) (USA only) Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

FCC Interference Statement (Part 15.105 (b)) (USA only) This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:

• Reorientorrelocatethereceivingantenna.• Increasetheseparationbetweentheequipmentandreceiver.• Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected.• Consultthedealeroranexperiencedradio/TVtechnicianforhelp.

Thermostats and outdoor sensor To comply with FCC and Industry Canada RF exposure limits for general population/ uncontrolled exposure, the antenna(s) used for these transmitters must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.

Portable Comfort Control This portable transmitter with its antenna complies with FCC and Industry Canada RF exposure limits for general population/uncontrolled exposure. This device must not be co-located or operating in conjunction with any other antenna or transmitter.

Section 7.1.2 of RSS-GEN Under Industry Canada regulations, this radio transmitter may only operate using an antenna of type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.

Section 7.1.3 of RSS-GEN Operation is subject to the following two conditions:

1 this device may not cause interference, and2 this device must accept any interference, including interference that may cause undesired operation of the device.

Page 24: 69-2688-07 - ComfortNet™ CTK04 Communicating Thermostat€¦ · Contact the Thermostat Recycling Corporation at or 800-238-8192 for information on how and where to properly and

Honeywell International Inc.

1985 Douglas Drive North

Golden Valley, MN 55422

http://customer.honeywell.com

Goodman Manufacturing Co., LP

Suite 500

5151 San Felipe

Houston, TX 77056®U.S.RegisteredTrademark.©2014HoneywellInternationalInc.69-2688—07M.S.Rev.01-14I/O-CHTSTAT03PrintedinU.S.A.

Need Help?Forassistancepleasevisitwww.ComfortNet1.com,orcalltoll-free:(888)593-9988