SPECIFICATION DATA
63-1380-01
Airflow Measuring Stations and DampersAMS, AMD-23, AMD-33 & AMD-42
APPLICATIONThe AMS is an accurate airflow measuring station furnished with a properly sized pressure transducer that outputs a signal proportional to cfm.
A field-supplied controller can use the transducer's signal to regulate a modulating actuator to the target set-point.
The AMD series is an AMS that includes a modulating actuator which controls a low-leakage damper to regulate airflow volumes to a target set-point.
A field supplied controller can use the transducer's signal along with the flow formula: CFM = Area * K * (Ptransducer)
m to regulate a modulating actuator to the target set-point. (K and m are factory supplied variables specific to each measuring station.) An optional, factory-supplied LON controller that accepts a target flow set-point as an input (either analog or digital) and outputs a 0-10 Vdc signal can be used to position a damper (sold separately for AMS) proportional to the airflow.
FEATURES• Factory supplied 0-10 Vdc pressure transducer• Optional factory supplied LON controller
(0-10 Vdc, 2-10 Vdc, or 4-20 mA)• Galvanized steel sleeves available• Clean wrap• 24 Vac modulating actuator mounted externally or
internally (NEMA 2) (AMD models only).
SPECIFICATIONS
Table 1. Specifications by model.*
* Additional specifications are shown in Table 2 (AMS) and Table 4 (AMD series).
AMS AMD-23 AMD-33 AMD-42
Velocity 300 to 3000 fpm(1.5 - 15.2 m/s)
300 to 2000 fpm(1.5 - 10.2 m/s)
300 to 3000 fpm(1.5 - 15.2 m/s)
300 to 3000 fpm(1.5 - 15.2 m/s)
Leakage — 6 cfm/ft2 @ 4 in. wg (110 cmh/m2 @ 1 kPa)3 cfm/ft2 @ 1 in. wg (55 cmh/m2 @ 0.25 kPa)
Operating Temperature -20 ºF to 180 ºF-29 ºC to 82 ºF
Consult factory for temperature lower than -20 °F (-29 °C)
Airflow Monitoring Accuracy 5% of reading
AIRFLOW MEASURING STATIONS AND DAMPERS
63--1380—01 2
AMS SpecificationsTable 2. Additional specifications of the AMS.
* Available when sleeve option is selected
Table 3. AMS size limitations.
* W and H dimensions furnished approximately 1/4 in. (6 mm) undersize.
** For sizes larger than listed, consult Honeywell. Fig. 1. AMS dimensions: Width (W) x Height (H) dimensions furnished approximately 1/4 in. (6 mm) undersize.
Fig. 2. Side view of AMS sideplate and sleeve, in inches (mm).
Construction Standard Optional
Airflow StraightenerFrame Material
16 ga (1.5mm)Galvanized Steel —
Sideplate/sleeve 8 in. (203mm)sideplate
8 in. (203mm)sleeve
Flange None * 1 1/2 in. (38mm);Upstream side,Downstream side,Both Sides
Air Straightener PolycarbonateHoneycomb —
W x H* Minimum SizeMaximum Size**
Single Section
Inches(mm)
6 x 8(152 x 203)
60 x 48(1524 x 1219)
SIDE PLATE
M34235
HEIGHT
WIDTH
8 (203)
M34236
AIRFLOW MEASURING STATIONS AND DAMPERS
3 63-1380—01
AMD Series SpecificationsTable 4. Additional specifications of AMD. Table 5. AMD series size limitations.
* W and H dimensions furnished approximately 1/4 in. (6 mm) undersize.
** For sizes larger than listed, consult Honeywell.
Fig. 3. AMD series dimensions: Width (W) x Height (H) dimensions furnished approximately 1/4 in. (6 mm) undersize..
Fig. 4. AMD mounting options. Measurements in inches (mm).
Construction Standard Optional
Frame Material Galvanized Steel —
Frame MaterialThickness
16 ga. (1.5 mm) 12 ga. (2.7 mm)14 ga. (2 mm)
Frame Type 5 in. x 1 in. hat channel —
Blade Material AMD-23/AMD-33:Galvanized steelAMD-42:Extruded aluminum
—
Blade Type AMD-23:3VAMD-33/AMD-42:Airfoil
—
Blade Action Parallel —
Linkage Plated steel out of airstream,concealed in jamb
Axle Bearings Synthetic (acetal)sleeve type Bronze, 304SS
Axle Material Plated steel 304SS
Blade Seals TPE Silicone
Jamb Seals 304SS —
Sleeve 12 in.(305 mm)
12 in. - 48 in.(305 mm - 1219 mm)
Sleeve Gauge 20 ga. 14 ga. (2 mm)16 ga. (1.5 mm)
Flange None 1 1/2 in. (38 mm);Upstream side,
Downstream side,Both Sides
Air Straightener PolycarbonateHoneycomb —
Actuator 24 Vac 50/60 Hz 24 Vac w/ auxiliaryswitches or manual
quadrant
W x H*
Minimum Size Maximum Size**
External InternalSingle
SectionMultiple Section**
Inches(mm)
6 x 6152 x 152
12 x 8305 x 203
48 x 741219 x 1880
144 x 1483658 x 3759
M34238
HEIGHT
WIDTH
DAMPER
M34239
WIDTH
HEIGHT
2 (51)STRAIGHTENER
SLEEVELENGTH SLEEVE
LENGTHSLEEVELENGTH
FLANGE ONDOWNSTREAM
FLANGE ONUPSTREAM
AIRFLOW MEASURING STATIONS AND DAMPERS
63--1380—01 4
WIRING
Fig. 5. Wiring Diagram for Controller.
M34237
AIRFLOW MEASURING STATIONS AND DAMPERS
5 63-1380—01
AMCA CERTIFIED LEAKAGE DATAAir leakage is based on operation between 32 °F (0 °C) and 120 °F (49 °C).
Tested for leakage in accordance with ANSI/AMCA Standard 500-D, Figure 5.
Tested for air performance in accordance with ANSI/AMCA Standard 500-D, Figures 6, 7 and 8.
TorqueData are based on a torque of 7.0 lb.in./ft² (0.79 Nm) applied to close and seat the damper during the test.
Table 6. Leakage classification.
* Leakage Class DefinitionsThe maximum allowable leakage is defined by AMCA as the following:• Leakage Class 1A - 3 cfm/ft2 @ 1 in. wg
(class 1A is only defined at 1 in. wg).• Leakage Class 1
— 4 cfm/ft2 @ 1 in. wg— 8 cfm/ft2 @ 4 in. wg— 11 cfm/ft2 @ 8 in. wg— 12.6 cfm/ft2 @ 10 in. wg
PRESSURE DROPThis pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of 0.075 lb/ft3 (1.201 kg/m3 ).
Actual pressure drop found in any HVac system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVac system.
AMCA Test FiguresFigure 6 illustrates a ducted damper exhausting air into an open area (AMCA 5.2). This configuration has a lower pressure drop than Figure 8 (AMCA 5.5) because entrance losses are minimized by a straight duct run upstream of the damper.
Fig. 6. AMCA 5.2 - Pressure drop.
Figure 7 illustrates a fully ducted damper (AMCA 5.3). This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Fig. 7. AMCA 5.3 - Pressure drop.
Figure 8 illustrates a plenum mounted damper (AMCA 5.5). This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system.
Fig. 8. AMCA 5.5 - Pressure drop.
Leakage Class*
MaximumDamper Width
1 in. wg(0.25 kPa)
4 in. wg(1 kPa)
8 in. wg(2 kPa)
60 in. (1524mm) 1A 1 1
D 4 (W) (H)3.14
5D
M34274
5D
M34275
6D
M34276
AIRFLOW MEASURING STATIONS AND DAMPERS
63--1380—01 6
AMD-23 PRESSURE DROP DATAAMCA 5.2
AMCA 5.3
AMCA 5.5
D 4 (W) (H)3.14
5D
M34274
12 x 12 in. (305 x 305 mm) 24 x 24 in. (610 x 610 mm) 36 x 36 in. (914 x 914 mm) 12 x 48 in. (305 x 1219 mm) 48 x 12 in. (1219 x 305 mm)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
500 0.05 500 0.03 500 0.03 500 0.04 500 0.03
1000 0.15 1000 0.10 1000 0.09 1000 0.11 1000 0.11
1500 0.31 1500 0.21 1500 0.18 1500 0.23 1500 0.22
2000 0.52 2000 0.36 2000 0.31 2000 0.39 2000 0.38
2500 0.80 2500 0.54 2500 0.46 2500 0.58 2500 0.57
3000 1.12 3000 0.76 3000 0.64 3000 0.81 3000 0.79
3500 1.51 3500 1.01 3500 0.86 3500 1.10 3500 1.06
4000 1.92 4000 1.32 4000 1.12 4000 1.43 4000 1.38
5D
M34275
6D
12 x 12 in. (305 x 305 mm) 24 x 24 in. (610 x 610 mm) 36 x 36 in. (914 x 914 mm) 12 x 48 in. (305 x 1219 mm) 48 x 12 in. (1219 x 305 mm)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
500 0.04 500 0.03 500 0.03 500 0.03 500 0.03
1000 0.12 1000 0.09 1000 0.07 1000 0.10 1000 0.09
1500 0.24 1500 0.17 1500 0.14 1500 0.20 1500 0.19
2000 0.40 2000 0.28 2000 0.23 2000 0.34 2000 0.33
2500 0.60 2500 0.43 2500 0.35 2500 0.51 2500 0.50
3000 0.84 3000 0.60 3000 0.48 3000 0.72 3000 0.71
3500 1.12 3500 0.80 3500 0.64 3500 0.97 3500 0.96
4000 1.44 4000 1.03 4000 0.82 4000 1.26 4000 1.24
M34276
12 x 12 in. (305 x 305 mm) 24 x 24 in. (610 x 610 mm) 36 x 36 in. (914 x 914 mm) 12 x 48 in. (305 x 1219 mm) 48 x 12 in. (1219 x 305 mm)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
500 0.07 500 0.05 500 0.05 500 0.06 500 0.05
1000 0.25 1000 0.20 1000 0.17 1000 0.20 1000 0.20
1500 0.54 1500 0.41 1500 0.36 1500 0.43 1500 0.42
2000 0.92 2000 0.71 2000 0.62 2000 0.74 2000 0.72
2500 1.41 2500 1.10 2500 0.96 2500 1.13 2500 1.11
3000 2.02 3000 1.54 3000 1.36 3000 1.59 3000 1.56
3500 2.73 3500 2.09 3500 1.84 3500 2.14 3500 2.12
4000 3.53 4000 2.76 4000 2.40 4000 2.78 4000 2.77
AIRFLOW MEASURING STATIONS AND DAMPERS
7 63-1380—01
AMD-33 PRESSURE DROP DATAAMCA 5.2
AMCA 5.3
AMCA 5.5
D 4 (W) (H)3.14
5D
M34274
12 x 12 in. (305 x 305 mm) 24 x 24 in. (610 x 610 mm) 36 x 36 in. (914 x 914 mm) 12 x 48 in. (305 x 1219 mm) 48 x 12 in. (1219 x 305 mm)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
500 0.041 500 0.03 500 0.025 500 0.034 500 0.036
1000 0.131 1000 0.094 1000 0.078 1000 0.103 1000 0.214
1500 0.266 1500 0.189 1500 0.156 1500 0.213 1500 0.214
2000 0.437 2000 0.314 2000 0.259 2000 0.357 2000 0.359
2500 0.658 2500 0.474 2500 0.388 2500 0.541 2500 0.547
3000 0.927 3000 0.652 3000 0.533 3000 0.757 3000 0.772
3500 1.245 3500 0.876 3500 0.706 3500 1.017 3500 1.034
4000 1.591 4000 1.143 4000 0.914 4000 1.326 4000 1.339
5D
M34275
6D
12 x 12 in. (305 x 305 mm) 24 x 24 in. (610 x 610 mm) 36 x 36 in. (914 x 914 mm) 12 x 48 in. (305 x 1219 mm) 48 x 12 in. (1219 x 305 mm)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
500 0.04 500 0.03 500 0.03 500 0.03 500 0.03
1000 0.12 1000 0.09 1000 0.07 1000 0.10 1000 0.09
1500 0.24 1500 0.17 1500 0.14 1500 0.20 1500 0.19
2000 0.40 2000 0.28 2000 0.23 2000 0.34 2000 0.33
2500 0.60 2500 0.43 2500 0.35 2500 0.51 2500 0.50
3000 0.84 3000 0.60 3000 0.48 3000 0.72 3000 0.71
3500 1.12 3500 0.80 3500 0.64 3500 0.97 3500 0.96
4000 1.44 4000 1.03 4000 0.82 4000 1.26 4000 1.24
M34276
12 x 12 in. (305 x 305 mm) 24 x 24 in. (610 x 610 mm) 36 x 36 in. (914 x 914 mm) 12 x 48 in. (305 x 1219 mm) 48 x 12 in. (1219 x 305 mm)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
Velocity (fpm)
Pressure Drop (in. wg)
500 0.07 500 0.05 500 0.05 500 0.06 500 0.05
1000 0.24 1000 0.19 1000 0.16 1000 0.19 1000 0.19
1500 0.50 1500 0.38 1500 0.34 1500 0.41 1500 0.41
2000 0.86 2000 0.65 2000 0.57 2000 0.71 2000 0.71
2500 1.33 2500 1.00 2500 0.88 2500 1.09 2500 1.10
3000 1.89 3000 1.43 3000 1.24 3000 1.54 3000 1.55
3500 2.57 3500 1.90 3500 1.67 3500 2.08 3500 2.10
4000 3.30 4000 2.52 4000 2.19 4000 2.70 4000 2.75
AIRFLOW MEASURING STATIONS AND DAMPERS
Automation and Control SolutionsHoneywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark© 2012 Honeywell International Inc.63-1380—01 M.S. 11-12 Printed in United States
AMD-42 PRESSURE DROP DATAPressure drop data for the AMD-42 is unavailable at the time of publication.
CERTIFICATIONS AND RATINGSAMS
Air measuring station meeting the following specifications shall be installed where shown on plans as an air monitor station integral to the minimum outside air damper. The air measuring damper shall control the minimum amount of outside air as recommended by ASHRAE Standard 62 or California Title 24.
Testing and ratings to be in accordance with AMCA standard 500-D.
Basis of design is Greenheck model AMS.
AMD series
Control dampers meeting the following specifications shall be installed where shown on plans as an air monitor station integral to the minimum outside air damper. The air measuring damper shall control the minimum amount of outside air as recommended by ASHRAE Standard 62 or California Title 24.
The air measuring damper shall consist of: 16 ga. (1.5 mm) galvanized steel hat channel frame with 5 in. (127 mm) depth; blades shall be 16 ga. (1.5 mm) galvanized steel 3 V type with three longitudinal grooves for reinforcement. Blades shall be completely symmetrical relative to their axle pivot point, presenting identical resistance to airflow and operation in either direction through the damper (blades that are non-symmetrical relative to their axle pivot point or utilize blade stops larger than 1/2 in. [13 mm] are unacceptable). Axles shall be 1/2 in. (13 mm) dia. plated steel turning in acetal bearings; TPE blade seals for 250 °F (121 °C) maximum temperature; flexible stainless steel jamb seals; and external (out of the airstream) blade-to-blade linkage.
Damper leakage rating to be in compliance with the IECC (International Energy Consumption Code) and not to exceed 3 cfm/ft2 (55 cmh/m2) at 1 in. wg (249 Pa). Testing and ratings to be in accordance with AMCA standard 500-D.
Basis of design is Greenheck model AMD-23.