51st annual biological safety conference · 2017-09-03 · 51st annual biological safety conference...

26
Integration of BSL-3 Laboratories into Existing Facilities Integration of BSL-3 Laboratories into Existing Facilities 51 st Annual Biological Safety Conference Reno, NV October 22, 2008 Scott Sandlin, AIA, CSI, LEED ® AP Perkins+Will Houston, Texas

Upload: others

Post on 29-May-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

1Integration of BSL-3 Laboratories into Existing Facilities

Integration of BSL-3 Laboratories into Existing Facilities

51st Annual Biological Safety Conference

Reno, NV October 22, 2008

Scott Sandlin, AIA, CSI, LEED® APPerkins+Will

Houston, Texas

Page 2: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

2Integration of BSL-3 Laboratories into Existing Facilities

Agenda

IntroductionGeneral BSL-3 Design IssuesModular OptionsEquipment ConsiderationsCase Study: ABSL3 Lab for BSL4 Support

• Existing Conditions

• As ConstructedSummary / Questions

Page 3: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

3Integration of BSL-3 Laboratories into Existing Facilities

Before You StartExperience, Understanding

An integrated team and process begins early in the planning phase; document goals and expected outcomes; revisit continuallyFocus is on the process in planning of facility, combining understanding of process with facility designLife Safety a key part of planning and development

Integrated ProcessAll team members “vertically integrated” for project responsibility; streamlines the processDrives the commissioning process, and ensures a well documented end productDelivers facility that meets functional and operational goals

Pre-plumbed stack locations

General BSL-3 Design Issues

Page 4: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

4Integration of BSL-3 Laboratories into Existing Facilities

Summary of Design Features (Secondary Barriers)

Dou

ble

Doo

r Ent

ry

Acc

ess

Con

trol D

evic

es

Per

sonn

el S

how

er-O

ut

Han

d W

ashi

ng S

ink

Han

ds F

ree

Han

d W

ashi

ng S

ink

Aut

ocla

ve A

vaila

ble

Pas

s-th

roug

h A

utoc

lave

Dun

k Ta

nk a

nd/o

r Fum

ig C

ham

ber

Sin

gle-

Pas

s A

ir, D

irect

iona

l Airf

low

HE

PA

Filt

ered

Exh

aust

HE

PA

Filt

ered

Sup

ply

Sup

ply/

Exh

aust

Inte

rlock

Gas

-Tig

ht D

ampe

rs (R

oom

Lev

el)

Vis

ual A

irflo

w/P

ress

ure

Mon

itor

HE

PA

Plu

mbi

ng V

ents

Effl

uent

Dec

onta

min

atio

n

Vac

uum

Lin

e P

rote

ctio

n

Mon

olith

ic W

alls

& C

eilin

g

Sea

mle

ss F

loor

ing

Airt

ight

Con

stru

ctio

n

Bre

athi

ng A

ir S

yste

m

Che

mic

al S

how

er

BSL-2 LaboratoryABSL-2 Animal Facility

BSL-3 LaboratoryABSL-3 Animal Facility

BSL-3 Ag AnimalBSL-4 Lab/Animal (Suit)

= Required by BMBL (5th ed.)= Not required by BMBL (5th ed.), however, generally considered as an enhancement

Page 5: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

5Integration of BSL-3 Laboratories into Existing Facilities

General BSL-3 Design Issues

Waste TreatmentHEPA Filter Exhaust ?Location in Building

Life SafetyUtility RoutingMechanical Equipment Room Location

Double door access (vestibule)Negative AirflowPlan to include personnel showerDecontamination

HEPA Filter Caisson

Page 6: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

6Integration of BSL-3 Laboratories into Existing Facilities

Pressure Differential vs. “Airtight”Sealing surface penetrationsPressure Decay test required for BSL-3-Ag

FinishesSeamless flooring optionsWashable/scrubbablesurfaces

Room Layout IssuesDesign for mobile caseworkHigh concentration of BSC’sSubstantial Lab Equipment

Planning for DuctworkAccess to filters, caissons, bioseal valves

General BSL-3 Design Issues

Page 7: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

7Integration of BSL-3 Laboratories into Existing Facilities

Dedicated MEP Systems

Critical Systems Back-UpN+1 Systems RedundancyBack-up Power for Fans

Use of Interstitial Space Highly Recommended

Detailing/Constructability/ Commissioning

“Off-the Shelf” Technology

Energy Conservation/ Sustainability should be a concern

HEPA Filters Above

Effluent decon if desired below

HEPA Filters…Above

General BSL-3 Design Issues

Page 8: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

8Integration of BSL-3 Laboratories into Existing Facilities

Future PlanningConsider locating lab on the upper-most lab floor

Interstitial access or mechanical penthouse is preferable

Consider GLP & Life Safety in locating lab

Consider support space adjacency BSL-2 & Core labs

Pre-plumbed stack locations

General BSL-3 Design Issues

Page 9: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

9Integration of BSL-3 Laboratories into Existing Facilities

Pre-plumbed stack locations

General BSL-3 Design Issues

Interstitial Option: Accessed from Corridor

Page 10: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

10Integration of BSL-3 Laboratories into Existing Facilities

General BSL-3 Design IssuesOperations and Maintenance

Plan for layout & utility systems redundancyLocation for Spares?Add excess electrical capacity for exhaust fans

Environmental ConsiderationsWind Analysis & HVAC Entrainment Study

Exhaust Entrainment Study

Page 11: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

11Integration of BSL-3 Laboratories into Existing Facilities

Future PlanningPlan for vertical exhaust duct runs

Stub stainless steel ductwork in now

Plan for layout & utility systems redundancy

Add excess electrical capacity for exhaust fans

Pre-plumbed stack locations

General BSL-3 Design Issues

Page 12: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

12Integration of BSL-3 Laboratories into Existing Facilities

Modular Lab Option

• Rapid reconfiguration

• Modules are 10’x12’

• Flexibility in HVAC Systems location

Courtesy of Dovetail Biocontainment

Page 13: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

13Integration of BSL-3 Laboratories into Existing Facilities

Layout Opportunities• Right-size the chamber (study

loads, items and run frequency)• Share autoclaves between lab

suites if protocol permits- evaluate system redundancy

needs• Newer designs incorporate water

economizer cycles & crushed door seals.

Pass-thru Sterilizers

Page 14: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

14Integration of BSL-3 Laboratories into Existing Facilities

Pass-thru Sterilizer Design

Utility Opportunities• Re-circulate cooling water, use

bldg. process water instead of domestic cold water (confirm w/ bio-safety protocol)

• Utilize bldg. plant steam vs. local electric steam generation

• Recover and re-circulate jacket condensate

• Utilize building plant compressed air

Pass-thru Sterilizers

Page 15: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

15Integration of BSL-3 Laboratories into Existing Facilities

Biological Safety Cabinet (BSC) selection and optimization

Class II, Type A & B1• Recirculating design utilizing

HEPA filtration:• Up to 30% exhausted via

HEPA into room (A)• 70% returned to work zone (A) Thimble design for exhaust

ducted installation (B1 – 30% recirc.)

Class II, Type B2 & B3• Total exhaust cabinet design

Exhausts conditioned air up to 1200 cu.ft/minute

Page 16: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

16Integration of BSL-3 Laboratories into Existing Facilities

HEPA Filtration on Exhaust

• Exhaust Filtration is not required by BMBL for BSL-3’s

• Filtration is becoming more common due to perceptions of User & community sensitivity

• Consider size and number of filters required

• Select and specify Lower DP HEPA Filters

Bag-in, bag-out HEPA filtration caisson

Page 17: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

17Integration of BSL-3 Laboratories into Existing Facilities

Aerial view of Keiller Building & BSL-4 Addition

Case Study: ABSL-3 Lab for BSL-4 Support

Keiller, Shope Lab & GNL

Page 18: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

19Integration of BSL-3 Laboratories into Existing Facilities

Case Study: ABSL-3 Lab for BSL-4 Support

Page 19: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

20Integration of BSL-3 Laboratories into Existing Facilities

Existing Facility Conditions • Unfinished basement• Low floor to floor height

Case Study: ABSL-3 Lab for BSL-4 Support

Page 20: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

21Integration of BSL-3 Laboratories into Existing Facilities

Low Headroom, Coordination of Underslab Utilities (Waste and Vent!)

Case Study: ABSL-3 Lab for BSL-4 Support

Page 21: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

22Integration of BSL-3 Laboratories into Existing Facilities

Low Headroom, Limitations due to Existing Structure, Equipment Coordination

Case Study: ABSL-3 Lab for BSL-4 Support

Page 22: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

23Integration of BSL-3 Laboratories into Existing Facilities

VFD Exhaust Drives

HEPA Exhaust with Decon Port Exhaust manifold in service closet

Case Study: ABSL-3 Lab for BSL-4 Support

Page 23: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

24Integration of BSL-3 Laboratories into Existing Facilities

Micro Isolator racksPortable isolators and change station

Case Study: ABSL-3 Lab for BSL-4 Support

Finished!

Page 24: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

25Integration of BSL-3 Laboratories into Existing Facilities

Case Study: ABSL-3 Lab for BSL-4 Support

ARC Sink – Utility Station Raised Ceiling for BSC installation

Page 25: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

26Integration of BSL-3 Laboratories into Existing Facilities

Case Study: ABSL-3 Lab for BSL-4 Support

Finished Corridor Animal Room Entry Detail

Page 26: 51st Annual Biological Safety Conference · 2017-09-03 · 51st Annual Biological Safety Conference Reno, NV October 22, 2008 ... Integration of BSL-3 Laboratories into Existing Facilities

27Integration of BSL-3 Laboratories into Existing Facilities

Hire a BSL3-experienced design team with a demonstrated commitment to understanding of how the lab is going to be used and maintained.

Insist on an integrated approach to planning, design and construction.

The devil is in the details: operational and physical!

HVAC system retrofit is often difficult due to space constraints and adjacency issues

Don’t depend on published cost data!

Plan for BSL-3 expansion now if it may be a possibility; route ductwork and provide adequate utility services

Summary