NFPA20
Update
2013
Edition
. , . . . . . . .
VicePresidentofEngineering
NFPA20Update2013Edition
GoalsandObjectives
Bytheendofthispresentation,the
participantwillbeableto:
1. Repeatthe
revision
cycle
for
NFPA
20
2. Discusshowtousetheprovisionsofthe2013
e itioneveni apreviouse itionis eing
enforced
3. Designafirepumpsystemforaverytall
building
4. Discussthedifferencesbetweenlimitedservice
controllersandregularfirepumpcontrollers
NFPA20Update2013
Revisioncycle
Whydoesthismatter?
Watermistpumps
Firepumpinstallationissues
Pumpsinseries
Highrisebuildings
Reliabilityofpowersupplies
Fuelsupply
Othermiscellaneous
items
RevisionCycle
ProposalsdueOctober2010
CommitteeROPMeeting,Jan.2011
ROPopenforcommentuntilAugust2011
Committee ROC Meetin Oct. 2011
VotedbyNFPAmembershipinJune2012
NFPAStandardsCouncilinAugust2012
IssuedinSept.2012with2013date
Electronicversionavailablenowfromwebsite
PrintedversionbylateOctober
Whydoesthismatter?
Weallneedtokeepuptodate
Limitourliability
Mostchangesareclarificationofoldtext
Manufacturers will chan e their roduct lines
tomeetthenewrules
Newtechnologyoralternatearrangements
(Equivalency)
Whydoesthismatter?
Newtechnologyoralternatearrangements
ForExample:NFPA20 2007
1.5Equivalency.Nothinginthisstandardisintended
topreventtheuseofsystems,methods,or
ev ceso equ va en orsuper orqua y,s reng ,fireresistance,effectiveness, durability,andsafety
overthoseprescribedbythisstandard.
Systemsmeetingthe2013editionofNFPA20
areequivalentorsuperiortothosemeeting
the2007edition
-
8/12/2019 515201310637 Pm
2/7
5/1/20
NFPA202013
FirePumpInstallationIssues
WaterMistPumps
Anumberofchangesthroughoutthe
document
Clarifiedthe
rules
for
multiple
small
volume
positivedisplacementpumpsusedasasingle
pumpingunitforawatermistsystem
Singlecontroller
HelpsNFPA20workwithNFPA750andlisted
watermistsystems
8
WithinSightof
ThereareanumberoflocationsinNFPA20
whereitspecifiesthattwodifferentpartsof
thepumpinstallationneedtobewithin
sightofeachother
Thistermwasdefinedaseachoftheitems
beingvisibleandnotmorethan50ftdistant
fromtheotheritem
9
Plans(4.2.3.1)
Plansneedtobedrawntoscale
Listof14itemsthatneedtobeincludedon
plans
10
PumpsinSeries
Proposalstoputallpumpsinseriesinthe
samepumproom
Ultimately,theseproposalsfailed,butbeon
the
lookout
for
this
in
future
editions
11
CommitteesConcernsaboutPumpsinSeries
Verticalstagingofpumpsishardtodo
correctly
Ifthehighpumpstartsbeforethelowpump,the
highpumpcouldbedamaged
Intercontro wiring etweencontro erscou e
damaged
Communicationbetweenpeopleinseparate
pumproomsisdifficult
Testingofpumpsisdifficult
-
8/12/2019 515201310637 Pm
3/7
5/1/20
VerticalStagingofPumps
To High Zone
Standpipe Risers
High Zone Pump
(Where will water
FirePump
Controller
To Low Zone
Standpipe Risers
Low Zone Pump
FirePump
Controller
PumpsinSeries
To Low Zone
To High Zone
Standpipe Risers
FirePump
Controller
tan p pe
Risers
Low Zone Pump
High
Zone
Pump
FirePump
Controller
Test equipment is
easier to arrange
PumpsinSeries NFPAMembership
Pumpscanbeverticallystaged,if:
Intercontrolwiringisatleastratedfor2hrs
Considerationisgiventoprovidingasafetesting
arrangement(cantjustuseclosedloopmetering)
Methodiscreatedforpeopleinpumproomsto
communicatewitheachother
Ownerneedstobeawareofimportanceoflow
zonepumpandneedtomaintain
SpaceintheRumpRoom(4.12.1.1.6)
Thepumproomneedstobedesignedwith
spacefor:
ClearancebetweencomponentsforITM
ClearancebetweencomponentsandwallsforITM
Clearancebetweencomponentsandenergized
electricalequipment
Orientationofthesuctionpipe
16
SuctionPipeWaterVelocity
Standardhassaidforyearsthatthemaximum
velocityis15ft/secinsuctionpipe
Standardhasalsoprovidedminimumpipesizes(in
Tables)anddefinedmaximumflows
W enyouputtoget ert e e ine maximum ows
andminimumpipesizes,youendupwithvelocities
of15.1ft/secand15.3ft/secinsomecases
Committeeclarifiedthatisokaybydeleting15
ft/secruleandaddinganotetotheTableonwhy
thesepipesizeswereselected
AgeofWaterSupplyTests
Anewsection4.6.1.2wasaddedtorequire
thatwatersupplytestsusedtodeterminethe
adequacyofwatersuppliesbedonewithin12
monthsofthesubmissionoftheworking
p ans.
18
-
8/12/2019 515201310637 Pm
4/7
5/1/20
TestHeaders
Thevalveonthepipetothetestheaderneeds
tobeinstalledevenifthetestheaderisnotin
anarea
subject
to
freezing
(4.20.3.3.1)
Thevalveneedstobesupervisedclosed
(4.16.2)
Testheadercanbeindoorsaslongasitisnot
inthepumproomandwatercanbe
dischargedduringtesting(4.20.1.4)
19
AccuracyofMeters
Forflowmeterlinesthatareloopedbackto
pumpsuctionorwatertanks
Ameans
will
need
to
be
included
downstream
ofthemetertotesttheflowsothatthe
accuracyofthemetercanbechecked
Couldbeadifferenttestheaderfromtheone
usedtotestthepump
Ortherecouldbeapipeconnectingthe
dischargefromthemetertothetestheader
20
MeterArrangement ElbowsandTeesinSuctionfor
HorizontalSplitCasePumps
Newthreedimensional(isometric)figures
wereaddedtotheannextoshowcorrectand
incorrectcombinationsofteesandelbows
22
ElbowsandTees
23
ElbowsandTees
24
-
8/12/2019 515201310637 Pm
5/7
5/1/20
QuestionsfromPart1
1. Whenweretheissuesdealingwiththe2013
editionofNFPA20votedonbythe
membershipof
the
NFPA?
2. Whyshouldyoucarewhatisinthe2013
editionsincethejurisdictionyouworkinhas
probablynotyetlegallyadoptedit?
HighRiseBuildings
Definition:morethan
75ft(23m)fromthe
lowestlevel
of
fire
departmentvehicle
accessto ig est oor
forhumanoccupancy>75ft
Chapter5 HighRise
RewriteofChapter
Sections5.1through5.5applytoallhighrise
buildings
Section5.6appliestoVeryTallBuildings
NoindicationwhatVeryTallBuildingsare,
butthereisanimplicationthatthesearethe
buildingsthataretootallfortheFire
Departmenttogetreasonablepressuretothe
topfromthestreet
Section5.6VeryTallBuildings
WaterSupplyTanks(paraphrased)
Wheretheprimarysourceisatank,youneedtwo
ormoretanks(compartmentsinasingletankare
okayiftheyarevalvedseparately)
e an s ave o es ze so a w enanyone
tankisoutofservice,youstillhaveatleast50%of
thedurationdemand
Eachtankneedsanautomaticrefillvalve
Eachtankneedsamanualrefillvalve
The
refill
valves
have
to
be
sized
and
arranged
to
providethefireprotectionsystemflowdemand
Section5.7VeryTallBuildings
WaterSupplyTanks(Section5.7.1.5)
Theautomaticandmanualfillvalvecombination
foreachtankortankcompartmentshallhaveits
ownconnectiontooneofthefollowing
pump
Areliabledomesticrisersizedtomeetthe
requirementsof5.7.1.4(fullflowdemandofsystem)
VeryTallBuilding
-
8/12/2019 515201310637 Pm
6/7
5/1/20
Section5.8FirePumpBackUp
Forpumpsservingzonesthatarepartiallyor
whollybeyondthepumpingcapabilityofthe
FireDepartment,
do
either
of
the
following:
Provideabackuppump(fullymeetingallsystem
eman s
Provideanauxiliarymeansofmeetingallofthe
systemdemands(acceptabletotheAHJ)
VeryTallBuilding
ReliablePowertoElectricMotors
Theannexnotethatdiscussestheattributesofareliablepowersupplywasmodified
Removedthediscussionofpoweroutagesduringstorms
standbypowerforallfirepumps
TheimpairmentproceduresofNFPA25couldbeusedwhenpoweroutagesoccurratherthanforcingeveryonewithanelectricmotordrivenfirepumptoinstallagenerator
33
LimitedServiceController
Ratherthaneliminatethem,upgradedthe
circuitbreaker
Onlydifferencebetweenfullservice
controllerswillbetheisolationswitch
34
DikesandFuelTanks
Thecommitteeclarifiedachangethatthey
triedtomakelastcycletostatethatdikesare
notrequiredwhendoublewalltanksareused
35
CleaningupFuel
Acommentwasacceptedbythecommitteeto
requirealistedactivefuelmaintenance
systemtobeinstalledonallfuelstoragetanks
This
was
overturned
by
the
NFPA
membership Theissueisstillvalid,thereneedstobeaplan
forhowallownerswillmaintaintheirfuel
-
8/12/2019 515201310637 Pm
7/7
5/1/20
AcceptanceTestForm
Theforminthestandardwasupdatedwithall
ofthenewrequirementssinceitwaslast
updated
37
QuestionsAfterPart2
3. Atankholding15,000gallonsisbeingused
asapartofafireprotectionsystemforthe
topfloors
in
abuilding
600
ft
tall.
How
many
automaticfillvalvesdoesthetankneed?
4. Aftermanufacturersstartimplementingthe
rulesinthe2013editionofNFPA13,whatis
themaindifferencegoingtobebetweena
limitedservicecontrollerandaregular(full
service)controller?
39