Final Report
Soil testing on Reclamation
Document ID
Document Name Soil testing on reclamation
Document N° 5138-CLI-RPT-010
Employer Housing Development Corporation Ltd.
Engineer Riyan Pvt Ltd
Contractor Dredging International nv Projectnr.
Project Name Hulhumalé Phase 2 Development Dredging and Reclamation Works 5138
Contract N° HDC/OHR/2014/38
Document Approval
Action Name Function Signature Date
Client Approval
Approved by Robert Van Veldhuizen Project Manager 05-Apr-2015
Checked by René Visser Works Manager 04-Apr-2015
Prepared by Pasila Venkateswara Rao Geologist 04-Apr-2015
Revision status
Rev. Date Description Prepared Checked Approved
02 17-Apr-2015 First Issue PVR RVI RVV
1.1 16-Apr-2015 Internal Review PVR RVI RVV
01 05-Apr-2015 First Issue PVR RVI RVV
0.1 04-Apr-2015 Internal Review PVR RVI RVV
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 2 of 45
Table of Contents
Abbreviations ......................................................................................................................................... 3
1 Introduction ..................................................................................................................................... 3 1.1 Project Information .................................................................................................................... 3
2 Scope ............................................................................................................................................... 4 2.1 Purpose ..................................................................................................................................... 4 2.2 Objectives.................................................................................................................................. 4
3 Responsibilities .............................................................................................................................. 4 3.1 Project Manager ........................................................................................................................ 4 3.2 Works Manager ......................................................................................................................... 4 3.3 QHSE Officer ............................................................................................................................ 4 3.4 Geologist ................................................................................................................................... 4
4 soil testing activities ...................................................................................................................... 5 4.1 Scope of soil testing .................................................................................................................. 5 4.2 Execution................................................................................................................................... 5
5 field density test ............................................................................................................................. 5 5.1 Scope ........................................................................................................................................ 5 5.2 Equipment ................................................................................................................................. 5 5.3 Procedure .................................................................................................................................. 5
6 Standard proctor compaction test................................................................................................ 6 6.1 Scope ........................................................................................................................................ 6 6.2 Equipment ................................................................................................................................. 6 6.3 Procedure .................................................................................................................................. 7
7 Plate bearing test ........................................................................................................................... 8 7.1 Scope ........................................................................................................................................ 8 7.2 Equipment ................................................................................................................................. 8 7.3 Procedure .................................................................................................................................. 8
8 Execution ........................................................................................................................................ 9
9 Conclusion .................................................................................................................................... 10
Annexure I Drawing with location points REC-01 to REC-10 Annexure II Field Density & Proctor Compaction test results
Annexure III Plate bearing test results Annexure IV Photographs
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 3 of 45
ABBREVIATIONS
EMPLOYER or HDC Housing Development Corporation Ltd
ENGINEER Riyan Pvt Ltd
CONTRACTOR or DI Dredging International nv
TSHD Trailing Suction Hopper Dredger
MSL Mean Sea Level
QHSE Quality, Health, Safety and Environment
ELS Engineering and Laboratory Services Ltd
1 INTRODUCTION
1.1 Project Information
Hulhumale development project was an undertaking that was initiated by the government of Maldives to address the issue of chronic congestion in the capital Male’. The phase 1 of the project commenced in October 1997 and the reclamation was completed in 2001. In line with the policies and strategies of
successive governments, the second phase of the project was commenced to address the recurring shortages of housing and land requirements linked to the diversification of the national economy. The Phase 2 development would be carried out by reclaiming the shallow Hulhumale lagoon on the
north of the existing Hulhumale reclaimed land to potentially create an additional land area of 244 ha (including Farukolhufushi).
Figure 1: Impression of Hulhumalé Phase 2 Development
The general scope of works for the reclamation and coastal protection works for the reclamation will be done under two separate contracts and would cover the following works:- 1. Carrying out dredging and reclamation works according to the final approved design and
specification. The required height of reclamation is 2 meters above mean sea level. 2. Carrying out the coastal protection works as per the final approved design and specification
including a detailed survey of the proposed alignment of the coastal structures
3. Carrying out test on completion to determine compliance to specification
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 4 of 45
Dredging International nv has been awarded the dredging and reclamation contract.
2 SCOPE
2.1 Purpose
The main purpose of this document is to provide a description of the soil testing works on the
reclamation area as part of the execution of the ‘Hulhumalé Phase Development: dredging and reclamation’ project.
2.2 Objectives
The objective of this soil testing procedures document is to ensure that all parties are well informed on the execution process of the soil testing on the finished reclamation area.
3 RESPONSIBILITIES
The most important key functions regarding the execution of the works are described in the sections
below
3.1 Project Manager
The Project Manager has the ultimate responsibility for the dredging and reclamation execution works. He shall communicate with all Project personnel, as required, taking account of their comments and recommendations and shall give them clear directives. The Project Manager reports directly to the
Area Manager of the Contractor and shall be responsible for the successful, safe and profitable conduct of this Project, including high expectations towards safety, environment, quality, security and Employer’s satisfaction
3.2 Works Manager
The Works Manager ensures that the works are performed according to the planning and he will
discuss and report deficiencies. The Works Manager will be responsible for the implementation of systems concerning QHSE during the execution of the works in close cooperation with the QHSE Officer. He will ensure that corrective measures are taken when required. He shall manage the Survey
and Operational departments.
3.3 QHSE Officer
The QHSE Officer is responsible for the Safe and Environmentally responsible execution of the works. The QHSE Advisor/s has the following responsibilities; - To provide advice and assistance to all Project personnel including service providers on HSE
issues; - To actively participate with work teams engaging in hazard identification and risk mitigation
strategies; (JSEA’s, SWMS, Take 5’s, pre-start and safety meetings);
- Conduct daily inspections at the workplace to identify any hazards and unsafe or unsatisfactory workplace HS conditions and practices;
- Monitor Project activities for compliance with Subcontractor policy, legislative, Project and
Contractor requirements; - Investigate or assist in the investigation of incidents at the workplace
3.4 Geologist
The geologist is responsible for all activities concerning soil testing. He will witness all tests performed by ELS from the side of the contractor. He will assist where necessary and use his experience with soil
testing to analyse the testing procedures and results.
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 5 of 45
4 SOIL TESTING ACTIVITIES
4.1 Scope of soil testing
The scope of the soil testing is to ensure conformity to the required compaction level for the reclamation area. These requirements state that the finished reclamation area should have a minimum dry density of 85% (degree of compaction) and a minimum bearing capacity of 150 kPa.
In order to know the degree of compaction, two tests will be performed. A field density test will be done to measure the in-situ density on the reclamation area and the maximum dry density will be deterimened by a standard Proctor test in a laboratory.
The bearing capacity will be checked by means of a plate bearing test.
4.2 Execution
The soil testing on the reclamation was performed by ELS, an independent soil testing laboratory. Branch office in Maldives :
ELS & Amin International (Pvt) Ltd Office / Lab : 52, Boduthakurumaafanu Magu, Male 20-01, Maldives. Tel : +960-7908053 / 3346000
Fax : +960-3324369 e-mail : [email protected]
The soil testing carried out on 10 different locations, which were determined by the Engineer. All tests were performed in the presence of Arumugam Vijay, Engineer’s representative and Pasila Venkateswara Rao, Contractor’s Geologist.
5 FIELD DENSITY TEST
5.1 Scope
A field density test is performed to determine the in-situ dry density of the sand on the reclamation area. This in-situ density is then compared to the maximum proctor density to know the degree of
compaction. The field density test is done by the sand replacement method using a sand pouring cone according to ASTM D 1556-90 norm.
5.2 Equipment
The following equipment is used for the field density test:
- Sand pouting cylinder with metal tray - Tools for leveling and excavation - Containers
- Calibrated dry sand - Balance
5.3 Procedure
An area of about 300 mm by 300 mm is prepared for the field density test. The location is first cleaned and leveled using a scraper. The metal tray with its central hole of 6.5 inch diameter is placed upon
the prepared surface. Using this central hole as reference, the soil is excavated up to 6.5 inch deep, using a chisel and trowel. The excavated soil is removed and weighed. The volume of the hole is determined by filling it with calibrated dry sand from a cone device. The weight of the soil removed is
divided by the volume of sand needed to fill the hole. This gives the in-situ density on the reclamation area. The excavated soil is also dried and weighed again to determine its moisture content and dry density.
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 6 of 45
The calculated in-situ dry density is later compared to the maximum Proctor density to obtain the
degree of compaction at the test location.
Figure 2: Procedure field density test
6 STANDARD PROCTOR COMPACTION TEST
6.1 Scope
The standard Proctor compaction test covers the laboratory compaction procedures used to determine
the relationship between the water content and the dry unit weight of soil samples. The test is performed in order to obtain the maximum dry density and consequently the degree of compaction at the test location.
The Standard Proctor Compaction test is done in accordance with Test Method ASTM D 698-91.
6.2 Equipment
The maximum Proctor density is determined in the laboratory. The following equipment is used: - Mould assembly with diameter 101.6 mm
- Rammer 2.5 kg - Balance
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 7 of 45
- Drying oven
- Mixing tools - Test sieve 9.5 mm
Figure 3: Equipment Proctor test
6.3 Procedure
An air dried soil sample is taken from the location at which the degree of compaction has to be known.
According to ASTM standard, the fraction of the sample which passes a 9.5 mm test sieve has to weigh about 16 kg. From this sample, at least four specimens with varying water contents are prepared by adding a
suitable amount of water. Each specimen is subjected to the same testing procedure. After adding the suitable amount of water, the sample is mixed thoroughly. The sample is then placed in 3 layers into the mould. Each layer is compacted by 25 blows from the rammer dropped from 30.5
cm high, creating compaction in the soil. The collar of the mould is detached and the excess soil is removed without disturbing the compacted soil. After, the weight of the mould with the soil is measured. The weight of the empty mould and base plate and the volume of the mould are known in
advance. From the weight difference and the volume, the bulk density of the soil sample is calculated. The moisture content is also determined from a representative specimen.
Figure 4: Schematic overview standard Proctor test
The above procedure is repeated for the rest of the samples with different water contents. Each time,
the dry unit weight is calculated based on the bulk density of the soil in the mould and the moisture content. A relationship between the dry unit weight and the water content can be established. This
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 8 of 45
data can be plotted in a graph, resulting in the compaction curve. The values of optimum moisture
content and maximum dry density are found from this compaction curve.
Figure 5: Example compaction curve
The in-situ dry density, measured using the sand replacement method, is then compared to the
maximum dry density. The ratio between both gives the degree of compaction.
7 PLATE BEARING TEST
7.1 Scope
The objective of the plate bearing test is to determine the soil bearing capacity of the in-situ soil. The test provides a direct measure of compressibility and gives information on the soil to a depth equal to
about two times the diameter of the bearing plate. The test is performed in accordance with BS 1377: Part 9: Section 4.1.
7.2 Equipment
The following equipment is used for the plate bearing field test: - Loading platform
- Hydraulic jack of 30 ton - Counter weight (e.g. steel pipes) - Bearing plates
- Settlement recording devices
7.3 Procedure
The test location, which should be regarded as semi-infinite in comparison to the plate diameter, is first prepared appropriately. All loose material and any embedded fragments are trimmed off and removed so that the area for the plate is leveled and as undisturbed as possible.
A calibrated 30 ton hydraulic jack is used to apply the load. A Tail handler machine and a Ramp greater than the test load is used to provide the reaction load.
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 9 of 45
Figure 6: Schematic overview plate bearing test
Settlements are measured using three calibrated dial gauges. The dial gauges are positioned at 120 degrees apart around the circumference of the plate. The required load is applied in at least six
loading steps. In each loading step, the load is maintained until the rate of settlement is less than 0.03 mm/min. Load and settlement readings are taken during this procedure. Each test is continued until a peak load is reached or until the ratio of load increment to settlement
increment reaches a minimum, steady magnitude. When the maximum load has been maintained for sufficient time, the load is released in three steps. In each step, the load is maintained till the rate of recovery is less than 0.03 mm/min. A Calibrated load ring of 50kN capacity (Calibration chart provided by ELS) was used to measure
readings of actual load applied. Generally Plate bearing tests will be performed up to 3 times the designed bearing capacity and when
the maximum load has been maintained for sufficient time, load released in three steps. In each step, the load maintained till the rate of recovery is less than 0.03mm/min.
8 EXECUTION
Contractor has assigned the practical execution of the soil testing to ELS International Ltd. The tests are part of the handover process from Contractor to Engineer and as such the tests were been executed in partial segments, the tests were not been conducted simultanously.
The details of executed tests at 10 locations can be found in the following table:
Sl.NO Name of
the Location
Co-ordinates Test Executed / Date Sub-
Contractor
1 REC-01 X: 338500 Y: 466900 a) Field density test on 12.03.2015 b) Lab Proctor compaction on 16.03.2015 c) Plate bearing test on 18.03.2015
ELS
2 REC-02 X: 338000 Y: 467100 a) Field density test on 12.03.2015 b) Lab Proctor compaction on 16.03.2015
c) Plate bearing test on 17.03.2015
ELS
3 REC-03 X: 338300 Y: 467400 a) Field density test on 12.03.2015
b) Lab Proctor compaction on 16.03.2015 c) Plate bearing test on 17.03.2015
ELS
4 REC-04 X: 338700 Y: 467400 a) Field density test on 12.03.2015 b) Lab Proctor compaction on 17.03.2015 c) Plate bearing test on 17.03.2015
ELS
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 10 of 45
5 REC-05 X: 338700 Y: 467900 a) Field density test on 12.03.2015 b) Lab Proctor compaction on 17.03.2015 c) Plate bearing test on 18.03.2015
ELS
6 REC-06 X: 339100 Y: 468100 a) Field density test on 12.03.2015 b) Lab Proctor compaction on 17.03.2015
c) Plate bearing test on 18.03.2015
ELS
7 REC-07 X: 338700 Y: 468300 a) Field density test on 12.03.2015
b) Lab Proctor compaction on 18.03.2015 c) Plate bearing test on 18.03.2015
ELS
8 REC-08 X: 339050 Y: 468590 a) Field density test on 12.03.2015 b) Lab Proctor compaction on 18.03.2015 c) Plate bearing test on 19.03.2015
ELS
9 REC-09 X: 338700 Y: 468800 a) Field density test on 12.03.2015 b) Lab Proctor compaction on 18.03.2015
c) Plate bearing test on 19.03.2015
ELS
10 REC-10 X: 338400 Y: 468600 a) Field density test on 12.03.2015
b) Lab Proctor compaction on 18.03.2015 c) Plate bearing test on 19.03.2015
ELS
9 CONCLUSION
At the proposed 10 Locations shown in Figure 8 Field density tests and Laboratory Standard Proctor
compaction tests were performed to determine the in-situ dry density and maximum dry density. The ratio between both given the degree of compaction. Based on the test results from Field density and Laboratory Standard Proctor compaction tests it is confirmed that the Degree of Compaction ranging
from 83.5% - 96.6%.(Test reports incorporated in Annexure-II) At the same locations Plate bearing tests also performed to determine the soil bearing capacity with
150 Kpa bearing, the tet results included with load versus settlement graphs, Maximum settlement encountered upto 5.52mm. (Test reports incorporated in Annexure-III)
The degree of compaction and maximum settlement achieved by 150Kpa bearing seems applicable to meet the requirement of Engineer for the designed Reclamation area.
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 11 of 45
Annexure I Drawing with location points REC-01 to REC-10
466,800
466,900
467,000
467,100
467,200
467,300
467,400
467,500
467,600
467,700
467,800
467,900
468,000
468,100
468,200
468,300
468,400
468,500
468,600
468,700
468,800
468,900
STN-009
STN-010
STN-011
BM-01
BM-02
BM-03
Zone 3
Zone 4
Zone 2Zone 5
Zone
6
Zone 1
HO
SPIT
AL
44
60 S
Q.M
SC
HO
OL
DH
IRA
AG
U S
ITE
MO
SQ
UE
SITE
HU
LH
UMA
LE
'F
ERR
YTE
RM
INA
L
JET
TY
TEMPORARY
BUILDING
BOUNDARY WALL
S TN-008
STN-009
STN- 010
STN- 011
BM- 01
BM -02
BM- 03
Zone 3
Zone 4
Zone 2Zone 5
Zone
6
Zone 1
Overview
Scale: 1/5000
All depths are in metres and are measured relative to Mean Sea Level.
All positions are calculated by RTK GNSS receivers.
GEODETIC INFORMATION
TIDE REDUCTION
POSITIONING
All coordinates are in metres.
COLOR LEGEND
RTK corrections are received from Contractor's base station located on Faru Island.
Semi-major axis:Reciprocal flatenning:
Projection Type:False Easting:False Northing:Longitude at origin:Latitude at origin:Scale factor at origin:
Vertical reference:
Mean Sea Level is physically defined by the benchmarks provided by Employer.
World Geodetic System 1984WGS846,378,137298.257223563
UTM Zone 43NTransverse Mercator
0
500,000075 E
0.9996
Mean Sea Level
Tide reduction to Mean Sea level is done by RTK Height corrected by the geoid separation.
-45.0
-2.0
0.0
1.0
1.75 1.80
2.00 2.05
3.0
7.0
1.90
Description
Cadfile:
Notes
AprdChkd
Do not scale this drawing
DateRev
A1
Date :
Checked
Employer :
Project :
Drawing No.
Scale
Drawn
Copyright reserved
Approved
CADFILE
0 23/03/2015 Internal review RVI RVV
Engineer :
Contractor :
JDC RVI RVV
1 : 5000 30/03/2015
5138-DR-104-PR-RECLA.dwg
Hulhumale Phase II
Hand overing areas with Degree of compactionTitle :
and Plate bearing test results
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 13 of 45
Annexure II Field Density & Proctor Compaction test results
Project.: Hulhumalé Phase-II Development
Client Dredging International
Test Location REC- 01 X 338500
Tested Depth Y 466900
Date 12/03/2015
Test No. 1
Elevation
Weight of Can + Sand 1 g 9658
Weight of Can + Sand 2 g 3880
Weight of Sand g 5778
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3165
Weight of Can + Wet soil g 728.60
Weight of Can +Dry soil g 664.20
Weight of Can g 124.50
Weight of Water g 64.40
Weight of Dry soil g 539.70
Moisture Content % 11.93
Weight of Can + soil from Hole g 5035
Weight of Can g 451
Weight of Wet soil g 4584
Bulk Density g/cm3 1.448
Dry Density g/cm3 1.294
Maximum Dry Density g/cm3 1.438
Degree of Compaction % 90.0
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 763.40 729.40 756.50 794.50 792.10
Wt. of dry soil + container g 738.80 685.40 690.10 703.90 685.32Wt. of container g 122.70 121.20 123.30 126.80 120.60Wt. of water g 24.60 44.00 66.40 90.60 106.78Wt. of dry soil g 616.10 564.20 566.80 577.10 564.72Moisture content % 3.99 7.80 11.71 15.70 18.91Wt. of mould + wet soil g 4680 4810 4960 4990 5005Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1397 1527 1677 1707 1722
Bulk density g/cm3 1.469 1.606 1.764 1.795 1.811
Dry density g/cm3 1.413 1.490 1.579 1.552 1.523
Maximum Dry Density (g/cm3) 12.20
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 1
1.438 Optimum Moisture content ( %)
X : 338500 Y : 466900 21/02/2015
REC 01 22/02/2015
BS 1377 part 4
1.41
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49
1.50
1.51
1.52
1.53
1.54
1.55
1.56
1.57
1.58
1.59
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 02 X 338000
Tested Depth Y 467100
Date 12/03/2015
Test No. 1
Elevation
Weight of Can + Sand 1 g 9553
Weight of Can + Sand 2 g 3925
Weight of Sand g 5628
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3053
Weight of Can + Wet soil g 854.80
Weight of Can +Dry soil g 807.90
Weight of Can g 128.00
Weight of Water g 46.90
Weight of Dry soil g 679.90
Moisture Content % 6.90
Weight of Can + soil from Hole g 5381
Weight of Can g 451
Weight of Wet soil g 4930
Bulk Density g/cm3 1.615
Dry Density g/cm3 1.511
Maximum Dry Density g/cm3 1.592
Degree of Compaction % 94.9
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 813.10 824.30 718.40 805.10 853.70
Wt. of dry soil + container g 787.60 785.30 674.50 743.50 770.40Wt. of container g 125.20 118.20 114.70 123.00 124.90Wt. of water g 25.50 39.00 43.90 61.60 83.30Wt. of dry soil g 662.40 667.10 559.80 620.50 645.50Moisture content % 3.85 5.85 7.84 9.93 12.90Wt. of mould + wet soil g 4760 4835 4915 4935 4940Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1477 1552 1632 1652 1657
Bulk density g/cm3 1.554 1.632 1.717 1.738 1.743
Dry density g/cm3 1.496 1.542 1.592 1.581 1.544
Maximum Dry Density (g/cm3) 8.50
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 2
1.592 Optimum Moisture content ( %)
X : 338500 Y : 467100 21/02/2015
REC 02 22/02/2015
BS 1377 part 4
1.47
1.48
1.49
1.50
1.51
1.52
1.53
1.54
1.55
1.56
1.57
1.58
1.59
1.60
2 3 4 5 6 7 8 9 10 11 12 13 14 15
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 03 X 338300
Tested Depth Y 467400
Date 12/03/2015
Test No. 1
Elevation
Weight of Can + Sand 1 g 9525
Weight of Can + Sand 2 g 3742
Weight of Sand g 5783
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3169
Weight of Can + Wet soil g 655.20
Weight of Can +Dry soil g 614.50
Weight of Can g 124.50
Weight of Water g 40.70
Weight of Dry soil g 490.00
Moisture Content % 8.31
Weight of Can + soil from Hole g 5375
Weight of Can g 451
Weight of Wet soil g 4924
Bulk Density g/cm3 1.554
Dry Density g/cm3 1.435
Maximum Dry Density g/cm3 1.552
Degree of Compaction % 92.4
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 793.30 746.30 815.10 835.30 857.50
Wt. of dry soil + container g 768.90 700.30 737.40 735.40 734.40Wt. of container g 123.40 122.90 128.40 130.80 125.60Wt. of water g 24.40 46.00 77.70 99.90 123.10Wt. of dry soil g 645.50 577.40 609.00 604.60 608.80Moisture content % 3.78 7.97 12.76 16.52 20.22Wt. of mould + wet soil g 4710 4835 4945 4945 4952Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1427 1552 1662 1662 1669
Bulk density g/cm3 1.501 1.632 1.748 1.748 1.755
Dry density g/cm3 1.446 1.512 1.550 1.500 1.460
Maximum Dry Density (g/cm3) 12.80
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 3
1.552 Optimum Moisture content ( %)
X : 338300 Y : 467400 21/02/2015
REC 03 22/02/2015
BS 1377 part 4
1.44
1.45
1.46
1.47
1.48
1.49
1.50
1.51
1.52
1.53
1.54
1.55
1.56
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 04 X 338700
Tested Depth Y 467400
Date 12/03/2015
Test No. 1
Elevation
Weight of Can + Sand 1 g 9493
Weight of Can + Sand 2 g 3639
Weight of Sand g 5854
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3222
Weight of Can + Wet soil g 790.50
Weight of Can +Dry soil g 746.00
Weight of Can g 127.90
Weight of Water g 44.50
Weight of Dry soil g 618.10
Moisture Content % 7.20
Weight of Can + soil from Hole g 5731
Weight of Can g 451
Weight of Wet soil g 5280
Bulk Density g/cm3 1.639
Dry Density g/cm3 1.529
Maximum Dry Density g/cm3 1.582
Degree of Compaction % 96.6
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 860.30 776.90 713.20 855.40 846.80
Wt. of dry soil + container g 838.20 740.20 668.30 778.90 750.40Wt. of container g 126.40 121.80 131.60 131.60 125.30Wt. of water g 22.10 36.70 44.90 76.50 96.40Wt. of dry soil g 711.80 618.40 536.70 647.30 625.10Moisture content % 3.10 5.93 8.37 11.82 15.42Wt. of mould + wet soil g 4700 4790 4910 4945 4965Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1417 1507 1627 1662 1682
Bulk density g/cm3 1.490 1.585 1.711 1.748 1.769
Dry density g/cm3 1.446 1.496 1.579 1.563 1.533
Maximum Dry Density (g/cm3) 9.40
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 4
1.582 Optimum Moisture content ( %)
X : 338700 Y : 467400 21/02/2015
REC 04 22/02/2015
BS 1377 part 4
1.42
1.44
1.46
1.48
1.50
1.52
1.54
1.56
1.58
1.60
1.62
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 05 X 338700
Tested Depth Y 467900
Date 12/03/2015
Test No. 5
Elevation
Weight of Can + Sand 1 g 9481
Weight of Can + Sand 2 g 3669
Weight of Sand g 5812
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3191
Weight of Can + Wet soil g 725.40
Weight of Can +Dry soil g 657.80
Weight of Can g 124.00
Weight of Water g 67.60
Weight of Dry soil g 533.80
Moisture Content % 12.66
Weight of Can + soil from Hole g 5542
Weight of Can g 451
Weight of Wet soil g 5091
Bulk Density g/cm3 1.596
Dry Density g/cm3 1.416
Maximum Dry Density g/cm3 1.590
Degree of Compaction % 89.1
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 851.90 777.90 819.10 767.70 750.70
Wt. of dry soil + container g 830.20 748.30 778.20 720.10 688.40Wt. of container g 127.90 121.80 130.80 125.00 125.00Wt. of water g 21.70 29.60 40.90 47.60 62.30Wt. of dry soil g 702.30 626.50 647.40 595.10 563.40Moisture content % 3.09 4.72 6.32 8.00 11.06Wt. of mould + wet soil g 4801 4845 4880 4915 4935Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1518 1562 1597 1632 1652
Bulk density g/cm3 1.597 1.643 1.680 1.717 1.738
Dry density g/cm3 1.549 1.569 1.580 1.589 1.565
Maximum Dry Density (g/cm3) 7.80
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
1.590 Optimum Moisture content ( %)
X : 338700 Y : 467900 16/03/2015
REC 05 19/03/2015
BS 1377 part 4
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 5
1.54
1.55
1.56
1.57
1.58
1.59
1.60
1.61
1.62
2 3 4 5 6 7 8 9 10 11 12 13
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 06 X 339100
Tested Depth Y 468100
Date 12/03/2015
Test No. 6
Elevation
Weight of Can + Sand 1 g 9447
Weight of Can + Sand 2 g 3908
Weight of Sand g 5539
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 2987
Weight of Can + Wet soil g 729.60
Weight of Can +Dry soil g 694.20
Weight of Can g 120.70
Weight of Water g 35.40
Weight of Dry soil g 573.50
Moisture Content % 6.17
Weight of Can + soil from Hole g 4495
Weight of Can g 451
Weight of Wet soil g 4044
Bulk Density g/cm3 1.354
Dry Density g/cm3 1.275
Maximum Dry Density g/cm3 1.528
Degree of Compaction % 83.5
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 834.50 847.00 865.10 836.90 831.90
Wt. of dry soil + container g 810.10 812.20 815.20 776.10 760.12Wt. of container g 121.80 128.00 131.80 123.40 125.00Wt. of water g 24.40 34.80 49.90 60.80 71.78Wt. of dry soil g 688.30 684.20 683.40 652.70 635.12Moisture content % 3.54 5.09 7.30 9.32 11.30Wt. of mould + wet soil g 4708 4768 4820 4870 4830Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1425 1485 1537 1587 1547
Bulk density g/cm3 1.499 1.562 1.617 1.669 1.627
Dry density g/cm3 1.448 1.486 1.507 1.527 1.462
Maximum Dry Density (g/cm3) 9.00
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 6
1.528 Optimum Moisture content ( %)
X : 339100 Y : 468100 16/03/2015
REC 06 19/03/2015
BS 1377 part 4
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49
1.50
1.51
1.52
1.53
1.54
2 3 4 5 6 7 8 9 10 11 12 13
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 07 X 338700
Tested Depth Y 468300
Date 12/03/2015
Test No. 7
Elevation
Weight of Can + Sand 1 g 9375
Weight of Can + Sand 2 g 3610
Weight of Sand g 5765
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3155
Weight of Can + Wet soil g 753.20
Weight of Can +Dry soil g 703.30
Weight of Can g 125.20
Weight of Water g 49.90
Weight of Dry soil g 578.10
Moisture Content % 8.63
Weight of Can + soil from Hole g 5038
Weight of Can g 451
Weight of Wet soil g 4587
Bulk Density g/cm3 1.454
Dry Density g/cm3 1.338
Maximum Dry Density g/cm3 1.402
Degree of Compaction % 95.4
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 653.70 721.10 680.60 727.30 718.20
Wt. of dry soil + container g 638.10 692.10 637.10 672.20 658.10Wt. of container g 127.10 130.70 131.50 123.40 121.80Wt. of water g 15.60 29.00 43.50 55.10 60.10Wt. of dry soil g 511.00 561.40 505.60 548.80 536.30Moisture content % 3.05 5.17 8.60 10.04 11.21Wt. of mould + wet soil g 4622 4665 4730 4745 4740Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1339 1382 1447 1462 1457
Bulk density g/cm3 1.408 1.454 1.522 1.538 1.532
Dry density g/cm3 1.367 1.382 1.401 1.397 1.378
Maximum Dry Density (g/cm3) 9.20
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 7
1.402 Optimum Moisture content ( %)
X : 338700 Y : 468300 16/03/2015
REC 07 19/03/2015
BS 1377 part 4
1.35
1.36
1.37
1.38
1.39
1.40
1.41
1.42
2 3 4 5 6 7 8 9 10 11 12 13
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 08 X 339050
Tested Depth Y 468590
Date 12/03/2015
Test No. 8
Elevation
Weight of Can + Sand 1 g 9378
Weight of Can + Sand 2 g 3758
Weight of Sand g 5620
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3047
Weight of Can + Wet soil g 749.40
Weight of Can +Dry soil g 698.20
Weight of Can g 124.30
Weight of Water g 51.20
Weight of Dry soil g 573.90
Moisture Content % 8.92
Weight of Can + soil from Hole g 5098
Weight of Can g 451
Weight of Wet soil g 4647
Bulk Density g/cm3 1.525
Dry Density g/cm3 1.400
Maximum Dry Density g/cm3 1.486
Degree of Compaction % 94.2
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 807.80 646.90 714.30 695.00 741.70
Wt. of dry soil + container g 784.20 621.00 668.30 646.10 681.10Wt. of container g 125.40 121.70 125.00 128.20 122.40Wt. of water g 23.60 25.90 46.00 48.90 60.60Wt. of dry soil g 658.80 499.30 543.30 517.90 558.70Moisture content % 3.58 5.19 8.47 9.44 10.85Wt. of mould + wet soil g 4650 4724 4812 4820 4825Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1367 1441 1529 1537 1542
Bulk density g/cm3 1.438 1.516 1.608 1.617 1.622
Dry density g/cm3 1.388 1.441 1.483 1.477 1.463
Maximum Dry Density (g/cm3) 9.00
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 8
1.486 Optimum Moisture content ( %)
X : 335090 Y : 468590 16/03/2015
REC 08 19/03/2015
BS 1377 part 4
1.38
1.39
1.40
1.41
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49
1.50
2 3 4 5 6 7 8 9 10 11 12 13
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase-II Develoment
Client Dredging International
Test Location REC- 09 X 338700
Tested Depth Y 468800
Date 12/03/2015
Test No. 9
Elevation
Weight of Can + Sand 1 g 9372
Weight of Can + Sand 2 g 3263
Weight of Sand g 6109
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 3412
Weight of Can + Wet soil g 703.00
Weight of Can +Dry soil g 663.30
Weight of Can g 121.40
Weight of Water g 39.70
Weight of Dry soil g 541.90
Moisture Content % 7.33
Weight of Can + soil from Hole g 5552
Weight of Can g 451
Weight of Wet soil g 5101
Bulk Density g/cm3 1.495
Dry Density g/cm3 1.393
Maximum Dry Density g/cm3 1.492
Degree of Compaction % 93.4
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 724.20 811.90 734.88 684.11 680.50
Wt. of dry soil + container g 703.22 778.56 690.70 635.10 620.12Wt. of container g 121.50 123.00 126.00 127.00 122.90Wt. of water g 20.98 33.34 44.18 49.01 60.38Wt. of dry soil g 581.72 655.56 564.70 508.10 497.22Moisture content % 3.61 5.09 7.82 9.65 12.14Wt. of mould + wet soil g 4685 4720 4800 4840 4850Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1402 1437 1517 1557 1567
Bulk density g/cm3 1.475 1.511 1.596 1.638 1.648
Dry density g/cm3 1.423 1.438 1.480 1.494 1.470
Maximum Dry Density (g/cm3) 9.80
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 9
1.492 Optimum Moisture content ( %)
X ; 338700 Y : 468800 16/03/2015
REC 09 19/03/2015
BS 1377 part 4
1.38
1.39
1.40
1.41
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49
1.50
2 3 4 5 6 7 8 9 10 11 12 13
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Project.: Hulhumalé Phase 2 Development: Dredging and Reclamation Works
Client Dredgimng International nv
Test Location REC- 10 X 338400
Tested Depth Y 468600
Date 12/03/2015
Test No. 10
Elevation
Weight of Can + Sand 1 g 9341
Weight of Can + Sand 2 g 3904
Weight of Sand g 5437
Bulk Density of Sand g/cm3 1.339
Volume of Funnel cm3 1150
Volume of Density Hole g/cm3 2910
Weight of Can + Wet soil g 684.50
Weight of Can +Dry soil g 634.50
Weight of Can g 131.00
Weight of Water g 50.00
Weight of Dry soil g 503.50
Moisture Content % 9.93
Weight of Can + soil from Hole g 4994
Weight of Can g 451
Weight of Wet soil g 4543
Bulk Density g/cm3 1.561
Dry Density g/cm3 1.420
Maximum Dry Density g/cm3 1.488
Degree of Compaction % 95.4
Signature ……………..
Tested byENGINEERING & LABORATORY SERVICES ( PVT ) LTD62/3 Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone : 0094 01 517037 / 517365 / 519727, Fax : 0094 01 509806, E-Mal [email protected]
DETERMINATION OF FIELD DENSITY TEST LABORATORY WORK SHEET
Coordinates
Project
Client
Type of soil
Coordinate Date of test
Location Date of reports
Test MethodCompaction mould Compacted by hand / machine
Diameter cm 10.15 Weight of Rammer (kg) 2.5
Height cm 11.75 Dropping Height (cm) 30.5
Volume cm3 950.74 Number of Layers 3
Weight g 3283 Blows per Layer 27
Trial No. 1 2 3 4 5
Wt. of wet soil + container g 680.45 712.35 650.75 738.90 760.60
Wt. of dry soil + container g 661.70 680.10 610.27 683.50 693.10Wt. of container g 124.55 128.00 125.00 124.40 124.40Wt. of water g 18.75 32.25 40.48 55.40 67.50Wt. of dry soil g 537.15 552.10 485.27 559.10 568.70Moisture content % 3.49 5.84 8.34 9.91 11.87Wt. of mould + wet soil g 4704 4762 4811 4836 4840Wt. of mould g 3283 3283 3283 3283 3283Wt. of wet soil g 1421 1479 1528 1553 1557
Bulk density g/cm3 1.495 1.556 1.607 1.633 1.638
Dry density g/cm3 1.444 1.470 1.483 1.486 1.464
Maximum Dry Density (g/cm3) 9.60
Signature
…………………….
Senior Lab Technician
Engineering & Laboratory Services (PVT) LTDSri Lanka office:62/3,Neelammahara Road,Katuwawala,Boralesgamuwa Sri Lanka.Tel:0094 011 2 517037 / 517365/ Fax:0094112509806 E mail. [email protected]
PROCTOR COMPACTION TEST - LABORATORY WORK SHEET
Hulhumalé Phase -II Development
Dredging International Job ref. EA/HUL/001
Coral sand Sample No. 10
1.488 Optimum Moisture content ( %)
X: 338400 Y : 468600 16/03/2015
REC 10 19/03/2015
BS 1377 part 4
1.38
1.39
1.40
1.41
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49
1.50
2 3 4 5 6 7 8 9 10 11 12 13
Dry
Den
sity
g/c
m
Moisture Content %
Dry Density-Moisture Relation
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 34 of 45
Annexure III Plate bearing test results
Quality is our Trademark
REPORT ON PLATE BEARING TESTS FOR
GEORECHNICAL INVESTIGATION FOR HULUMALE PHASE II PROJECT
CLIENT: M/S. DREDGING INTERNATIONAL (PVT) LTD.
Engineering & Laboratory Services (Pvt) Ltd 62/3 Neelammahara Road
Katuwawala, Boralesgamuwa, Sri Lanka Tel: 011-4309494, 011- 2517365;
Fax: 011-2509806 Email: [email protected] Web: www.elslanka.com
04th April 2015
Document No: ML/FT/1022
00 04/04/2015 Plate Bearing Test Report for
Geotechnical Investigation for Hulumale Phase II Project
Tiran Jayasinghe BSc. Eng.
Eng. R. Mahinda Rathnasiri
Rev Date Description Prepared By
Approved By
CONTENT
Page No
1.0 INTRODUCTION………………………………….……………………………01
2.0 SCOPE…………………………………………….………………………….....01
3.0 TEST PROCEDURE
3.1 Plate Bearing Tests………………………….……………………………..02
5.0 RESULTS & CONCLUSION…………………………………………………..02
List of Annexure
Annexure I: Plate Bearing Test Results
Page 1 of 11
1. INTRODUCTION
M/s. Dredging International (Pvt) Ltd. requested Engineering & Laboratory Services (Pvt)
Ltd. to carry out total number of 10 plate-bearing tests at the un-compacted reclaimed sand
area for Geotechnical Investigation at Hulumale Phase II Project.
2. SCOPE
The objective of a plate bearing test in accordance with BS 1377: Part 9 is to determine
vertical deformations and strength characteristics of soil in-situ by assessing the force and
amount of penetration with time when a rigid plate is made to penetrate the soil.
3. TEST PROCEDURE
3.1. PLATE BEARING TEST
In this site, ten plate load tests were done at the locations specified by the client. Application
of the load to the plate of 300mm diameter was done directly through a calibrated Hydraulic
Jack. Reaction load was obtained by jacking against heavy counter weight and settlements
were measured using three number of calibrated dial gauges. The dial gauges were positioned
at 120 degrees apart around the circumference of the plate.
The loads were applied in a single cycle to 452 kN / m2 in 5 equal increments and unloaded
to zero. In each loading stage, the settlement was measured at specified time as shown in the
result sheets. An average final settlement of the plate was calculated for each load to obtain
the stress vs. settlement curve.
Page 2 of 11
4. RESULTS & CONCLUSION
Plate Load Test
The maximum applied pressure beneath the plate neglecting the load of plate and the jack; q
in kPa is calculated from the following equation.
q = P/A
where,
P is the applied maximum force in kN.
A is the area of the plate in m2
The Load vs settlement results obtained from the tests are summarized as in the Tables
below. The load vs settlement graphs are shown together with the detailed test results in the
Annexure I.
Table 1: Load- Settlement data for Location REC 01 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.59
182.50 1.03
272.47 1.46
362.59 1.84
452.42 2.18
301.90 2.12
151.52 1.93
0.00 1.30
Figure 1: Load- Settlement behavior for Location REC 01 (Test Level: Ground Surface)
Page 3 of 11
Table 2: Load- Settlement data for Location REC 02 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.38
182.50 0.65
272.47 0.91
362.59 1.15
452.42 1.40
301.90 1.35
151.52 1.19
0.00 0.60
Figure 2: Load- Settlement behavior for Location REC 02 (Test Level: Ground Surface)
Table 3: Load- Settlement data for Location REC 03 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.68
182.50 1.08
272.47 1.42
362.59 1.78
452.42 2.19
301.90 2.13
151.52 2.04
0.00 1.30
Page 4 of 11
Figure 3: Load- Settlement behavior for Location REC 03 (Test Level: Ground Surface)
Table 4: Load- Settlement data for Location REC 04 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.77
182.50 1.28
272.47 1.87
362.59 2.50
452.42 3.33
301.90 3.25
151.52 3.10
0.00 2.16
Page 5 of 11
Figure 4: Load- Settlement behavior for Location REC 04 (Test Level: Ground Surface)
Table 5: Load- Settlement data for Location REC 05 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.73
182.50 1.59
272.47 2.63
362.59 3.55
452.42 5.18
301.90 4.15
151.52 3.99
0.00 2.98
Page 6 of 11
Figure 5: Load- Settlement behavior for Location REC 05 (Test Level: Ground Surface)
Table 6: Load- Settlement data for Location REC 06 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.60
181.79 0.97
270.07 1.29
362.59 1.60
452.42 1.87
302.61 1.84
151.52 1.70
0.00 1.09
Figure 6: Load- Settlement behavior for Location REC 06 (Test Level: Ground Surface)
Page 7 of 11
Table 7: Load- Settlement data for Location REC 07 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.27
181.79 0.52
270.07 0.80
362.59 1.05
452.42 1.31
302.61 1.25
151.52 1.07
0.00 0.42
Figure 7: Load- Settlement behavior for Location REC 07 (Test Level: Ground Surface)
Table 8: Load- Settlement data for Location REC 08 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 1.77
181.79 2.58
331.47 3.51
362.59 4.38
452.42 5.52
302.61 5.50
151.52 5.32
0.00 4.25
Page 8 of 11
Figure 8: Load- Settlement behavior for Location REC 08 (Test Level: Ground Surface)
Table 9: Load- Settlement data for Location REC 09 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 1.22
181.79 1.95
270.07 2.62
362.59 3.28
452.42 3.99
302.61 3.62
151.52 3.44
0.00 2.91
Page 9 of 11
Figure 9: Load- Settlement behavior for Location REC 09 (Test Level: Ground Surface)
Table 10: Load- Settlement data for Location REC 10 (Test Level: Ground Surface)
Applied Pressure (kPa)
Settlement (mm)
0.00 0.00
91.53 0.75
181.79 1.31
270.07 1.77
362.59 2.22
452.42 2.63
302.61 2.56
151.52 2.32
0.00 1.56
I '
rtorrnal Sreu {J-U/m2l
l·ig.un: 10: Lnad- Settkment bcluwior for Location RI:.C 10 (Test Level: Ground Surface)
I h~ load '~ 'elllttllent graphs for all ten l ocation~ clenrl) sho" that the Load settlement
lx:ha' ttlr o l the p l•tle is ncarl~ linear.
rhl: lin~·ar hcha' illltr of the load-<.etth:ment behaviour upto 452.421-.Pa ind icates that the soil
lw' nt '' rcad11.:d thr) idding ~tagc nnJ the ultimate carrying capacity of the plate has not been
reached durin!! the loading stage. Theret\.-.re. the ultimate carrying capacity of the plate is
high~:r tha n the maximum load applied (-152.42 kPa) .
1t is H t:nmnwnl) accepted fact that the ultimate currying capacity of toundations on sand
incrcu:-.c' "ith the \\ idt h of the fuunJation. Following. nssumpt ions are made:
• r: l'll:ct' of the ground" ater tabk on the ultimate bearing capacity of the plate and tht::
pn 1tot: pe l\ \Uilllat ion arc simi la.r: and
• I hl· 1~1 i lurt' mude \l f tht> prntot~ p.e, founJat ion is same as that or the plate.
l ~a".:d 1111 thl' above assumptions and the plate load test results. it is reasonable to concl\llk
that an~ pr\llllt~ pc li.lntin~ at the tested locati ons "ider than the plate and having a vertical
~.......:.:.;---l.lo.!..r...:" , 11 I 50 h. Pa "ttl ha' L a ti1ctor of sa fety of 3.0 or more against shear failure.
~
\ • Hill a ~~~\1~1 i ~
In~· (I k1n-..). \I ) . ( ~c~nh .. ::tl Engineering)
Chanl'rl'd (.' i' i l l-. ng.in~.er
(;cncral \lauagcr
E;'IICINEEH.l~(; & 1..\BOR.\TORY SERVICES (PVT) LTD
Page I (J 111' I I
Engineering & Laboratory Services (Pvt) Ltd
Page 11 of 11
Annexure I: Plate Bearing Test Results
EL~ PLATE BEARING TEST Test Format No: ELS·ML-50
TEST METHOD • BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT OAT A
Client Dredging International (Pvt) Ltd Job No MUFT/1022
ProJeCt; Geotechnical Investigation at Huiumale Phase II Date of test 18.03.2015
Coordinate E· N- Elevation (rnJ 1.8 m Date of Report 24.03.2015
Locat1on REC 01 Test No· 01
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m' Maintained Pump Dial Reading Settlement (mm) Average
Period Scale Load Normal s 1 S2 53 S1 S2 S3 Settlement
Time Reading (kN}
Stress (min} (kpa)
(diV) mm
Loading
9.00 0 0 0 0 50.00 50.00 50.00 0.00 0.00 0.00 0.00
0 153 6.47 92 49.61 49.02 49.79 0.39 0.98 0.21 0.53
1 49.59 48.99 49.79 0.41 1.01 0.21 0.54
2 49.59 48.97 49.79 0.41 1.03 0.21 0.55
5 49.57 48.90 49.77 0.43 1.10 0.23 0.59
10 49.55 48.90 49.77 0.45 1.10 0.23 0.59
9.10 0 306 12.90 182 49.25 48 47 49.54 0.75 1.53 0.46 0.91
1 49.21 48.41 49.53 0.79 1.59 0.47 0.95
2 49.19 48.38 49.51 0.81 1.62 0.49 0,97
5 49.16 48.35 49.50 0.84 1.65 0.50 1.00
10 49.13 48.29 49.48 0.87 1,71 0.52 1.03
9.20 0 458 i9 .26 272 4885 4804 49.20 1.15 1.96 0.80 130
1 48.77 47.95 49.17 1.23 2.05 0.83 1.37
2 48.75 47.92 49.15 1.25 2.08 0.85 1.39
5 48.72 47.87 49.13 1.28 2.13 0.87 1.43
10 48.69 47 82 49.11 1.31 2.18 0.89 1.46
9.30 0 611 25.63 363 ~8.43 47.67 48.83 1.57 2.33 1.17 1.69 '1 48.37 47,60 48.78 1.63 2.40 1.22 1 75
2 48.34 47 59 48.77 1_66 2.41 1.23 1.77
5 48.30 47.54 48.73 1.70 2.46 1.27 1.81
10 48.26 47.51 48.71 1.74 2.49 1.29 1.84
9.40 0 764 31.98 452 47.99 47.27 48.42 2.01 2.73 1.58 2.11
1 47.95 47.27 48.41 2.05 2.73 1.59 212
2 . 47.95 47 26 48 41 2.05 2.74 1.59 2.13
5 47.91 4723 48.39 2.09 2.77 1.61 2.16
2 47.89 47.20 48,38 2.11 2 .80 1.62 2.18
Unloadmg
9.50 0 509 21 ,34 302 47,95 47.20 48.50 2.05 2.80 1.50 2.12 1 47,95 47.2.0 48,50 2.05 2.80 1.50 2.12 2 47 95 47 20 48.50 2.05 2.80 1.50 2.12 5 47Jl5 47 20 48.50 2.05 2.80 1 50 2.12
10 47.95 47 20 48..50 2.05 2.80 1.50 2.12
Te(;j] f'_ Checked by: Cetified~
(.70.~1: :-... .. ::11--i.l.mu1LJ _ .... .. . .. . .. .. ..... ...
ENGINEE!R(NG & LABORATOR~ICES (PVT) LTD
6213. Neelainmahara Road, Katuwaw.ala, Boralesgamuwa, Sri Lanka.
Telephone: 0094 011 4309494/2517037 /2517365, Fax: 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST
Test Format No: ELS-ML-50 TEST METHOD- BS 1377: PART 9:
SECTION 4.1 Revision No. 00 PROJECT OAT A
Client: Dredgtng International (Pvt) Ltd Job No. MLIFTI1022
Pro1ect. Geotechnical Investigation at Hulumale Phase If Date of test 18.03.2015
Coordinate E . N - Elevation (m) 1.8 rn Date of Report 24 03.2015
Location REC 01 Test No: 01
TEST DATA Plate size 0.300 m Area of Plate 0.071 m
2
Maintained Pump Dial Reading Settlement (mm) Average Scale Load
Normal Time Period Stress
Read1ng (kN) (kpa) 51 S2 53 51 S2 53 Settlement (min) (div) mm
10.00 0 254 10 71 152 48.16 47.28 48.76 1.84 2.72 1.24 1.93 1 48.16 47.28 48.77 1.84 2.72 1.23 1.93 2 48.16 47.28 48.77 1.84 2.72 1.23 1 93 5 48.16 47.28 48.77 1.84 2.72 1.23 1.93
10 48.16 47.28 48.77 1.84 2.72 1.23 1.93 10 10 0 0 0 0 48.74 48.01 49.34 1.26 1.99 0.66 1.30
1 48.74 48.01 49.34 1.26 1.99 0.66 1.30 2 48.74 48.01 49.34 1.26 1.99 0.66 1.30 5 48.74 48.01 49.35 1.26 1.99 0.65 1.30
10 48.75 48.01 49.35 1.25 1.99 0 .65 uo
I
Tes~ !I'_ ... . · ·:JJf7·~~:£~ ~ ~~~ift~d. ~~~;_ ·)} ENGIN~E IIWAG & LABORATORY SERVICES PVT ) LTD 'J
62/3, Neelammahara Road, Katuwawala. Boralesgamuwa, Sri Lanka. Telephone: 0094 011 430949412517037 / 2517365, Fax: 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377; PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No. MUFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 18.03.2015
Coordinate E - N- I Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 01 Test No: 01
TEST DATA Plate size 0.300 m Area of Plate 0.071 m 2
0 50 100 150 200 250 300 350 400 450 500
0 00 f-o. -4... l I l - j .,....
~ I I l • .... ~ ~ I -
I -r--r-. ' I ' 1,00 -- I --~ .... ~ ... _
I ~ I f- -f--..... ~ ....
-~w I r-- .... _
- - ( -~ ·-- T-, -~ ~~-- I I ~ro-o ........ 2.00 . ' J E I I I !
.... _ E 1 I I - I I I ' I ~ I I c Q> I E I I I I I Q> 3 00 -E i I Q> II) I I I I
I I I
I i I I I I I 4.00
-r-t- !
I I I 5 ,00 I I I I
I I I I Normal Sress (kN/m2 )
-~ Teste~ t_ [J;b~ Cetified by:~
• ~ v.jll_ '
E"NGINEERlff3 & LABORATORY'SERVTCES (PVT) LTD '.'"" 62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sn Lanka. Telephone : 0094 011 4309494/2517037 /2517365, Fax : 0094 01 2509806, E-Mail : [email protected].
El~ PLATE BEARING TEST
TEST METHOD- BS 1377: PART 9: Test Format No: ELS-ML-50
SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredgrng International (Pvt) Ltd Job No. MUFT/1022 Project: Geotechnical Investigation at Hulumale Phase II Date of test 17.03.2015
Coordinate E _ N- Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 02 Test No: 02
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m~ Maintained
Period Pump Dial Reading Settlement (mm)
Normal I-S-,-=;;;;_S~2.;;,.;;;.~S....,.3-+---,S,..-1~;.;;...;;;.._;,S-=-2~.,....;..:.;~S-3---l Average Settlement
Time (m1n)
Loading
1.3.10 0 0 1
13.20 0
2 5
10
13.30 _a 1 2
Scale Load Reading (kN)
(div)
.. lS l Q -N..
306 12.90
Stress (kpa)
so·.oQl 0.00 .49t17" cr.M 4~.vz · '0:33
.. W1!111lll', ~". 14~:ra -~a.- ·. 49.i70 o~i
L 49.._70· It,~ 182 49.50 49.23 49.54 0.50
49.50 49.18 49.48 0.50
49.49 49.17 49.48 0.51
49.47 49.15 49.46 0.53
49.46 49.13 49.45 0.54
mm
(l.OO ' 0.00_ :I -· _0.00 .014,4 o2~
., 0.'33
0>52 o:2a 0:.38 ..0.~ 0,3Q1 0.3Q o:'s3 O.SQ
ctS3 -o_aa 0.77 0.46 0.58
0.82 0.52 0.61
0.83 0.52 0.62
0.85 0.54 0.64
0.87 0.55 0.65
O.:rz -
t..'t5 ; . 0_.75'. 0.87
5 t.i.-1. - . 0.8~
10 13.40 0 611 25.63 363 49.17 48.62 49.10 0.83 1.38
1 49.16 48.58 49.07 0.84 1.42
2 49.1 5 48.55 49.05 0.85 1.45
5 49.14 48.49 48.99 0.86 1.51
1 0 49.11 48.46 48.97 0.89 1.54
Unloading 14 00 0 509 21.34 302 49.02 48.14 48.76 0.98 1.86
1 49.02 48.15 48.78 0.98 1.85
2 49.03 48.15 48.78 0.97 1.85
5 49.03 48.15 48.78 0.97 1.85 10 49.03 48.15 48.78 0.97 1.85
0.91 0,90 1.04
0.93 1.06
0.95 1.08
1.01 1.13
1.03 1.15
~..f~· - : '·- -~·1.26_
'l,:Z'S'· ·. ~ . . 1.40: .. ·u.s 11· _· 1.4«f -
1.24 1.36
1.22 1.35
1.22 1.35
1.22 1.35
1.22 1.35
Test~~ f C~by ...... ~~ I .. ( .... . ;[)~ ..
Cetified by: ¢_ ENGINEEk(NG & LABORATORY SER'IiiCES (PVT) LTD
62/3, Neelammahara Road, Katuwawala. Boralesgamuwa. Sri Lanka. Telephone : 0094 011 4309494/ 2517037 /2517365, Fax: 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST
Test Format No: ELS-ML-50 TEST METHOD- BS 1377: PART 9:
SECTION 4.1 Revision No. 00
PROJECT DATA
Client Dredging International (Pvt) Ltd Job No. MUFTI1022 Project: Geotechnical Investigation at Hulumale Phase II Date of test 17 03.2015
Coordinate E- N. Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 02 Test No: 02
TEST DATA Plate size 0.300 m Area of Plate 0.071 m"
Maintained Pump Dial Reading Settlement (mm) Average Scale Load Normal
Time Period Stress Reading (kN) (kpa) S1 S2 S3 S1 S2 S3 Settlement
(min) (d iv) mm 14.10 0 254 10.71 152 49.22 48.25 48.95 (;).78 1.75 1.05 1.19
1 49.22 48.26 48.95 0.78 1.74 1~05 1.19 2 49.21 48.26 48.95 0.79 U4 1:05 1.19
5 49.21 48.26, 48,95 0.79 1.74 1.05 1.19 10 49.21 48.26 48.95 0.79 ~.74 1.05 1.19
14.20 0 0 0 0 49.76 48.93 49.49 0.24 1.07 0.51 0.61 1 49.77 48.94 49.49 0.23 1.06 0.51 0.60 2 49.77 48.94 49.49 0.23 1.06 0.51 0.60
5 49.78 48.94 49.49 0.22 1.06 0.51 0.60 10 49 78 48.94 49.49 0.22 1.06 0.51 0.60
. .
_.,
Test~~L=l -- C,9-es~ed by: ~~~Ir:~d.~~.: ... ~ ~-' .-:a · r:·~ :11~ ( .... tJ~w~ .. .. .,§
·~ _.-;;[,7 '~· ~~ ENGINE!! lNG & LABORATORY'SERVICES (PVT) LTD fl 6213, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
I Telephone: 0094 011 4309494/2517037 /2517365, Fax: 0094 01 2509806, E-Mail: [email protected].
EL~ PROJECT OAT A
PLATE BEARING TEST TEST METHOD· BS 1377: PART 9:
SECTION 4.1
Test Format No: ELS·ML-50
Revision No. 00
Client: Dredging International (Pvt) Ltd Job No. ML/FT/1022
Project: Geotechnical lnvest1gation at Hulumale Phase II Date of test 17.03.2015
Coordinate E- N - Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 02 Test No: 02
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m
Normal Sress (kN/m2 1
0 50 100 150 200 250 300 350 400 450 500
ooo.---~~------~--.... ~--........ --.... ----r-----,-r--r~~ ~--~~--~~~ --~--1 ~~, r-- • - • ~ - .. . ~ . J _ -+ ...1..__
1 00
E 2.00 E
' I
c ' I
4> E 4> 3.00 E 4> Ill
. , ' 4 00 -~~-·-
-·----~----· ---- J - i ..1
500 I
I
'
' •• .,. --1 ' ' -· r . \ ,.. ......... t t i ~· ~~ ..
t '
• l L • '~- · - •· I
+-1
. I ' • ' I I
~--- .. , ... T I
I • .. - I ., ; • i 1 . -+-hf----'----!--~+--~1--•-- ·-......-!- "-+-
L __ • --· 1 . - [ . . , . I I
t-.... • ~ ~
I ... J J
__ __ l ~ 4--• ~-+--.l
..... -~·-. ----+
Cetified by: ~
62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka. Telephone: 0094 011 4309494/2517037 /2517365, Fax : 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST
Test Format No: ELS-ML-50 TEST METHOD - BS 1377: PART 9:
SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No. MUFTfi022
ProJect: Geotechnical Investigation at Hulumale Phase II Daie of test 17.03.2015
Coordinate E - N - Elevation (mJ 1.8 m Date of Report 24.03.2015
Location REC 03 Test No: 03
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
Maintained Pump Dial Reading Settlement (mm) Average Period Scale Load
Normal s 1 S 2 S 3 S1 S2 S3 Settlement Time
Reading (kNJ Stress
(min) (kpa) (div) mm
Loading
9.10 0 0 0 0 50.00 50.00 50.00 0.00 0.00 0.00 0.00
0 153 647 92 49.18 49.44 49.59 0.82 0.56 0.41 0.60
1 49.16 49.40 49.56 0.84 0.60 0.44 0.63
2 49.15 49.40 49.56 0.85 0.60 0.44 0.63
5 49.15 49.40 49.56 0.85 0.60 0.44 0.63
10 49.11 49.32 49.53 0.89 0.68 0.47 0.68
9.20 0 306 12.90 182 48.72 49.77 49.21 1.28 023 0.79 0.77
1 48.66 49.14 49.18 1.34 0.86 0.82 1.01
2 48.65 49.13 49.17 1.35 0.87 0.83 1 02
5 48.60 49.11 49.15 1.40 0.89 0.85 1.05
10 48.58 49.08 49.11 1.42 0.92 0.89 1.08
9.30 0 458 19.26 272 48.36 48.85 48.90 1.64 1.15 1.10 DO 1 48.29 48.81 48.88 1.71 1.19 1.12 1.34"
>
2 48.25 48.81 48.86 1.75 1.19 1.14 1.36,.
5 48.21 48.77 48.83 1.79 1.23 1.11 1.4'0
10 48.19 48.75' 48.80 1.81 1.25 0' 1.20 1.42
9.40 0 611 25.63 363 47.96 48.58 48.62 2.04 1.42 1.38 1.61
1 47.90 48.52 48.58 2.10 1.48 1.42 1.67
2 47.86 48.50 48.56 2.14 1.50 1.44 1.69
5 47.80 48.47 48.52 2.20 1.53 1.48 1.74
10 47.75 48.42 48.48 2.25 1.58 1.52 1.78
9.50 Q 764 31.98 452 47.52 48.28 4B.a2 2.48 1.72 1.68 1.96
"t 47.45 48.23 48.27 2.55 1.77 1.73 2.02
2 . 47.39 48.20 48.24 2.61 1.80 1.76 2.06
5 47 31 48.14 48.18 2.69 1.86 1.82 2.12
2 47.24 48.09 48.10 2.76 1.91 1.90 2.~9
Unloading
10.00 0 509 21 34 302 47.32 48.05 48.22 2.68 1.95 1.78 2.i4
1 47.33 48.05 48.22 2.67 1.95 1.78 2.1 3
2 47 33 48.05 48.23 2.67 1.95 1.77 2.13
5 47.33 48.05 48.23 2.67 1.95 1.77 2.13 10 47.33 48.05 48.23 2.67 1.95 1.77 2.13
Testedb~ C hecked by: Cetified by: ¢:_ ~~ ...... /~ . ( ·~~ .~ ··············· ····· ·
ENGINEERi!4G & LABORATORVSERVICES (PVT) LTD ,.
~...,.-
62/3. Neelammahara Road, Katuwawala. Boralesgamuwa. Sri Lanka.
Telephone : 0094 011 430949412517037 I 2517365 , Fax: 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST
Test Format No: ELS·ML·SO TEST METHOD - BS 1377: PART 9:
SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No. MLJFT/1022
ProJect Geotechnical Investigation at Hutumale Phase II Date of test 17.03.2015
Coordinate E . N. Elevation 1m) 1.8 m Date of Report 24.03.2015
Location REC 03 Test No 03
TEST DATA Plate size 0.300 m Area of Plate 0.071 m:.:
Maintained Pump Dial Reading Settlement (mm) Average Scale Load Normal
T1me Period Stress Reading (kN)
(kpa) S1 S2 S3 S1 S2 S3 Settlement (min) (div) mm
10.10 0 254 10.71 152 47.42 48.10 48.35 2.58 1.90 1.65 2.04
1 47.42 46.10 48.35 2.58 1.90 1.65 2.04
2 47.42 48.10 48.35 2.58 1.90 1.65 2.04
5 47.42 48.10 48.35 2.58 1.90 1.65 2.04 10 47.42 48.10 48.35 2.58 1.90 1.65 2.04
10.20 0 0 0 0 48.11 48.92 49.02 1.89 1.08 0.98 1.32
1 48.1 4 48.93 49.02 1.86 1.07 0.98 1.30
2 48.15 48.93 49.02 1.85 1.07 0.98 1.30
5 48.16 48.93 49.02 1.84 1.07 0.98 1.30
10 48.16 48 .93 49.02 1.84 1.07 0.98 1.30
Tested~ Cheel y: ~~ti.f~~~.~~~ -~ ~ .••.. ~'.F J'J'.:JL:I ... ... , .. )-tl1~· - )~ _ .r I _9--. ENGINE~~ING & LABORATORY .SERVICES (PVT) LTD <' ...
62/3, Neelammahara Road, Katuwawala. Boralesgamuwa, Sn Lanka. Telephone: 0094 011 4309494/2517037 / 2517365, Fax: 0094 01 2509806, E·Mail : [email protected].
EL~ PROJECT OAT A
PLATE BEARING TEST TEST METHOD· BS 1377: PART 9:
SECTION 4.1
Test Format No: ELS-ML-50
Revision No. 00
Client: Dredging International (Pvt) Ltd Job No. MUFT/1022
ProJect: Geotechnical Investigation at Hulumale Phase II Date of test 17.03.2015
Coordinate E- N- Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 03 Test No: 03
TEST DATA Plate size 0.300 m Area of Plate 0.071 m
Normal Sress (kN/m2)
0 50 100 150 200 250 300 350 400 450 500
0.00 ..-------.---r-T'"""!'"-:-....,.----r---r-:----:---.-. -. -:-1-:---;----r-----.--r-......... ----,
E E
c Q)
E Q)
~ (/)
1.00
2.00 . ' J
3.00
-i
- . --~~------1-·
4 00 ~ ' . . . ' . ..
' .
"-' t I ~ •- -.....-""T---- • --- - · • 1 -~- !
l ..... - .. - ~-.. - •
.. • I ..
•-; I
..
, ~· I
.... - ;--
. I
I l . .
' ..
. - . - -i-t- ,___._ •. . . -t ' 500 ~------~~~~~-~-~--~----------~'~' ~~--~~----~----~
Cetified by~
E-Mail : [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD· BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Cllent: Dredging International (Pvt) Ltd Job No. MUFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 17.03.2015
Coordinate E- N- Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 04 Test No: 04
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m 2
Maintained Pump
Dial Reading Settlement (mm) Average Period Normal s 1 S2 S3 S1 S2 S3 Settlement
Time Scale Load
Stress (min}
Reading (kN) (kpa) (div}
mm
Loadmg
9.10 0 0 0 0 50.00 50.00 5at00 0.00 0100 - e.oo .. 0.00 ''·
0 153 6.47 92 49.30 49.31 49.26 0.70 0.69 0.74 0.71
1 49.26 49.27 49.23 0.74 0.73 0.77 0.75 2 49.25 49.27 49.23 0.75 0.73 0.77 0.75
5 49.25 49.27 49.23 0.75 0.73 0.77 0.75 10 49.24 49.23 49.21 0.76 0.77 0.79 0.77
9.20 0 306 12.90 182 48.92 48.84 48.75 1.08 1.16 1.25 1.16
1 48.89 48.78 48.72 1.11 1.22 1.28 1.20
2 48.87 48.77 48.71 1.13 1.23 1.29 1.22
5 48.83 48.72 48.67 1.17 1.28 1.33 1.26
10 48.81 48.69 48.65 1.19 1.31 1.35 1.28
9.30 0 458 19.26 272 48.50 48.32 48.26 1.50 1.6~fi l_;t .74 1.64 1 48.42 48.24 48.18 1.58 1.76 - ~ ' 1.82 1.72
2 48.39 48.20 48.15 1.61 1~ ~1.ad'i 1.85 1.75 5 ' 48.35 48.14 48.09 1.65 1.86.!'1'P 1.91 1.81
10 48.29 48.06 48.04 1.71 1.94 :1.96 1.87 9.40 0 611 25.63 363 48.03 47.78 47.72 1.97 2.22 2.28 2.16
1 47.93 47.67 47.65 2.07 2.33 2.35 2.25 2 47.89 47.66 47.62 2.11 2.34 2.38 2.28 5 47.75 47.52 47.48 2.25 2.48 2.52. 2.42
10 47.67 47.44 47.40 2.33 2.56 2.60 2.50 9.50 o ~ 764 31.98 452 47.22 46.98 46.94 2.78 3.02 3.06 2.95
j 47.13 46.89 46.85 2.87 3.11 3.15 3.04 2 47.06 46.81 46.79 2.94 3.19 3.21 3.11 5 46.95 ~6.70 46.68 3.05 3.30 3.32 '3.22 2 46.8.5 46.58 46.57 3.15 3.42 3.43 3.33
Uni08CIIng 10.00 0 509 21.34 302 46.93 46.65 46.66 3.07 3.35 3.34 3.25
1 46.93 46.65 46.66 3.07 3.35 3.34 3.25
2 46.93 46.65 46.66 3.07 3.35 3.34 3.25
5 46.93 46.65 46.66 3.07 3.35 3.34 3.25 10 46.93 46.65 46.66 3.07 3.35 3.34 3:-25
Test~~ 1Jj};;;1 CheeKed by:
'! ' ' ' ''~-~---- ~~ti.fi~d- ~~ -¢: ENGINE~iJNG & LA BORA TORY seRVices PVT L TO
62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri LanKa.
Telephone : 0094 01.1 4309494/ 2517037 /2517365, Fax : 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST
Test Format No: ELS·ML·50 TEST METHOD- BS 1377: PART 9:
SECTION 4.1 Revision No. 00
PROJECT OAT A
Client Dredg1ng International (Pvt) Ltd Job No. MUFT/1022
ProJeCt' Geotechnical lnvest1gation at Hulumale Phase II Date of test 17.03.2015
Coordinate E . N. Elevation (m) 1.8 m Date of Report 24.03.2015
Locat1on REC 04 Test No: 04
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
Maintained Pump
Dial Reading Settlement (mm) Average
Normal Period Scale Load
Time Reading (kN)
Stress S1 S2 S3 S1 S2 S3 Settlement (kpa)
(mln> (div) mm
10 10 0 254 10.71 152 47.09 46.78 46.82 2.91 3.22 3.18 3.10 1 47.09 46.78 46.82 2.91 3.22 318 3.10
2 47.09 46.78 4682 2.91 3.22 3.18 3.10
5 47.09 46.78 4682 2.91 3.22 3.18 3.10
10 47.09 46.78 46.82 2.91 3.22 3.18 3.10
1020 0 0 0 0 48.02 47.69 47 82 1.98 2..31 2.18 2.16
1 48.02 47.69 47.82 1.98 2.31 2.18 2.16
2 48.02 47.69 47.82 1.98 2.31 2.18 2.16
5 48.02 47.69 47.82 1.98 2.31 2.18 2.16
10 48.02 47.69 47.82 1.98 2.31 2.18 2.16
-I ~~tifi~~- ~~~ ' ,¢=_ ~~ Tested b?J;j._ Ch~by
.,. ~-t:h ·Tt ... c .. J~-; ~I ..
ENGJN~!!:NG & LABORATORY SERVICES (PVT) LTD 62/3, Nee mmahara Road Katuwawala Borales amuwa, ' ' g Sri Lanka. Telephone : 0094 011 4309494/2517037 /2517365, Fax: 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No. MLIFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 17.03.2015
Coordinate E- N - I Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 04 Test No; 04
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
0 50 100 150 200 250 300 350 400 450 500
0.00 r'N. I l I I I I I I I I I I I I
I I I I II ~ ..J. I I I I ' I I I I I I I I I I' r-- I
I :r .... I 1 00 -.J ...
I I .... r-- I I I I
I ~ .... I +- - - -
1' .... l l - I I ! l I .... ~ E 2.00
I ,_1 I I I r-1'..._ E ~ I
~ ,r"'N., I I H--~ I ! I I I .... I' I . ... I I
* I I I I I r""r--. I:
Q)
E I I rt-{... I I I I I r-- r-- I Q) 3.00 3 I I i I I I I I r---~I ' I I I I I r-....,~ Q)
U) I
I I I 1 I I I I
I I~ I I I I i l I 4.00 I I I f-i
I I I I I I . ' I I I I I
5 00 I I I I I
Normal Sress (kN/m2)
/ •{~.b_
Cetified by: ¢ r· T•zj1- . c7?JJM ~
• r~ik · --·...,. . I ENGINEE~Ir4G & LABORATORY SSRVfCES PVT LTD ( ) 62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka. Telephone: 0094 011 4309494/2517037 I 2517365, Fax: 0094 01 2509806, E-Mail : [email protected].
EL~
Period
(min)
PLATE BEARING TEST TEST METHOD NBS 1377: PART 9.:
Test Format No:
Pump Scale
Reading (dlv)
Load (kN)
SECTION 4.1
Normal Stress (kpa)
Revision No.
Cetified by: ----n(_ ... ......... ... . ~
62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Average Settlement
mm
Telephone : 0094 011 4309494/2517037 /2517365, Fax : 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client. Dredg.ng International (Pvt) Ltd Job No. MUFT/1022
ProJect Geotechnical Investigation at Hulumale Phase II Date of test 18.03.2015
Coordtnate E - N. Elevation (m) 1.8m Date of Report 24.03.2015
Location REC05 Test No: 05
TEST DATA Plate size 0.300 m Area of Plate 0.071 m'
Maintained Pump Dial Reading_ Settlement (mm} Average Scale Load
Normal Time Period Stress
Reading (kN) (kpa) S1 S2 S3 S1 S2 S3 Settlement (min) (div) mm
7.00 0 254 10.71 152 41.70 45.59 45.65 3.30 4.41 4.35 4.02
1 41.70 45.63 45.69 3.30 4.37 4.31 3.99
2 41.70 45.63 45.69 3.30 4.37 4.31 3.99
5 41.70 45.63 45.69 3.30 4.37 4.31 3.99
10 41.70 45.63 45.69 3.30 4.37 4.31 3.99 7 10 0 0 0 0 42.60 46.72 46.46 2.40 3.28 3.54 3.07
1 42.61 46.86 46.59 2.39 3.14 3.41 2.98
2 42.61 46.86 46.59 2.39 3.14 3.41 2.98
5 42.61 46.86 46.59 2.39 3.14 341 2.98
10 42.61 46.86 46.59 2.39 3.14 3.41 2.98
-Tested~~ CheJet y:
Cetlfied by: ~ ~] [(" ""' " '~ ........... .. , .. ... ........ .... ~j ......... - ' ENGINE~NG & LABORATORN;I5RVICES (PVT) LTD ·'
62/3, Neelammahara Road, Katuwawata, Boralesgamuwa, Sn Lanka. Telephone ·: 0094 011 4309494/2517037 /2517365, Fax: 0094 01 2509806, E-Mail: [email protected].
EL$ PLATE BEARING TEST Test Format No: ELS-ML-50 TEST METHOD - BS 1377: PART 9:
SECTION 4.1 Rev ision No. 00
PROJECT DATA
Clfent: Dredging International (Pvt) ltd Job No. MUFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 18.03.2015
Coordinate E- N - !Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC05 Test No: 05
TEST DATA
Plate size 0.300 m Area of Plate 0 .071 m2
0 50 100 150 200 250 300 350 400 450 500
000 ~ .
1 00 1- - 1· -' --
2.00 '- -I- '
3.00 ~looo.lt I
4 00 . -5 00 '-1 I
-t . . . - : -- \- . - -- . .
~ - . ' -· -1- -E 6.00 ' E I - 7.00 - ' I --' .. . c r-+-- . !
4> 8.00 t- ' i E ,__ . f=1=
. "-1 . . . 4> 9.00 ~i:"-
. . E ' ~·
. -. . 4> T t =r-'-1:: -· -(/) 10.00 . .
t- -+ l i . 11 ,00 --=l-
. . -l • ' I . -r--•- I . ' .
12 00 .• . . . . ' . -. r--·- . .....,
13.00 . 1--1 -
14.00 l==l=. I , . . - -r-1500 . Normal Sress (kN/m2 )
. -, .... ..,
Tested,. '1-;-,L _ Chec~ by: Cetified by·¢ ~~~ 1/ ~~ ):?
1 ~tt~ / (( ENGlf\J'EER ttG-ac LA BORA TORY~CES (PVT) l TO 62/3, Neela~mahara Road, Katuwawala, Boralesgamuwa, Sri Lanka. Telephone : 0094 011 4309494/ 2517037 I 2517365, Fax: 0094 01 2509806, E-Mall: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS·ML-50
TEST METHOD~ BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No. ML/FT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 18.03.2015
Coordinate E- N. Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 06 Test No: 06
TEST DATA Plate size 0.300 m Area of Plate 0.071 m2
Maintained Pump Dial Reading Settlement (mm) Average Penod Scale Load
Normal 6 1 82 S3 S1 S2 S3 Settlement Time
Reading (kN) Stress
(min) (kpa) (div) mm
Loading
15.00 0 0 0 0 50.00 45.00 50.00 0.00 0.00 0.00 0.00
0 152.8 6.47 92. 44.61 44.05 49.65 5.39 0.95 0.35 2.23
1 49.59 44.02 49.63 0.41 0.98 0.37 0.59
2 49,58 44.02 49.63 0.42 0.98 0.37 0.59
5 49.57 44.01 49.62 0.43 0.99 0.38 0.60
10 49.56 44.01 49.62 0.44 0.99 0.38 0.60
15.10 0 305.6 12.85 182 49.29 43.63 49.29 0.71 1.37 0.71 0.93
1 49.27 43.60 49.27 0.73 1.40 0.73 0.95
2 49.27 43.59 49.26 0.73 1.41 0.74 0.96
5 49.25 43.58 49.25 0.75 1.42 0.75 0.97
10 49.25 43.59 49.25 0.75 1.42 0.75 0.97
15.20 0 454.4 19.09 270 49.03 73.31 48.98 0.97 -28.31 1.02 -8.77
1 49.00 43.27 48.95 1.00 1.73 1.05 1.26
2 48.99 43.26 48.94 i.£:)1 1.74 1.06 1.27
5 48.97 43.23 48.91 1.03 1.77 1.09 1.30
10 48.96 43.20 48.98 1.04 1.80 1.02 1.29
15.30 0 611.2 25.63 363 48.97 73.01 48.69 1.03 -28.01 1.31 -8.56
1 48.76 42.97 48.65 1.24 2.03 1.35 1.54
2 48.75 42.95 48.64 1.25 2.05 1.36 1.55
5 48.73 42.92 48.61 1.27 2.08 1.39 1.58
10 48.70 42.90 48.59 1.30 2.10 1.41 1.60
15.40 0 764.0 31.98 452 48.57 42.69 48.42 1.43 (~~2.3~ ·1.58 1.77
1 48.53 42.67 46.40 1.47 ··.2.33 1.6~ 1.80
2 48.52 42.64 48.38 1.48 2.36 1.62 ;,, 1.82
5 48.50 42.60 48.35 1.50 2.40 1.65 1.85
10 48.48 42.58 48.33 1.52 2.42 1.67 1.87
Unloading
15.50 0 509.0 21.39 303 48.53 42.59 48.37 1.47 2.41 1.63 1.84
1 48.53 42.59 48.37 1.47 2.41 1.63 1.84
2 48.53 42.59 48.37 1.47 2.41 1.63 1.84
5 48.53 42.59 48.37 1.47 2.41 1.63 1.84
10 48.53 42.59 48.37 1.47 2.41 1.63 1.84 ...
Tested~ Checked by: Cetified by:_¢ ~
'!<~-~-----~
-·-··L1t · rtt ·. . .. ····· · ····· ···· ··· .. . .....---ENGINEERING & LABORATORYSERVICES (PVT) LTD
62/3, Neelammanara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone: 0094 011 4309494/2517037/2517365. Fax: 0094 01 2509806, E-Mail : [email protected].
I
El~ PLATE BEARING TEST
TEST METHOD- BS 1377: PART 9: Test Format No: ELS-ML-50
SECTION 4.1 Revision No. 00 PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No.
Project: Geotechnical Investigation at Hulumale Phase II Date of test
Coordinate E - N- I Elevation (m) 1 .8 m Date of Report
Location REC 06
TEST DATA Plate size
Maintained
Time Period
(min)
16.00 0
0.300 m Pump Scale Load
Reading (kN) {div)
Test No:
Area of Plate 0.071 m:.: Dial Reading Settlement (mm) Normal 1--_..;;...:.r.:-.:....;..::...::...:,;.;.;_..__+--__::...=,.:.:~.;..;;;...;~~~--1
Stress (kpa) S1 S2 S3 S1 S2 S3
MUFT/1022
18.03.2015
24.03.2015
06
Average
Settlement mm
1 ~:2~ ~Q · .. - . ~:m
2 ,5
10 16.10 0 0 0 49.18 43.53 48.99 0.82 1.47 1.01
1 49.18 43.53 48.99 0.82 1.47 1.01
2 49.18 43.53 48.99 0.82 1.47 1.01
5 49.19 43.53 49.00 0.81 1.47 1.00 10 49.19 43.53 49.00 0.81 1.47 1.00
Tested);Jr{'{ L_ __ Che:ace by:
..... L::Ji~J.J/L "(~· .)~~ -~-~--- \ ~
Cetified by:-4 ... ... ........ ~
~NGINEE'RING & LABORATORY SERVICES (PVT) LTD 62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
1.10
1.10
1.10
1.09
1.09
Telephone : 0094 011 4309494/ 2517037/2517365, Fax : 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD - BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client Dredging International (Pvt) Ltd Job No. MUFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 18.03.201 5
Coordinate E- N- I Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC06 Test No: 06
TEST DATA
Plate size 0.300 m Area of Plate 0.071 mz
0 50 100 150 200 250 300 350 400 450 500
0.00 [...J.... ! I j I I I
r-t-- I I I I I I IJ" r-r-~ I I , I I I I ~
r-r-~- I I I 1 00 ~ -l. l
- - I I -t-r-- I I I
-H-t-~- I ' I ..,.... :-- I I I I I I r-r-... r-~~-' I I I I
r-r-... • 2.00 I I I - i l I ' E E I I I ~ I I I .... 3.00 c: -f-Gl
I I I E Gl
I r E I I Gl I I I I I I I (/) 4.00 I I I I I I , I
I I J I I i I j I I I I I -H- I I --r-r--r·-r --+ I~~~ ~ I L I J ! I I I I I I I I I
5.00 ·-rrr H 1 1 1 I '
I I ' I I I I I I l I I -f I I . -r-t-r-r 1 1 I I I I I I I i I I I I I I I
I ! I I I I I i --t-r I I I I I !
I I I I I I I 6.00
Normal Sress (kN/m2 )
-A
~,,~-
Tes~ :-;;£ Chr~ Cetified by::;;;;t;;:.._ "'{djP, ;1~
~= "' ~ ENGINE~~ lNG & LABORATORY SER-VICES (PVT) L TO 62/3, Neerammahara Road, Katuwawala. Boralesgamuwa, Sn Lanka. Telephone : 0094 011 4309494/2517037 / 2517365, Fax: 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No. ML/FT/1022
ProJect: Geotechnical Investigation at Hulumale Phase Jl Date of test 18.03.2015
Coord mate E. N- Elevation (m) 1.8m Date of Report 24.03.2015
Locat1on REC07 Test No: 07
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
Maintained Pump Dial Reading Settlement (mm) Average Period Scale Load Normal s 1 S2 S3 S1 S2 S3 Settlement
Time Reading (kN)
Stress
(min) (kpa) (div) mm
Loading
1'1.30 0 0 0 0 50.00 45.00 50.00 0.00 ·0.00 0.00 0.00 0 152.8 6.47 92 49.63 44.71 49.75 0.17 0.29 G.25 0.24
1 49.82 44.70 49.75 0.18 0.30 0.25 0.24
2 49.82 44 .68 49.73 0.~8 0.32 0.27 0.26'
5 49.82 44.67 49.73 0.18 0.33 0.27 0.26 -10 49..81 44.65 49.72 0.19 0.35 0.28 0.27
11.40 0 305.6 12.85 182 49.66 44.46 49.54 0.34 0,54 0.46 0.45
1 49.65 44.40 49.49 0.35 0.60 0.51 0.49
2 49.65 44.40 49.49 0.35 0.60 0.51 0.49
5 49.62 44.38 49.48 0.38 0.62 0.52 0.51
10 49.58 44.37 49.48 0.42 0.63 0.52 0.52 11.50 0 454.4 19.09 270 49.39 44.25 49.27 0.61 0.75 Q.73 0.70
1 49.36 44.20 49.22 0.64 0.80 0.78 0.74
2 49.34 44.19 49.22 0.66 0.81 0.78 0.75
5 - 49.33 44.17 49.20 0.67 0.83 0.80 0.77 10 49.29 44.14 49.18 0.71 0.86 0.82 0.80
'12 .00 0 611.2 25.63 363 49.14 44.00 48.98 0.86 1.00 1.02 0.96
1 49.10 43.96 48.95 0.90 1.04 1.05 1.00
2 49.07 43.95 48.93 0.93 1.05 1.07 1.02
5 49.04 43.94 48.92 0.96 1.06 1.08 1.03
10 49.01 43.93 48.92 0.99 1.07 1.08 1.05 12.10 0 764.0 31.98 452 48.88 43.78 48.76 1.12 1.22 1.24 <11
I'" 1.1iij¥\i k··
1 48.86 43.73 48.73 1.14 1.27 1.27 1.23'l9-·
2 48.85 43.72 48.72 1.15 1.28 1.28 ~ ~ 1.24
5 48.84 43.68 48.69 1.16 1.32 1.31 1.26"'
10 48.80 43.62 48.65 1.20 • 1.38 1.35 {31
Unloadinq
12 .20 0 509.0 21.39 303 48.83 43.68 48.74 1.17 1.32 1.26 1.25
1 48,83 43.68 48.74 1.17 1.32 1.26 1,25
2 48.83 43.68 48.74 1.17 1.32 1.26 1.25
5 48.83 43.68 48.74 1.17 1.32 1.26 1.25 10 48.83 43.68 48.74 1.17 1.32 1.26 1.25
Cetified by:¢.
~,,
Tested ~_j~L ~
Checked by: .--:;
... r.JJ.u--.... {{5[':[!~ ~ c __ ......... ~ .... .. .. ... t
ENGINE ·,RING & LABORATORY SEBVfC'ES-(PVT) L TO ,., 62/3, Nee'lammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone: 0094 011 4309494/2517037 /2517365. Fax: 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT OAT A
Client· Dredging International (Pvt) Ltd Job No. MLJFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 18.03.2015
Coordinate E - N - Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 07 Test No: 07
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
Maintained Pump Dial Reading Settlement (mm) Average
Scale Load Normal
Time Period Stress Reading (kN} (kpa) S1 S2 S3 S1 S2 S3 Settlement
(min) (d [v) mm
Unloadmg
12.20 0 509.0 21 .39 303 48.83 43.68 48.74 1.17 1.32 1.26 1.25
1 48.83 43.68 48.74 1.17 1.32 1.26 1.25
2 48.83 43.68 48.74 1.17 1.32 1.26 1.25
5 48.83 43.68 48.74 1.17 1.32 1.26 1.25
10 48.83 43.68 48.74 117 1.32 1.26 1.25
12.30 0 254.0 10.71 152 49.04 43.76 48.73 0.96 1.24 1.27 1.16
1 49.02 43.81 48.92 0.98 1.19 1.08 1.08
2 49.01 43.81 48.97 0.99 1.19 1.03 1.07
5 49.01 43.81 48.97 0.99 1.19 1.03 1.07
10 49.01 43.81 48.97 0.99 1.19 1.03 1.07
12.40 0 0.0 0 0 49.53 44.47 49.71 0.47 0.53 0.29 0.43
1 49.55 44.47 49.71 0.45 0.53 0.29 0.42
2 49.55 44.47 49.72 0.45 0.53 0.28 0.42
5 49.55 44.47 49.72 0.45 0.53 0.28 0.42
10 49.55 44.47 49.72 0.45 0.53 0.28 0.42
.
d-~
Teste~ Cl)ecl<ed by: Cetified by:
--··i·~~ ... .... JL~ .....-: .... -. ~ ... *. 0 •••• ' ••••• 0 •••
·,
ENGINE~RING & LABORATORY SERVICES (PVT) L TO 62/3, Neelammahara Road, Katuwawafa. Boralesgamuwa, Sri Lanka. Telephone : 0094 011 4309494/2517037 / 2517365, Fax: 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD · BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client. Dredging International (Pvt) ltd Job No. MLIFT/1022
Project· Geotechnical Investigation at Hulumale Phase II Date of test 18.03.2015
Coordinate E - N - Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 07 Test No: 07
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
0 $0 100 150 200 250 300 350 400 450 500
000 ' I [ ! - I I I I I r I I
~ -1.00 --r--foo
I -· . I I I I I r1 I l 1--~ ~~-- i I + l I I I I I
2.00 I I - i I I I E -E rl·' -1- I I I I ~ r-,- - t-
~ I ..... 3.00 T I I I c: I (1)
I I I I I - I I l E I I ' (I)
-h I I I I I I I I 'E (I) I I I I (/) 4.00
I I I l I I I I
1 f-~ - I ' I
t-- - T I I 5.00 i I
t-- ' I I I
6.00 I
Normal Sress (kN/m2)
'"" . ·<
Teste?,bf/-z:L ~~~
Checked by: Cetified by:¢ ~
·-~r. L./1. ( ~~# -ENGINEGAJNG & LABORATORY SERVICES (PVT) LTD 62/3, Neelammahara Road. Katuwawala, Boralesgamuwa, Sri Lanka. Telephone : 0094 011 4309494/2517037 /2517365, Fax : 0094 01 2509806, E-Mail : [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD· BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client: Dredging International (Pvt) Ltd Job No. MUFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 19.03.2015
Coordinate E- N- Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC08 Test No: 08 TEST DATA
Plate size 0.300 m Area of Plate 0.071 m;l
Maintained Pump Dial Reading Settlement (mm) Average Period Scale Load
Normal s 1 S2 S3 S1 S2 S3 Settlement Time
Reading (kN) Stress
(min) (kpa) (diV) mm
Loading
16.40 0 o· 0 0 50.00 45.00 50.00 0.00 0.00 0.00 0.00
0 152.8 6.47 92 48.75 43.32 48.34 1.25 1.68 1.66 1.53
1 48.65 43.21 4.8.24 1.35 1.79 1.76 1.63
~ 48.63 43.20 48.22 1.37 1.80 1.78 1.65
5 48.56 43.10 48.13 1.44 1.90 1.87 1.74
10 48.53 43.06 48.09 1.47 1.94 1.91 1.77
16.50 0 305.4 12.85 182 48.12 42.52 47.58 1.88 2.48 2.42 2.26
1 47.97 42.37 47.44 2.03 2.63 2.56 2.41
2 47.93 42.32 47.40 2.07 2.68 2.60 2.45
5 47.87 42.25 47.34 2.13 2.75 2.66 2.51
10 47.81 42.19 47.27 2.19 2.81 2.73 2.58
17.00 0 458.4 23.43 . 331 47.41 41.60 46.78 2.59 ~3.4611. 3.22 3.07
1 4726 41.42 46.61 2.74 ~.58 ,.3.39 3.24
2 47.20 41.33 46.53 2.80 3.67 3.47 3.31
5 ~ 47.10 41.21 46.52 2.90 3.79 3148 3.39
10 47.02 41.12 46.33 2.98 3.88 3.67 3.51
17 10 0 611.2 25.63 363 46.74 40.57 45.96 3.26 4.43 4.04 3.91
1 46.58 40.34 45.78 3.42 4.66 4.22 4.10
2 46.55 40.29 45.74 3.45 4.71 4.26 4.14
5 46.45 40.15 45.61 3.55 4.85 4.39 4.26
10 46.33 40.04 45.50 3.67 4.96 4.50 4.38
17.20 0 764.0 31.98 4-52 45.94 39.14 45.00 4.06 5.86 5.00 4.91
1 45.85 38.99 44.87 4.15 6.01 5.13 5.10
2 45.72 .38.82 44.74 4.28 6.18 5.26 5.24
5 45.66 38.60 44.60 4.34 6.40 5.40 5.38
10 45.48 38.50 44.45 4.52 6.50 5.55 5.52
Unloading
17.30 0 509.0 21.39 303 45.48 38.51 44.50 4.52 6.49 5.50 5.50
1 45.48 38.51 44.50 4.52 6.49 5.50 5.50
- 2 45.48 38.51 44.50 4.52 6.49 5.50 5.50
5 45.48 38.51 44.50 4.52 6.49 5.50 5.50 10 45.48 38.51 44.50 4.52 6.49 5.50 5.50
~
Cetified by:¢. ~
Tes~L Checked by: ~
-~~· : .. -~-- ·r ·lJ~~ •···· · · ···· ··· · ··· ···
E"NGUQEERING & LABORATORY $1:RVICES PVT L TO
62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Telephone: 0094 011 4309494/2517037 /2517365. Fax: 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- 85 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client Dredging International (Pvt) Ltd Job No. MUFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 19.03.2015
Coordinate E- N- Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC08 Test No: 08 TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
Maintained Pump Dial Reading Settlement (mm) Average
Scale Load Normal
Time Period Stress Reading (kN) (kpa) S1 S2 S3 S1 S2 S3 Settlement
(min) (div) mm
Unloading
17.30 0 509.0 21.39 303 45.48 38.51 44.50 4.52 6.49 5.50 5.50
1 45.48 38.51 44.50 4.52 6.49 5.50 5.50
2 45.48 38.51 44.50 4.52 6.49 5.50 5.50
5 45.48 38.51 44.50 4.52 6.49 5.50 5.50
10 45.48 38.51 44.50 4.52 6.49 5.50 5.50
17.40 0 254.{) 1CH fBa ~$ :sa·. 76 44.66 -4:38 6.24 5.34 -5.32 1 -- ~5.63 ~.76 44.66 4.31 6.24 5.3~ 5..S2 -2 - 45.63 -~8.76 44.66 '4 .37 6.24 5.~ '5.32 5 ~~~3 ·aa·.7e -
-- ~ 44.{)6 4.37' 6.24 5.34 5.32
-10 - '~- -.-r~3 . 3S:.76 ·A4:66 4~1 6.24 5.34' 5.32 -
17.50 0 0.0 0 0 46.62 39.83 45.70 3.38 5.17 4.30 4.28
1 46.64 39.84 45.72 3.36 5.16 4.28 4.27
2 46.64 39.85 45.72 3.36 5.15 4.28 4.26
5 46.66 39.85 45.73 3.34 5.15 4.27 4.25
10 46.67 39.85 45.74 3.33 5.15 4.26 4.25
. .
Tes~~ .. / 4--·:...
Ch·;rby Cetified by: ---} ··-~· ~ri .... , .. ~£A~ ~ ...... ·· ········ ········ ···
(.___ IT,.... ~>· - ..;.~
~-NGINEfRING & LABORATORY'SERVICES (PVT) L TO 62/3, Neelammahara Road, Katuwawala. Boralesgamuwa. Sri Lanka. Telephone: 0094 011 4309494/2517037 /2517365, Fax : 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST
TEST METHOD- BS 1377: PART 9: Test Format No: ELS-ML-50
SECTION 4.1 PROJECT DATA
Client. Dredging International (Pvt) Ltd
Project Geotechnical Investigation at Hulumale Phase II
Coordmate E • N • I Elevation (m)
Location REC 08 TEST DATA
Plate size 0.300 m
000
200
300
0
4 00 l-r-
5.00 ~t
6 DO 7.00
50
E 8.00 1=--~
~ 900
- 10 00 c: (I)
E Cl)
E Cl) VI
1100
1:2 00
13.00 .....:
1400 ·==-~
15.00 .-=f :-::c........... 16 00 -i='
17 00 -....:........:== 18.00 19.00 . -'-i-·-1-'- -'--
20 00
100
Area of Plate
150 200 250
=
Normal Sress (kN/m2)
ENGINE~ING & LABORATORY Sf:RV'ICES (PVT) L TO
300
62/3, Neelammahara Road, Katuwawala. Boralesgamuwa, Sri Lanka.
Revision No. 00
Job No. MUFT/1022
Date of test 19.03.2015
1.8 m Date of Report 24.03.2015 Test No: 08
350 400 450 500
-·-
Cetified by:~
Telephone : 0094 011 4309494/2517037 I 2517365, Fax : 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST
TEST METHOD- BS 1377: PART 9:
Maintained Pump Period Scale
Reading (min) (div)
Load (kN)
Normal Stress (kpa)
Checked by:
4.1
mmahara Road, Katuwawala, Boralesgamuwa, Sri Lanka.
Test Format No:
Revision No.
Average Settlement
mm
Telephone: 0094 011 4309494/2517037/2517365, Fax: 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT OAT A
Client. Dredging International (Pvt) Ltd Job No. ML/FT/1022
ProJect: Geotechnical Investigation at Hulumale Phase II Date of test 19.03.2015
Coordinate E- N - Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC09 Test No: 09 TEST DATA
Plate size 0.300 m Area of Plate 0.071 m' Maintained Pump Dial Reading Settlement(mm} Average
Scale Load Normal
Time Penod Stress Reading (kN) (kpa) S1 S2 S3 S1 S2 S3 Settlement
(min) (div) mm 15.40 0 254.0 10.71 152 46.35 41.75 46.54 3.65 3.25 3.46 3.45
1 46.35 41.75 46.55 3.65 3.25 3.45 3.45
2 46.35 41.75 46.55 3.65 3.25 3.45 3.45
5 46.36 41.75 46.56 3.64 3.25 3.44 3.44 10 46.36 41.75 46.57 3.64 3.25 3.43 3.44
15.50 0 0.0 0 0 46.81 42.51 46.93 3.19 2.49 3.07 2.92
1 46.81 42.52 46.94 3.19 2,48 3.06 2.91
2 46.81 42.52 46.94 3.19 2.48 3.06 2.91
5 46.81 42.52 46.94 3.19 2.48 3.06 2.91
10 46.81 42.52 46.94 3.19 2.48 3.06 2.91
....
¢-'IJ~
Tested~ Chec~ed by: Cetified by: -:o f'::tt) J. ~. / ........ ~ ... . • • • •• • • ~ ~ •• 4 ..........
1! I
ENGINEERING & LABORATORY SERVICES PVT l TO ( ) 62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri lanka. Telephone : 0094 011 4309494/2517037 / 251 7365, Fax: 0094 01 2509806, E-Matl : [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT OAT A
Client: Dredging International (Pvt) ltd Job No. MUFT/1022
Project: Geotechnical Investigation at Hulumale Phase II Date of test 19.03.2015
Coordinate E- N- I Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC09 Test No: 09 TEST DATA
Plate size 0.300 m Area of Plate 0.071 m2
0 50 100 150 200 250 300 350 400 450 500
0.00 kt± f-J_ f-1 I I ' I I
~ 1.00 I r-,.._
I I ' r-- I I I I I ,.....
! I f-j_l r--- I
H-~- - r- r r---2.00 I I I I ,..... I I I I - I I ' I I r-,.._!o.. I E I E ' I IJI N.. - I l ' I I I r--- ,.., I - 3.00 N-- J....l_ I I , ,..... c ' Cl> I I r-~oo. I I I ~"'-~ E I I : Cl> I I i
,..... E Cl> I I ' I I i'-.. I t/) 4.00 I ! i- -
I I i I I
I : ri I
.=H-+=!- I I I I 5.00 f-l-1--1
I I I I I I ' ' I I I
t-1-! i I I I I I i I I I I I i I I I I
6.00 -~-ri ' I I I I I I I I I
Normal Sress (kN/m2 )
.
' Tested~H- Checked by: Cetified by: ~ ( -:tt,~~AA. ~ ~~ . . //...-
:.-;'~~
~NGINEE~IJQG & LABORATORY S5f3YJCES (PVT) LTD 62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka. Telephone: 0094 011 4309494/2517037/2517365, Fax: 0094 01 2509806, E-Mail : [email protected].
EL~
Period
(min)
PLATE BEARING TEST 'TEST METHOD- BS 1377: PART 9:
Pump Scale
Reading (div)
Load (kN)
Normal Stress (kpa)
4.1
Test Format No:
Revision No.
Cetified by: ~
62/3, Neelammahara Road, Katuwawala, Boralesgamuwa, Sri Lanka. Telephone: 0094 011 4309494/2517037/2517365, Fax : 0094 01 2509806, EHMail: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT OAT A
Client Dredging International (Pvt) Ltd Job No. ML/FT/1022
Prot eel Geotechnical Investigation at Hulumale Phase II Date of test 19.03.2015
Coordinate E - N· Elevation (m) 1.8 m Date of Repo1i 24.03.2015
Locat1on REC 10 Test No: 10
TEST DATA Plate size 0.300 m Area of Plate 0.071 m.:
Maintained Pump Dial Reading Settlement (mm) Average
Scale Load Normal
T1me Period Stress Reading. (kNJ (kpa) S1 S2 S3 S1 S2 S3 Settlement
(m in) (div) mm Unloadmg
9 .30 0 509.0 21.39 303 48.08 42.06 47.19 1.92 2.94 2.81 2.56
1 48.08 42.06 47.19 1.92 2.94 2.81 2.56
2 48.08 42.06 47.19 1.92 2.94 2.81 2.56
5 48.08 42.06 47.19 1.92 2.94 2.81 2.56
10 48.08 42.06 47.19 1.92 2.94 2.81 2.56
9.40 0 254.0 10.71 152 48.36 42.16 47.52 1.64 2.84 2.48 2.32
1 48.36 42.16 47.52 1.64 2.84 2.48 2.32
2 48.36 42.16 47.52 1.64 2.84 2.48 2.32
5 48.36 4216 47.52 1.64 2.84 2.46 2.32
10 48.36 42.16 47.52 1.64 2.84 2.48 2.32
9.50 0 0.0 0 0 49.02 42.96 48.20 0.98 2.04 1.80 1.61
1 49.02 42.97 48.21 0.98 2.03 1.79 1.60
2 49.02 42.97 48.22 0.98 2.03 1.78 1.60
5 49.03 43.02 48.25 0.97 1.98 1.75 1.57
10 49.03 43.04 48 .25 0.97 1.96 1.75 1.56
-
Testedbf.~~ Checked by· Cetiffed by: ¢- 'I:( 1,'
. ; . ~~---:::- ; .... ,(~-tti . p, . ... .... .. .. , ............. . -- -p: -
ENGINEERING & LABORATORY SERVICES (PVT) L TO 62/3, Neelammahara Road, Katuwawala, Boralesgamuwa. Sri Lanka. Telephone: 0094 011 4309494/2517037 I 2517365. Fax: 0094 01 2509806, E-Mail: [email protected].
EL~ PLATE BEARING TEST Test Format No: ELS-ML-50
TEST METHOD- BS 1377: PART 9: SECTION 4.1 Revision No. 00
PROJECT DATA
Client Dredging International (Pvt) Ltd Job No. MUFT/1022
Project Geotechnical Investigation at Hulumale Phase II Date of test 19.03.2015
Coordinate E- N- J Elevation (m) 1.8 m Date of Report 24.03.2015
Location REC 10 Test No: 10
TEST DATA
Plate size 0.300 m Area of Plate 0.071 m"
0 50 100 150 200 250 300 350 400 450 500
0.00 hi.. I -H I -l ..,.... .... I I I I I
I ........
~ I I ! I I
1-1- I ........ I I I I 1.00 t
.... _ I-..!. I I I I I
l I ~ l"'i--- I ~I '
,.. .... ~ - 1 I -r-.... I I I I .... I-
2.00 I i""i--- I I I ... r-.. - . - I I I i I I-to-E E I I
' I r"'o
' - I I I L 300 ~ I I I I I I I 4> I I E 2!
~+ I I i T I ~ I I
rn 4 00 '
-~ I I I
I I I I .I I I I
...J.-'- ~ I I ! ~ I I I I -n I I -
5 00 , I l
1-' - I I I I u I
I I ' I I I I l I - -,-
f ; I I I
I I I I I I i I I I I I -r I
600 Normal Sress (kN/m2 )
.
...
Tested,b~i- Che~ Cetified by:
~ ~~':·
I ~-!f!!JI-------- ..,.:1/:!!!JJIJ.-'
ENGINE!~ING & LABORATORY ~~ES (PVT) LTD 6213, Neelammahara Road. Katuwawala, Boralesgamuwa, Srr Lanka. Telephone: 0094 011 4309494/2517037 /2517365, Fax: 0094 01 2509806, E-Mail: [email protected].
Document Title
Revision
5138-CLI-RPT-010 Soil testing on Reclamation 02
Page 45 of 45
Annexure IV Photographs
Pictures: