R TECHNICAL INFORMATION 272 SOUTH EAST Erith (Head Office) Tel: 01322 441165 Fax: 01322 440492 SOUTH WEST Bristol Tel: 0117 966 6333 Fax: 0117 953 3602 MIDLANDS Birmingham Tel: 0121 321 1745 Fax: 0121 355 5320 NORTH Leeds Tel: 0113 2533565 Fax: 0113 253 6373 EASTERN Peterborough Tel: 01733 558485 Fax: 01733 562015 NORTH WEST Manchester Tel: 01204 793111 Fax: 01204 797977 WALES Cardiff Tel: 02920 450044 Fax: 02920 464724 NORTH EAST Teesside Tel: 01642 678633 Fax: 01642 674487 TABLE 4E4A Multicore 90 0 C armoured thermosetting insulated cables (Copper Conductors) Current Ratings 7 Ambient temperature : 30°C Ground ambient temperature: 20°C Conductor operating temperature:90°C CURRENT-CARRYING CAPACITY (amperes): Conductor cross- sectional area 1 Reference Method C (clipped direct) Reference Method E (in free air or on a perforated cable tray horizontal or vertical 1 two core cable, single phase a.c. or d.c. 2 1 three- or four- core cable, three-phase a.c. 3 1 two core cable, single phase a.c. or d.c. 4 1 three- or four- core cable, three-phase a.c. 5 (mm²) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 (A) 25 33 44 56 78 99 131 162 197 251 304 353 406 463 546 628 728 (A) 29 39 52 66 90 115 152 188 228 291 354 410 472 539 636 732 847 (A) 23 31 42 53 73 94 124 154 187 238 289 335 386 441 520 599 673 (A) 27 36 49 62 85 110 146 180 219 279 338 392 451 515 607 698 787 Reference Method D (direct in groundor in ducting in ground, in or around buildings) 1 two core cable, single phase a.c. or d.c. 6 1 three- or four- core cable, three-phase a.c. 7 (A) 21 28 36 44 58 75 96 115 135 167 197 223 251 281 324 365 - (A) 25 33 43 53 71 91 116 139 164 203 239 271 306 343 395 446 - NOTES: 1. Where a conductor operates at a temperature exceeding 70°C it must be ascertained that the equipment connected to the conductor is suitable for the conductor operat- ing temperature (see Regulation 512.1.2). 2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceed- ing 70°C, the current ratings given in the equiv- alent table for 70°C ther- moplastic insulated cables (Table 4D4A) must be used (see also Regulation 523.1) VOLTAGE DROP (per ampere per metre) TABLE 4E4B Conductor operating temperature: 90°C Conductor cross- sectional area 1 Two-core cable, d.c. 2 Two-core cable, single-phase a.c. 3 Three- or four-core cable, three-phase a.c. 4 (mm²) 1.5 2.5 4 6 10 16 (mV/A/m) 31 19 12 7.9 4.7 2.9 (mV/A/m) 31 19 12 7.9 4.7 2.9 r x z (mV/A/m) 27 16 10 6.8 4.0 2.5 r x z 25 35 50 70 95 120 150 185 240 300 400 1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.120 1.85 1.35 0.99 0.67 0.50 0.40 0.32 0.26 0.20 0.16 0.13 0.160 0.155 0.155 0.150 0.150 0.145 0.145 0.145 0.140 0.140 0.140 1.90 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.190 1.60 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.175 0.140 0.115 0.140 0.135 0.135 0.130 0.130 0.130 0.125 0.125 0.125 0.120 0.120 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.185 0.165 All tables are reproduced by kind permission of The Institution of Engineering & Technology from IEE Regs, 17th Edition However, it should be noted that in order to apply these tables correctly, reference is required to appendix 4 of the 17th edition of the wiring regualtions which may be obtained from: Institution of Engineering & Technolgy, Michael Faraday House,Six Hills Way, Stevenage, Hertfordshire, ENGLAND, SG1 2AY.

Upload: amir-sultan

Post on 28-Dec-2015

3 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 4e4a

R

TE

CH

NIC

AL

INF

OR

MA

TIO

N

272 SOUTH EAST

Erith (Head Office)

Tel: 01322 441165

Fax: 01322 440492

SOUTH WEST

Bristol

Tel: 0117 966 6333

Fax: 0117 953 3602

MIDLANDS

Birmingham

Tel: 0121 321 1745

Fax: 0121 355 5320

NORTH

Leeds

Tel: 0113 2533565

Fax: 0113 253 6373

EASTERN

Peterborough

Tel : 01733 558485

Fax: 01733 56 2 0 1 5

NORTH WEST

Manchester

Tel: 01204 793111

Fax: 01204 797977

WALES

Cardiff

Tel: 02920 450044

Fax: 02920 464724

NORTH EAST

Teesside

Tel: 01642 678633

Fax: 01642 674487

TABLE 4E4A Multicore 900C armoured thermosetting insulated

cables (Copper Conductors)

Current Ratings

7

Ambient temperature : 30°C

Ground ambient temperature: 20°C

Conductor operating temperature:90°C CURRENT-CARRYING CAPACITY (amperes):

Conductor

cross-

sectional

area

1

Reference Method C

(clipped direct)

Reference Method E

(in free air or on a perforated

cable tray horizontal or vertical

1 two

core cable,

single phase

a.c. or d.c.

2

1 three- or four-

core cable,

three-phase a.c.

3

1 two

core cable,

single phase

a.c. or d.c.

4

1 three- or four-

core cable,

three-phase a.c.

5

(mm²)

1.5

2.546

1016

2535507095

120150185240300

400

(A)

25

3344567899

131162197251304

353406463546628

728

(A)

29

39526690115

152188228291354

410472539636732

847

(A)

23

3142537394

124154187238289

335386441520599

673

(A)

27

36496285110

146180219279338

392451515607698

787

Reference Method D

(direct in groundor in ducting in

ground, in or around buildings)

1 two

core cable,

single phase

a.c. or d.c.

6

1 three- or four-

core cable,

three-phase a.c.

7

(A)

21

2836445875

96115135167197

223251281324365

-

(A)

25

3343537191

116139164203239

271306343395446

-

NOTES:

1. Where a conductor

operates at a temperature

exceeding 70°C it must

be ascertained that the

equipment connected to

the conductor is suitable

for the conductor operat-

ing temperature (see

Regulation 512.1.2).

2. Where cables in this

table are connected to

equipment or accessories

designed to operate at a

temperature not exceed-

ing 70°C, the current

ratings given in the equiv-

alent table for 70°C ther-

moplastic insulated cables

(Table 4D4A) must be

used (see also Regulation

523.1)

VOLTAGE DROP (per ampere per metre) TABLE 4E4B Conductor operating temperature: 90°C

Conductor

cross-

sectional

area

1

Two-core

cable, d.c.

2

Two-core cable,

single-phase a.c.

3

Three- or four-core cable,

three-phase a.c.

4

(mm²)

1.5

2.546

1016

(mV/A/m)

31

19127.94.72.9

(mV/A/m)

31

19127.94.72.9

r x z

(mV/A/m)

27

16106.84.02.5

r x z

25

35

50

70

95

120

150

185

240

300

400

1.85

1.35

0.98

0.67

0.49

0.39

0.31

0.25

0.195

0.155

0.120

1.85

1.35

0.99

0.67

0.50

0.40

0.32

0.26

0.20

0.16

0.13

0.160

0.155

0.155

0.150

0.150

0.145

0.145

0.145

0.140

0.140

0.140

1.90

1.35

1.00

0.69

0.52

0.42

0.35

0.29

0.24

0.21

0.190

1.60

1.15

0.86

0.59

0.43

0.34

0.28

0.22

0.175

0.140

0.115

0.140

0.135

0.135

0.130

0.130

0.130

0.125

0.125

0.125

0.120

0.120

1.65

1.15

0.87

0.60

0.45

0.37

0.30

0.26

0.21

0.185

0.165

All tables are reproduced by kind permission of The Institution of Engineering & Technology from IEE Regs, 17th Edition However, it should be noted that in

order to apply these tables correctly, reference is required to appendix 4 of the 17th edition of the wiring regualtions which may be obtained from: Institution

of Engineering & Technolgy, Michael Faraday House,Six Hills Way, Stevenage, Hertfordshire, ENGLAND, SG1 2AY.