400kv substation training report
DESCRIPTION
in this ppt substation equipment are described.TRANSCRIPT
![Page 1: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/1.jpg)
-Shailendra YadavEE-42(0705420096)
1
![Page 2: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/2.jpg)
INTRODUCTION OF SUBSTATION
It is situated at 26°34’2’’N & 80°32’57’’E coordinates in Dahi Chowki 6.64 km far from Unnao railway station.
Constructed during 1994-98 by CGL.
The whole substation is divided in three parts:132kv switchyard400/220kv switchyard765kv switchyard (Under construction)
2
![Page 3: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/3.jpg)
INCOMING & OUTGOING LINE OF SUBSTATION
•Unnao to Lucknow (400KV & 220KV both separate)•Unnao to Bareily-1 (400KV) •Unnao to Bareily-2 (400KV)•Unnao to Agara (400KV)•Unnao to Panki Kanpur(400KV & 220KV both separate)•Unnao to Anpara (400KV)•Unnao to PGCIL Lucknow-1 (400KV)•Unnao to PGCIL Lucknow-2 (400KV)•One bus bar for 400/220KV 315MVA ICT-1 & ICT-2 line.
3
![Page 4: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/4.jpg)
OUTDOOR EQUIPMENT USED IN SUBSTATION
Two 100MVA 220/132KV transformer Two 315MVA 400/220KV transformer Shunt reactor Capacitor bank SF6 circuit breaker Isolators Lightning arresters Current transformer Capacitor voltage transformer Wave trap Isolators
4
![Page 5: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/5.jpg)
TransformerH.V. side bushing CT
COOLING SYSTEM(ONAN)
ConservaterTank
L.V. side bushing CTs
5
![Page 6: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/6.jpg)
Oil pump
Oil pump is used for circulating oil forcelly.
Radiator plates are used for increasing surface area for natural air cooling.
Radiator plates
Earthing plate
6
![Page 7: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/7.jpg)
we use Cooling fans for forced air cooling of transformer . Total six fans are used for each 100MVA and eight fans are used for each 315 MVA transformer.But all fans never start at same time . It start in pairs .
COOLING FANS
7
![Page 8: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/8.jpg)
Tertiary terminal
Tertiary terminal mostly opened.
The output voltage of tertiary terminal is 11KV in 100MVA transformer and 33KV in 315 MVA transformer
Pressure relief valve box
8
OLTC chamber
![Page 9: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/9.jpg)
9
TERMINALS ON TANK COVER
![Page 10: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/10.jpg)
In these photos we can see fogging near transformer due to operation fire protection system.
10
![Page 11: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/11.jpg)
BUCHHOLZ RELAY
Buchholz relay is a safety device mounted on some oil-filled power transformers and reactors. It is used as a protective device sensitive to the effects of dielectric failure inside the equipment.
11
![Page 12: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/12.jpg)
OTI & WTI
OTI –oil temp. indicator measure temp. of oil filled in transformer. In OTI has two mercury bulb.
WTI- winding temp. indicator measure winding temp of transformer. It has four mercury bulb.
OTI panelWTI panel
mercury bulb
12
![Page 13: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/13.jpg)
CURRENT TRANSFORMER
In electrical engineering, a current transformer (CT) is used for measurement of electric currents. Current transformers, together with voltage transformers (VT) (potential transformers (PT)), are known as instrument transformers. When current in a circuit is too high to directly apply to measuring instruments, a current transformer produces a reduced current accurately proportional to the current in the circuit, which can be conveniently connected to measuring and recording instruments.
13
![Page 14: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/14.jpg)
14
PROTECTION DIAGRAM
![Page 15: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/15.jpg)
A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra high voltage signals and provide low voltage signals either for measurement or to operate a protective relay.The device has at least four terminals, a high-voltage terminal a ground terminal and at least one set of secondary terminals. CVTs are typically single-phase devices
CAPACITOR VOLTAGE TRANSFORMER
15
![Page 16: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/16.jpg)
Cross sectional view of CVT
1 - Primary terminal2 - Cast aluminum bellow housing3 - Stainless steel expansion bellow4 - Compression spring5 - Insulated voltage connection6 - Capacitor elements7 - Insulator (porcelain or composite)8 - Voltage divider tap connection9 - Cast-epoxy bushing10 - HF terminal connection11 - Ferro-resonance suppression device12 - Secondary terminals13 - Oil level sight-glass14 - Aluminum terminal box15 - Intermediate transformer16 - Oil/air block17 - Oil sampling device18 - Compensating reactor19 - Aluminum cover plate
16
![Page 17: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/17.jpg)
1. High Voltage terminal2. Compensation reactor3. Intermediate voltage transformer4. Ground terminal5. Ferro-resonance suppression device6. Damping resistor7. Carrier (HF) terminal (optional)8. Overvoltage protective device9. Secondary terminals10. Link, to be opened for test purposes
PRINCIPLE CIRCUIT DIAGRAM OF CVT
17
![Page 18: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/18.jpg)
CIRCUIT BREAKER
A circuit breaker is an automatically-operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit.In this image we can see a SF6 circuit breaker with double break system.
18
![Page 19: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/19.jpg)
ISOLATORS
An isolators switch are used to completely de-energized an electrical circuit. High-voltage isolation switches are used in electrical substations to allow isolation of apparatus such as circuit breakers and transformers, and transmission lines, for maintenance.
Isolating rod
Earth link rod
19
![Page 20: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/20.jpg)
PANTOGRAPH ISOLATORS
In open state In close state
20
![Page 21: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/21.jpg)
Central rotating double break isolator
21
![Page 22: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/22.jpg)
Wave trap
Wave trap are used in power system for carrier communication. It trap the higher frequency above 50Hz. It is the effort to utilize the same transmission line between two substation for the purpose of communications
22
![Page 23: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/23.jpg)
23
![Page 24: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/24.jpg)
LIGHTNING ARRESTOR
The overvoltage protection is obtained by the use of lightning / surge arresters.Lightning Arresters or Surge Arresters are always connected in Shunt to the equipment to be protected, they provide a low impedance path for the surge current to the ground.Mostly in present days zinc oxide (ZnO) gapless arresters are in use.
24
![Page 25: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/25.jpg)
INTERPOSING C.T.
The interposing CTs are used for Power transformer Differential Protection circuit. In a delta/Star Power transformer, the cts will be connected star and delta formation, for eliminating Zero sequence current on star side. There will be mismatch of secondary current , to maintain equilibrium, interposing Cts will be connected to Delta formed CTs.
25
![Page 26: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/26.jpg)
RELAYS
Differential relay
O/F protection +FFR
Group A trip relay
CB trouble relay
Group B trip relay
DR earth switch relay
O/C protection relays
Breaker failure relay
RES E/F +O/LProtection relay
26
![Page 27: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/27.jpg)
Relay testing boxA outer view of Relay
Relay conti….
27
![Page 28: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/28.jpg)
SHUNT REACTOR
Shunt Reactor is a thyristor controlled high impedance transformer.A stable bus voltage can be maintained by providing variable reactive power based on the bus voltage deviations due to the load variations.
28
![Page 29: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/29.jpg)
SHUNT CAPACITOR BANK
Shunt capacitor banks are used to improve the quality of the electrical supply.provide capacitive reactive compensation.Power factor correction.
29
![Page 30: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/30.jpg)
30
![Page 31: 400kv Substation Training report](https://reader031.vdocuments.mx/reader031/viewer/2022012302/546c2dd7b4af9fa5778b49bb/html5/thumbnails/31.jpg)
31