Performance Evaluation of Microgrids in Occurrence of Intentional Islanding 2013 IEEE PES Conference on Innovative Smart Grid Technologies (ISGT Latin America) Marianna N. Bacelar Tatiana M. L. Assis Glauco N. Taranto COPPE / UFRJ 15 /04/2013

Upload: others

Post on 01-Jun-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Performance Evaluation of Microgrids in Occurrence of 

Intentional Islanding2013 IEEE PES Conference on Innovative Smart Grid Technologies 

(ISGT Latin America)

Marianna N. BacelarTatiana M. L. AssisGlauco N. Taranto

COPPE / UFRJ

15 /04/2013

Page 2: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

AgendaI. Introduction

II. Simulation resultsI. Intentional islandingII. Microgrid survival III. Reconnection

III. Conclusion

Page 3: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Increase in requests for connections of small 

generators in distribution networks: government 

incentives

Possibility of islanding operation with microgrids 

disconnected from the main system

Brazilian grid procedures for distribution networks

I.  Introduction

Page 4: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

II. Study Case

An actual rural feeder in the Rio de Janeiro State 

Two small‐hydro generators(2 x 6,6 MVA)

The DG capacity is able to supply the feeder load: 9,2MWmax

Page 5: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

III. Analysis

Simulation tool: software Simulight with three‐phase 

modeling

Performed analysis:

I. Intentional islandingII. Microgrid survival 

Short‐circuit

Daily load curve

III. Reconnection

Page 6: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

A) Intentional Islanding

Event: 

Three‐phase short‐circuit at bus 49

Consequences:

Protection action 

Microgrid islanding

Is the islanding well‐succeeded???

Page 7: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

A) Intentional Islanding

Islanding feasibilityScenarios:

Unsuccessful islanding: Heavy load and low generation scenario

Well‐succeeded islanding: All other scenarios

Load GenerationHeavy 9,3 MW Hight 9 MWMedium 6,2 MW Intermediate 6 MWLight 3,1 MW Low 3 MW

Page 8: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Frequency at both sides of the coupling circuit breaker

Medium load and Intermediate  generation scenario

Page 9: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Microgrid Voltages

Page 10: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

B) Microgrid Survival Operating in islanded mode

I) Phase to ground short circuit at #292

49

162

Load G

157

Load AP

100

120

292

Load D

127

Microgrid339 13,8 kV

340 25 kV

341265272

Load RC

Load L

238

DG

Page 11: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Measures during the short‐circuit

GD frequency during the short‐circuit

Three phase currents Three phases voltages at the fault point

Microgrid voltages

Page 12: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

B) Microgrid Survival Operating in islanded mode

II) Daily load curve

49

162

Load G

157

Load AP

100

120

292

Load D

127

Microgrid339 13,8 kV

340 25 kV

341265272

Load RC

Load L

238

DG

Page 13: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

GD Power GenerationMicrogrid loads: Active power

Measures  at both sides of the coupling circuit breaker

Capacitor bank on

Capacitor bank off

Page 14: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

C) ReconnectionReconnecting the microgrid to the main grid

I) Forced circuit breaker 

closing

coupling circuit breaker

Page 15: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Measures  at both sides of the coupling circuit breaker

Frequency

Voltage Voltage angle

microgridreconnection

1 s

Page 16: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Torsional effort evaluation during the random reconnection

Page 17: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

C) ReconnectionReconnecting the microgrid to the main grid

II) Synchronism check relay

25

Page 18: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Measures  at both sides of the coupling circuit breakerVoltage Voltage angle

additionalsignal toAVR

microgridreconnection

8,79 s

Page 19: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Torsional effort evaluation during controlled reconnection

Page 20: 4 #372 – Performance Evaluation of Microgrids in ...tarang/Simulight/Slides_ISGTLA_2013_Bacelar.pdf · Performance Evaluation of Microgrids in Occurrence of ... Microsoft PowerPoint

Increase of distributed generationPotential to implement the intentional islandingBenefits for the system

The paper has analyzed a actual microgrid and the results have shown:

Success of islanding depends strongly on the balance of load x generation in microgrid at the time of islandingThe synchronized reconnection is important to avoid prohibitive mechanical stress

III.  Conclusion