39.44 kw dc solar pv...

10
SOLAR MODULE (TYP.) PROJECT SITE SOUTHWEST RESEARCH CENTER 14585 STATE HWY H MT. VERNON, MO 65712 REVISION SHEET NUMBER: PROJ. NO.: 1 2 3 4 5 6 7 8 A B C D E DATE: REVISION NO DRWN DATE CHKD DATE APPVD DATE 1 2 3 4 5 6 7 8 F TITLE SHEET 02/26/18 T-1 0 SOLAR PHOTOVOLTAIC ARRAY 1711-02 SOUTHWEST RESEARCH CENTER 14548 STATE HWY H MT. VERNON, MO 65712 0 PK 02/26/18 SCHEMATIC SET 1 PK 03/21/18 FINAL OWNER REVIEW SET 224 N. 7TH STREET ST. LOUIS, MO 63101 www.microgridenergy.com FINAL OWNER REVIEW SET MARCH 21, 2018 39.44 kW DC SOLAR PV PROJECT PV SYSTEM SUMMARY SYSTEM SIZE DC (kW) 39.44 SYSTEM SIZE AC (kW) 30.0 DC/AC RATIO @PF = 1 MODULE INFORMATION MODULE QUANTITY STRING INFORMATION INVERTER INFORMATION INVERTER QUANTITY INTERCONNECTION VOLTAGE RACKING TYPE/MAKE SYSTEM TILT & AZIMUTH 1.32 GCL-P6/72H 340 116 MODULES 9-10 MODULES PER STRING FRONIUS SYMO 10.0-3 3 SYMO 10.0-3 208V FLUSH-MOUNTED, SNAPNRACK 26.57 DEGREES, 175 DEGREES SHEET INDEX SHEET TITLE SCALE SHEET # T-1 TITLE SHEET VARIES E-1 ELECTRICAL SPECIFICATIONS N.T.S. 1/16" = 1'-0" 1/16" = 1'-0" N.T.S. E-3 ELECTRICAL LABELING PROJECT INFORMATION APPLICABLE CODES T-1 2 SCALE 1" = 1'-0" PROJECT SITE PLAN T-1 1 SCALE N.T.S. AREA MAP 2015 INTERNATIONAL BUILDING CODE (IBC) 2015 INTERNATIONAL PLUMBING CODE (IPC) 2015 INTERNATIONAL MECHANICAL CODE (IMC) 2015 FUEL GAS CODE (IFGC) 2015 INTERNATIONAL FIRE CODE (IFC) 2014 NFPA 70 NATIONAL ELECTRICAL CODE (NEC) 2013 ASHRAE 90.1 ENERGY STANDARD FOR BUILDINGS E-2 ONE-LINE DIAGRAM ELECTRICAL SITE PLAN E-4 N.T.S. DATA SHEETS E-5 ELECTRICAL ELEVATION DETAILS ARRAY RACKING PLAN - PARTIAL ROOF ELECTRICAL SCHEDULES & CALCS. E-6 E-7 E-8 DATA SHEETS E-9 N.T.S. N.T.S. N.T.S. N.T.S.

Upload: others

Post on 15-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

SOLAR

MODULE

(TYP.)

PROJECT SITE

SOUTHWEST RESEARCH CENTER

14585 STATE HWY H

MT. VERNON, MO 65712

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

TIT

LE

S

HE

ET

02/26/18

T-1

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HWY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

FINAL OWNER REVIEW SET

MARCH 21, 2018

39.44 kW DC SOLAR PV PROJECT

PV SYSTEM SUMMARY

SYSTEM SIZE DC (kW)39.44

SYSTEM SIZE AC (kW)30.0

DC/AC RATIO @PF = 1

MODULE INFORMATION

MODULE QUANTITY

STRING INFORMATION

INVERTER INFORMATION

INVERTER QUANTITY

INTERCONNECTION VOLTAGE

RACKING TYPE/MAKE

SYSTEM TILT & AZIMUTH

1.32

GCL-P6/72H 340

116 MODULES

9-10 MODULES PER STRING

FRONIUS SYMO 10.0-3

3 SYMO 10.0-3

208V

FLUSH-MOUNTED, SNAPNRACK

26.57 DEGREES, 175 DEGREES

SHEET INDEX

SHEET TITLE SCALESHEET #

T-1 TITLE SHEET VARIES

E-1 ELECTRICAL SPECIFICATIONS N.T.S.

1/16" = 1'-0"

1/16" = 1'-0"

N.T.S.

E-3

ELECTRICAL LABELING

PROJECT INFORMATION

APPLICABLE CODES

T-1

2

SCALE

1" = 1'-0"

PROJECT SITE PLAN

T-1

1

SCALE

N.T.S.

AREA MAP

2015 INTERNATIONAL BUILDING CODE (IBC)

2015 INTERNATIONAL PLUMBING CODE (IPC)

2015 INTERNATIONAL MECHANICAL CODE (IMC)

2015 FUEL GAS CODE (IFGC)

2015 INTERNATIONAL FIRE CODE (IFC)

2014 NFPA 70 NATIONAL ELECTRICAL CODE (NEC)

2013 ASHRAE 90.1 ENERGY STANDARD FOR BUILDINGS

E-2

ONE-LINE DIAGRAM

ELECTRICAL SITE PLAN

E-4

N.T.S.

DATA SHEETS

E-5ELECTRICAL ELEVATION DETAILS

ARRAY RACKING PLAN - PARTIAL ROOF

ELECTRICAL SCHEDULES & CALCS.E-6

E-7

E-8

DATA SHEETSE-9

N.T.S.

N.T.S.

N.T.S.

N.T.S.

AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
Page 2: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

SECTION 10 05 00 RACEWAYS AND BOXES

SECTION 10 07 00 - PANELBOARDS

A. ALL ELECTRICAL WORK SHALL COMPLY WITH ALL APPLICABLE CITY, COUNTY, STATE, AND SERVING ELECTRICAL UTILITY CODES,ORDINANCES, RULES, AND REGULATIONS.

B. ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF NEW RACEWAYS AND EQUIPMENT SHALL BE THE RESPONSIBILITYOF THE ELECTRICAL CONTRACTOR. ALL WORK SHALL BE PERFORMED BY A TRADESMAN EXPERIENCED IN THE WORK REQUIRED.ALL FINISHES SHALL MATCH EXISTING ADJACENT FINISHES. PATCH ALL OPENINGS IN FIRE RATED WALLS IN A MANNERMAINTAINING THE ORIGINAL FIRE AND SMOKE RATINGS.

C. THE TERM "PROVIDE" MEANS "TO FURNISH NEW AND INSTALL, READY FOR THE INTENDED USE AND IN COMPLETE OPERATINGCONDITION."

D. COORDINATE ELECTRICAL SERVICE CONNECTIONS TO COMPONENTS FURNISHED BY UTILITY COMPANIES AND FURNISHED BY THECONTRACTOR THAT REQUIRE UTILITY COMPANY APPROVAL.

E. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF EQUIPMENT. MANY OFFSETS, BENDS, PULLBOXES, SPECIAL FITTINGS, ETC. WILL BE REQUIRED WHICH ARE NOT INDICATED. CAREFULLY STUDY DRAWINGS AND PREMISES INORDER TO DETERMINE BEST METHODS, EXACT LOCATIONS, CONDUIT ROUTES, BUILDING OBSTRUCTIONS, ETC., TO INSTALLAPPARATUS AND EQUIPMENT. INSTALL APPARATUS AND EQUIPMENT IN MANNER AND LOCATIONS TO AVOID OBSTRUCTIONS,PRESERVE HEADROOM, AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.

F. FURNISH ALL MATERIALS, TOOLS, AND LABOR AND PAY ALL PERMITS AND FEES REQUIRED FOR THE ELECTRICAL INSTALLATIONUNLESS OTHERWISE NOTED ON PLANS. ALL PERMITS AND INSPECTIONS SHALL BE PROVIDED AS REQUIRED BY THE LOCAL CODEAUTHORITY.

A. COPPER & ALUMINUM CONDUCTORS: COMPLY WITH NEMA WC 70.

B. ALUMINUM ALLOY CONDUCTORS: PROVIDE COMPACT STRANDED ALUMINUM ALLOY CONDUCTORS TYPICAL OF ALCAN STABILOY®(AA-8030) OR OF A RECOGNIZED 8000 SERIES ALUMINUM ALLOY CONDUCTOR MATERIAL BY THE ALUMINUM ASSOCIATION AND U.L.LISTED AND LABELED.

C. CONDUCTOR INSULATION: COMPLY WITH NEMA WC 70 FOR TYPES AS SHOWN ON DOCUMENTS.

D. AC FEEDERS: STRANDED. MATERIAL AS SHOWN ON DOCUMENTS.a. DC PV SOURCE CONDUCTORS: COPPER STRANDED.b. DC PV FEEDERS: ALUMINUM STRANDED (IF CONDUCTOR IS #1

0 OR LARGER).c. BRANCH CIRCUITS: COPPER. SOLID FOR NO. 12 AWG AND SMALLER; STRANDED FOR NO. 10 AWG AND LARGER.

E. CONDUCTOR INSULATION APPLICATIONS AND WIRING METHODSa. OPERATING TEMPERATURE: ALL CONDUCTOR INSULATION SHALL BE RATED FOR 90 DEG C.b. BRANCH CIRCUIT CONDUCTORS: TYPE THHN/THWN-2, COPPERc. DC PHOTOVOLTAIC SOURCE CIRCUITS & DC FEEDERS: TYPE 2KV PV-WIRE; AC FEEDER BETWEEN INVERTERS AND POCC: 600V.

G. PROVIDE TWIST-ON CONNECTORS, UL LISTED, IDENTIFIED AND MARKED FOR CONDUCTOR SUITABILITY, LIVE-ACTION SQUARE-WIRESPRING AND SHELL RATED FOR 105° C. CONNECTORS USE FOR OUTDOORS SHALL BE PRE-FILLED THERMOPLASTIC POLYESTERHOUSING WITH SILICONE-BASED SEALANT.

H. PV WIRE SHALL BE ROUTED IN SUCH A MANNER TO THAT WILL CONCEAL THE CABLING AS MUCHAS POSSIBLE FROM VIEW. ALL RUNS, WHETHER EXPOSED OR CONDUIT, SHALL BE SYMMETRICAL, RECTILINEAR, AND ORDERLY. ALL WIRING SHALL BE SECURED SUCH THAT IT IS NOT TOUCHING THE CANOPY ROOF, BUILDING ROOF, GROUND, STRUCTURE, OR ANY OTHER INCIDENTAL SURFACE, OR HANGING IN SUCH A WAY THAT THE WIRING COULD EASILY MOVE WITH WIND FORCE.

a. INSTALL EXPOSED CABLES PARALLEL AND PERPENDICULAR TO SURFACES OF EXPOSED STRUCTURAL MEMBERS, AND FOLLOWSURFACE CONTOURS WHERE POSSIBLE.

b. ATTACH CABLING TO STRUCTURE UTILIZING MECHANICAL MEANS SUCH AS J-HOOKS, SNAKE TRAY, STAINLESS STEEL OR GALVANIZEDCLIPS, OR ZIP-TIES. WHEN USING ZIP-TIES, THEY SHALL MEET THE FOLLOWING CRITERIA: UV RESISTANT, MINIMUM 40LB TENSILESTRENGTH, TEMPERATURE RANGE -20°F TO +165°F OR BETTER, AND UL LISTED. BASIS OF DESIGN SHALL BE HELLERMANNTYTONPVDF SOLAR TIES, OR APPROVED EQUAL. IF USING ZIP-TIES, NO MORE THAN 6 CONDUCTORS SHALL BE BUNDLED IN EACH ZIP-TIE.

c. IN THE MODULE RACKING SYSTEM, INTER-ROW RUNS OF PV WIRE SHALL BE SUPPORTED IN (PROPERLY SECURED) EMT, IMC, OR UVRATED RACEWAY, AND APPROVED BY THE MICROGRID ENERGY PROJECT MANAGER PRIOR TO INSTALL.

d. SECURE PV WIRE CONDUCTORS WITHIN 12" OF ALL CONNECTORS, AND EVERY 48" THEREAFTER.e. UTILIZE CONDUIT RACEWAY AT CONNECTIONS TO COMBINER BOXES.

I. NEATLY TRAIN AND LACE WIRING INSIDE OF BOXES, ENCLOSURES, EQUIPMENT, PANELBOARDS, AND SWITCHBOARDS.

J. USE MANUFACTURER-APPROVED PULLING COMPOUND OR LUBRICANT WHERE NECESSARY; COMPOUND USED MUST NOTDETERIORATE CONDUCTOR OR INSULATION. DO NOT EXCEED MANUFACTURER'S RECOMMENDED MAXIMUM PULLING TENSIONSAND SIDEWALL PRESSURE VALUES.

K. CONNECTIONS:a. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING

SPECIFIED IN UL 486A AND UL 486B.b. WHEN CONNECTING DISSIMILAR METALS PROVIDE A U.L. LISTED COMPRESSION METHOD TO INHIBIT THE POSSIBILITY OF

CONTACT BETWEEN THE TWO TYPES OF METALS.c. MAKE SPLICES AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND THAT POSSESS EQUIVALENT OR BETTER

MECHANICAL STRENGTH AND INSULATION RATINGS THAN UNSPLICED CONDUCTORS.

I. CONDUCTORS:a. INSULATED CONDUCTORS: COPPER WIRE OR CABLE INSULATED FOR 600 V UNLESS OTHERWISE REQUIRED BY APPLICABLE

CODE OR AUTHORITIES HAVING JURISDICTION.

J. CONDUCTOR TERMINATIONS AND CONNECTIONS:a. PIPE, ROD, AND EQUIPMENT GROUNDING CONDUCTOR TERMINATIONS: BOLTED CONNECTORS.b. CONNECTIONS TO STRUCTURAL STEEL: EXOTHERMIC WELDED CONNECTIONS.

K. EQUIPMENT GROUNDING:a. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTOR WITH ALL FEEDERS, BRANCH CIRCUITS, AND DC SOURCE CIRCUITS.

D. GROUNDING ELECTRODES:a. GROUND RODS: COPPER-CLAD; 8 FEET BY 5/8 INCH IN DIAMETER.

E. GROUNDING UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS:a. COMPLY WITH IEEE GROUNDING REQUIREMENTS.b. PAD-MOUNTED EQUIPMENT: INSTALL A GROUND RING AROUND THE PAD WITH GROUND RODS AS DETAILED ON THE DRAWINGS.

F. INSTALLATION:a. GROUNDING CONDUCTORS: ROUTE ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE, UNLESS OTHERWISE INDICATED

OR REQUIRED BY CODE. AVOID OBSTRUCTING ACCESS OR PLACING CONDUCTORS WHERE THEY MAY BE SUBJECTED TOSTRAIN, IMPACT, OR DAMAGE.

b. BONDING STRAPS AND JUMPERS: INSTALL IN LOCATIONS ACCESSIBLE FOR INSPECTION AND MAINTENANCE, EXCEPT WHEREROUTED THROUGH SHORT LENGTHS OF CONDUIT.

BONDING TO STRUCTURE: BOND STRAPS DIRECTLY TO BASIC STRUCTURE, TAKING CARE NOT TO PENETRATE ANYADJACENT PARTS.BONDING TO EQUIPMENT MOUNTED ON VIBRATION ISOLATION HANGERS AND SUPPORTS: INSTALL SO VIBRATION IS NOTTRANSMITTED TO RIGIDLY MOUNTED EQUIPMENT.USE EXOTHERMIC-WELDED CONNECTORS FOR OUTDOOR LOCATIONS.

c. GROUND RODS: DRIVE RODS UNTIL TOPS ARE 2 INCHES BELOW FINISHED FLOOR OR FINAL GRADE, UNLESS OTHERWISE INDICATED.d. INTERCONNECT GROUND RODS WITH GROUNDING ELECTRODE CONDUCTOR BELOW GRADE AND AS OTHERWISE INDICATED.

SECTION 10 03 00 - LOW VOLTAGE CONDUCTORS AND CABLES

SECTION 10 01 00 - COMMON WORK RESULTS FOR ELECTRICAL

SECTION 10 04 00 - GROUNDING AND BONDING

ELECTRICAL SPECIFICATIONS

A. METAL AND NONMETALLIC CONDUITS, TUBING, AND FITTINGS:a. LISTING AND LABELING: METAL AND NONMETALLIC CONDUITS, TUBING, AND FITTINGS SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, AND

MARKED FOR INTENDED LOCATION AND APPLICATION.b. RNC: TYPE EPC-40-PVC, COMPLYING WITH NEMA TC 2 AND UL 651 UNLESS OTHERWISE INDICATED.c. RIGID HDPE: COMPLY WITH UL 651A.d. FITTINGS FOR ENT AND RNC: COMPLY WITH NEMA TC 3; MATCH TO CONDUIT OR TUBING TYPE AND MATERIAL.

C. BOXES:a. GENERAL REQUIREMENTS FOR BOXES, ENCLOSURES, AND CABINETS: BOXES, ENCLOSURES, AND CABINETS INSTALLED IN WET

LOCATIONS SHALL BE LISTED FOR USE IN WET LOCATIONS.b. SHEET METAL OUTLET AND DEVICE BOXES: COMPLY WITH NEMA OS 1 AND UL 514A.c. CAST-METAL OUTLET AND DEVICE BOXES: COMPLY WITH NEMA FB 1, ALUMINUM, TYPE FD, WITH GASKETED COVER.d. NONMETALLIC OUTLET AND DEVICE BOXES: COMPLY WITH NEMA OS 2 AND UL 514C.e. SMALL SHEET METAL PULL AND JUNCTION BOXES: NEMA OS 1.f. FOR A FLAT/LOW SLOPE ROOF, CONDUITS SHOULD ENTER VIA A JUNCTION BOX POSITIONED ON TOP OF THE ROOF PENETRATION. THE JUNCTION BOX

WILL SERVE TO KEEP WATER FROM ACCUMULATING ON TOP OF THE PITCH POCKET. THE CONDUITS SHOULD ENTER THE JUNCTION BOX FROM THESIDE OR BOTTOM OF THE JUNCTION BOX, AND NOT FROM THE TOP.

g. WHERE OPEN-AIR PV WIRE IS RUN DIRECTLY INTO A JUNCTION BOX, WIRE GLANDS SHALL BE USED THAT ARE LISTED FOR THE NUMBER AND SIZE OFWIRES, AND SHALL BE LISTED AS "CORD GRIPS" OR "STRAIN RELIEFS". PV WIRE ENTERING A WIRE GLAND SHALL BE PROVIDED WITH DRIP LOOP THATDIVERTS WATER AWAY FROM THE WIRE GLAND.

h. CONNECTIONS TO NEMA-3/3R (OR HIGHER) CONDUIT BODIES, WIREWAYS, AND JUNCTION BOXES SHALL BE MADE WITH UL-LISTED WEATHER-TIGHTCONNECTORS TO MAINTAIN THE ENCLOSURES NEMA RATING.

D. RACEWAY APPLICATION:a. OUTDOORS: APPLY RACEWAY PRODUCTS AS SPECIFIED BELOW UNLESS OTHERWISE INDICATED:

EXPOSED CONDUIT ON STRUCTURES NOT SUBJECT TO PHYISCAL DAMAGE: EMTEXPOSED CONDUIT ON STRUCTURES WHERE SUBJECT TO PHYISCAL DAMAGE: IMC OR RMCUNDERGROUND CONDUIT: RMC, TYPE EPC-40-PVC, DIRECT BURIED.BOXES AND ENCLOSURES, ABOVE GROUND: NEMA 250, TYPE 3R.

b. INDOORS: APPLY RACEWAY PRODUCTS AS SPECIFIED BELOW UNLESS OTHERWISE INDICATED:EXPOSED, NOT SUBJECT TO PHYSICAL DAMAGE: EMT.CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT.BOXES AND ENCLOSURES: NEMA 250, TYPE 1

E. MINIMUM RACEWAY SIZE: 3/4-INCH (16-MM) TRADE SIZE INDOORS, 1" OUTDOORS UNLESS NOTED OTHERWISE.

F. RACEWAY FITTINGS: COMPATIBLE WITH RACEWAYS AND SUITABLE FOR USE AND LOCATION.a. RIGID AND INTERMEDIATE STEEL CONDUIT: USE THREADED RIGID STEEL CONDUIT FITTINGS UNLESS OTHERWISE INDICATED.

COMPLY WITH NEMA FB 2.10.b. PVC EXTERNALLY COATED, RIGID STEEL CONDUITS: USE ONLY FITTINGS LISTED FOR USE WITH THIS TYPE OF CONDUIT.

PATCH AND SEAL ALL JOINTS, NICKS, AND SCRAPES IN PVC COATING AFTER INSTALLING CONDUITS AND FITTINGS. USESEALANT RECOMMENDED BY FITTING MANUFACTURER AND APPLY IN THICKNESS AND NUMBER OF COATS RECOMMENDED BYMANUFACTURER.

c. EMT: USE SETSCREW (INDOORS) OR COMPRESSION (OUTDOORS), STEEL FITTINGS. COMPLY WITH NEMA FB 2.10.d. FLEXIBLE CONDUIT: USE ONLY FITTINGS LISTED FOR USE WITH FLEXIBLE CONDUIT. COMPLY WITH NEMA FB 2.20.

G. COMPLETE RACEWAY INSTALLATION BEFORE STARTING CONDUCTOR INSTALLATION.

H. INSTALL CONDUITS PARALLEL OR PERPENDICULAR TO STRUCTURE LINES.

I. SUPPORT CONDUIT WITHIN 12 INCHES (300 MM) OF ENCLOSURES TO WHICH ATTACHED.

J. INSTALL PULL WIRES IN EMPTY RACEWAYS. USE POLYPROPYLENE OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN 200-LB(90-KG) TENSILE STRENGTH. LEAVE AT LEAST 12 INCHES (300 MM) OF SLACK AT EACH END OF PULL WIRE. CAP UNDERGROUNDRACEWAYS DESIGNATED AS SPARE ABOVE GRADE ALONGSIDE RACEWAYS IN USE.

K. FASTEN JUNCTION AND PULL BOXES TO OR SUPPORT FROM BUILDING STRUCTURE. DO NOT SUPPORT BOXES BY CONDUITS.

A. CONSTRUCT PANELBOARDS TO UL STANDARDS AND PROVIDE UL LABELS.

B. MANUFACTURERSa. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, ACCEPTABLE MANUFACTURERS (INCL. BREAKERS) ARE AS FOLLOWS:

GESQUARE DEATONSIEMENS

C. ENCLOSURES SHALL BE 5-1/4" - 5-3/4" DEEP WITH REQUIRED GUTTER SPACE AT THE LUG END (TOP OR BOTTOM) OF THE PANEL. PANELS MOUNTEDEXTERIOR TO BUILDINGS OR IN WET LOCATIONS SHALL BE NEMA 3R TYPE. WHERE CABLES FEED THROUGH THE PANELS, CABINET SHALL HAVE ANADDITIONAL 4 INCH WIDTH ADDED TO THE GUTTER SPACE ON ONE SIDE.

D. PROVIDE PANELBOARDS WITH COPPER BUS (PHASE BUSES, BUS FINGERS, ETC.), RATING AS SCHEDULED ON DRAWINGS.E. PANELBOARDS SHALL BE PROVIDED WITH A NEUTRAL BUS AND GROUND BUS COMPLETE WITH NECESSARY LUGS AND TERMINALS. NEUTRAL AND

GROUND BARS CAN BE DUAL RATED ALCU9. ALL SPACES SHALL HAVE BUS FULLY EXTENDED AND DRILLED FOR THE FUTURE INSTALLATION OFBREAKERS.

F. BUS WORK SHALL BE FABRICATED OF HARD DRAWN COPPER OR ALUMINUM. LUGS SHALL BE SIZED AND PROVIDED FOR CONNECTION OF FEEDERSINDICATED.

G. ALL CURRENT-CARRYING PARTS OF THE BUS ASSEMBLY SHALL BE PLATED.H. PROVIDE FEED-THRU LUGS WHERE NOTED. WHERE FEED-THRU LUGS ARE NOT POSSIBLE DUE TO A SUBFEED, PROVIDE DOUBLE MAIN LUGS.I. CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE, MOLDED CASE, QUICK-MAKE, QUICK-BREAK, THERMAL MAGNETIC, TRIP INDICATING, HAVE COMMON TRIP

ON ALL MULTIPLE POLE BREAKERS, AND BE RATED FOR AT LEAST 75 DEG C.J. EACH CIRCUIT BREAKER IS TO BE FURNISHED WITH AN EXTERNALLY OPERABLE MECHANICAL MEANS TO TRIP THE CIRCUIT BREAKER, ENABLING

MAINTENANCE PERSONNEL TO VERIFY THE ABILITY OF THE CIRCUIT BREAKER TRIP MECHANISM TO OPERATE, AS WELL AS EXERCISE THE CIRCUITBREAKER OPERATING MECHANISMS.

K. CIRCUIT BREAKERS IN 480V PANELBOARDS SHALL BE FULL ADJUSTABLE LSI CIRCUIT BREAKERS WITH ELECTRONIC TRIP FOR FRAME SIZES 400A ANDGREATER.

E. CIRCUIT BREAKERS - ELECTRONIC TRIP CIRCUIT BREAKERS: AS SCHEDULED ON THE DRAWINGS, ELECTRONIC CIRCUIT BREAKERS SHALL HAVE, AT AMINIMUM, ADJUSTMENTS FOR LONG TIME, SHORT TIME AND INSTANTANEOUS TRIP. PROVIDE INTEGRAL GROUND FAULT SENSING WITH ADJUSTABLEGROUND FAULT TRIP.

F. PROVIDE A TYPED DIRECTORY CARD, CARD HOLDER AND PLASTIC COVER ON THE INSIDE OF COVER FOR CIRCUIT NUMBERS, TERMINALIDENTIFICATION, ETC.

G. BRANCH CIRCUIT CONDUCTORS SHALL BE NEATLY FORMED INTO GROUPS, SECURED WITH TAPE OR TIE WRAPS, AND CAREFULLY PLACED INTOGUTTER SPACE.

A. THE SWITCHBOARD BUSSING (AND ALL OTHER CURRENT CARRYING PARTS SUCH AS FINGERS, NEUTRAL AND GROUND BUSES) SHALL BE PLATEDCOPPER. THE BUSSING SHALL BE OF SUFFICIENT CROSS-SECTIONAL AREA TO MEET UL 891 TEMPERATURE RISE REQUIREMENTS.

B. THE MAIN CIRCUIT BREAKER IN 208V AND 480V SWITCHBOARDS SHALL BE AN INDIVIDUALLY MOUNTED AND BUSSED MOLDED CASE CIRCUIT BREAKERWITH A FULL ELECTRONIC TRIP UNIT.

a. INDIVIDUALLY MOUNTED MAINS SHALL BE LOCATED (TOP, MIDDLE, OR BOTTOM) PER MANUFACTURERS REQUIREMENTS BASED ON LOCATION OFCABLING ENTRANCE INTO SECTION. PROVIDE MINIMUM DISTANCE BETWEEN CABLE ENTRY OPENING AND TERMINATION LUGS OF MAIN OCPD PERMANUFACTURER (AND LOCAL UTILITY).

b. GROUND FAULT PROTECTION SHALL BE INCLUDED AT THE MAIN DISCONNECT FOR 480/277V SWITCHBOARDS 1000 AMPERES AND LARGER. GROUNDFAULT TRIP SHALL BE OF THE RESIDUAL TYPE AND INTEGRAL PART OF THE BREAKER. THE GROUND FAULT SYSTEM SHALL INCLUDE A MEMORY CIRCUITFOR POSITIVE TRIP ACTION DESPITE INTERMITTENT ARCING GROUND FAULTS.

C. FOR MAIN FUSIBLE SWITCH:a. INDIVIDUALLY MOUNTED BOLTED PRESSURE TYPE FUSE SWITCH. SWITCH SHALL BE UL LISTED FOR 100% OF THE CONTINUOUS RATING WITHOUT

EXCEEDING 60 DEG C RISE OVER A MAXIMUM 40 DEG C AMBIENT.b. SWITCH SHALL BE FURNISHED WITH CLASS L FUSE CLIPS AND BE UL LISTED FOR 200kAIC INTERRUPTING CAPACITY.

SECTION 10 15 00 - IDENTIFICATION

c. SWITCH SHALL UTILIZE STORED ENERGY DEAD FRONT OPERATING MECHANISM TO PROVIDE QUICK POSITIVE SWITCHING INDEPENDENT OF THE SPEEDOF THE OPERATING HANDLE. SWITCH SHALL BE MANUALLY OPERATED (AND ELECTRICALLY TRIPPED).

d. FUSE ACCESS DOOR SHALL BE MECHANICALLY INTERLOCKED WITH THE OPERATING HANDLE AND SHALL HAVE PROVISIONS FOR LOCKING IN THE OPENPOSITION.

e. INDIVIDUALLY MOUNTED MAINS SHALL BE LOCATED (TOP, MIDDLE, OR BOTTOM) PER MANUFACTURERS REQUIREMENTS BASED ON LOCATION OFCABLING ENTRANCE INTO SECTION. PROVIDE MINIMUM DISTANCE BETWEEN CABLE ENTRY OPENING AND TERMINATION LUGS OF MAIN OCPD PERMANUFACTURER (AND LOCAL UTILITY).

D. CIRCUIT BREAKER DISTRIBUTION SECTIONS:a. DISTRIBUTION CIRCUIT BREAKERS SHALL BE GROUP MOUNTED IN FRAME SIZES 100 AMP THROUGH 1200 AMP. FRAME SIZES LARGER THAN 1200 AMP

SHALL BE INDIVIDUALLY MOUNTED.b. EACH CIRCUIT BREAKER IS TO BE FURNISHED WITH AN EXTERNALLY OPERABLE MECHANICAL MEANS TO TRIP THE CIRCUIT BREAKER, ENABLING

MAINTENANCE PERSONNEL TO VERIFY THE ABILITY OF THE CIRCUIT BREAKER TRIP MECHANISM TO OPERATE, AS WELL AS EXERCISE THE CIRCUITBREAKER OPERATING MECHANISMS.

c. CIRCUIT BREAKERS IN 480V SWITCHBOARDS SHALL BE FULL ADJUSTABLE LSI CIRCUIT BREAKERS WITH ELECTRONIC TRIP FOR FRAME SIZES 400A ANDGREATER. WHEN GROUND FAULT PROTECTION IS REQUIRED ON THE MAIN OVERCURRENT DEVICE, FULLY ADJUSTABLE LSIG CIRCUIT BREAKERS

WITH ELECTRONIC TRIP UNITS SHALL BE PROVIDED FOR FEEDER CIRCUIT BREAKER FRAME SIZES 400A AND GREATER.d. ELECTRONIC TRIP CIRCUIT BREAKERS: AS SCHEDULED ON THE DRAWINGS, ELECTRONIC CIRCUIT BREAKERS SHALL HAVE, AT A MINIMUM,

ADJUSTMENTS FOR LONG TIME, SHORT TIME AND INSTANTANEOUS TRIP. PROVIDE INTEGRAL GROUND FAULT SENSING WITH ADJUSTABLE GROUNDFAULT TRIP.

E. PROVIDE A COORDINATION STUDY OF THE ELECTRICAL SYSTEM AND RECOMMEND SET POINTS FOR ALL OF THE OVERCURRENT AND GROUND FAULTTRIP ADJUSTMENTS ON THE EQUIPMENT PROVIDED. THE COORDINATION STUDY AND SET POINT RECOMMENDATIONS SHALL BE SUBMITTED TO THECONSULTING ENGINEER FOR APPROVAL. SUBMITTAL SHALL BE ON OR BEFORE DATE OF SWITCHBOARD AND PANELBOARD EQUIPMENT SUBMITTAL.

A. MANUFACTURERSa. SUBJECT TO COMPLIANCE WITH REQUIREMENTS. ACCEPTABLE MANUFACTURERS AS FOLLOWS:

COOPER BUSSMANN, INC.EDISON FUSE, INC.MERSENLITTELFUSE, INC.

B. CHARACTERISTICS: NEMA FU 1, NONRENEWABLE CARTRIDGE FUSES WITH VOLTAGE RATINGS CONSISTENT WITH CIRCUIT VOLTAGES.PHOTOVOLTAIC DC SOURCE CIRCUITS: 1000VDC, SUPPLEMENTAL CLASS

C. MEDIUM VOLTAGE EXPULSION FUSES: REFERENCE MEDIUM VOLTAGE SWITCHGEAR SPECIFICATION.INSTALL FUSES IN FUSIBLE DEVICES. ARRANGE FUSES SO RATING INFORMATION IS READABLE WITHOUT REMOVING FUSE.

D. DISCONNECT SWITCHES:a. FUSIBLE SWITCH ASSEMBLIES (USE ONLY WHEN OVERCURRENT PROTECTION IS REQUIRED): NEMA TYPE HEAVY DUTY, QUICK MAKE, QUICK BREAK,

LOAD INTERRUPTER, ENCLOSED KNIFE SWITCH WITH EXTERNALLY OPERABLE HANDLE.b. NONFUSIBLE SWITCH ASSEMBLIES: NEMA TYPE HEAVY DUTY, QUICK MAKE, QUICK BREAK, LOAD INTERRUPTER, ENCLOSED KNIFE SWITCH WITH

EXTERNALLY OPERABLE HANDLE.

E. SPECIAL ATTENTION MUST BE GIVEN TO THE RAPID-SHUTDOWN PROVISIONS OF NEC 2014, INCLUDING INSTALLATION REQUIREMENTS FOR DCCOMBINERS, INVERTERS, REMOTE CONTACTORS, AND LOW VOLTAGE CIRCUITRY. WHERE REQUIREMENTS ARE NOT EXPLICITLY CALLED OUT IN THEPLANS, CONTRACTOR MUST CLARIFY REQUIREMENTS WITH MICROGRID ENERGY PROJECT MANAGER PRIOR TO INSTALLING THE ABOVE LISTEDCOMPONENTS.

A. SURGE PROTECTION EQUIPMENT SHALL BE CONSTRUCTED AND LISTED IN ACCORDANCE TO THE LATEST ISSUES OF UL 1449, UL 1283, ANSI/IEEE C62.41,ANSI/IEEE C62.45 AND NEMA LS1.

B. MANUFACTURERS: CURRENT TECHNOLOGY, LIEBERT, LEA INTERNATIONAL, EATON, SIEMENS, GE, SQUARE D, OR APPROVED EQUAL.C. THE MAXIMUM CONTINUOUS OPERATING VOLTAGE (MCOV) OF THE UNITS SHALL BE NOT LESS THAN 115% OF THE RATED VOLTAGE.D. THE MAXIMUM UL 1449 VOLTAGE PROTECTION RATING SHALL NOT EXCEED 400 VOLTS (L-N) AND THE MAXIMUM CLAMPING VOLTAGE RATING SHALL NOT

EXCEED 600 VOLTS (L-N) FOR AN ANSI/IEEE C62.41 CATEGORY C3 WAVEFORM.E. THE UNIT SHALL PROVIDE 80,000A OF PROTECTION FOR THE FOLLOWING MODES: LINE-TO-NEUTRAL (EACH PHASE), LINE-TO-GROUND (EACH PHASE),

AND NEUTRAL TO GROUND.

A. PROVIDE LUMINAIRE AND DRIVER PRODUCT DATA AS PART OF EQUIPMENT SUBMITTALB. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS, INCL. MANUFACTURERS INSTRUCTIONS FOR MOUNTING TO CANOPIES. PROVIDE

MOUNTING DETAIL TO MICROGRID ENERGY PRIOR TO MOUNTING.

A. WARNING LABELS AND SIGNS:c. COMPLY WITH NFPA 70 AND 29 CFR 1910.145.

B. SELF-ADHESIVE WARNING LABELS:a. FACTORY-PRINTED, MULTICOLOR, PRESSURE-SENSITIVE HIGH PERFORMANCE VINYL ADHESIVE LABELS, CONFIGURED FOR

DISPLAY ON FRONT COVER, DOOR, OR OTHER ACCESS TO EQUIPMENT UNLESS OTHERWISE INDICATED.b. LABEL CONSTRUCTION: ULTRAVIOLET RESISTANT INK, PERMANENT ACRYLIC ADHESIVE BASE.c. SERVICE TEMPERATURE: -40°F TO 175°F, OR BETTER.d. BASIS OF DESIGN: HELLERMANNTYTON "CHECK-HT" LABELS, OR APPROVED EQUAL. NO HANDWRITTEN OR NON-PERMANENT LABELS ARE ALLOWED.

C. COLOR-CODING FOR PHASE AND VOLTAGE LEVEL IDENTIFICATION, 1000 V AND LESS: USE THE COLORS LISTED BELOW FOR FEEDERAND BRANCH-CIRCUIT CONDUCTORS.

a. COLOR SHALL BE FACTORY APPLIED OR, FOR SIZES LARGER THAN NO. 1/0 AWG IF AUTHORITIES HAVING JURISDICTION PERMIT,FIELD APPLIED.

b. COLORS FOR 208/120-V CIRCUITS:PHASE A: BLACK.PHASE B: RED.PHASE C: BLUE.NEUTRAL: WHITEGRND GREEN

c. COLORS FOR VOLTAGES HIGHER THAN 208V & LESS THAN OR EQUAL TO 600V:PHASE A: BROWNPHASE B: ORANGEPHASE C: YELLOWNEUTRAL: WHITE WITH COLORED STRIPE OR GRAYGRND GREEN

d. COLORS FOR PHOTOVOLTAIC (DC) CIRCUITS:UNGROUNDED CONDUCTORS POSITIVE: REDUNGROUNDED CONDUCTORS NEGATIVE: BLACK

GRND: GREEN OR BAREe. FIELD-APPLIED, COLOR-CODING CONDUCTOR TAPE: APPLY IN HALF-LAPPED TURNS FOR A MINIMUM DISTANCE OF 6 INCHES

(150 MM) FROM TERMINAL POINTS AND IN BOXES WHERE SPLICES OR TAPS ARE MADE. APPLY LAST TWO TURNS OF TAPE WITHNO TENSION TO PREVENT POSSIBLE UNWINDING. LOCATE BANDS TO AVOID OBSCURING FACTORY CABLE MARKINGS.

D. WARNING LABELS FOR PHOTOVOLTAIC EQUIPMENT.a. INSTALL REQUIRED LABELS PER NEC 690 & AS INDICATED ON DOCUMENTS.

E. EQUIPMENT TO BE LABELED:a. MV SWITCHGEAR (WHEN SWITCHGEAR IS PROVIDED AS PART OF CONTRACTOR SCOPE)b. PANELBOARDSc. SOURCE CIRCUIT CONDUITS, ENCLOSURES, AND ELECTRICAL CABINETSd. INVERTERSe. COMBINER BOXES (WHEN INCLUDED IN THE PROJECT)

SECTION 10 09 00 - FUSES, DISCONNECT SWITCHES, RAPID SHUTDOWN

SECTION 10 08 00 - SWITCHBOARDS

SECTION 10 10 00 - SURGE SUPPRESSION

SECTION 10 11 00 - SITE LIGHTING

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

EL

EC

TR

IC

AL

S

PE

CIF

IC

AT

IO

NS

02/26/18

E-1

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

Page 3: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

INV-01

P1

INV-02

INV-03

ACCP

CHAIR/TABLE

STORAGE

108

KITCHEN

107

MECH. RM./STORAGE

106

1

E-5JB-02 (WALL

MOUNTED

BELOW SOFFIT)

AREA PLANNED

FOR FUTURE

SOLAR PV

EXPANSION

PV PROD

METER

PV DISCO

"PVD"

2

E-5

CONSUMPTION

METER

AC CONDUIT

FROM "ACCP" TO

PV PROD METER

P2

JB-01

STR.

1-1

STR.

1-2

STR.

1-3

STR.

1-4

STR.

2-1

STR.

2-2

STR.

2-3

STR.

2-4

STR.

3-1

STR.

3-2

STR.

3-3

STR.

3-4

STRING ID (TYP.), SEE 3/E-5

"STRING WIRING DIAGRAM"

SOLAR MODULE (TYP.)

DC CONDUIT (OVER &

AROUND OVERHANG)

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

EL

EC

TR

IC

AL

S

IT

E P

LA

N

02/26/18

E-2

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

E-2

1

SCALE

1/8" = 1'-0"

ELECTRICAL SITE PLAN - 1ST FLOOR

E-2

2

SCALE

1/8" = 1'-0"

GENERAL NOTESA. CONDUCTORS FOR PHOTOVOLTAIC MODULES SHALL BE ROUTED IN SUCH A MANNER THAT WILL CONCEAL THE CABLING AS MUCH AS POSSIBLE FROM

VIEW (I.E. SUPPORTED UNDER SOLAR MODULES).

B. ALL RUNS, WHETHER EXPOSED OR CONDUIT, SHALL BE SYMMETRICAL, RECTILINEAR, AND ORDERLY. ALL WIRING SHALL BE SECURED SUCH THAT IT ISNOT TOUCHING THE CANOPY ROOF, BUILDING ROOF, GROUND, STRUCTURE, OR ANY OTHER INCIDENTAL SURFACE, OR HANGING IN SUCH A WAY THATTHE WIRING COULD EASILY MOVE WITH WIND FORCE. INSTALL EXPOSED CABLES PARALLEL AND PERPENDICULAR TO SURFACES OF EXPOSEDSTRUCTURAL MEMBERS, AND FOLLOW SURFACE CONTOURS WHERE POSSIBLE.

C. ATTACH CABLING TO STRUCTURE UTILIZING MECHANICAL MEANS SUCH AS J-HOOKS, SNAKE TRAY, STAINLESS STEEL OR GALVANIZED CLIPS, ORZIP-TIES. WHEN USING ZIP-TIES, THEY SHALL MEET THE FOLLOWING CRITERIA: UV RESISTANT, 40 LB TENSILE STRENGTH, TEMPERATURE RANGE -20°FTO +165°F, OR BETTER, AND UL LISTED. BASIS OF DESIGN SHALL BE HELLERMANNTYTON PVDF SOLAR TIES, OR APPROVED EQUAL. IF USING ZIP-TIES,NO MORE THAN 6 CONDUCTORS SHALL BE BUNDLED IN EACH ZIP-TIE.

D. SECURE ALL MODULE WIRING WITHIN 12" OF ALL CONNECTORS, AND EVERY 48" THEREAFTER.

E. ALL JUNCTION BOXES OR COMBINERS SHALL BE INSTALLED IN READILY ACCESSIBLE LOCATIONS. POSITION THE ROOF PENETRATION JUNCTION BOXOVER THE PENETRATION SUCH THAT IT DIVERTS RAINWATER AWAY FROM FALLING ON THE TOP OF THE PENETRATION. CONDUIT PENETRATIONS INTOALL JUNCTION BOXES SHALL BE ON THE SIDES OR BOTTOM, AND NOT THE TOP SURFACE.

F. CONNECTIONS TO NEMA-3/3R (OR HIGHER) CONDUIT BODIES, WIREWAYS, AND JUNCTION BOXES SHALL BE MADE WITH UL-LISTED WEATHER-TIGHTCONNECTORS TO MAINTAIN THE ENCLOSURE'S NEMA RATING.

G. WIRE GLAND OR CABLE GRIP SHALL BE UL-LISTED FOR NUMBER AND SIZE OF CONDUCTORS TO PROVIDE STRAIN RELIEF FOR ALL CONDUCTORSPENETRATING A CONDUIT BODY.

H. OPEN-AIR RATED CONDUCTORS ENTERING CONDUIT BODES SHALL BE PROVIDED WITH DRIP LOOP THAT DIVERT WATER AWAY FROM WIRE GLANDS.

I. CONDUITS SHALL BE INSTALLED SUCH THAT THERE IS NO GREATER THAN FOUR (4) 90 DEGREE BENDS IN ANY SINGLE RUN. WHERE REQUIRED, INSTALLPULLBOXES SIZED PER NEC 314.28 & 314.70.

ELECTRICAL SITE PLAN - ROOF

AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
Page 4: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

100'-0"

28'-6

"

1'-2"

4'-1"

2'-41 2"

4'-1"

2'-41 2"

4'-1"

2'-41 2"

4'-1"

1'-2"

1 2"

STANDING SEAM (12" O.C.)

SOLAR MODULE (TYP.) RAIL (TYP.)

STANDING SEAM

CLAMP (TYP.)

12"

4'-0" 4'-0"

ROOF FACE DIMENSION

1'-41 2"

1'-33 4"

RACKING SCHEDULE

ROW MODULES MODULE MID-CLAMPS MODULE END-CLAMPS 162" RAILS 122" RAILS SPLICES SEAM CLAMPS

1

29 56 4 12 4 14 50

2

29 56 4 12 4 14 50

3

29 56 4 12 4 14 50

3

29 56 4 12 4 14 50

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

AR

RA

Y R

AC

KIN

G P

LA

N - P

AR

TIA

L

02/26/18

E-3

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

E-3

1

SCALE

3/16" = 1'-0"

ARRAY RACKING PLAN - PARTIAL ROOF PLAN

GENERAL NOTESA. CONDUCTORS FOR PHOTOVOLTAIC MODULES SHALL BE ROUTED IN

SUCH A MANNER THAT WILL CONCEAL THE CABLING AS MUCH ASPOSSIBLE FROM VIEW (I.E. SUPPORTED UNDER SOLAR MODULES).

B. ALL RUNS, WHETHER EXPOSED OR CONDUIT, SHALL BESYMMETRICAL, RECTILINEAR, AND ORDERLY. ALL WIRING SHALL BESECURED SUCH THAT IT IS NOT TOUCHING THE CANOPY ROOF,BUILDING ROOF, GROUND, STRUCTURE, OR ANY OTHER INCIDENTALSURFACE, OR HANGING IN SUCH A WAY THAT THE WIRING COULDEASILY MOVE WITH WIND FORCE. INSTALL EXPOSED CABLESPARALLEL AND PERPENDICULAR TO SURFACES OF EXPOSEDSTRUCTURAL MEMBERS, AND FOLLOW SURFACE CONTOURS WHEREPOSSIBLE.

C. ATTACH CABLING TO STRUCTURE UTILIZING MECHANICAL MEANSSUCH AS J-HOOKS, SNAKE TRAY, STAINLESS STEEL OR GALVANIZEDCLIPS, OR ZIP-TIES. WHEN USING ZIP-TIES, THEY SHALL MEET THEFOLLOWING CRITERIA: UV RESISTANT, 40 LB TENSILE STRENGTH,TEMPERATURE RANGE -20°F TO +165°F, OR BETTER, AND UL LISTED.BASIS OF DESIGN SHALL BE HELLERMANNTYTON PVDF SOLAR TIES,OR APPROVED EQUAL. IF USING ZIP-TIES, NO MORE THAN 6 CONDUCTORS SHALL BE BUNDLED IN EACH ZIP-TIE.

D. IN THE MODULE RACKING SYSTEM, INTER-ROW RUNS OF PV WIRESHALL BE SUPPORTED IN (PROPERLY SECURED) EMT, IMC, OR UVRATED RACEWAY, AND APPROVED BY THE MICROGRID ENERGYPROJECT MANAGER PRIOR TO INSTALL.

E. SECURE ALL MODULE WIRING WITHIN 12" OF ALL CONNECTORS, ANDEVERY 48" THEREAFTER.

F. ALL JUNCTION BOXES OR COMBINERS SHALL BE INSTALLED IN READILY ACCESSIBLE LOCATIONS. POSITION THE ROOF PENETRATION JUNCTION BOX OVER THE PENETRATION SUCH THAT ITDIVERTS RAINWATER AWAY FROM FALLING ON THE TOP OF THE PENETRATION. CONDUIT PENETRATIONS INTO ALL JUNCTION BOXESSHALL BE ON THE SIDES OR BOTTOM, AND NOT THE TOP SURFACE.

G. CONNECTIONS TO NEMA-3/3R (OR HIGHER) CONDUIT BODIES, WIREWAYS, AND JUNCTION BOXES SHALL BE MADE WITH UL-LISTEDWEATHER-TIGHT CONNECTORS TO MAINTAIN THE ENCLOSURE'SNEMA RATING.

H. WIRE GLAND OR CABLE GRIP SHALL BE UL-LISTED FOR NUMBER ANDSIZE OF CONDUCTORS TO PROVIDE STRAIN RELIEF FOR ALL CONDUCTORS PENETRATING A CONDUIT BODY.

I. OPEN-AIR RATED CONDUCTORS ENTERING CONDUIT BODES SHALL BEPROVIDED WITH DRIP LOOP THAT DIVERT WATER AWAY FROM WIREGLANDS.

J. CONDUITS SHALL BE INSTALLED SUCH THAT THERE IS NO GREATERTHAN FOUR (4) 90 DEGREE BENDS IN ANY SINGLE RUN. WHEREREQUIRED, INSTALL PULLBOXES SIZED PER NEC 314.28 & 314.70.

AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
AutoCAD SHX Text
6
AutoCAD SHX Text
12
Page 5: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

1. PROVIDE ARC FLASH WARNING SIGNAGE AS PER NEC 110.16.

2. AC DISCONNECT IS TO BE LOCATED WITHIN CLEAR VISUAL SITE OF THE INTERCONNECTION POINT AND AS IS PRACTICABLE TO THE UTILITY INTERCONNECTION

POINT.

3. INVERTER IS LISTED FOR UTILITY INTERCONNECTION AND HAS NO POTENTIAL TO ISLAND WHEN GRID FAILS. INVERTERS COMPLY WITH RAPID SHUTDOWN PER

NEC 690.12.

4. INSTALL ROOF-MOUNTED CONDUIT MINIMUM 3.5" ABOVE ROOF ON DURA BLOCKS OR EQUIVALENT.

5. INSTALLATION TO FOLLOW NEC AND STATE AND NATIONAL BUILDING CODE GUIDELINES.

6. EQUIPMENT GROUNDING CONDUCTORS ON AC AND DC SIDE ARE SIZED ACCORDING TO NEC 250.122.

7. ALL MODULES ARE CERTIFIED TO MEET UL 1703. ALL INVERTERS ARE CERTIFIED TO MEET UL 1741.

8. COMPONENTS IN HEAVY LINE TYPE ARE NEW AND ARE INCLUDED IN THIS SCOPE, INCLUDING INTERCONNECTION AT EXISTING 1000KVA TRANSFORMER.

GENERAL NOTES

EQUIPMENT SUMMARY

KEY ITEM DETAIL QNTY

1 SOLAR MODULEGCL-P6/72H 340, 340W, Isc = 9.49A, Voc = 46.6V

116

2

GRID INTERACTIVE INVERTER - "INV-01",

"INV-02", & "INV-03"

FRONIUS, SYMO 10.0-3, 600VDC, 208/120VAC, WALL MOUNTED RM. 1083

3 AC COMBINER PANELBOARD - "ACCP"

200A, 208/120V, 3P/4W, 35KAIC, MLO, (3) 40A CB, WALL MOUNTED RM. 108

1

4 PV PRODUCTION METER

LOCUS LGATE 320 METER W/ 320A, 208/120V 7-TERMINAL METER SOCKET, NEMA

3R. PV GENERATION WIRED TO THE LINE SIDE TERMINALS (TOP OF METER

BLOCK). CELL-ENABLED. WALL MOUNTED EAST EXTERIOR WALL.

1

5 CONSUMPTION METER

LOCUS LGATE EXTEND 2.0, 200A CTs FOR EXISTING 3/0 "UTILITY" FEEDS TO "P1" &

"P2". WALL MOUNTED EAST INTERIOR WALL.

1

6 FUSED PV MAIN DISCONNECT - "PVD"

VISIBLE, LOCKABLE, SERVICE ENTRANCE RATED DISCONNECT. 200A, 600V, 3P/4W,

35KAIC, NEMA 3R, W/ 175A FUSES. WALL MOUNTED EAST EXTERIOR WALL.

1

7 EXISTING PANELBOARD - "P1"

200A, 208/120V, 3P/4W, xxKAIC, MLO, WALL MOUNTED RM. 106. POCC ON

AVAILABLE BARRELS IN EXISTING LUGS.

1

8 EXISTING PANELBOARD - "P2"200A, 208/120V, 3P/4W, xxKAIC, MLO, WALL MOUNTED RM. 106.

1

9 EXISTING JUNCTION BOXWITH H6811-400A SERIES SPLIT-CORE CTS, WALL MOUNTED RM. 106.

1

10 EXISTING SWITCHBOARD - "MDP"1000A, 208/120V, 3P/4W, xxKAIC

1

ARRAY SECTION EAST

40 MODULES - 13.6 kW DC

4 STRINGS OF 10 MODULES

4 PARALLEL STRINGS

PV DC

DISCONNECT

600VDC

15A

15A

15A

DC

AC

ARRAY SECTION CENTER

40 MODULES - 13.6 kW DC

4 STRINGS OF 10 MODULES

4 PARALLEL STRINGS

PV DC

DISCONNECT

600VDC

15A

15A

15A

DC

AC

M

175A

M

40A/3P

40A/3P

1

2

2

A

B

C

C

DD

H

CONDUCTOR SCHEDULE

KEY CONDUCTORS CU/AL TYPE LOCATION NOTES

A2-#10, 1-#6G IN OPEN AIR

CUPV WIRE, 600VDC

ROOF DC STRINGS

B24MAX-#10, 3-#8G, 2" EMT

CUTHWN-2, 600VDC

ROOF TO RM. 108 DC STRINGS

C3-#8, 1-#10N, 1-#10G, 1" EMT

CUTHWN-2, 600VAC

RM. 108AC CONDUCTORS "INV-01", "INV-02", "INV-03" TO "ACCP"

D

3-#3/0, 1-#6N, 1-#6G, 2" EMT (BY OTHERS)

CUTHWN-2, 600VAC

RM. 108 TO RM. 106,

INTR./EXTR. RUN

AC CONDUCTORS "PVD" TO "P1" (SIZED FOR FUTURE EXPANSION). (BY

OTHERS).

E3-#12, 1-#12N, 1-#12G, 3/4" EMT

CUTHWN-2, 600VAC

RM. 106

AC CONDUCTORS (PROVIDING AC POWER AND VOLTAGE REFERENCE

TO LGATE EXTEND).

F

LOCUS LGATE EXTEND CT WIRING (X1

WHITE, X2 BLACK), 3/4" EMT

CU -- RM. 106 LGATE EXTEND CONSUMPTION MONITORING

G#22, MULTI-CONDUCTOR, 3/4" EMT

CU BELDEN 3106A RM.106 & EXTR. RS485 CONNECTION BETWEEN LGATE EXTEND AND LGATE 320

HETHERNET, 3/4" EMT

CU CAT-5/CAT-6 RM.108 & TO LAN INVERTER DAISY CHAIN. CAT-5/CAT-6 TO LAN BY OTHERS.

VOLTAGE = 208/120V, 3P/4W, 60Hz.

CURRENT = 83.1A x 1.25 = 103.875A

3

4

6

7

B

PLAN NOTES

X

1

X

2

X

3

SHORT CIRCUIT FAULT SCHEDULE

X EQUIPMENTVOLTAGE (V)

CONDUCTORS CU/AL

CONDUIT (S OR N)

LENGTH

(FT)

C OR Z VALUE f M

FAULT (A)

X

0

UTILITY XFMR, 150kVA, 208/120V (SECONDARY)

X

1

EXISTING PANELBOARD - "P2"

X

2

FUSED PV MAIN DISCONNECT - "PVD"

X

3

AC COMBINER PANEL - "ACCP"

4 PARALLEL STRINGS

PV DC

DISCONNECT

600VDC

15A

15A

15A

DC

AC

2

C

B

ARRAY SECTION WEST

36 MODULES - 12.24 kW DC

9 STRINGS OF 4 MODULES

40A/3P

H

H

8

X

0

TO EXISTING

LOADS

TO EXISTING

LOADS

FROM EXISTING

150kVA XMFR

BANK

15A/3P

5

E

F

G

CTs

F

TO EXISTING

LOADS

10

9

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

ON

E-L

IN

E D

IA

GR

AM

02/26/18

E-4

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

E-4

1

SCALE

N.T.S.

ONE-LINE DIAGRAM

AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Page 6: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

ACCP

INV-01 INV-02INV-03

6'-11

1 2"8"

DROP CEILING

1. #6 BARE COPPER GND CONDUCTORS SHALL BE RUN FROM THE GROUND SPLICE IN THE

JUNCTION BOX BACK TO ALL THE RACKING WHICH HOLDS SOLAR MODULES FEEDING THE

DESIGNATED JUNCTION BOX. MODULES AND RACKING SHALL BE CONTINUOUSLY GROUNDED.

REFER TO RACKING DRAWINGS FOR INTEGRAL GROUNDING DETAILS.

2. REFER TO SHEET E-4 FOR EQUIPMENT GROUNDING CONDUCTOR SIZES.

3. TEST GROUNDING RESISTANCE AT POCC. IF GREATER THAN 25Ω, RETEST OR REINSTALL

GROUNDING.

4. THIS DETAIL SHOWS TYPICAL EQUIPMENT GROUNDING CONNECTIONS. DEVICES/EQUIPMENT

SHOWN MAY NOT BE INCLUDED IN THIS SITE. ALL DEVICES/EQUIPMENT INCLUDED IN THIS SITE

MAY NOT BE SHOWN. REFER TO PLANS AND WIRING DIAGRAMS FOR EQUIPMENT.

JB-01

JB-02

G

G

JB-03

G

INV-01

G

INV-02

G

ACCP

G

CONSUMPTION

METER

PV

PROD

METER

PVD

G

G

G

EXISTING "MDP"

EXISTING GROUNDING

ELECTRODES (TYP.)

#3/0 CU GEC

(2) 3/4" X 10' CU

GROUND RODS

MODULE

RACKING

GROUNDING NOTES

SEE NOTE #2

SEE NOTE #2

SEE NOTE #1

INV-03

G

P2

G

PV PROD

METER

PVD

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

ON

E-L

IN

E D

IA

GR

AM

02/26/18

E-5

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

E-5

2

SCALE

N.T.S.

PV EQUIPMENT WALL, WEST ELEVATION (INTERIOR)

E-5

1

SCALE

1" = 1'-0"

EQUIPMENT WALL, EAST ELEVATION (EXTERIOR)

E-5

4

SCALE

N.T.S.

E-5

3

SCALE

N.T.S.

TYPICAL GROUNDING SCHEMATIC

Page 7: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

PANEL "ACCP"208/120 VOLTS 3 ɸ 4 W 200 A AMP MLO 35000 A.I.C. RATING

200 A AMP BUS SURFACE MOUNTED

CKT NO. TRIP/ POLES DESCRIPTION DEMAND LOADVA WIRE SIZE

1,3,5 40/3 INVERTER "INV-01" 10000 ONE-LINE DIAGRAM

2,4,6 40/3 INVERTER "INV-02" 10000 ONE-LINE DIAGRAM7,9,11 40/3 INVERTER "INV-03" 10000 ONE-LINE DIAGRAM

8,10,12 40/3 SPARE - FUTURE EXPANSION (BY OTHERS) 10000 ONE-LINE DIAGRAM

13,15,17 40/3 SPARE - FUTURE EXPANSION (BY OTHERS) 10000 ONE-LINE DIAGRAM

-- -- -- --

-- -- -- --

-- -- -- --

Load CategoryConnected Load (KVA)

xDemandFactor =

Demand Load(KVA) TOTAL CONN. LOAD: 50 KVA

Equipment 50.0 1.25 62.5 TOTAL DEMAND LOAD: 62.5 KVA

TOTAL DEMAND LOAD: 138.5 AMPS

SPARE CAPACITY (175A FUSE): 36.5 AMPS

AC CIRCUIT CALCULATIONSASSUMPTIONS· NEC 2014 APPLIES· SUN-EXPOSED CONDUITS· MAX 3 CONDUCTORS CONDUIT FILL (NEUTRAL CARRIES ZERO CURRENT) (ARTICLE 705.95(B))· ASHRAE 2% TEMP = 34C· MINIMUM SIZING - VOLTAGE DROP NOT ACCOUNTED FOR. SEE ONE-LINE DIAGRAM FOR ACTUAL SIZING· ALL TERMINALS 75C RATED OR BETTER

SINGLE 10.0kW INVERTER: FULL OUTPUT CURRENT = 27.7A Imax = 27.7 X 1.00 = 27.7A (ARTICLE 690.8(A)(3))REQUIRED AMPACITY = Imax X 1.25 = 27.7 X 1.25 = 34.625ATOTAL AMPACITY (75C COLUMN NEC TABLE 310.15(B)(16)) = 50A USING #8 CUBACK CHECK FOR TEMP: (310.15(B)(16) 90C COLUMN AMPACITY) X (CONDUIT FILL) X (AMPACITY TEMP CORRECTION) MUST BE GREATER THAN Imax. FOR #8 50A X 1 X 0.96 = 48.0A 48.0A > 27.7A THEREFORE #8 IS ACCEPTABLE MINIMUM SIZE.

INVERTER OCPD: 27.7A X 1.25 = 34.625A NEXT HIGHER SIZE = 40A

COMBINED DC GEC/AC EGC PER NEC 2014: GROUNDED DC SYSTEMS: SIZE PER LARGER OF TABLES 250.122 OR 250.66. FOR UNGROUNDED DC SYSTEMS: SIZECOMBINED CONDUCTOR PER TABLE 250.122 BASED ON AC OCPD SIZE. THIS IS UNGROUNDED SYSTEM: USE #10 EGC/GECNEUTRAL CONDUCTOR: NOT SMALLER THAN GROUND- USE #10TOTAL SINGLE INVERTER CIRCUIT MINIMUM SIZE BEFORE VOLTAGE DROP = 3# 8, #10 NEU #10 GND IN 1" CONDUIT BEFORE VOLTAGE DROP ADJUSTMENTSPROTECTED BY 40A OCPD. SEE ONE LINE DIAGRAM FOR VOLTAGE-DROP ADJUSTED FINAL SIZES. ________________________________________________________________________________________________________________________________

175A FEEDER (SIZED FOR FUTURE EXPANSION): FULL OUTPUT CURRENT = 27.7A X 5 = 138.5A Imax = 138.5 X 1.00 = 138.5A (ARTICLE 690.8(A)(3))REQUIRED AMPACITY = Imax X 1.25 = 138.5A X 1.25 = 173.125ATOTAL AMPACITY (75C COLUMN NEC TABLE 310.15(B)(16)) = 200A USING 3/0 CUBACK CHECK FOR TEMP: (310.15(B)(16) 90C COLUMN AMPACITY) X (CONDUIT FILL) X (AMPACITY TEMP CORRECTION) MUST BE GREATER THAN Imax. FOR 3/0 CU: 200.0A X 1 X 1 = 200.0A 200.0A > 138.5A THEREFORE #3/0 CU IS ACCEPTABLE SIZE.

FEEDER OCPD: 138.5A X 1.25 = 173.125A NEXT HIGHER SIZE = 175A

COMBINED DC GEC/AC EGC PER NEC 2014: GROUNDED DC SYSTEMS: SIZE PER LARGER OF TABLES 250.122 OR 250.66. FOR UNGROUNDED DC SYSTEMS: SIZECOMBINED CONDUCTOR PER TABLE 250.122 BASED ON AC OCPD SIZE. THIS IS UNGROUNDED SYSTEM: USE #6 EGC/GECNEUTRAL CONDUCTOR: NOT SMALLER THAN GROUND- USE #6TOTAL SINGLE INVERTER CIRCUIT MINIMUM SIZE BEFORE VOLTAGE DROP = 3-#3/0, #6 NEU #6 GND IN 2" CONDUIT BEFORE VOLTAGE DROP ADJUSTMENTSPROTECTED BY 175A OCPD. SEE ONE LINE DIAGRAM FOR VOLTAGE-DROP ADJUSTED FINAL SIZES.________________________________________________________________________________________________________________________________

POINT TO POINT FAULT CURRENT:3Ø TRANSFORMER IF.L.A = (kVA x 1000)/(EL-L x 1.732)MULTIPLIER = 100/%ZTRANSFORMERf = (1.732 x L x I3Ø)/(C x n x EL-L)M = (1)/(1 + f)IS.C. = IF.L.A x MWHERE:L = LENGTH (FEET) OF CONDUCTOR TO FAULTC = CONSTANT (BASED ON CONDUCTOR SIZE)n = NUMBER OF CONDUCTORS PER PHASEI3Ø = AVAILABLE SHORT-CIRCUIT CURRENT IN AMPERES AT BEGINNING OF CIRCUITE = VOLTAGE OF CIRCUIT

DC AMPACITY CALCULATIONSASSUMPTIONSNEC 2014 APPLIESROOF SUN-EXPOSED CONDUITSMAX 24 CONDUCTORS CONDUIT FILL (DERATE 45% PER TABLE 310.15(B((3)(a))ASHRAE 2% HI TEMP = 34C, LOW = -29C (SPRINGFIELD REGIONAL AIRPORT)ALL TERMINALS 75C RATED OR HIGHERSOLAR PANEL GCL 340W - Isc=9.49A

SINGLE STRING: SHORT CIRCUIT CURRENT (Isc) =9.49A Imax = 9.49A X 1.25 = 11.86A (ARTICLE690.8(A)(1))

MINIMUM CONDUCTOR AMPACITY = Imax X 150% = 11.86 X 1.25 = 14.83A (ARTICLE 690.8(B)(1))

TOTAL AMPACITY ( 75C COLUMN NEC TABLE 310.15(B)(16)) = 35A USING #10 CU

BACK CHECK FOR TEMP: (310.15(B)(16) 90C COLUMN AMPACITY) X (CONDUIT FILL) X (AMPACITY TEMPCORRECTION) MUST BE GREATER THAN Imax.

FOR #10 35A X 0.45 X .76 = 11.97A 11.97A > 11.86A THEREFORE #10 IS ACCEPTABLE MINIMUM SIZE.

STRING OCPD: 11.86A X 1.25 =14.83A NEXT HIGHER SIZE = 15A (ARTICLE 690.9(B))

MAXIMUM STRING VOLTAGE

46.6V

10

0.32%/C

-19°C (SPRINGFIELD REGIONAL AIRPORT)

MODULES IN SERIES & Voc: 10*46.6V = 466V

25°C(STC) MIN. TEMP.: 25°C-(-19°C) = 44°C

TEMP. COEFF. & TEMP. DIFF.: 0.32%/C*44°C = 14.08%

466V*(1+14.08/100) = 531.61V

MODULE Voc @ STC

MODULES IN SERIES

MODULE Voc TEMP. COEFF.

MIN. EXPECTED TEMP. (ASHRAE)

STRING Voc

TEMP. DIFFERENCE

% VOLTAGE INCREASE

MAX. VOLTAGE

GCL-P6/72H (OR APPROVED SUBSTITUTE)MODULE PART NUMBER

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

EL

EC

TR

IC

AL

S

CH

ED

. &

C

AL

CS

.

02/26/18

E-6

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

E-6

1

SCALE

N.T.S.

ELECTRICAL SCHEDULE & CALCS

AutoCAD SHX Text
TRANSFORMER I = (kVA x 1000)/(E x 1.732)
Page 8: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

A. CAUTION LABEL FOR PHOTOVOLTAIC SYSTEM CONNECTED. APPLIEDTO ALL PHOTOVOLTAIC AC DISCONNECTING MEANS AND TO NEWBILLING METER. LABEL WITH YELLOW BACKGROUND AND BLACKLETTERS.

B. WARNING LABEL FOR DUAL POWER SOURCE PRESENT. APPLY TOUTILITY METER AND PULL BOXES.

C. WARNING LABEL FOR DISCONNECTING MEANS WHERE BOTH SIDESMAY BE ENERGIZED IN THE OPEN POSITION. APPLY TO PHOTOVOLTAICAC DISCONNECTING MEANS, ALL PANELBOARDS, AND ALL PULL BOXES.

D. LABELS FOR AC DISCONNECTS IDENTIFICATION. APPLY TOPHOTOVOLTAIC AC DISCONNECTING MEANS. LABEL WITH REDBACKGROUND AND WHITE LETTERS LABEL (WITH WHITE STRIPE ALONGCENTER), YELLOW BACKGROUND AND BLACK LETTERS.

E. LABEL FOR AC DISCONNECTS IDENTIFICATION. APPLY TOPHOTOVOLTAIC AC DISCONNECTING MEANS. LABEL WITH REDBACKGROUND AND WHITE LETTERS. INFORMATION IN BLACK LETTERSWITHIN WHITE BOXES.

F. LABEL FOR DC DISCONNECT IDENTIFICATION. APPLY TO ALL COMBINERBOXES AND RE-COMBINERS. LABEL WITH RED BACKGROUND ANDWHITE LETTERS. LABEL WITH WHITE STRIPE ALONG CENTER.

G. LABEL FOR DC DISCONNECT INFORMATION. APPLY TO ALL COMBINERBOXES AND RE-COMBINERS. LABEL WITH RED BACKGROUND ANDWHITE LETTERS. INFORMATION IN BLACK LETTERS WITHIN WHITEBOXES.

H. WARNING LABEL FOR DC DISCONNECTS. APPLY TO ALL COMBINERBOXES AND RE-COMBINERS.

I. GENERIC EQUIPMENT NUMBERING LABEL: ONE PER SWITCHBOARD,ONE PER PANELBOARD, ONE PER INVERTER AND ONE PERTRANSFORMER.

J. CONDUIT RUN FROM RACKING TO INVERTERS AND COMBINER BOXESTO INVERTER (AS NEEDED).

K. ARC FLASH WARNING LABEL SHALL BE PLACED ON ALL EQUIPMENT ASREQUIRED BY CEC 110.16 INCLUDING, BUT NOT LIMITED TO, COMBINERBOXES, DISCONNECTS, INVERTERS, PANELBOARDS, ANDSWITCHBOARDS. TOTAL QUANTITY TO BE DETERMINED BYCONTRACTOR.

L. WARNING LABEL FOR EACH JUNCTION BOX, COMBINER BOX,DISCONNECT, AND DEVICE WHERE UNGROUNDED DC CONDUCTORSMAY BE EXPOSED DURING SERVICE.

M. PANELBOARDS WARNING LABEL. SHALL BE PLACED ON ALLPANELBOARDS IN WHICH BUS HAS BOTH UTILITY INTERACTIVEINVERTER(S) AND UTILITY FEEDER CONNECTED.

N. STAMPED BRASS, ALUMINUM, OR STAINLESS STEEL TAG, INDICATINGTHE ADDRESS. (INSTALLED AT PV PRODUCTION METER AND NEWBILLING METER).

O. STAMPED BRASS, ALUMINUM, OR STAINLESS STEEL TAG, MAKRED "PVPROD METER". (INSTALLED AT PV PRODUCTION METER).

P. RAPID SHUTDOWN LABEL TO BE INSTALLED A PV AC DISCONNECT. REDHEADING WITH WHITE LETTER. SITE DIAGRAM IN BLACK LINE TYPE WITHWHITE BACKGROUND

4"

< < EQUIP # # > >

1"

3/8"

5"

3/8"

POWER SOURCE

WARNING: PHOTOVOLTAIC

1 1/14

"

2 1/2"

4"

WARNING!

Appropriate Personal Protection

Equipment Required

3/8"

5/32"

ARC FLASH AND

SHOCK HAZARD

1/4"

2 1/2"

4"

WARNING!

ELECTRICAL SHOCK HAZARD

THE DC CONDUCTORS OF THIS

PHOTOVOLTAIC SYSTEM ARE

UNGROUNDED AND MAY BE

ENERGIZED

3/8"

5/32"

1 3/4"

4"

WARNING!

3/8"

5/32"

INVERTER OUTPUT CONNECTION

DO NOT RELOCATE THIS

OVERCURRENT DEVICE

CAUTION: PHOTOVOLTAIC

SYSTEM CONNECTED

5"

1"

1/4"

4 3/4"

WARNING: DUAL POWER SOURCE

2ND SOURCE IS PHOTOVOLTAIC SYSTEM

!

3/4"

5/32"

2 1/2"

4"

WARNING!

ELECTRICAL SHOCK HAZARD

DO NOT TOUCH TERMINALS

TERMINALS ON BOTH LINE AND

LOAD SIDES MAY BE ENERGIZED

IN THE OPEN POSITION

3/8"

5/32"

6"

PHOTOVOLTAIC AC DISCONNECT

MAXIMUM AC OPERATING CURRENT:

2 1/2"

175A

NOMINAL OPERATING AC VOLTAGE: 208V

1/4"

5/32"

AC DISCONNECT

5"

PHOTOVOLTAIC

3/8"

2 1/2"

DC DISCONNECT

3"

PHOTOVOLTAIC

3/8"

1 1/4"

3 3/4"

2 1/2"

6/32"

5/32"

OPERATING CURRENT:

OPERATING VOLTAGE:

PV SYSTEM DC DISCONNECT

MAX. SYSTEM VOLTAGE:

SHORT CIRCUIT CURRENT:

36A

382V

532V

48A

LABELS AND MARKINGS LEGEND

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

3"

4"

WARNING!

3/8"

ELECTRICAL SHOCK HAZARD

DO NOT TOUCH TERMINALS

TERMINALS ON BOTH LINE AND

LOAD SIDES MAY BE ENERGIZED

IN THE OPEN POSITION

DC VOLTAGE IS ALWAYS PRESENT

WHEN SOLAR MODULES

ARE EXPOSED TO SUNLIGHT

5/32"

SOLAR PV SYSTEM

3/8"

FED BY SOLAR PV SYSTEM

PV AC DISCONNECT

5"

1"

1/4"

INV-01 & INV-02

TURN RAPID SHUTDOWN SWITCH TO THE"OFF" POSITION TO SHUT DOWN

CONDUCTORS OUTSIDE THE ARRAY.CONDUCTORS WITHIN THE ARRAYREMAIN ENERGIZED IN SUNLIGHT.

CAUTION

1/4"

6"

8"

3/8"

INSTALLED AT PV PRODUCTION METER, PV ACDISCONNECT "PVD", AND MAIN SERVICE DISCONNECT.

EQUIPPED WITH

RAPID SHUTDOWN

AC DISCONNECT -

"PVD"

PV PRODUCTION

METER

SERVICE

DISCONNECT FEEDS

PANELBOARD "P2"

P2

SOLAR ARRAY - ROOF MOUNTED

INV-01

INV-02

INV-03

3 3/4"

2 1/2"

6/32"

5/32"

OPERATING CURRENT:

OPERATING VOLTAGE:

PV SYSTEM DC DISCONNECT

MAX. SYSTEM VOLTAGE:

SHORT CIRCUIT CURRENT:

36A

344V

479V

48A

INV-03

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

EL

EC

TR

IC

AL

L

AB

EL

IN

G

02/26/18

E-7

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

E-7

1

SCALE

N.T.S.

ELECTRICAL LABELING

GENERAL NOTES1. SOLAR MODULES ARE SUPPLIED FROM THE MANUFACTURER WITH

MARKINGS PRE-APPLIED TO MEET THE REQUIREMENTS OF THENATIONAL ELECTRIC CODE (NEC).

2. FINAL LABEL QUANTITIES, TEXT, AND LOCATIONS TO BEDETERMINED BY CONTRACTOR. FINAL LABEL QUANTITIES, TEXT,AND LOCATIONS TO BE DETERMINED BY CONTRACTOR.

3. THE LABELING, MARKING, IDENTIFICATION, AND GROUPINGREQUIREMENTS OF THE 2011 EDITION OF THE NEC SHALL BEAPPLICABLE TO THIS PHOTOVOLTAIC PROJECT.

4. IN ADDITION TO NEC REQUIRED LABELING, ALL MAJOR ELECTRICALEQUIPMENT SHALL BE IDENTIFIED PER SPECIFICATIONS IN THISPLAN SET. LABELS SHALL BE SUITABLE FOR THE ENVIRONMENT INWHICH THEY ARE INSTALLED.

5. INTERCONNECTION EQUIPMENT AND MATERIALS, INCLUDINGSHARED EQUIPMENT WITH THE UTILITY, SHALL BE LABELED PERUTILITY SPECIFICATIONS.

6. ALL WARNING, CAUTION, AND/OR DANGER LABELS TO COMPLY WITHANSI Z535.4-2011 STANDARD FOR PROPER TEXT SIZE, DESIGN, ETC.

Page 9: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

DA

TA

S

HE

ET

S

02/26/18

E-8

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com

Page 10: 39.44 kW DC SOLAR PV PROJECToperations-webapps.missouri.edu/pdc/adsite/projects/cp172501/reference/FOR REFERENCE...project site southwest research center 14585 state hwy h mt. vernon,

REVISION

SHEET NUMBER:

PROJ

. NO.

:

1 2 3 4 5 6 7 8

A

B

C

D

E

DATE

:RE

VISI

ONNO

DRW

NDA

TECH

KDDA

TEAP

PVD

DATE

1 2 3 4 5 6 7 8

F

DA

TA

S

HE

ET

S

02/26/18

E-9

0

SOLAR PHOTOVOLTAIC ARRAY

1711-02

SOUTHWEST RESEARCH CENTER

14548 STATE HIGHWAY H

MT. VERNON, MO 65712

0P

K02/26/18

SC

HE

MA

TIC

S

ET

1P

K03/21/18

FIN

AL

O

WN

ER

R

EV

IE

W S

ET

224 N

. 7T

H S

TR

EE

T

ST

. LO

UIS

, M

O 63101

ww

w.m

icrogridenergy.com