32 line protection.pdf
TRANSCRIPT
Line Protection
1
LINE PROTECTION OLEH :
SUPRIYANTO, ST., MT
PROTEKSI JARINGAN DISTRIBUSI
1. Circuit breakers & relays
2. Fuses: Unique in their time-overcurrent characteristics
3. Sectionalizers: Unique in their own right
4. Reclosers
Line Protection
2
SETTING OCRGANGGUAN FASA – FASA [ TUNDA WAKTU
.max
%80
2,11,1
maxminmax
minmaxmin
]2....[min8,0max
]1.....[min
max
2
max
arusbebanI
k
k
IIII
IIII
II
k
IkI
D
S
SETSETSETSET
SETSETSETSET
HSSET
D
SSEI
PROTEKSI JARINGAN DISTRIBUSISETTINGS RULES
Selectivity : time dial
Curves are to be adjusted in order to maintain “margin” or separation
• 0.3 seconds between relay curves
• 3 to 6 cycles (0.05—0.1 seconds of this gets “used up” due to device operation (breaker, recloser, etc.)
• Remember to account for differing values of maximum available fault current at each bus…this will allow faster operating times
Line Protection
3
KOORDINASI OCR
# DEFINITE TIME
A B C
t
I
0,3 det
0,8 det
1,3 det
det5,04,0
t
ttt
IIII
ABC
HSSASBSC
KOORDINASI OCR
# INVERSE TIME
A B C
t
I
TMS ATMS B TMS C
SETING WAKTU DENGAN PEMILIHAN TD / TMSTD = TIME DIALTMA = TIME MULTIPLE SETTING
Line Protection
4
SETTING ELEMEN INSTANTANEOUS
DIMAKSUDKAN UNTUK GANGGUAN 3 FASA ,TETAPI HARUSMEMPERHATIKAN ARUS KETAHANAN KABEL .
abelkemampuankSET
HSSETHS
II
III
2
312 minmin
SETTING INSTANT
212
121
SETSETSETSET
SETSETSETSET
IIII
IIII
KOORDINASI OCR
# INSTANTANEOUS
A B C
CIBinstI
BIAinstI
HSSET
HSSET
3
3
2,1.
2,1.
Line Protection
5
KOORDINASI DARI RELAI KOMBINASI TUNDA WAKTUDENGAN INSTANT /
A B C
t
I
TMS ATMS B TMS C
t
I
t A
t B
t Ct INST t INST
t INST t INST
PROTEKSI JARINGAN DISTRIBUSI(SETTINGS RULES)
1. Set pickup at no more than 1/3 minimum fault current in the zone
2. Set pickup at least 2.5x the peak load expected at the device
Line Protection
6
PROTEKSI JARINGAN DISTRIBUSISETTINGS RULES
Sensitivity (reach) for ground relays:(ground relays “see” LLG, SLG faults)
1. Set pickup at no more than 1/3 of minimum fault current (smallest of the above types) in the zone
2. Typical setting: 240 amps
3. Remember, phase relays react to all faults, ground relays only react to LLG, SLG faults
PROTEKSI JARINGAN DISTRIBUSISETTINGS RULES
Selectivity : pickup value
Each device is to be considered in its own zone
• Set pickup• ≤ 1/3 minimum fault current in the zone
• ≥ 2.5x the peak load expected at the device
• Good idea to stagger pickup values along feeder to avoid miscoordination for overload trips; nature of radial loading allows this to be done.
Line Protection
7
DISTRIBUTION PROTECTION & SECTIONALIZING DEVICES
Circuit breakers & relays
• Most versatile in terms of settings – pickup and time dial are field adjustable
Fuses: Unique in their time-overcurrentcharacteristics
Sectionalizers: Unique in their own right
Reclosers
• Extremely common device, but they are really just circuit breakers in a specific application…same rules & tactics apply as breakers & relays!
FUSE
Fuse dan Recloser diterapkan pada feeder radial dalambentuk 3 fasa atau satu fasa (Blackburn, J. L. 1998). Fuseyang dirancang untuk tegangan di atas 600V masuk dalamkategori Fuse Cut Out atau tenaga (Gonen, T,1986),meskipun secara spesifik digunakan untuk tegangan 34.5kV atau lebih.
Line Protection
8
TIPE LINKLink terdiri dari tipe K (cepat) atau T (lambat). Fusetipe expulsion memadamkan busur api gangguan padasaat arus gangguan mencapai zero crossing. Fusejenis ini paling umum digunakan pada jaringan udara
•Fuse dan Fuse Link
Line Protection
9
Karakteristik dari pelebur ialah lamanya waktupemutusan yang tergantung dari besarnya arus yangmengalir pada peleburnya.
Perbedaan kurva antara kedua tipe didasarkan pada“speed ratio”, yaitu perbandingan antar arus lelehminimum pada 0,1 detik dan arus leleh minimum pada300 atau 600 detik. Untuk fuse link tipe “K” (tipe cepat)speed ratio = 6-8. Untuk fuse link tipe “T” (tipe lambat)speed ratio = 10-13. (Gonen, T.,1986).
Fused cutout
Inexpensive
Reliable
Line Protection
10
Fuse link
FUSES - GENERAL
Purposes
• To protect equipment from high overload currents
• To protect the system from failed equipment
• For sectionalizing
Design
• Generally consists of a “fusible element” made of soft metal
• All fuses have a maximum load current they can carry
Line Protection
11
EXPULSION FUSES - CONTINUED
Operation
• When exposed to the high current of a fault, the fusible element heats and melts
• Heat from arc releases de-ionizing gases from lining of fuse tube
• As these gases build up, the arc is stretched, compressed & cooled
• The arc that is drawn across the severed pieces of metal is then extinguished to open the circuit
• Circuit is interrupted when the current passes through zero
Considered to be “zero-awaiting” devices because they await the passing zero point to extinguish an arc
EXPULSION FUSES - CONTINUED
Application
• Most often located outdoors, typically in fused cutouts
Expulsion fuse “speed” characteristics
• Type KS (Slow links) – Used to protect transformers and distribution lines while remaining relatively insensitive to current transients
• Type K (Faster) – Used to protect tap lines which need to be de-energized quickly whenever a fault occurs, and also to protect capacitor banks
• Many others (T, N, Q, QA, etc.)
Relatively low cost
Line Protection
12
TypeNominalRating *
Maximum Load Current150% Nominal (Amps)**
Interrupting Capacity(Amps)
57
101520253040506580
7.510.515
22.530
37.5456075
97.5100 ***
Interrupting capacity is determined by thecutout -- not by the fuse.The cutout can interrupt12,000 Amps (asymmetrical)
7,500 Amps (symmetrical)
100 100 ***
KS
K & KS
K
Line Protection
13
KONSEP DASAR KOORDINASI PROTEKSI
Champbell, HE, (1988)
Line Protection
14
PERTIMBANGAN TERMAL THD FUSE PADA PROSES REC
Champbell, HE, (1988)
KONSEP KOORDINASI PROTEKSI
Champbell, HE, (1988)
Line Protection
15
DISTRIBUTION PROTECTION & SECTIONALIZING DEVICES
Circuit breakers & relays
• Most versatile in terms of settings – pickup and time dial are field adjustable
Fuses: Unique in their time-overcurrent characteristics
Sectionalizers: Unique in their own right
Reclosers
• Extremely common device, but they are really just circuit breakers in a specific application…same rules & tactics apply as breakers & relays!
Single phase pole top recloser
Oil-filled tank
Current-operated solenoid
Hydraulic trip & reclose timing mechanisms
Interrupting contacts (oil)
Typical 2,500-4,000 amp interrupting rating
Typical 50-200 amp load rating
Inexpensive, fault sensing & interrupting, automatic reclosing
Line Protection
16
Current (Amps)
Tim
e (S
econ
ds)
100 2K300 700 3K0.030.05
1
0.1
0.7
Time-Current Curves for a 50A Hydraulic Recloser
C
B
A
Slow Trips
Fast Trip
7
5
32
0.5
0.3
0.2
0.07
50 4K 5K1K500
Reclosers on Distribution Feeder
Reclosers
FCB
Line Protection
17
DISTRIBUTION PROTECTION & SECTIONALIZING DEVICES
Circuit breakers & relays
• Most versatile in terms of settings – pickup and time dial are field adjustable
Fuses: Unique in their time-overcurrent characteristics
Sectionalizers: Unique in their own right
Reclosers
• Extremely common device, but they are really just circuit breakers in a specific application…same rules & tactics apply as breakers & relays!
Line Protection
18
Single phase hydraulic sectionalizer
Works in conjunction with upstream reclosing devices
Inexpensive, fault sensing but non-interrupting
Single phase cutout-mounted sectionalizer
Works in conjunction with upstream reclosing devices
Inexpensive, fault sensing but non-interrupting
Solid dielectric
Line Protection
19
Purpose of a Sectionalizer
The purpose of a sectionalizer is to automatically isolate a faultedsection of feeder, but unlike a fuse or recloser, it cannot actuallyinterrupt fault current. Instead, the sectionalizer opens only afterthe line has been temporarily de-energized by an upstream breakeror recloser.
SECTIONALIZER CHARACTERISTICS
Specifically designed for the protection of single-phase lateral lines
Located on the distribution line in locations similar to tap fuses
Cannot actually interrupt fault current
Operates in conjunction with a line recloser or with the substation FCB
Senses the presence and removal of an overcurrent, and drops out while the upstream device is open after that device has operated for a preset number of counts
Line Protection
20
SECTIONALIZER CHARACTERISTICS (CONTINUED)
Basically a counting device
• It counts the number of times it sees fault current flow and then subsequently removed.
• If the preset count is reached, the sectionalizer opens while the upstream protective device (recloser or breaker) is open.
• If the preset count is not reached, the sectionalizer will reset to a zero count after approximately 25 seconds.
Sometimes considered a “smart fuse,” but it is much better to call it a “smart switch”
HOW IS THE OPERATION OF A SECTIONALIZER SIMILAR TO THAT OF A FUSE?
Like a fuse, the sectionalizer is intended to operate in conjunction with a source-side recloser or with the substation FCB
Like a fuse, it isolates (sectionalizes) the faulted portion of the line from the main line
Line Protection
21
HOW IS THE OPERATION OF A SECTIONALIZER DIFFERENT FROM THAT OF A FUSE?Main advantage is that it has no time-current characteristics that must be coordinated with another device
Can discriminate between temporary and permanent faults
Can be used over the full range of available fault currents
Will not operate due to cold-load pickup
Can be used in close-in taps where high available fault current prevents fuse coordination
Cannot acquire “pre-damage” problems
Like a fuse, it isolates (sectionalizes) the faulted portion of the line from the main line
Recloser -- Sectionalizer Coordination
Reclosers
Sectionalizer(Set to 3 Counts)
Three-PhasePrimary
AFCB
Line Protection
22
Quiz on Sectionalizers
1. Explain the function of the sectionalizer in the figure below:
Reclosers
Sectionalizer(Set to 3 Counts)
FCB
Quiz on Sectionalizers
1. Explain the function of the sectionalizer in the figure below:
Ans. • If a permanent fault occurs downstream of the sectionalizer, the
sectionalizer counts the number of times that fault current flows, followed by an interruption.
• At the count of “3” (i.e., the recloser has operated twice on its fast curve and once on its delay curve), the sectionalizer drops out and therefore isolates the faulted branch of the circuit. The recloser then re-energizes the rest of the circuit.
• If the fault is a temporary fault, the recloser will trip and reclose, and the fault will be gone.
• The sectionalizer will have counted to “1”, but since the fault has disappeared and the circuit is restored, it will time out after 25 seconds and return its count to zero.
Line Protection
23
2. What is the main advantage of sectionalizers over fuses?
Ans. The sectionalizer has no time-current curve to coordinate with other devices --thus making coordination easier.