3 smart positioner

21
February 6, 2022 PMI Revision 00 1 SMART POSITIONER SYSTEM

Upload: njc6151

Post on 10-Apr-2015

165 views

Category:

Documents


11 download

TRANSCRIPT

Page 1: 3 Smart Positioner

April 11, 2023 PMI Revision 00 1

SMART POSITIONER

SYSTEM

Page 2: 3 Smart Positioner

April 11, 2023 PMI Revision 00 2

Pressure Sensor Position Sensor

Microprocessor

Current Generator

EPC

0 to1.4 mA

COMMON SUPPLY

OUTPUT

EXHAUST

EXHAUST

4.5 to 7.5 psi

Temperature Sensor

Push Buttons LCD

Operating Logic Block of Digital Positioner

Page 3: 3 Smart Positioner

April 11, 2023 PMI Revision 00 3

• Hart Protocol transmit waveform• Two Way Digital Communication

How Digital Positioners Communicate

Page 4: 3 Smart Positioner

April 11, 2023 PMI Revision 00 4

History Lesson

Smart - HARTSmart - HARTSVI PositionerSVI Positioner

ValVueValVue

Smart - FieldBus FVP Positioner

ValVue FFSmart - HARTSmart - HART

SVI II PositionerSVI II PositionerValVue ™ 2.0ValVue ™ 2.0

Conventional Conventional PositionerPositioner

Value & Value & PerformancePerformance

Smart - HARTSmart - HARTDLT LevelDLT Level

Smart - HARTSmart - HARTAMSAMS

- Compliance- Compliance- SNAP ON® - SNAP ON®

Page 5: 3 Smart Positioner

April 11, 2023 PMI Revision 00 5

• Diagnostics Online or On Demand:

– Advance Valve Signatures– Step Response & Stroking Speed– Friction– Valve Travel Odometer– Calibration & Configuration History– Valve Signatures stored @ the Valve

Available Diagnostics

Page 6: 3 Smart Positioner

April 11, 2023 PMI Revision 00 6

Flow Curves

0

20

40

60

80

100

0 20 40 60 80 100Input

Out

put

Quick Opening

LinearEqual % 50Equal % 30

Traditional Characterization

Page 7: 3 Smart Positioner

April 11, 2023 PMI Revision 00 7

Positioner Custom characterizationSolves Many Issues

Page 8: 3 Smart Positioner

April 11, 2023 PMI Revision 00 8

Ease of set-up & Calibration Self Tuning- Special Settings Improved Accuracy Custom Characterization Curves Diagnostics – Lower Maintenance Costs Severe Applications – Remote Mounting Basic Digital Positioner Closes Price Gap Lower Total Cost of Ownership

Digital PositionerBenefits- New Installations

Page 9: 3 Smart Positioner

April 11, 2023 PMI Revision 00 9

Pro’s Improved Performance New Diagnostics Capabilities Longer Valve Life & Less Trim Repairs Lower Maintenance Time & Costs Plant Standardization

Con’s Somebody has to do the leg work and training Initial Investment takes few years to see

return

Digital PositionerRetrofits – Pro’s & Con’s

Page 10: 3 Smart Positioner

April 11, 2023 10

PC Solutions

Control Evolution

Past Present Future

DCS Solutions

Analog

Proprietary Bus

Field Based Application Solutions

Open Field Bus

Page 11: 3 Smart Positioner

April 11, 2023 PMI Revision 00 11

Diagnostics TestingBasic vs. Advanced

Online vs. Offline

Page 12: 3 Smart Positioner

April 11, 2023 PMI Revision 00 12

• Position Signature

Dynamic Statistical Analysis

2” 78200 0.375” Stroke

Page 13: 3 Smart Positioner

April 11, 2023 PMI Revision 00 13

• Position Signature

• Zoom Scale @ 11 %

Dynamic Statistical Analysis

2” 78200 0.375” Stroke

Page 14: 3 Smart Positioner

April 11, 2023 PMI Revision 00 14

• Position Signature

• Zoom Scale @ 11 %

• Blue Trace Signal to Retract

Dynamic Statistical Analysis

2” 78200 0.375” Stroke

Page 15: 3 Smart Positioner

April 11, 2023 PMI Revision 00 15

• Position Signature

• Zoom Scale @ 11 %

• Blue Trace Signal to Retract

• Red Trace Signal to Extend

Dynamic Statistical Analysis

2” 78200 0.375” Stroke

Page 16: 3 Smart Positioner

April 11, 2023 PMI Revision 00 16

• Position Signature

• Zoom Scale @ 11 %

• Blue Trace Signal to Retract

• Red Trace Signal to Extend

• Note Galling indications for the 6 % of initial stroke

Dynamic Statistical Analysis

2” 78200 0.375” Stroke

Page 17: 3 Smart Positioner

April 11, 2023 PMI Revision 00 17

• Position Signature

• Zoom Scale @ 11 %

• Blue Trace Signal to Retract

• Red Trace Signal to Extend

• Note Galling indications for the 6 % of initial stroke

• Also note that 6% of 0.375 is 0.022 “ of stroke

Dynamic Statistical Analysis

2” 78200 0.375” Stroke

Page 18: 3 Smart Positioner

April 11, 2023 PMI Revision 00 18

• Position Signature

• Zoom Scale @ 11 %

• Blue Trace Signal to Retract

• Red Trace Signal to Extend

• Note Galling indications for the 6 % of initial stroke

• Also note that 6% of 0.375 is 0.022 “ of stroke

• Notice 0.8 mA dead zone due to Friction from 20 mA to 19.2 mA

Dynamic Statistical Analysis

2” 78200 0.375” Stroke

Page 19: 3 Smart Positioner

April 11, 2023 PMI Revision 00 19

As Built Factory Signature for 2 Inch Rising Stem

• #6 Multispring Actuator

• Air to Open

• Spring to Close

• 11 - 23 # Bench Range

• Teflon / Kevlar Packing

• Factory Signature Speed Range 1

Original Findings

Page 20: 3 Smart Positioner

April 11, 2023 PMI Revision 00 20

Incorrect Stem Adjustment

• Signature compares current and factory signature

• Note: Dramatic shift to right of curves

• Note: Diagnostic data spring range has shifted

• Indication: Incorrect stem adjustment or overseated plug.

• Recommendation: Readjust stem position & retest

Original Findings Current Findings

Page 21: 3 Smart Positioner

April 11, 2023 PMI Revision 00 21

THANK YOU