3. Distributor type MULTI FDX (3 phase)
237 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.1 Power supply
External wiring procedure- The power supply work is needed only to the outdoor unit. The power supply to the BD unit and the indoor unit is conduct-
ed through the transmission wiring. Therefore, the power supply work can be carried out at just one place of the outdoorunit. It will contribute to simplify the work procedure and to save cost.
- Wiring cable size must comply with the applicable local and national code.
Outdoor unit
Power source
Circuit breaker
Indoor unit
BD unit
R
Earth wire
Type Outdoor unit Capacity [kBtu/h(kW)] Circuit breaker capacity Power supply
A6UW368FA0 [FM37AH UE0] 33(9.7)
Heat pumpA7UW428FA3 [FM41AH U33] 46(13.5)
20A 3ø, 380-415V, 50HzA8UW488FA3 [FM49AH U33] 53(15.5)
A9UW548FA3 [FM57AH U33] 57(16.7)
-
Heat pump 50Hz/R410A _ 238
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
3.2 List of functions
O : Applied X : Not applied – : No relationOption : Model name & price are different according to options, and assembled in factory with main unit.Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.
Defrost / DeicingHigh Pressure SwitchLow Pressure SwitchPhase protectionRestart Delay (3-minutes)Self DiagnosisSoft StartTest FunctionAuto operation(Artificial intelligence) Auto Restart OperationCentral control(LGAP)PDI(Power Distribution Indicator)PI485Thermistor
O O O OO X X XO O O OO O O OO O O OO O O OO O O OO O O OO O O OO O O OO O O O
PQNUD1S00 PQNUD1S00 PQNUD1S00 PQNUD1S00PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0
- - - -
FunctionCategoryA6UW368FA0[FM37AH UE0]
A7UW428FA3[FM41AH U33]
A8UW488FA3[FM49AH U33]
A9UW548FA3[FM57AH U33]
Reliability
Convenience
Others
CAC NetworkFunction
-
3. Distributor type MULTI FDX (3 phase)
239 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.3 Specifications
Dimensions W x H x D mm(inch)Net Weight kg(lbs)Max. Number of Connectable Indoor UnitsCompressor Type(Inverter) Qty x Model
Motor TypeOil Charge volume ccOil Type
Refrigerant Charge (at 5m) g(oz)TypeControl
Heat Exchanger Rows x Column x FPIDefrosting Method
Fan Capacitor μF/VacDriveDischarge direction Side / TopAir Flow Rate CMM(CFM)
Noise Level(H/L) Sound Pressure at 1m dB(A)±3Piping connections Liquid(Ø) mm(inch)
Gas(Ø)Max. Interunit Total Piping(Main+Total Branch) mPiping Length Main Piping m
Total Branch Piping mEach Branch Piping m
Max. Elevation Indoor Unit~Outdoor Unit mDifference Indoor Unit~Indoor Unit m
870 x 1,038 x 320 (34.3 x 40.9 x 12.6) 950 x 1,380 x 330 (37.4 x 54.3 x 12.3)80(176) 108(238)
6 7Twin rotary Twin-Rotary
1 x 5KD240X 5JD420ZBLDC BLDC900 1,300
FV50S FV50S2,800(98.8) 4,800(169.3)
R410A R410AEEV EEV
2R x 48C x 18 2R x 64C x 17Reversing cycle Reversing cycle
- -Direct Drive Direct Drive
Side Side32(1,130) x 2 60(2,119) x 2
51/47 586.35(1/4) 9.52(3/8)
15.88(5/8) 19.05(3/4)100 12540 5560 7020 1530 3015 15
Running Current Cooling AHeating A
Starting Current (Cooling/Heating) APower Supply Ø / V / HzPower Supply Cable (outdoor) No. x mm2
Power and transmission cable (outdoor to BD) No. x mm2
Power and transmission cable (BD to indoor) No. x mm2
3.4 ~ 5.4 ~ 6.0 1.5~7.2~8.13.5 ~ 5.4 ~ 6.1 1.7~7.5~8.0
4.8 -3 / 380-415 / 50 3/380-415/50
5 x 2.5 5 x 2.5(including earth)4 x 1.25 (Including Earth) 4 x 1.25(including earth)4 x 0.75 (Including Earth) 4 x 0.75(including earth)
Nominal Capacity Cooling kW(Min~Rated~Max) Btu/h
Heating kWBtu/h
Nominal Input Cooling kW(Min~Rated~Max) Heating kWEnergy labelTesting Combination
6.33~9.67~10.8 2.8~13.5~14.121,600~33,000~37,000 9,600~46,000~48,000
6.68~11.1~12.3 3.2~14.1~15.222,800~38,000~42,000 10,752~48,000~52,000
1.80~3.00~3.45 0.8~4.0~4.91.83~3.05~3.51 0.89~3.9~5.1
A/A A/A
MS07AH N40 x 6EA MS07AH N40 x 7EA
A6UW368FA0[FM37AH UE0]
A7UW428FA3[FM41AH U33]
Outdoor Unit
Note :1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2. Due to our policy of innovation some specifications may be changed without notification.3. At least two indoor units should be connected.4. Minimum combination capacity rate should be more than 40%5. Wiring cable size must comply with the applicable local and national code.
Conversion FormulakW = Btu/h × 0.0002931CFM = CMM × 35.3
-
Heat pump 50Hz/R410A _ 240
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
Dimensions W x H x D mm(inch)Net Weight kg(lbs)Max. Number of Connectable Indoor UnitsCompressor Type(Inverter) Qty x Model
Motor TypeOil Charge volume ccOil Type
Refrigerant Charge (at 5m) g(oz)TypeControl
Heat Exchanger Rows x Column x FPIDefrosting Method
Fan Capacitor μF/VacDriveDischarge direction Side / TopAir Flow Rate CMM(CFM)
Noise Level(H/L) Sound Pressure at 1m dB(A)±3Piping connections Liquid(Ø) mm(inch)
Gas(Ø)Max. Interunit Total Piping(Main+Total Branch) mPiping Length Main Piping m
Total Branch Piping mEach Branch Piping m
Max. Elevation Indoor Unit~Outdoor Unit mDifference Indoor Unit~Indoor Unit m
950 x 1,380 x 330 (37.4 x 54.3 x 12.3) 950 x 1,380 x 330 (37.4 x 54.3 x 12.3)108(238) 108(238)
8 9Twin-Rotary Twin-Rotary
5JD420Z 5JD420ZBLDC BLDC1,300 1,300
FV50S FV50S4,800(169.3) 4,800(169.3)
R410A R410AEEV EEV
2R x 64C x 17 2R x 64C x 17Reversing cycle Reversing cycle
- -Direct Drive Direct Drive
Side Side60(2,119) x 2 60(2,119) x 2
58 599.52(3/8) 9.52(3/8)
19.05(3/4) 19.05(3/4)135 14555 5580 9015 1530 3015 15
Running Current Cooling AHeating A
Starting Current (Cooling/Heating) APower Supply Ø / V / HzPower Supply Cable (outdoor) No. x mm2
Power and transmission cable (outdoor to BD) No. x mm2
Power and transmission cable (BD to indoor) No. x mm2
1.8~8.0~8.4 2.3~8.1~9.12.1~7.5~8.3 2.5~8.0~8.7
- -3/380-415/50 3/380-415/50
5 x 2.5(including earth) 5 x 2.5(including earth)4 x 1.25(including earth) 4 x 1.25(including earth)4 x 0.75(including earth) 4 x 0.75(including earth)
Nominal Capacity Cooling kW(Min~Rated~Max) Btu/h
Heating kWBtu/h
Nominal Input Cooling kW(Min~Rated~Max) Heating kWEnergy labelTesting Combination
3.3~15.5~17.0 4.0~16.7~18.5211,400~52,800~58,000 13,800~57,000~63,200
3.7~16.4~17.29 4.5~17.87~18.7512,768~56,000~59,000 15,456~61,000~64,000
0.94~4.6~5.4 1.0~4.91~5.71.13~4.45~5.2 1.49~4.55~5.65
A/A A/AMS07AH N40 x 5EAMS09AH N40 x 3EA
MS09AH N40 x 8EA
A8UW488FA3[FM49AH U33]
A9UW548FA3[FM57AH U33]
Outdoor Unit
Note :1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2. Due to our policy of innovation some specifications may be changed without notification.3. At least two indoor units should be connected.4. Minimum combination capacity rate should be more than 40%5. Wiring cable size must comply with the applicable local and national code.
Conversion FormulakW = Btu/h × 0.0002931CFM = CMM × 35.3
-
3. Distributor type MULTI FDX (3 phase)
241 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.4 Combination tableThe individual indoor unit capacity can be calculated as follows depending on the total connected capacity of all indoor units.
16 9,600 2.8 16,000 4.7 17,600 5.2 800 1,333 1,533 18 10,800 3.2 18,000 5.3 19,800 5.8 900 1,500 1,725 19 11,400 3.3 19,000 5.6 20,900 6.1 950 1,583 1,821 21 12,600 3.7 21,000 6.2 23,100 6.8 1,050 1,750 2,013 23 13,800 4.0 23,000 6.7 25,300 7.4 1,150 1,917 2,204 24 14,400 4.2 24,000 7.0 26,400 7.7 1,200 2,000 2,300 25 15,000 4.4 25,000 7.3 27,500 8.1 1,250 2,083 2,396 26 15,600 4.6 26,000 7.6 28,600 8.4 1,300 2,167 2,492 27 16,200 4.7 27,000 7.9 29,700 8.7 1,350 2,250 2,588 28 16,800 4.9 28,000 8.2 30,800 9.0 1,400 2,333 2,683 30 18,000 5.3 30,000 8.8 33,000 9.7 1,500 2,500 2,875 31 18,300 5.4 30,500 8.9 33,550 9.8 1,550 2,583 2,971 32 18,600 5.5 31,000 9.1 34,100 10.0 1,600 2,667 3,067 33 18,900 5.5 31,500 9.2 34,650 10.2 1,650 2,750 3,163 34 19,200 5.6 32,000 9.4 35,200 10.3 1,700 2,833 3,258 35 19,500 5.7 32,500 9.5 35,750 10.5 1,750 2,917 3,354 36 21,600 6.3 33,000 9.7 37,000 10.8 1,800 3,000 3,450 37 22,200 6.5 33,942 9.9 37,336 10.9 1,807 3,012 3,464 38 22,800 6.7 34,507 10.1 37,958 11.1 1,811 3,019 3,472 39 23,400 6.9 34,884 10.2 38,373 11.2 1,814 3,024 3,477 40 24,000 7.0 35,239 10.3 38,763 11.4 1,819 3,032 3,486 41 24,600 7.2 35,565 10.4 39,121 11.5 1,823 3,038 3,494 42 25,200 7.4 35,594 10.4 39,153 11.5 1,824 3,040 3,496 43 25,800 7.6 35,947 10.5 39,542 11.6 1,831 3,051 3,509 44 26,400 7.7 36,167 10.6 39,784 11.7 1,835 3,059 3,518 45 27,000 7.9 36,167 10.6 39,784 11.7 1,835 3,059 3,518 46 27,600 8.1 36,300 10.6 39,930 11.7 1,838 3,063 3,523
Total indoor unitcapacity(kBtu/h)
Min
Cooling capacity
Rating MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Models : A6UW368FA0[FM37AH UE0]
[Cooling capacity]
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB
2. Heating Capacity is based on : indoor temp.20°C DB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 16~46 Btu/h(40%~130%)
5. At least two indoor units should be connected.
Example) • Outdoor unit model : A6UW368FA0[FM37AH UE0]• Total indoor units combination : 7k + 9k + 9k + 9k + 9k• Each indoor unit combinational capacity?
- Qodu(rated) : 33 kBtu/h- ∑Qidu(rated) : 43 kBtu/h
∴ Qidu(combi) : [7k] = 33 x –––– = 5.4k But/h743
Qidu(combi) : [9k] = 33 x –––– = 6.9k But/h943
Individual indoor unit combinational capacity
[Qidu(combi)]
Outdoor unit rated capacity[Qodu(rated)]
x –––––––––––––––––––––––––––––––––––––––––––=Individual indoor unit rated capacity [Qidu(rated)]
Total connected indoor unit rated capacity [∑Qidu(rated)]
-
Heat pump 50Hz/R410A _ 242
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
[Heating capacity]
16 10,750 3.2 17,920 5.3 19,710 5.8 813 1,356 1,559 18 12,100 3.5 20,160 5.9 22,180 6.5 915 1,525 1,754 19 12,770 3.7 21,280 6.2 23,410 6.9 966 1,610 1,851 21 14,110 4.1 23,520 6.9 25,870 7.6 1,068 1,779 2,046 23 15,460 4.5 25,760 7.5 28,340 8.3 1,169 1,949 2,241 24 16,130 4.7 26,880 7.9 29,570 8.7 1,220 2,033 2,338 25 16,800 4.9 28,000 8.2 30,800 9.0 1,271 2,118 2,436 26 17,470 5.1 29,120 8.5 32,030 9.4 1,322 2,203 2,533 27 18,140 5.3 30,240 8.9 33,260 9.7 1,373 2,288 2,631 28 18,820 5.5 31,360 9.2 34,500 10.1 1,423 2,372 2,728 30 20,160 5.9 33,600 9.8 36,960 10.8 1,525 2,542 2,923 31 20,830 6.1 34,720 10.2 38,190 11.2 1,576 2,626 3,020 32 21,500 6.3 35,840 10.5 39,420 11.6 1,627 2,711 3,118 33 21,510 6.3 35,850 10.5 39,440 11.6 1,678 2,796 3,215 34 22,050 6.5 36,750 10.8 40,420 11.8 1,728 2,881 3,313 35 22,580 6.6 37,630 11.0 41,400 12.1 1,779 2,965 3,410 36 22,800 6.7 38,000 11.1 42,000 12.3 1,830 3,050 3,508 37 23,150 6.8 38,580 11.3 42,430 12.4 1,822 3,037 3,493 38 23,350 6.8 38,920 11.4 42,810 12.5 1,818 3,030 3,484 39 23,490 6.9 39,150 11.5 43,070 12.6 1,815 3,025 3,478 40 23,560 6.9 39,270 11.5 43,190 12.7 1,800 3,000 3,449 41 23,640 6.9 39,410 11.5 43,350 12.7 1,790 2,983 3,430 42 23,630 6.9 39,380 11.5 43,320 12.7 1,785 2,974 3,421 43 23,770 7.0 39,610 11.6 43,570 12.8 1,762 2,937 3,377 44 23,850 7.0 39,740 11.6 43,720 12.8 1,747 2,911 3,348 45 23,860 7.0 39,770 11.7 43,740 12.8 1,742 2,904 3,339 46 23,910 7.0 39,840 11.7 43,830 12.8 1,739 2,899 3,334
Total indoor unitcapacity(kBtu/h)
Min
Heating capacity
Rating MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB
2. Heating Capacity is based on : indoor temp.20°C DB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 16~46 Btu/h(40%~130%)
5. At least two indoor units should be connected.
-
3. Distributor type MULTI FDX (3 phase)
243 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
Models : A7UW428FA3[FM41AH U33]
[Cooling capacity]
16 9,600 2.8 16,000 4.7 17,600 5.2 796 1,327 1,526 18 10,800 3.2 18,000 5.3 19,800 5.8 893 1,489 1,712 19 11,400 3.3 19,000 5.6 20,900 6.1 943 1,572 1,807 21 12,600 3.7 21,000 6.2 23,100 6.8 1,042 1,737 1,998 23 13,800 4.0 23,000 6.7 25,300 7.4 1,011 1,684 1,937 24 14,400 4.2 24,000 7.0 26,400 7.7 1,053 1,755 2,019 25 15,000 4.4 25,000 7.3 27,500 8.1 1,096 1,826 2,100 26 15,600 4.6 26,000 7.6 28,600 8.4 1,161 1,935 2,225 27 16,200 4.7 27,000 7.9 29,700 8.7 1,227 2,044 2,351 28 16,800 4.9 28,000 8.2 30,800 9.0 1,292 2,153 2,476 29 17,400 5.1 29,000 8.5 31,900 9.3 1,357 2,262 2,602 30 18,000 5.3 30,000 8.8 33,000 9.7 1,423 2,372 2,727 31 18,600 5.5 31,000 9.1 34,100 10.0 1,488 2,481 2,853 32 19,200 5.6 32,000 9.4 35,200 10.3 1,554 2,590 2,978 33 19,800 5.8 33,000 9.7 36,300 10.6 1,619 2,699 3,104 34 20,400 6.0 34,000 10.0 37,400 11.0 1,685 2,808 3,229 35 21,000 6.2 35,000 10.3 38,500 11.3 1,750 2,917 3,355 36 21,600 6.3 36,000 10.5 39,600 11.6 1,816 3,026 3,480 37 22,200 6.5 37,000 10.8 40,700 11.9 1,859 3,099 3,564 38 22,800 6.7 38,000 11.1 41,800 12.2 1,903 3,172 3,648 39 23,400 6.9 39,000 11.4 42,900 12.6 1,947 3,245 3,732 40 24,000 7.0 40,000 11.7 44,000 12.9 1,991 3,318 3,816 41 24,600 7.2 41,000 12.0 45,100 13.2 2,035 3,391 3,900 42 25,200 7.4 42,000 12.3 46,000 13.5 2,083 3,472 3,993 43 25,400 7.4 42,333 12.4 46,167 13.5 2,132 3,553 4,086 44 25,600 7.5 42,667 12.5 46,333 13.6 2,180 3,634 4,179 45 25,800 7.6 43,000 12.6 46,500 13.6 2,229 3,714 4,271 46 26,000 7.6 43,333 12.7 46,667 13.7 2,277 3,795 4,364 47 26,200 7.7 43,667 12.8 46,833 13.7 2,325 3,876 4,457 48 26,400 7.7 44,000 12.9 47,000 13.8 2,370 3,950 4,550 49 26,600 7.8 44,333 13.0 47,167 13.8 2,418 4,030 4,643 50 26,800 7.9 44,667 13.1 47,333 13.9 2,400 4,000 4,736 51 27,000 7.9 45,000 13.2 47,500 13.9 2,400 4,000 4,829 52 27,200 8.0 45,333 13.3 47,667 14.0 2,400 4,000 4,900 53 27,400 8.0 45,667 13.4 47,833 14.0 2,400 4,000 4,900 54 27,600 8.1 46,000 13.5 48,000 14.1 2,400 4,000 4,900
Total indoor unitcapacity(kBtu/h)
Min
Cooling capacity
Rated MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 16~54 Btu/h(40%~130%)
5. At least two indoor units should be connected.
-
Heat pump 50Hz/R410A _ 244
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
[Heating capacity]
16 10,752 3.0 17,920 5.0 19,533 6.0 887 1,478 1,700 18 11,880 3.0 19,800 6.0 21,582 6.0 975 1,625 1,868 19 12,540 4.0 20,900 6.0 22,781 7.0 1,029 1,715 1,972 21 13,860 4.0 23,100 7.0 25,179 7.0 1,137 1,896 2,180 23 15,180 4.0 25,300 7.0 27,577 8.0 1,355 2,259 2,869 24 15,840 5.0 26,400 8.0 28,776 8.0 1,400 2,333 2,963 25 16,500 5.0 27,500 8.0 29,975 9.0 1,488 2,480 3,150 26 17,160 5.0 28,600 8.0 31,174 9.0 1,535 2,559 3,250 27 17,820 5.0 29,700 9.0 32,373 9.0 1,579 2,631 3,342 28 18,480 5.0 30,800 9.0 33,572 10.0 1,622 2,703 3,433 29 19,140 6.0 31,900 9.0 34,771 10.0 1,665 2,776 3,525 30 19,800 6.0 33,000 10.0 35,970 11.0 1,709 2,848 3,617 31 20,460 6.0 34,100 10.0 37,169 11.0 1,752 2,920 3,708 32 21,120 6.0 35,200 10.0 38,368 11.0 1,795 2,992 3,800 33 21,780 6.0 36,300 11.0 39,567 12.0 1,839 3,064 3,892 34 22,440 7.0 37,400 11.0 40,766 12.0 1,882 3,136 3,983 35 23,100 7.0 38,500 11.0 41,965 12.0 1,925 3,209 4,075 36 23,760 7.0 39,600 12.0 43,164 13.0 2,008 3,346 4,250 37 24,420 7.0 40,700 12.0 44,363 13.0 2,050 3,417 4,340 38 25,080 7.0 41,800 12.0 45,562 13.0 2,093 3,488 4,430 39 25,740 8.0 42,900 13.0 46,761 14.0 2,135 3,559 4,520 40 26,400 8.0 44,000 13.0 47,960 14.0 2,178 3,630 4,610 41 27,060 8.0 45,100 13.0 49,159 14.0 2,220 3,701 4,700 42 27,600 8.0 46,000 13.0 50,000 15.0 2,235 3,725 4,731 43 27,700 8.0 46,167 14.0 50,167 15.0 2,250 3,749 4,762 44 27,800 8.0 46,333 14.0 50,333 15.0 2,264 3,773 4,792 45 27,900 8.0 46,500 14.0 50,500 15.0 2,279 3,798 4,823 46 28,000 8.0 46,667 14.0 50,667 15.0 2,293 3,822 4,854 47 28,100 8.0 46,833 14.0 50,833 15.0 2,308 3,846 4,885 48 28,200 8.0 47,000 14.0 51,000 15.0 2,322 3,870 4,915 49 28,300 8.0 47,167 14.0 51,167 15.0 2,340 3,900 5,100 50 28,400 8.0 47,333 14.0 51,333 15.0 2,340 3,900 5,100 51 28,500 8.0 47,500 14.0 51,500 15.0 2,340 3,900 5,100 52 28,600 8.0 47,667 14.0 51,667 15.0 2,340 3,900 5,100 53 28,700 8.0 47,833 14.0 51,833 15.0 2,340 3,900 5,100 54 28,800 8.0 48,000 14.0 52,000 15.0 2,340 3,900 5,100
Total indoor unitcapacity(kBtu/h)
Min
Heating capacity
Rating MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 16~54 Btu/h(40%~130%)
5. At least two indoor units should be connected.
-
3. Distributor type MULTI FDX (3 phase)
245 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
Models : A8UW488FA3[FM49AH U33]
[Cooling capacity]
19 11,400 3.0 19,000 6.0 20,900 6.0 943 1,572 1,807 21 12,600 4.0 21,000 6.0 23,100 7.0 1,042 1,737 1,998 23 13,800 4.0 23,000 7.0 25,300 7.0 1,011 1,684 1,937 24 14,400 4.0 24,000 7.0 26,400 8.0 1,053 1,755 2,019 25 15,000 4.0 25,000 7.0 27,500 8.0 1,096 1,826 2,100 26 15,600 5.0 26,000 8.0 28,600 8.0 1,161 1,935 2,225 27 16,200 5.0 27,000 8.0 29,700 9.0 1,227 2,044 2,351 28 16,800 5.0 28,000 8.0 30,800 9.0 1,292 2,153 2,476 29 17,400 5.0 29,000 8.0 31,900 9.0 1,357 2,262 2,602 30 18,000 5.0 30,000 9.0 33,000 10.0 1,423 2,372 2,727 31 18,600 5.0 31,000 9.0 34,100 10.0 1,488 2,481 2,853 32 19,200 6.0 32,000 9.0 35,200 10.0 1,554 2,590 2,978 33 19,800 6.0 33,000 10.0 36,300 11.0 1,619 2,699 3,104 34 20,400 6.0 34,000 10.0 37,400 11.0 1,685 2,808 3,229 35 21,000 6.0 35,000 10.0 38,500 11.0 1,750 2,917 3,355 36 21,600 6.0 36,000 11.0 39,600 12.0 1,816 3,026 3,480 37 22,200 7.0 37,000 11.0 40,700 12.0 1,859 3,099 3,564 38 22,800 7.0 38,000 11.0 41,800 12.0 1,903 3,172 3,648 39 23,400 7.0 39,000 11.0 42,900 13.0 1,947 3,245 3,732 40 24,000 7.0 40,000 12.0 44,000 13.0 1,991 3,318 3,816 41 24,600 7.0 41,000 12.0 45,100 13.0 2,035 3,391 3,900 42 25,200 7.0 42,000 12.0 46,000 13.0 2,083 3,472 3,993 43 25,800 8.0 43,000 13.0 47,300 14.0 2,132 3,553 4,086 44 26,400 8.0 44,000 13.0 48,400 14.0 2,180 3,634 4,179 45 27,000 8.0 45,000 13.0 49,500 15.0 2,229 3,714 4,271 46 27,600 8.0 46,000 13.0 50,600 15.0 2,277 3,795 4,364 47 28,200 8.0 47,000 14.0 51,700 15.0 2,325 3,876 4,457 48 28,800 8.0 48,000 14.0 52,800 15.0 2,374 3,957 4,550 49 29,006 8.0 48,343 14.0 53,171 16.0 2,422 4,037 4,643 50 29,211 9.0 48,686 14.0 53,543 16.0 2,471 4,118 4,736 51 29,417 9.0 49,029 14.0 53,914 16.0 2,519 4,199 4,829 52 29,623 9.0 49,371 14.0 54,286 16.0 2,568 4,280 4,921 53 29,829 9.0 49,714 15.0 54,657 16.0 2,616 4,360 5,014 54 30,034 9.0 50,057 15.0 55,029 16.0 2,713 4,522 5,200 55 30,240 9.0 50,400 15.0 55,400 16.0 2,760 4,600 5,300 56 30,446 9.0 50,743 15.0 55,771 16.0 2,760 4,600 5,400 57 30,651 9.0 51,086 15.0 56,143 16.0 2,760 4,600 5,400 58 30,857 9.0 51,429 15.0 56,514 17.0 2,760 4,600 5,400 59 31,063 9.0 51,771 15.0 56,886 17.0 2,760 4,600 5,400 60 31,269 9.0 52,114 15.0 57,257 17.0 2,760 4,600 5,400 61 31,474 9.0 52,457 15.0 57,629 17.0 2,760 4,600 5,400 62 31,680 9.0 52,800 15.0 58,000 17.0 2,760 4,600 5,400 63 31,680 9.0 52,800 15.0 58,000 17.0 2,760 4,600 5,400
Total indoor unitcapacity(kBtu/h)
Min
Cooling capacity
Rated MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 19~63 Btu/h(40%~130%)
5. At least two indoor units should be connected.
-
Heat pump 50Hz/R410A _ 246
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
[Heating capacity]
19 12,540 4.0 20,900 6.0 22,781 7.0 1,136 1,894 2,178 21 13,860 4.0 23,100 7.0 25,179 7.0 1,256 2,093 2,407 23 15,180 4.0 25,300 7.0 27,577 8.0 1,497 2,495 2,869 24 15,840 5.0 26,400 8.0 28,776 8.0 1,546 2,576 2,963 25 16,500 5.0 27,500 8.0 29,975 9.0 1,643 2,739 3,150 26 17,160 5.0 28,600 8.0 31,174 9.0 1,696 2,826 3,250 27 17,820 5.0 29,700 9.0 32,373 9.0 1,743 2,906 3,342 28 18,480 5.0 30,800 9.0 33,572 10.0 1,791 2,986 3,433 29 19,140 6.0 31,900 9.0 34,771 10.0 1,839 3,065 3,525 30 19,800 6.0 33,000 10.0 35,970 11.0 1,887 3,145 3,617 31 20,460 6.0 34,100 10.0 37,169 11.0 1,935 3,225 3,708 32 21,120 6.0 35,200 10.0 38,368 11.0 1,983 3,304 3,800 33 21,780 6.0 36,300 11.0 39,567 12.0 2,030 3,384 3,892 34 22,440 7.0 37,400 11.0 40,766 12.0 2,078 3,464 3,983 35 23,100 7.0 38,500 11.0 41,965 12.0 2,126 3,543 4,075 36 23,760 7.0 39,600 12.0 43,164 13.0 2,217 3,696 4,250 37 24,420 7.0 40,700 12.0 44,363 13.0 2,264 3,774 4,340 38 25,080 7.0 41,800 12.0 45,562 13.0 2,311 3,852 4,430 39 25,740 8.0 42,900 13.0 46,761 14.0 2,358 3,930 4,520 40 26,400 8.0 44,000 13.0 47,960 14.0 2,405 4,009 4,610 41 27,060 8.0 45,100 13.0 49,159 14.0 2,452 4,087 4,700 42 27,600 8.0 46,000 13.0 50,000 15.0 2,474 4,123 4,742 43 28,400 8.0 47,333 14.0 51,000 15.0 2,496 4,159 4,783 44 29,200 9.0 48,667 14.0 52,000 15.0 2,517 4,195 4,825 45 30,000 9.0 50,000 15.0 53,000 16.0 2,539 4,231 4,866 46 30,800 9.0 51,333 15.0 54,000 16.0 2,561 4,268 4,908 47 31,600 9.0 52,667 15.0 55,000 16.0 2,582 4,304 4,949 48 32,400 9.0 54,000 16.0 56,000 16.0 2,604 4,340 4,991 49 32,486 10.0 54,143 16.0 56,214 16.0 2,700 4,500 5,240 50 32,571 10.0 54,286 16.0 56,429 17.0 2,700 4,500 5,240 51 32,657 10.0 54,429 16.0 56,643 17.0 2,700 4,500 5,240 52 32,743 10.0 54,571 16.0 56,857 17.0 2,700 4,500 5,240 53 32,829 10.0 54,714 16.0 57,071 17.0 2,700 4,500 5,240 54 32,914 10.0 54,857 16.0 57,286 17.0 2,700 4,500 5,240 55 33,000 10.0 55,000 16.0 57,500 17.0 2,670 4,450 5,200 56 33,086 10.0 55,143 16.0 57,714 17.0 2,670 4,450 5,200 57 33,171 10.0 55,286 16.0 57,929 17.0 2,670 4,450 5,200 58 33,257 10.0 55,429 16.0 58,143 17.0 2,670 4,450 5,200 59 33,343 10.0 55,571 16.0 58,357 17.0 2,670 4,450 5,200 60 33,429 10.0 55,714 16.0 58,571 17.0 2,670 4,450 5,200 61 33,514 10.0 55,857 16.0 58,786 17.0 2,670 4,450 5,200 62 33,600 10.0 56,000 16.0 59,000 17.0 2,670 4,450 5,200 63 33,600 10.0 56,000 16.0 59,000 17 .0 2,670 4,450 5,200
Total indoor unitcapacity(kBtu/h)
Min
Heating capacity
Rating MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 19~63 Btu/h(40%~130%)
5. At least two indoor units should be connected.
-
3. Distributor type MULTI FDX (3 phase)
247 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
Models : A9UW548FA3[FM57AH U33]
[Cooling capacity]
23 13,800 4.0 23,000 7.0 25,300 7.0 1,011 1,684 1,937 24 14,400 4.0 24,000 7.0 26,400 8.0 1,053 1,755 2,019 25 15,000 4.0 25,000 7.0 27,500 8.0 1,096 1,826 2,100 26 15,600 5.0 26,000 8.0 28,600 8.0 1,161 1,935 2,225 27 16,200 5.0 27,000 8.0 29,700 9.0 1,227 2,044 2,351 28 16,800 5.0 28,000 8.0 30,800 9.0 1,292 2,153 2,476 29 17,400 5.0 29,000 8.0 31,900 9.0 1,357 2,262 2,602 30 18,000 5.0 30,000 9.0 33,000 10.0 1,423 2,372 2,727 31 18,600 5.0 31,000 9.0 34,100 10.0 1,488 2,481 2,853 32 19,200 6.0 32,000 9.0 35,200 10.0 1,554 2,590 2,978 33 19,800 6.0 33,000 10.0 36,300 11.0 1,619 2,699 3,104 34 20,400 6.0 34,000 10.0 37,400 11.0 1,685 2,808 3,229 35 21,000 6.0 35,000 10.0 38,500 11.0 1,750 2,917 3,355 36 21,600 6.0 36,000 11.0 39,600 12.0 1,816 3,026 3,480 37 22,200 7.0 37,000 11.0 40,700 12.0 1,859 3,099 3,564 38 22,800 7.0 38,000 11.0 41,800 12.0 1,903 3,172 3,648 39 23,400 7.0 39,000 11.0 42,900 13.0 1,947 3,245 3,732 40 24,000 7.0 40,000 12.0 44,000 13.0 1,991 3,318 3,816 41 24,600 7.0 41,000 12.0 45,100 13.0 2,035 3,391 3,900 42 25,200 7.0 42,000 12.0 46,000 13.0 2,083 3,472 3,993 43 25,800 8.0 43,000 13.0 47,300 14.0 2,132 3,553 4,086 44 26,400 8.0 44,000 13.0 48,400 14.0 2,180 3,634 4,179 45 27,000 8.0 45,000 13.0 49,500 15.0 2,229 3,714 4,271 46 27,600 8.0 46,000 13.0 50,600 15.0 2,277 3,795 4,364 47 28,200 8.0 47,000 14.0 51,700 15.0 2,325 3,876 4,457 48 28,800 8.0 48,000 14.0 52,800 15.0 2,374 3,957 4,550 49 29,300 9.0 48,833 14.0 53,650 16.0 2,422 4,037 4,643 50 29,800 9.0 49,667 15.0 54,500 16.0 2,471 4,118 4,736 51 30,300 9.0 50,500 15.0 55,350 16.0 2,519 4,199 4,829 52 30,800 9.0 51,333 15.0 56,200 16.0 2,568 4,280 4,921 53 31,300 9.0 52,167 15.0 57,050 17.0 2,616 4,360 5,014 54 31,800 9.0 53,000 16.0 57,900 17.0 2,713 4,522 5,200 55 31,950 9.0 53,250 16.0 58,231 17.0 2,817 4,696 5,400 56 32,100 9.0 53,500 16.0 58,563 17.0 2,896 4,826 5,550 57 32,250 9.0 53,750 16.0 58,894 17.0 2,896 4,826 5,650 58 32,400 9.0 54,000 16.0 59,225 17.0 2,896 4,826 5,650 59 32,550 10.0 54,250 16.0 59,556 17.0 2,946 4,910 5,650 60 32,700 10.0 54,500 16.0 59,888 18.0 2,946 4,910 5,650 61 32,850 10.0 54,750 16.0 60,219 18.0 2,946 4,910 5,650 62 33,000 10.0 55,000 16.0 60,550 18.0 2,946 4,910 5,650 63 33,150 10.0 55,250 16.0 60,881 18.0 2,946 4,910 5,650 64 33,300 10.0 55,500 16.0 61,213 18.0 2,946 4,910 5,650 65 33,450 10.0 55,750 16.0 61,544 18.0 2,946 4,910 5,650 66 33,600 10.0 56,000 16.0 61,875 18.0 2,946 4,910 5,650 67 33,750 10.0 56,250 16.0 62,206 18.0 2,946 4,910 5,650 68 33,900 10.0 56,500 17.0 62,538 18.0 2,946 4,910 5,650 69 34,050 10.0 56,750 17.0 62,869 18.0 2,946 4,910 5,650 70 34,200 10.0 57,000 17.0 63,200 19.0 2,946 4,910 5,650 71 34,200 10.0 57,000 17.0 63,200 19.0 2,946 4,910 5,650 72 34,200 10.0 57,000 17.0 63,200 19.0 2,946 4,910 5,650 73 34,200 10.0 57,000 17.0 63,200 19.0 2,946 4,910 5,650
Total indoor unitcapacity(kBtu/h)
Min
Cooling capacity
Rated MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 23~73 Btu/h(40%~130%)
5. At least two indoor units should be connected.
-
Heat pump 50Hz/R410A _ 248
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
[Heating capacity]
23 15,180 4.0 25,300 7.0 27,577 8.0 1,497 2,495 2,869 24 15,840 5.0 26,400 8.0 28,776 8.0 1,546 2,576 2,963 25 16,500 5.0 27,500 8.0 29,975 9.0 1,643 2,739 3,150 26 17,160 5.0 28,600 8.0 31,174 9.0 1,696 2,826 3,250 27 17,820 5.0 29,700 9.0 32,373 9.0 1,743 2,906 3,342 28 18,480 5.0 30,800 9.0 33,572 10.0 1,791 2,986 3,433 29 19,140 6.0 31,900 9.0 34,771 10.0 1,839 3,065 3,525 30 19,800 6.0 33,000 10.0 35,970 11.0 1,887 3,145 3,617 31 20,460 6.0 34,100 10.0 37,169 11.0 1,935 3,225 3,708 32 21,120 6.0 35,200 10.0 38,368 11.0 1,983 3,304 3,800 33 21,780 6.0 36,300 11.0 39,567 12.0 2,030 3,384 3,892 34 22,440 7.0 37,400 11.0 40,766 12.0 2,078 3,464 3,983 35 23,100 7.0 38,500 11.0 41,965 12.0 2,126 3,543 4,075 36 23,760 7.0 39,600 12.0 43,164 13.0 2,217 3,696 4,250 37 24,420 7.0 40,700 12.0 44,363 13.0 2,264 3,774 4,340 38 25,080 7.0 41,800 12.0 45,562 13.0 2,311 3,852 4,430 39 25,740 8.0 42,900 13.0 46,761 14.0 2,358 3,930 4,520 40 26,400 8.0 44,000 13.0 47,960 14.0 2,405 4,009 4,610 41 27,060 8.0 45,100 13.0 49,159 14.0 2,452 4,087 4,700 42 27,600 8.0 46,000 13.0 50,000 15.0 2,487 4,146 4,768 43 28,400 8.0 47,333 14.0 51,000 15.0 2,523 4,205 4,835 44 29,200 9.0 48,667 14.0 52,000 15.0 2,558 4,264 4,903 45 30,000 9.0 50,000 15.0 53,000 16.0 2,593 4,322 4,971 46 30,800 9.0 51,333 15.0 54,000 16.0 2,629 4,381 5,038 47 31,600 9.0 52,667 15.0 55,000 16.0 2,664 4,440 5,106 48 32,400 9.0 54,000 16.0 56,000 16.0 2,699 4,499 5,174 49 32,700 10.0 54,500 16.0 56,833 17.0 2,735 4,558 5,242 50 33,000 10.0 55,000 16.0 57,667 17.0 2,770 4,617 5,309 51 33,300 10.0 55,500 16.0 58,500 17.0 2,805 4,676 5,377 52 33,600 10.0 56,000 16.0 59,333 17.0 2,841 4,734 5,445 53 33,900 10.0 56,500 17.0 60,167 18.0 2,876 4,793 5,512 54 34,200 10.0 57,000 17.0 61,000 18.0 2,911 4,852 5,580 55 34,326 10.0 57,211 17.0 61,158 18.0 2,911 4,852 5,400 56 34,453 10.0 57,421 17.0 61,316 18.0 2,911 4,852 5,340 57 34,579 10.0 57,632 17.0 61,474 18.0 2,911 4,852 5,340 58 34,705 10.0 57,842 17.0 61,632 18.0 2,736 4,560 5,371 59 34,832 10.0 58,053 17.0 61,789 18.0 2,736 4,560 5,402 60 34,958 10.0 58,263 17.0 61,947 18.0 2,736 4,560 5,433 61 35,084 10.0 58,474 17.0 62,105 18.0 2,736 4,560 5,464 62 35,211 10.0 58,684 17.0 62,263 18.0 2,730 4,550 5,650 63 35,337 10.0 58,895 17.0 62,421 18.0 2,730 4,550 5,650 64 35,463 10.0 59,105 17.0 62,579 18.0 2,730 4,550 5,650 65 35,589 10.0 59,316 17.0 62,737 18.0 2,730 4,550 5,650 66 35,716 10.0 59,526 17.0 62,895 18.0 2,730 4,550 5,650 67 35,842 11.0 59,737 18.0 63,053 18.0 2,730 4,550 5,650 68 35,968 11.0 59,947 18.0 63,211 19.0 2,730 4,550 5,650 69 36,095 11.0 60,158 18.0 63,368 19.0 2,730 4,550 5,650 70 36,600 11.0 61,000 18.0 64,000 19.0 2,730 4,550 5,650 71 36,600 11.0 61,000 18.0 64,000 19.0 2,730 4,550 5,650 72 36,600 11.0 61,000 18.0 64,000 19.0 2,730 4,550 5,650 73 36,600 11.0 61,000 18.0 64,000 19.0 2,730 4,550 5,650
Total indoor unitcapacity(kBtu/h)
Min
Heating capacity
Rating MaxBtu/h kW Btu/h kW Btu/h kW Min Rated Max
Input (W)
Note :1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is constant. Values for changes in capacity are fixed after accounting for variations in operating frequency and should be used as reference values.
4. Total capacity index of indoor unit should be within 23~73 Btu/h(40%~130%)
5. At least two indoor units should be connected.
-
3. Distributor type MULTI FDX (3 phase)
249 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.5 Dimensions1) Outdoor units
76, S
eong
san-
dong
, Cha
ngw
on C
ity, G
yeon
gnam
,64
1-71
3, K
orea
ww
w.lg
e.co
m/a
ircon
ditio
ner
CH
AS
SIS
CO
DE
: UE
2
OU
TD
OO
R U
NIT
A6U
W36
8FA
0 [F
M37
AH
UE
0]
Gas
pip
e co
nnec
tion
Par
t Nam
e
Air
disc
harg
e gr
ille
Liqu
id p
ipe
conn
ectio
n
Ear
th s
crew
Pow
er &
tran
smis
sion
con
nect
ion
5No. 2 431
Rem
ark
Hea
ting
Cap
acity
Coo
ling
Cap
acity
Pow
er s
uppl
y
Liqu
id(Ø
)
Gas
(Ø)
Pip
ing
Con
nect
ions
mm
(inch
)
mm
(inch
)
6.35
(1/4
)
15.8
8(5/
8)
kW/V/H
z
kWB
tu/h
Btu
/h
Ø
33,0
00
38,0
00
3/ 3
80~
415
/ 50
9.67
11.1
Tech
nica
l Spe
cific
atio
n
4
320
5
1060
1038
460
301
261492
45
71
870
546
10
10
55
162
32
330
339
Not
e
1. U
nit s
houl
d be
inst
alle
d in
com
plia
nce
with
the
inst
alla
tion
man
ual i
n
the
prod
uct b
ox.
2. U
nit s
houl
d be
gro
unde
d in
acc
orda
nce
with
the
loca
l reg
ulat
ions
or
a
pplic
able
nat
iona
l cod
es.
3. A
ll el
ectr
ical
com
pone
nts
and
mat
eria
ls to
be
supp
lied
on th
e si
te
m
ust c
ompl
y w
ith th
e lo
cal r
egul
atio
ns o
r in
tern
atio
nal c
odes
.
4. E
lect
rical
cha
ract
eris
tics
chap
ter
shou
ld b
e co
nsid
ered
for
elec
tric
al
w
ork
and
desi
gn. E
spec
ially
the
capa
city
of p
ower
cab
le a
nd c
ircui
t
bre
aker
for
outd
oor
unit
shou
ld b
e m
ore
than
that
of e
lect
rical
cha
ract
eris
tics
chap
ter.
1
-
Heat pump 50Hz/R410A _ 250
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
1. U
nit s
houl
d be
inst
alle
d in
com
plia
nce
with
the
inst
alla
tion
man
ual i
n
the
prod
uct b
ox.
2. U
nit s
houl
d be
gro
unde
d in
acc
orda
nce
with
the
loca
l reg
ulat
ions
or
a
pplic
able
nat
iona
l cod
es.
3. A
ll el
ectr
ical
com
pone
nts
and
mat
eria
ls to
be
supp
lied
on th
e si
te
m
ust c
ompl
y w
ith th
e lo
cal r
egul
atio
ns o
r in
tern
atio
nal c
odes
.
4. E
lect
rical
cha
ract
eris
tics
chap
ter
shou
ld b
e co
nsid
ered
for
elec
tric
al
w
ork
and
desi
gn. E
spec
ially
the
capa
city
of p
ower
cab
le a
nd c
ircui
t
bre
aker
for
outd
oor
unit
shou
ld b
e m
ore
than
that
of e
lect
rical
cha
ract
eris
tics
chap
ter.
76, S
eong
san-
dong
, Cha
ngw
on C
ity, G
yeon
gnam
,64
1-71
3, K
orea
ww
w.lg
e.co
m/a
ircon
ditio
ner
CH
AS
SIS
CO
DE
: U3
OU
TD
OO
R U
NIT
A7U
W42
8FA
3[FM
41A
H U
33]
A8U
W48
8FA
3[FM
49A
H U
33]
A9U
W54
8FA
3[FM
57A
H U
33]
Tech
nica
l Spe
cific
atio
n
Not
e
Par
t Nam
e
Air
disc
harg
e gr
ille
Gas
pip
e co
nnec
tion
Liqu
id p
ipe
conn
ectio
n
No. 2 31
Rem
ark
Sup
port
er
Hea
ting
Cap
acity
Coo
ling
Cap
acity
Pow
er s
uppl
y
Mod
el N
ame
Liqu
id(Ø
)
Gas
(Ø)
Pip
ing
Con
nect
ions
mm
(inch
)
mm
(inch
)
kW kW Btu
/h
Btu
/h
Ø/V
/Hz
A7U
W42
8FA
3[F
M41
AH
U33
]A
8UW
488F
A3
[FM
49A
H U
33]
A9U
W56
8FA
3[F
M57
AH
U33
]
3 / 3
80-4
15 /
50
13.5
46,0
00
14.1
48,0
00
9.52
(3/8
)
19.0
5(3/
4)
3 / 3
80-4
15 /
50
15.7
52,8
00
16.4
56,0
00
9.52
(3/8
)
19.0
5(3/
4)
3 / 3
80-4
15 /
50
16.7
57,0
00
17.8
7
61,0
00
9.52
(3/8
)
19.0
5(3/
4)
[Uni
t : m
m]
-
3. Distributor type MULTI FDX (3 phase)
251 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.6 Piping diagrams1) Outdoor unit
Models : A6UW368FA0 [FM37AH UE0]
LOC. Description PCB Connector
Th1 Thermistor for outdoor air temperature CN_TH2
Th2 Thermistor for condensing temperature CN_TH2
Th3 Thermistor for discharge pipe temperature CN_TH3
Th4 Thermistor for suction pipe temperature CN_TH3
ReversingValve
Outdoor Unit
Th1
Th3
Th2
Th4
Acc
umul
ator
S/V1
H/P Switch
Lowpressure
S/W
Field piingLiquid(Ø6.35)
Field piingGas(Ø15.88)
Comp.(Inveter)
HeatExchanger
Oil Separator
COOLINGHEATING
REFRIGERANT FLOW • S/V1: Hot Gas for oil return • H/P Switch: High Pressure Switch • L/P Switch: Low Pressure Switch
-
Heat pump 50Hz/R410A _ 252
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
Models : A7UW428FA3 [FM41AH U33], A8UW488FA3 [FM49AH U33], A9UW548FA3[FM57AH U33]
Th1
Th2
Th3
Th4
L/P
S/V(2)
S/V(1)
ReversingValve
HeatExchanger
Ø9.52Capillary
EEV
InverterCompressor
Accumulator
Oil Separator
Ø19.05
Refrigerant Flow
Cooling
Heating
LOC. Description PCB Connector
Th1 Thermistor for outdoor air temperature CN_TH1
Th2 Thermistor for condensing temperature CN_TH1
Th3 Thermistor for discharge pipe temperature CN_TH2
Th4 Thermistor for suction pipe temperature CN_TH2
S/V(1) Solenoid Valve for Hotgas CN_HOT GAS
S/V(2) Solenoid Valve for Oil Separator CN_OIL/S
L/P Low Pressure Switch CN_L/PRESS
[Unit : mm]
-
3. Distributor type MULTI FDX (3 phase)
253 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.7 Wiring diagrams1) Outdoor unit
Models : A6UW368FA0 [FM37AH UE0]
-
Heat pump 50Hz/R410A _ 254
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
Models : A7UW428FA3 [FM41AH U33], A8UW488FA3 [FM49AH U33], A9UW548FA3[FM57AH U33]
-
3. Distributor type MULTI FDX (3 phase)
279 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.9 Capacity coefficient factor1) Rate of change in capacity due to the main piping lengthRate of change in cooling capacity
Rate of change in heating capacity
Main piping pength rate of change in capacity
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
0 10 20 30 40 50 60 70 80
Main piping length(m)
Rat
e of
cha
nge
in c
apac
ity(%
)
Heating
Cooling
5 10 20 30 40 50 60 70 80
100.0 95.5 95.6 92.7 89.7 86.8 83.9 80.9 78.0
Main piping length(m)
Rate of changein cooling capacity(%)
5 10 20 30 40 50 60 70 80
100.0 99.6 98.7 97.8 96.9 96.0 95.1 94.2 93.3
Main piping length(m)
Rate of changein heating capacity(%)
-
Heat pump 50Hz/R410A _ 280
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
2) Rate of change in capacity due to the branch piping length
7k Btu/h(2.1 kW) models 9k Btu/h(2.6 kW) modelsPipingLength
5 100.0 100.010 98.0 99.515 96.0 98.920 94.0 98.4
Rate of Change in CapacityCooling(%) Heating(%)
PipingLength
5 100.0 100.010 97.0 98.315 94.0 96.520 91.0 94.8
Rate of Change in CapacityCooling(%) Heating(%)
PipingLength
5 100.0 100.010 97.8 99.215 95.5 98.420 93.3 97.6
Rate of Change in CapacityCooling(%) Heating(%)
PipingLength
5 100.0 100.010 97.8 99.515 95.5 99.020 93.3 98.5
Rate of Change in CapacityCooling(%) Heating(%)
PipingLength
5 100.0 100.010 97.5 99.515 95.0 98.920 92.5 98.4
Rate of Change in CapacityCooling(%) Heating(%)
12k Btu/h(3.5 kW) models 18k Btu/h(5.3 kW) models
24k Btu/h(7.0 kW) models
-
3. Distributor type MULTI FDX (3 phase)
281 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3) Calculation of actual system capacity① Outdoor unit rated capacity
Qodu(rated) [from specification table]
② Outdoor unit capacity at Ti, To temperature.Qodu(Ti, To) [from capacity table]
③ Outdoor unit capacity coefficient factorF(Ti, To) = Qodu(Ti, To) / Qodu(rated)
④ Piping correction factor [from capacity voefficient factor table]Fmain (length, elevation) for main piping length or elevationFbranch (length, elevation) for branch piping length or elevation
⑤ Individual indoor unit combinational capacityQidu (combi) = Qodu(rated) x Qidu(rated) / Qidu(rated-total)
⑥ Individual indoor unit actual capacityQidu (actual) = Qodu(combi) x F(Ti, To) x Fmain (length, elevation) x Fbranch (length, elevation)
Example) • Outdoor unit model : A7UW428FA3 [FM41AH U33]• Total indoor units combination : 7k(A room) + 7k .... + 9k• Outdoor temperature : 39°CDB• Indoor temperature : 19.5°CWB (A room)• Main piping length (O/D to BD) : 40m• Branch piping length (BD to I/D) : 10m (A room)• Indoor unit actual coding capacity in A room?
- Qodu (rated) : 11.7 kW- Qodu (Ti, To) :
1) Combination ratio : Qodu (rated - total) / Qodu (rated) = 115%2) From capacity table at Ti, To
110% : 11.4 kW120% : 11.4 kW∴ Qodu (Ti, To) = 115%
- F(Ti, To) : 11.4 kW / 11.7 kW = 97%- Fmain (length, elevation) = 89.8% (40m)- Fbranch (length, elevation) = 96.0% (7k, 10m)
- Qidu(combi) [7k] = 40k x ––––– = 6.1 k Btu/h
∴Qidu(actual) [7k] = 6.1k x 0.97 x 0.898 x 0.96= 5.05 k Btu/h
7k
46k
-
Heat pump 50Hz/R410A _ 282
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
3.10 Operation limit
Cooling
Indoor Unit [°C DB]
OutdoorUnit
[°C DB]
-10
-5
21
43
46
18 32
Continuousoperation
Operative
-15
-10
16 30
Operative
24
OutdoorUnit
[°C DB]
Indoor Unit [°C DB]
Heating
Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrease
War
min
g up
Ope
ratio
n
Continuousoperation
-
3. Distributor type MULTI FDX (3 phase)
283 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.11 Electrical characteristics
Notes :1. Voltage range
Voltage supplied to the unit terminals should be within the mini-mum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOPMCA = (1.25 x RLA) + Load1 + Load2MOP = (2.25 x RLA) + Load1 + Load2- Load1 : sum of current for all other motors- Load2 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Select proper circuit breaker as given below MCA < Circuit breaker ≤ MOP
6. Recommended circuit breaker is ELCB (Earth Leakage circuitbreaker)
7. MSC & RLA are measured as the compressor only test condi-tion.
8. MSC values
9. RLA is measured during each individual compressor test condi-tion.Ex) 5.0 : RLA of (inv. comp.)
10. OFM is measured as the outdoor unit test condition
(Example) Selection of proper circuit breaker
① Model : A7UW428FA3[FM41AH U33]② MCA = (1.25 x RLA) + Load1 + Load2
= (1.25 x 6.1) + 0 + (0.73 x 2) = 9.09 A
③ MOP = (2.25 x RLA) + Load1 + Load2= (2.25 x 6.1) + 0 + (0.73 x 2) = 15.19 A→ Finally select circuit breaker 20A
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Unit
Model Type MCA MOP MSC RLA KW FLAVoltage Voltage range Hz
Power Compressor OFM
A6UW368FA0[FM37AH UE0]
A7UW428FA3[FM41AH U33]
A8UW488FA3[FM49AH U33]
A9UW548FA3[FM57AH U33]
7.17 12.17 - 5.0 0.065*2 0.46*2
9.09 15.19 - 6.1 0.12*2 0.73*2
9.96 15.79 - 6.8 0.12*2 0.73*2
11.09 18.79 - 7.7 0.12*2 0.73*2
Multiinverter
50 380~415MIN.:342MAX.:456
-
Heat pump 50Hz/R410A _ 284
3. Distributor type MULTI FDX (3 phase)
Part 2 Product data_Outdoor units
3.12 Field wiring diagramModels : A6UW/A7UW/A8UW/A9UW
Notes: 1. All wiring, component and materials to be procured on the site should be according to the standard2. Use copper conductor only3. Install circuit breaker for safety4. Unit should be grounded in compliance with the applicable local and national codes5. Wiring cable size must comply with the applicable local and national code.
R T N 1(N) 2(N) 3(A) 3(B)S
Terminal Block outdoor
S
R S T
T NR
NG
Power supply
Main switch
Circuit breaker
Power cable 5 core x 2.5mm2
(Including earth)
Fuse
1(L) 2(N) S
1(L) 2(N) S 1(L) 2(N) S 1(L) 2(N) S 1(L) 2(N) S 1(L) 2(N) S 1(L) 2(N) S 1(L) 2(N) S 1(L) 2(N) S
1(L) 2(N) S
1(L) 2(N)
Terminal block indoor
3
1(L) 2(N)
Terminal block indoor
3
1(L) 2(N)
Terminal block indoor
3
1(L) 2(N)
Terminal block indoor
3
1(L) 2(N)
Terminal block indoor
3
1(L) 2(N)
Terminal block indoor
3
1(L) 2(N)
Terminal block indoor
3 1(L) 2(N)
Terminal block indoor
3
Outdoor unit
Distributor box Distributor box
Ground wire from BD unit
TRANSMISSION LINE
POWER SUPPLY CABLE
G
-
3. Distributor type MULTI FDX (3 phase)
285 _ Heat pump 50Hz/R410A
Part
2 Pr
oduc
t dat
a_O
utdo
or u
nits
3.13 Sound levelsOverall
A7UW428FA3[FM41AH U33]
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
A8UW488FA3[FM49AH U33] A9UW548FA3[FM57AH U33]
Octave Band Center Frequency (Hz)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearing Threshold
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearing Threshold
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearing Threshold
1m
D
Model
A6UW368FA0[FM37AH UE0]A7UW428FA3[FM41AH U33]A8UW488FA3[FM49AH U33]A9UW548FA3[FM57AH U33]
50Hz, 380-415V
Sound Pressure Level(dBA)351585859
Octave Band Center Frequency (Hz)
A6UW368FA0[FM37AH UE0]
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
Oct
ave
Ba
nd
So
un
d P
ress
ure
Le
vel (
dB
re
20
µP
a )
Oct
ave
Ba
nd
So
un
d P
ress
ure
Le
vel (
dB
re
20
µP
a )
Oct
ave
Ba
nd
So
un
d P
ress
ure
Le
vel (
dB
re
20
µP
a )
Oct
ave
Ba
nd
So
un
d P
ress
ure
Le
vel (
dB
re
20
µP
a )
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate Hearing Threshold
Notes:- Sound measured at 1m away from the center of the unit.- Data is valid at free field condition- Data is valid at nominal operation condition- Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particularroom in which the equipment is installed.
- The operating conditions are assumed to be standard.
Sound pressure level
-
4. Installation of outdoor unit
139 _ Heat pump 50Hz/R410A
Part
3 D
esig
n an
d in
stal
latio
n
L1
L2
L3
L4
L5
L6
Within 30m
Installation of the outdoor unit is at higher elevation than the indoor units.
Max 30m
A
B
Main piping
Branch piping
R
R
A6UW368FA0 [FM37AH UE0]A7UW406FA5[FM40AH UH5]
Installation of the outdoor unit is at lower elevation than the indoor units.
C
C
Piping
Total system piping length
Total branch piping length(L1+ L 2+ L 3+ L 4+ L 5+ L 6)
Each branch piping length(L1 , L2 , L3 , L4 , L5 , L6)
Total main piping length ( A + B )
A7UW406FA5[FM40AH UH5]
50
50
15
100
[Unit: m]
AIndoor unit ÷ Outdoor unit 30
Indoor unit ÷ Indoor unit ( C ) 15
Indoor unit ÷ BD unit 15
BD unit ÷ BD unit 15
Maximum elevation difference A7UW406FA5[FM40AH UH5]
[Unit: m]
BD unit
BD unit
BD unit
BD unit
Indoor units
Indoor units
-
Heat pump 50Hz/R410A _ 140
4. Installation of outdoor unit
Part 3 Design and installation
L7
L1
L2
L3
L4
L5
L6
A
C
C
B
Main piping
Branch piping
A7UW428FA3[FM41AH U33]
R
R
Installation of the outdoor unit is at higher elevation than the indoor units.
Installation of the outdoor unit is at lower elevation than the indoor units.
Max 30m
Max 30m
Piping
Total system piping length
Total branch piping length(L1+ L 2+ L 3+ L 4+ L 5+ L 6 + L 7)
Each branch piping length(L1 , L2 , L3 , L4 , L5 , L6 , L7)
Total main piping length ( A + B )
A7UW428FA3[FM41AH U33]
55
70
15
125
[Unit: m]
AIndoor unit ÷ Outdoor unit 30
Indoor unit ÷ Indoor unit ( C ) 15
Indoor unit ÷ BD unit 15
BD unit ÷ BD unit 15
Maximum elevation differenceA7UW428FA3[FM41AH U33]
[Unit: m]
BD unit
BD unit
BD unit
BD unit
Indoor units
Indoor units
-
4. Installation of outdoor unit
141 _ Heat pump 50Hz/R410A
Part
3 D
esig
n an
d in
stal
latio
n
Indoor units
Indoor units
L4
L8
L1
L2
L3
L5
L6
L7
A
B C
C
Main piping
Branch piping
A8UW486FA3[FM48AH U33]A8UW488FA3[FM49AH U33]
R
R
Installation of the outdoor unit is at higher elevation than the indoor units.
Installation of the outdoor unit is at lower elevation than the indoor units.
Max 30m
Max 30m
Piping
Total system piping length
Total branch piping length(L1+ L 2+ L 3+ L 4+ L 5+ L 6 + L 7 + L 8)
Each branch piping length(L1 , L2 , L3 , L4 , L5 , L6 , L7 , L8)
Total main piping length ( A + B )
A8UW486FA3[FM48AH U33]
55
80
15
135
A8UW488FA3[FM49AH U33]
55
80
15
135
[Unit: m]
AIndoor unit ÷ Outdoor unit 30 30
Indoor unit ÷ Indoor unit ( C ) 15 15
Indoor unit ÷ BD unit 15 15
BD unit ÷ BD unit 15 15
Maximum elevation differenceA8UW486FA3[FM48AH U33]
A8UW488FA3[FM49AH U33]
[Unit: m]
-
Heat pump 50Hz/R410A _ 142
4. Installation of outdoor unit
Part 3 Design and installation
A
B
C D
D
Main piping
Branch piping
A9UW566FA3[FM56AH U33]A9UW548FA3[FM57AH U33]
Installation of the outdoor unit is at higher elevation than the indoor units.
Installation of the outdoor unit is at lower elevation than the indoor units.
Max 30m
Max 30m
Piping
Total system piping length
Total branch piping length(L1+ L 2+ L 3+ L 4+ L 5+ L 6 + L 7 + L 8 + L 9)
Each branch piping length(L1 , L2 , L3 , L4 , L5 , L6 , L7 , L8 , L9)
Total main piping length ( A + B + C
A9UW548FA3[FM57AH U33]
A9UW566FA3[FM56AH U33]
55
90
15
145
55
90
15
145
[Unit: m]
Indoor unit ÷ Outdoor unit 30
Indoor unit ÷ Indoor unit ( D ) 15
Indoor unit ÷ BD unit 15
BD unit ÷ BD unit 15
30
15
15
15
Maximum elevation differenceA9UW548FA3[FM57AH U33]
A9UW566FA3[FM56AH U33]
[Unit: m]
L1
L2
L3
BD Unit
L4
L5
L6
BD Unit
L7
L8
L9
BD UnitR
BD Unit
Indoor units
Indoor units
Indoor units
R
-
4. Installation of outdoor unit
143 _ Heat pump 50Hz/R410A
Part
3 D
esig
n an
d in
stal
latio
n
4.8.2 Refrigerant chargeThe calculation of the additional charge should be taken into account for the additional length of pipe.
■ (1Ø)Additional charge (g) = ((A Room Installation Length – Standard Length ) x 20g/m
+ (B Room Installation Length – Standard Length ) x 20g/m +.. )- CF(Correction Factor) x 150
❈ CF = Max. number of connectable indoor unit – Total number of connected indoor unit
■ (1Ø , 3Ø) Additional charge (g) = (( Total Main piping Length - Main Standard Length ) x 50g/m
+ (A Room Branch Length – Standard Length ) x 20g/m + (B Room Branch Length – Standard Length ) x 20g/m+ (C Room Branch Length – Standard Length ) x 20g/m +.. ) - CF(Correction Factor) x 100
❈ CF = Max. number of connectable indoor unit – Total number of connected indoor unit
If the total additional charge value after calculation comes out to be negative, then do not consider additional charge.
NOTE
Long pipe setting
1) Open the top cover of outdoor unit.
2) Select one of the two selectable modes as follows.• If total additional charge value after calculation
comes out to be positive, move the slide switch to"LONG" position.
3) Close the top cover and check whether the productworks normally.
A2UW146FA5[MU2M15 UL0], A2UW166FA5[MU2M17 UL0]
Do not open the top cover or set the pipelength when operating the product.
CAUTION
NORMALLONG
Pipe length
ModelMain piping length Branch piping length
Standard length(m) Additional refrigerant(g/m) Standard length(m) Additional refrigerant(g/m)
A7UW406FA5[FM40AH UH5] 5 50 5 20
A8UW486FA3[FM48AH U33] 5 50 5 20
A9UW566FA3[FM56AH U33] 5 50 5 20
ModelMain piping length Branch piping length
Standard length(m) Additional refrigerant(g/m) Standard length(m) Additional refrigerant(g/m)
A6UW368FA0 [FM37AH UE0] 5 40 5 25
A7UW428FA3[FM41AH U33] 5 50 5 20
A8UW488FA3[FM49AH U33] 5 50 5 20
A9UW548FA3[FM57AH U33] 5 50 5 20
-
4. Installation of outdoor unit
151 _ Heat pump 50Hz/R410A
Part
3 D
esig
n an
d in
stal
latio
n
4.9 Y-Branch and branch distributor(BD) unit4.9.1 Branch (Accessory)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the sizeof the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulation in each kit.
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)Facing upwards
Viewed from point A in direction of arrow
Horizontalplane
Within 10°
A
A B
To outdoor unit
To BD unit
A
B
Liquid and gaspipe jointsInsulation
(included with kit)
Insulation forfield piping
Tape(insulation tape)
(field supply)
Gas PipeModel Name
PMBL5620
Liquid Pipe
Ø19.05
Ø19.05
[unit:mm]
Ø19.05
Ø28.58
Ø9.52
Ø12.7
Ø9.52
Ø9.52
Do not use general electrical insulation tape, because it may get loose or get detached.
CAUTION
Y- Branch
-
Heat pump 50Hz/R410A _ 152
4. Installation of outdoor unit
Part 3 Design and installation
Branch kit(PMBL1203F0)
Thermal insulation work
• Securely wrap the refrigerant and the branch pipe by using thermal insulation materials provided.When using thermal insulation materials released, use withstand heat insulation materials.(thicknessof more than 10mm)
• Securely adhere thermal insulation materials wrapping the branch pipe so that they do not widen. After wrapping them with auxiliary materials , bound them with a band .
• Finish the work by wrapping with a vinyl tape after the insulation material work.
• When installing the branch pipe, direction and angle of installation is not limited.• Take care so that burrs and foreign material may not enter into the cutting surface when connecting.
Thermal insulation materialsThermal insulation materials
Thermal insulation materials
Thermal insulationmaterials
Vinyl Tape
Vinyl TapeVinyl Tape
Vinyl Tape
Band
Band
Band
Gas Pipe Liquid Pipe
[unit:mm]
Ø19.05Ø9.52Ø9.52
-
4. Installation of outdoor unit
153 _ Heat pump 50Hz/R410A
Part
3 D
esig
n an
d in
stal
latio
n
4.9.2 Branch distributor(Accessory)1) General information
Model name: Functional description:• Distribution of refrigerant to various indoor uits.
• 3 types available (2, 3, 4 indoor units)
• Consists of EEV's inside
• Controlling PCB inside the unit
• Internally insulated
• Flare joints for easy installation and labour cost saving
• Compact design
BD unit
PMBD3620
PMBD3630
PMBD3640
Product
Multi FDX
2) Specifications :
ModelConnectable indoor units Number of indoor units
Capacity Btu/hPowre source (ø, Hz, V)Power consumption WRuning current ADimensions W x H x D mm(inch)Net Weight kgConnecting cable Direction indoor unit No. x mm2
Direction outdoor unit No. x mm2
Piping connection Liquid(ø) mm(inch)(To outdoor unit) Gas(ø) mm(inch)Piping connection Liquid(ø) mm(inch)(To indoor unit) Gas(ø) mm(inch)Accessories Hanger EA
Screw EAManual EA
1~2 1~3 1~47k/9k/12k/18k/24k 7k/9k/12k/18k/24k 7k/9k/12k/18k/24k
1, 50, 220-240 1, 50, 220-240 1, 50, 220-24010 10 10
0.05 0.05 0.05302 x 143 x 252(11.9 x 5.6 x 9.9) 302 x 143 x 252(11.9 x 5.6 x 9.9) 302 x 143 x 252(11.9 x 5.6 x 9.9)
4.8 4.9 5.04 x 0.75 (including earth) 4 x 0.75 (including earth) 4 x 0.75 (including earth)4 x 1.25 (including earth) 4 x 1.25 (including earth) 4 x 1.25 (including earth)
9.52(3/8) 9.52(3/8) 9.52(3/8)19.05(3/4) 19.05(3/4) 19.05(3/4)
6.35(1/4) x 2EA 6.35(1/4) x 3EA 6.35(1/4) x 4EA9.52(3/8) x 2EA 9.52(3/8) x 3EA 9.52(3/8) x 4EA
4 4 48 8 81 1 1
PMBD3620 PMBD3630 PMBD3640
1. The maimum height between any two BD units or any tow indoor units should be 10m.Set up the BD unit and indoor unit within 15m.
2. The piping connection must suit the piping sizes of the indoor unit which will be connected. (If need, use the connector which is included in the indoor unit)
3. The BD unit should be installed inside the building.
4. Wiring cable size must comply with the applicable local and national code.
NOTE
-
Heat pump 50Hz/R410A _ 154
4. Installation of outdoor unit
Part 3 Design and installation
3) Installation of BD unit
① Branch distributor unit We recommend BD unit installation at indoor side. but, ifyou install it outdoor side, care should be taken againstwater and other factors which may damage the pcb.
③ Installation of BD unit• This unit may be installed suspended from the ceiling or
mounted on the wall.
• This unit may only be installed horizontally , as shown inthe diagram below. (Side B is facing up) However, it maybe freely installed in any direction, forward or backward,and to the sides.
• Be sure to secure a 600mm square opening for serviceand inspection as shown in the diagram below, for bothceiling - suspended installation and wall-mounted installa-tion.
• BD unit does not require drain treatment as it uses inter-nal insulation.
• Service direction is the side B and C
• The piping for the indoor unit may be led around in direc-tion A
• The inclination of side B must be within ±5 degree for-ward or backward or to the sides.
Available condition
Temp : Max. 54
Humidity : Max.80% PCB
② Connection of piping (flare work)• No brazing & easy installation
• Be sure to mark all the local refrigerant piping(liquidpipes, gas pipes, etc.) for each indoor unit designatingclearly to which room it belongs to. (A, B, C, D)
NOTE
- Unit for variable refrigerant volume system
5030
(111
)
Min
30
Min 400
Min 400
(Servicing space)
(Side view)
(Bottom view)
B
C
505050
505050(56)
50(3
8)
(36)
Main Pipe
Cover ControlBranch Pipe
60300
432
72
(150
)
Inspection opening
600
250
or m
ore
600
(298
)
250
Ø19.05
Ø9.52
Suspension bolt pitch.245
(337
)
A
(EEV service)
(Controller service)
[Unit : mm]
-
4. Installation of outdoor unit
155 _ Heat pump 50Hz/R410A
Part
3 D
esig
n an
d in
stal
latio
n
• This unit has two different installation types: (1) Ceiling-suspended type and (2) wall-mounted type.
• Choose the proper installation pattern according to the location of installation.
① Ceiling-suspended type ②Wall-mounted type
Screws(M5)Screws(M5)
BD unit
Nut(M10 or M8)Nut(M10 or M8)
Flat washerFlat washer
Hanging boltHanging bolt(M10 or M8)
Procedure(1) Fix the furnished hanger metal with two screws.(4 loca-
tions in total).
(2) Using an insert-hole-in- anchor, hang the hanging bolt.
(3) Install a hexagon nut and a flat washer (locally-procured)to the hanging bolt as shown in the figure.
(4) After checking the level of the unit, tighten the hexagonnut.
Procedure(1) Fix the furnished hanger metal with two screws.
(3 locations in total).
(2) After checking with a level that the unit is level, fix theunit
* Block up the parts of hanger holes (2 places) byusing insulation polyethylene form after installingthe hanger.(This is to prevent condensation)
NOTE
• Do not install near bedrooms, the sound of refriger-ant flowing through the piping may sometimes beaudible.
CAUTION
-
Heat pump 50Hz/R410A _ 156
4. Installation of outdoor unit
Part 3 Design and installationA
B
C
CN-PWR
A room
B room
c room
A
B
C
CN-PWR
Connection wire for indoor units(4wires, 0.75mm2)
Connection wire for outdoor units(4wires, 1.25mm2)
① Remove the control cover, unscrew the two screws and slide the cover in thedirection of the arrow given below.
② Perform wiring with reference to the wiring diagram on a control cover of the out-door unit. Secure 300 mm for the pulling-out section of harness. Fix the wires com-pletely with wire clamps.
③ Put in the cover in the direction of the arrow then tighten the screws.
4) Electrical Wiring of BD Unit
• Connect refrigerant pipes and connection wires to the appropriate ports marked with matching alphabets (A, Band C) on this unit.
• Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoor units to termi-nal board numbers.(A, B and C) Always fix each ground wire separately with a ground screw.(See the figurebelow.)
• After completing the wiring, fix the outer coating of wires securely with wire clamps. The wire clamp on indoorunit side is furnished. Follow the procedure below to install.
• Refer to the circuit diagram on the control cover inside outdoor unit.
In case of 3 rooms
-
4. Installation of outdoor unit
157 _ Heat pump 50Hz/R410A
Part
3 D
esig
n an
d in
stal
latio
n
④ Connection of piping
• When connecting indoor units, make sure to connect refrigerant pipes and connection wires to the appropriate connection portsmaked with matching alphabets. (A, B, C, D)
• Be sure to mark all the local refrigerant piping(liquid pipes, gas pipes,etc.) for each indoor unit designating clearly which room it belongs in.(A, B, C, D)
NOTE
For flaring work the piping, follow the instructions in the installation manual to each unit.
a) Align the center of the pipings and sufficiently tight-en the flare nut by hand.
b) Tighten the flare nut with a wrench.
c) Wrap the insulation material around the connect-ing portion.
① Overlap the Refrigarant cable insulation material and theindoor unit pipe insulation material. Bind them togetherwith vinyl tape so that there is no gap.
②Wrap the area which accommodates the rear pipinghousing section with vinyl tape.
③ Align the center of the piping and sufficiently tighten thebrass cap by hand.
④ Tighten the brass cap with a wrench.
⑤Wrap the joint part with insulation.
Flare nut
Pipes
CASE. 1
BD Unit side flare
BD Unit side flare
Indoor unit side flare
Indoor unit side flare
Ø 9.52(7k/9k/12k Btu/h)
Connecting socket
Flare nutPipes
CASE. 2
Ø 9.52
Ø12.7(18k/24k Btu/h)
Ø 9.52
Spanner (fixed)
Connection pipe
Flare nut
Torquewrench
A B C D
• Never use the plastic cap for sealing.• Make sure to use brass cap with the end of pipe sealed or
welded tightly.
CAUTION
NOTE
[Unit : mm]
-
Heat pump 50Hz/R410A _ 158
4. Installation of outdoor unit
Part 3 Design and installation
⑤ Branch pipe connection (BD unit ↔ indoor unit)
a) While piping installation you must use the connector.
• PMBD36** BD Unit
b) Align the center of the pipings and sufficiently tighten the flare nut by hand
*Connecting pipe size
Indoor Units Gas Liquid
18k, 24kⓐ ⓑ ⓐ ⓑ
Ø9.52(3/8)→Ø12.7(1/2) Not necessary
Indoor Units Gas side Liquid side5k Ø9.52(3/8) Ø6.35(1/4)7k Ø9.52(3/8) Ø6.35(1/4)9k Ø9.52(3/8) Ø6.35(1/4)12k Ø9.52(3/8) Ø6.35(1/4)18k Ø12.7(1/2) Ø6.35(1/4)24k Ø12.7(1/2) Ø6.35(1/4)
[Connector]
a b
[Unit : mm(inch)]
[Unit : mm(inch)]