    HYDRONIC SYSTEMJ.ILANGUMARAN

  • 8/2/2019 2.Hydronic System

    2/17

    6"

    10"5"

    5"

    10"5"5"

    CONDENSER

    10"

    10"

    5"5"

    P.S.

    P.S.

    6"

    5"5"

    5"5"

    10"

    CONDENSER

    CONDENSER

    5"

    5"10"

    10"

    5"

    5"

    CONDENSER WATER PUMPS

    ( ONE STAND BY )

    HYDRONIC SYSTEM

  • 8/2/2019 2.Hydronic System

    3/17

    HYDRONIC SYSTEM - BASIC COMPONENTS

    LOAD HEATSOURCE HEAT

    * CHILLERS

    * HOT WATER

    TERMINAL UNITS

    *

    EXPANSION

    CHAMBER PUMPS

    * SOURCE * LOAD * PUMP

    * DISTRIBUTION SYSTEM ( PIPING NETWORK )

    * EXPANSION CHAMBER

    GENERATORS * F.C.U.

    . . .

    DISTRIBUTION SYSTEM

  • 8/2/2019 2.Hydronic System

    4/17

    WATER IS USED TO CARRY HEAT FROM POINT OF

    GENERATION SUCH AS COOLING / HEATING COIL TO APOINT WHERE IT CAN BE REJECTED SUCH AS

    REFERIGERANT MACHINE & HOT WATER GENERATOR

    COOLING & DEHUMIDIFICATION

    COMPRESSOR

    CHILLING MACHINE

    COIL-CHW

    AIR FLOW

    WATER RETURN

    45F CHILLED WATER SUPPLY

    CONDENSOR

    TO SPACE

    55F CHILLED

    WATER PIPE LINES

    HEAT REJECTED TO

    REFRIGERANT

    ie. AT COOLER

    * AHU'S

    * FCU'S

    TERMINAL UNITS

    WATER & AIR

    BETWEEN CHILLED

    HEAT EXCHANGE

  • 8/2/2019 2.Hydronic System

    5/17

    AIR FLOW

    TO SPACE

    HOT WATER SUPPLY

    HEATING COIL

    HOT WATER SUPPLY

    HEATING - HOT WATER & COIL

    HOT WATER RETURN PIPE

    HOT WATERGENERATOR 100F

    ELECTRIC HEATERS

    HEAT REJECTED TO HEAT EXCHANGE

    BETWEEN HOT

    WATER & AIR

    TERMINAL UNITS* AHU'S * FCU'S

  • 8/2/2019 2.Hydronic System

    6/17

    CONDENSOR

    COMPRESSOR

    COOLING

    TOWER

    WATER RETURN

    CHILLING MACHINE

    AIR OUT

    AIR IN CONDENSOR

    WATER IS USED TO CONDENSE THE REFERIGERANT TOLIQUID. IT THUS TRANSPORTS THE HEAT OF

    CONDENSATION TO COOLING TOWER FOR REJECTION

    TO ATMOSPHERE

    WATER PIPE LINES

    HEAT OF REFRIGERANT

    CONDENSATION REJECTED

    TO COOLING TOWER

    ie. ATMOSPHERE

    HEAT TRANSFER

    BETWEEN REFRIGERANT

    AND WATER

    WATER SUPPLY

  • 8/2/2019 2.Hydronic System

    7/17

    WATER IS USED ASA CARRIER OF HEAT,

    IT IS THE COOLANT

    OR COOLINGMEDIUM.

    IT TRANSPORTS THE

    BLOCK A

    MECHANICAL

    PLANT ROOM

    HIGH SIDE

    LOW SIDE

    CHILLED WATER

    F.C.U.

    RETURN

    CHILLED WATER

    SUPPLY

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    DISTRIBUTION NETWORK

    SOURCE -

    GENERATION OF

    COOLING/HEATING

    SPACE HEAT TOCHILLING MACHINE.

    WATER IS A

    SECONDARYREFERIGERANT

    BLOCK D

    BLOCK B

    BLOCK C

    L

    L

    L

    DISTRIBUTION NETWORK

    AHU

    AHU

    AHU

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

    F.C.U.

  • 8/2/2019 2.Hydronic System

    8/17

    CHILLER FLOW RATE

    HEAT CARRYING CAPACITY OF PIPING

    Q = MASS FLOW RATE x SP. HEAT x TEMP.

    RANGEQ BTU/HR = GALLONS/MINUTE x 8.33

    POUND/GALLON x 60 x 1 x T0 F

    = GALLON/MINUTE x 500 x

    T0

    F T0 F = BTU/HR PER GPM, FLOW RATE

    8 = 4000 3.0 GPM / TR.

    10 = 5000

    2.4 GPM / TR.15 = 7500

    20 = 10,000

  • 8/2/2019 2.Hydronic System

    9/17

    STATIC HS = STATIC HD

    THERE IS NO UNBALANCED

    STATIC HEAD.

    EVEN WHEN PUMP IS NOT IN

    OPERATION, THE ENTIRE

    PIPING IS FILLED WITH

    WATER

    ATMOSPHERIC

    PRESSURE

    EXPANSION

    TANK

    CHILLED WATER

    CLOSED RECIRCULATING TYPE

    THE PRESSURE AT THEHIGHEST POINT =

    SYSTEM PRESSURE + STATIC

    HEIGHT & LIQUID

    (EXPANSION TANK WATER

    LEVEL )

    COOLER

    RETURN

    WATER

    44F

    SUPPLY

    PUMP

    TERMINAL

    UNITS

    54F

    CHILLED

  • 8/2/2019 2.Hydronic System

    10/17

    AHU / FCU

    AHU / FCU

    AHU / FCU

    B

    C

    D

    G

    F

    E

    10 FT

    10 FT

    10 FT

    10 FT

    10 FT

    DIRECT RETURN

    COOLERA H

    40 FT

    PUMP

    PARALLEL PATHS- A-B-G-H ( 100 FT. ) SHORTEST PATH

    - A-B-C-F-G-H (120 FT.)

    - A-B-C-D-E-F-G-H ( 140 FT. ) LONGEST PATH

  • 8/2/2019 2.Hydronic System

    11/17

    SEAMLESS IS EXPENSIVE & HENCE NOT USED

    GENERALLY FOR HVAC SYSTEM

    FOR CHILLED & CONDENSER WATER PIPING

    ERW CLASS -C PIPES ARE USED

    CLASS A IS NEVER USED

    FOR DRAINS ERW CLASS B GI PIPE IS USED

  • 8/2/2019 2.Hydronic System

    12/17

    CONTROL VALVES

    CONTROL VALVES ARE USED ACROSS THE

    COOLING / HEATING COILS FOR VARYING

    WATER FLOW IN RESPONSE TO CHANGINGLOAD.

    -

    3 WAY MOTORISED - DIVERTING

    2 WAY MOTORISED

    3 WAY VALVES ARE USED FOR CONSTANTPUMPING SYSTEM, WHILE 2 WAY VALVES ARE

    USED FOR VARIABLE PUMPING SYSTEM.

  • 8/2/2019 2.Hydronic System

    13/17

    3 WAY MOTORISED MIXING VALVE

    COIL

    AB A

    B

    CHW / HOT

    WATER INCHW / HOT

    MOSTLY USED IN RETURN LINE OF COOLING /

    HEATING COILS. THERE ARE TWO INLETS AND ONE

    OUTLET. THE PORT DESIGN IS SUCH THAT IT

    CANNOT BE USED IN PLACE OF DIVERTING VALVE.

    FLOW VARIES THROUGH THE COIL. THE TOTAL

    FLOW REMAINS REMAINS SAME.

  • 8/2/2019 2.Hydronic System

    14/17

    3 WAY MOTORISED DIVERTING VALVE

    COIL

    AB A

    B

    CHW / HOT

    WATER IN

    THERE IS ONE INLET AND TWO OUTLETS. THE

    PORT DESIGN IS SUCH THAT IT CAN BE USED IN

    PLACE OF MIXING VALVE. DIVERTING VALVES

    ARE EXPENSIVE AND ARE NOT COMMONLY

    USED.

    WATER OUTCHW / HOT

  • 8/2/2019 2.Hydronic System

    15/17

    CHILLER4"4"

    8" 4"4"

    8"

    4"

    4"

    EXPAN.TANK

    4"

    AHU4000 CFM 4000 CFMAHU 4000 CFMAHU

    8"8"

    "

    8"8"

    CHILLED WATER FLOW DIAGRAM

    CHILLER

    CHILLER

    8"

    4"

    4"

    4"4"8"

    8"

    4"

    FLOW RATE / MACHINE = 1226 LPM

    =WATER TEMPERATURE IN 53F ( 11.6 C )

    =WATER TEMPERATURE OUT 45F ( 7.2C )

    4"

    ( ONE STAND BY )

    3 NOS. CHILLED WATER PUMP

  • 8/2/2019 2.Hydronic System

    16/17

    6"

    10"5"

    5"

    ""5"

    CONDENSER

    10"

    5"5"

    P.S.

    P.S.

    6"

    CONDENSER WATER FLOW DIAGRAM

    5"5"

    5"5"

    10"

    CONDENSER

    CONDENSER

    5"

    5"10"

    10"

    5"

    5"

    CONDENSER WATER PUMPS

    ( ONE STAND BY )