DC powered data centers DC powered data centers in the world in the world Keiichi Hirose, Ph.D. Senior Research Engineer R&D Headquarters NTT Facilities, Inc. Tokyo Japan LVDC Workshop LVDC Workshop SMB Strategic Group 4 SMB Strategic Group 4 on LVDC distribution systems on LVDC distribution systems up to 1 500 V up to 1 500 V 29th & 30th of September 2011 29th & 30th of September 2011 (Dresden/Germany) (Dresden/Germany)

Upload: lequynh

Post on 17-Mar-2019

232 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

DC powered data centersDC powered data centersin the worldin the world

Keiichi Hirose, Ph.D.Senior Research EngineerR&D HeadquartersNTT Facilities, Inc. Tokyo Japan

LVDC Workshop LVDC Workshop SMB Strategic Group 4SMB Strategic Group 4on LVDC distribution systems on LVDC distribution systems up to 1 500 Vup to 1 500 V

29th & 30th of September 201129th & 30th of September 2011(Dresden/Germany)(Dresden/Germany)

Page 2: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

2

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Motivation

Use of DC powerUse of DC power

Page 3: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

3

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

The trend of energy for telecom and computer( e.g. in Japan)

0

10

20

30

40

50

60

1993

1994

1995

1996

1997

1998

1999

2000

2001

2002

2003

2004

2005

2006

2007

2008

2009

2010

[TWh]

Main frame

IT equipment(routers, servers)

PCs (business use)

User’s terminals

Carriers

Others

PCs (home use)

■18% increasein 5 years

■1% of total energyconsumed in Japan

■4% of all electricityconsumed in Japan

Page 4: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

4

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Increasing load power

Page 5: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

5

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Telecom power supply system

Page 6: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

6

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

An Issue in telocom central office

Past Today

Page 7: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

7

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Best solution to the issue

Past Today

Page 8: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

8

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

What is a data center?

Page 9: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

9

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Typical AC and DC power systems in Data Centers

UPS

DC

AC

Utility Grid

Gen-set

DC power plant

AC ACDC

Battery

ICT equipment

CPU

CPUAC DC DC

Gen-set Battery

Utility Grid

DCAC

MechanicalSW

MechanicalSW

Static SW

ICT equipment

Page 10: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

10

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

AC or DC ?

CommunicationComputer FusionTechnology

Page 11: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

11

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

• Reduce in voltage drop• Wire size reduction• Equipment footprint reduction, simpler interfaces, and potentially lower costs

• High efficiency operation

• High reliability• No phase balancing• No Harmonics

issues

AC

Battery

CPUDC

DC system (48 Vdc)DC system (48 Vdc)

DC DC48 Vdc

AC ACDC

Battery

ICTEquipment

CPU

AC UPS

AC systemAC system

ACDC DC AC

ICTEquipmentDC UPS

Utility Grid

Utility Grid

AC

Battery

CPUDC DC DC380 Vdc1 2

ICTEquipmentDC UPS

Utility Grid

DC system (HVDC)DC system (HVDC)

Comparison of AC, 48 Vdc, and HVDC Systems

• Easy integration with renewable energy resources

Page 12: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

12

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

NTT-F’s Activities (History)

TelecomSystemLow Voltage DC (Low Voltage DC (--48 Vdc)48 Vdc)

High Voltage DC High Voltage DC (300~400 Vdc)(300~400 Vdc)

DC PowerPromotion

2000

In-house IT System2001

DC poweredData Center2006

NEDO Sendai Project2004

HVDC Distribution SystemWith Intel 2007 NTT News release

June 2008

Page 13: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

13

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

NTT-F Launched a 48 VDC-powered Data Center on December 2006

Operation center

Racks for operation and monitoring system

NTT East Saitama Shin-toshinBuilding

1,200A@DC48V30 Racks

Page 14: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

14

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Low Voltage 48 VDC power system

Battery Banks

DC Power Distribution UnitRectifierAC MainCables

RearFront

Page 15: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

15

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC voltage converted from AC power source

Page 16: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

16

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC powered sites in Europe, US, and Japan

Operating data centersPlanned datacenters

DC power in buildingsDC microgrids

Page 17: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

17

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

SwedenNetpower350/380

VDC

JapanNTT Group380 VDC

JapanOther Demos

380 VDC

FranceTelecom350/380 VDC

New ZealandTelecom NZ

220 VDC

USValidus

550 VDC

USIntel Corp.400 VDC

USUCSD

380 VDC

KOREA300/380 VDC

USSyracuce Univ.

380VDC

China Telecom

240/380 VDC

Tiwan IT Manufacture

380 VDC

USDuke Energy

380 VDC

DC powered 0perational/Demo Sites for ICT use

China Mobile380 VDC

Page 18: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

18

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

300-400VDC Operational and Demo Sites Worldwide

100 kWFeb-11Atsugi City, KanagawaNTT

100 kWDec-10TokyoNTT EAST

30 kWAug-10Choriotte, NCDuke Energy

500 kWOct-10Hammaro KarlstadCompare Test Lab

18 kWJan-10EskilstunaSwedish Energy Agency

150 kWDec-09Syracuse, NY Syracuse Univ

20 kWNov-09San Diego, CAUniv of Calif/San Diego

N/AJun-09Seoul, KoreaKorea Telecom

4.5kWJun-09Hammaro KarlstadCompare Test Lab

100 kWJan-09Toshima-ku, TokyoNTT Facilities

100 kWJan-09Mitaka City, TokyoNTT Lab.

100 kWJan-09Mitaka City,TokyoNTT Data Corp

6kWJun-08Soderhamm Soderhamm Teknikpark

4.5kWMar-08Stockholm Ericsson

31.5kWNov-07Lannion FranceFrance Telecom

50 kWMay-07AichiNTT Univ. Microgrid

20kWFeb-07Sendai NTT NEDO Project

4.5kWMar-06TorebodaElicom

9kWMar-06GnestaGnesta Municipality

Max kWOp DateLocationSite

Page 19: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

19

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Gnesta Project, Sweden

Page 20: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

20

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Hammaro/Eskilstuna/Toredoba, HVDC(DC350V)

DC350V

Transformer

PVFC

ACMain

Hammaro 10 kVEskilstuna 0.4 kVToreboda 0.4 kV

Page 21: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

21

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC power in office, Toredoba, Sweden

Page 22: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

22

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Next generation data center

• Smart grid data center– Providing intelligent energy

management across systems and facilities

Construction May 29, 2009Installation September 2009Launched November 2009

Page 23: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

23

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Server room in the data center

Page 24: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

24

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC Power Demonstrations by NTT Facilities

Tokyo Metropolitan 100 KW x 5 sites

Sapporo

SendaiNEDO Project300VDC Demo

Osaka

Fukuoka

380VDC NTT lab.

380VDC NTT Facilities380VDC NTT Data Corp.

Aichi380VDC Microgird

In university campus

380VDC NTT EAST*

* : The demonstration was supported by Ministry of Internal Affairs and Communications, Japan in 2010.

380VDC NTT container type

Page 25: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

25

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Modular type data center powered by 380 VDC

Page 26: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

26

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Power supply unit (PSU)

380 Vdc 100-240 Vac Same output for servers(same dimensions)

Page 27: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

27

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

A Basic configuration of 380 VDC power system

Basement

Voltagebooster

HVDC

HVDC

HVDC

HVDCHVDC Rectifier HVDC PDU

19-inch Rack

OptionOption

N+1

HVDCHVDC Rectifier

HVDC lighting

Dummy loads

Battery bankCharger

IT equipment

Power strip, plug & socket

Three-phaseAC main AC PDU

Wall mountedHVDC Switch

Page 28: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

28

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

NTT-F’s site

•3 types of HVDC power system•Power Distribution Units•Dummy loads•Intel’s HVDC servers

•100-kW simulated DC server loads

For basic characteristics of HVDC power system,short circuit tests, transient tests, voltage dips, and so on…

Page 29: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

29

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Existing ac lighting and new dc lighting

380VDC lighting in NTT DATA’s site

New dc lighting

Wall switch fordc lighting

Page 30: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

30

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

380 VDC Power strip in the 19 inch’s rack

Plug

Page 31: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

31

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Other use of 380 VDC plug & socket-outlet

Chung Cheng University in TaiwanSeptember 2010

Page 32: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

32

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Future plan by Korea telecom

Page 33: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

33

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

What is NEDO Sendai Demonstration?

•• 4 year project (FY 2004 4 year project (FY 2004 -- 2007)2007)•• Multiple power quality supply (4 AC and 1 DC)Multiple power quality supply (4 AC and 1 DC)•• A demo for the future ICT societyA demo for the future ICT society

PV Panels50 kWp

DVRs200 kVA600 kVA

MCFC250 kWGas Gen-

sets350 kW X 2

Here is DC Demo system in this building.

Page 34: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

34

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC Power Distribution Unit4 branches (With Static Switches)

430 VDC

400 VAC

IntegratedPowerSupply

AC/DC

AC mainDC/DC

300VDC

Batteries

48 VDCServers

Lightings

Fans

SupplySide

CustomerSideDC/DC

PV panels(50 kWp)

20 kW

N+1

300 VDC HVDCServers

DC/DC

DC/DC

5 kW

5 kW

N+1

48 VDC

Intel and NTT-F are cooperating on the 300 Vdc test during the NEDO Sendai project.

DC Circuit System Configuration

Page 35: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

35

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC Loads

Fan (DC Fan (DC --48V)48V) Lighting (DC Lighting (DC --48V)48V)

Servers (DCServers (DC--48V)48V)(HP BL20p)(HP BL20p)

IntelIntel’’s HVDC serverss HVDC servers

Page 36: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

36

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Campus DC Microgrid in Aichi Institute of Technology

Yakusa Campus / TOYOTA City

Library

Power Stationfor DGs

PV Panels

Batteries

DC Power PlantHydro Power

Wind Turbines

Educational Facility

This project is supported by the Ministry of Education, Culture, Sports, Science and Technology.

Page 37: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

37

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC Microgrid Project: Campus

G

PV WG PV

Battery DCLoad

ACLoad

DC bus 350VDC bus 350V

6.6 kV/ 210 V

750 kVA Gen-set

10 kW 10 kW 20 kW

Utility Grid

Building #1 Building #2

HVDC Servers

=~

==

=~ =

=

~=

ACLoad

~=

Page 38: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

38

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Barriers to 380/400VDC power system

Technical IssuesTechnical Issues-Breaking-current-Earthing, EMC, Noise-Power quality and reliability-Power architecture-Power electronics engineering (e.g. SiC)

Legal and Standard IssuesLegal and Standard Issues-Common voltage and system configuration-Safety requirements-Working groups and committees

Market promotionMarket promotion-Cost evaluation (total cost of ownership) -PR / Advertising-Consortium of HVDC power suppliers for ICT Systems

Page 39: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

39

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC power workshops in the U.S and Japan

US workshop- EPRI DC Power Production, Delivery and Use Workshop- June 1-2, 2006- At George Washington Univ. (Washington D.C)- No. of Attendees: 70 persons

Manufacture: 21, Engineer: 20, Researcher: 10,Utility: 7, etc.

Japan workshop- IEEJ Research committee for survey on “DC power distribution and application”- At Tokyo- No. of Attendees: 20 Persons

University prof. : 7, Manufacture: 6, Engineer: 3Researcher: 2, Utility: 2

George Washington Univ.

Question:What is the most important item for DC power applications?

Page 40: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

40

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Important items for DC power (in 2006)

Actual operation, Know-howDC type appliances

4. Experience

Cost-benefit analysis5. EconomicsCircuit topology, promotion, etc.Others

Plug & socket-outlet3. ConnectorIntelligent circuit breaker2. Safety and ProtectionInternational standards (Voltage, range)1. Standards, codes

NoteItems

Actual operation, Know-how,DC type appliances

3. Experience

Cost-benefit analysis4. Economics

DC circuit breaking, Prevention electric shock, etc.2. Safety and Protection

International standards (Voltage, range),regulation and law

1. Standards, codesNoteItems

c.f. US NEC covers both AC and DC, and the products can be UL listed today.(LVDC workshop in Washington DC, April 8, 2011)

Page 41: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

41

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

DC Voltage Standard

Page 42: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

42

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

400 Vdc system (today)

StorageBank

ProtectionDevice

Utility grid(AC main)

Loads(IT system)

XPower

Converter

AC in

DC out Y

Today

- Near future -The 400 Vdc class system is capability to expand another loads (electrical vehicle and household appliance).

Scope of discussion

Page 43: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

43

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

400 Vdc system (Option)

StorageBank

ProtectionDevice

Utility grid(AC main)

DistributedEnergy Source

Loads(IT system)

XPowerConverter

AC in

DC out

ElectricVehicle

Householdappliances

Future

- Near future -The 400 Vdc class system is capability to expand another loads (electrical vehicle and household appliance).

Y

Page 44: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

44

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

International cooperation

France, Japan, Sweden, and US colleagues worked together for the 33th INTELEC.

Page 45: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

45

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Acknowledgement

I would like to thank:☺- John Åkerlund, Netpower, Sweden- Marek Szpek, Emerson, Sweden- BJ Sonnenberg, Emerson, USA- Dennis Symanski, EPRI, USA- Didier Marquet, France Telecom- And all of my colleagues

Page 46: 2.3.1 DC powered data centers in the world Hirose Keiichize.bot.free.fr/NTT_DC_Datacenter.pdf · 380VDC NTT lab. 380VDC NTT Data Corp. 380VDC NTT Facilities Aichi 380VDC Microgird

46

Copyright © 2011 NTT Facilities, Inc. All rights reserved.

Questions?