2188029_02en
TRANSCRIPT
-
8/10/2019 2188029_02en
1/136
On-Load Tap-ChangerVACUTAP VR I II III/VR I HD
Technical Data
2188029/02 EN
-
8/10/2019 2188029_02en
2/136
All rights reserved by Maschinenfabrik Reinhausen
Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibitedunless expressly permitted.
Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents,utility models or designs.
The product may have been altered since this document was published.
We reserve the right to change the technical data, design and scope of supply.
Generally the information provided and agreements made when processing the individual quotations and ordersare binding.
The original operating instructions were written in German.
-
8/10/2019 2188029_02en
3/136
Table of contents
Maschinenfabrik Reinhausen 2013 32188029/02 EN VACUTAP VR I II III/VR I HD
1 General ................................................................................................................................ 71.1 On-load tap-changer designations ...................................................................................................... 7
1.2 Summary of the technical data ........................................................................................................... 9
1.3 Rated insulation level ........................................................................................................................ 16
2 Technical data .................................................................................................................. 17
2.1 Step capacity diagram VRC and VRE .............................................................................................. 17
2.2 Step capacity diagram VRD, VRF, VRG* ......................................................................................... 17
2.3 Step capacity diagram VRC, VRE electrical arc furnace operation)*................................................ 18
2.4 Step capacity diagram VRD, VRF, VRG* (electrical arc furnace operation)** .................................. 18
2.5 Step capacity diagram VRC/VRE I HD ............................................................................................. 19
2.6 Step capacity diagram VRD/VRF/VRG* I HD ................................................................................... 19
2.7 Step capacity diagram VRC/VRE I HD (electrical arc furnace operation)* ....................................... 20
2.8 Step capacity diagram VRD/VRF/VRG* I HD (electrical arc furnace operation)** ............................ 20
2.9 Rated withstand voltages of the internal insulation ........................................................................... 21
2.10 On-load tap-changer VACUTAP VRC with multiple coarse change-over selector......................... 24
3 Special designs ................................................................................................................ 26
3.1 Parallel bridges for parallel connections ........................................................................................... 26
3.2 On-load tap-changer combination VACUTAP VRC I/VR II / VRF I/VRF II for delta connection .... 26
3.3 On-load tap-changer VACUTAP VRC III 700 Y, VRC I 701/1001/1301 undVRC I HD 701/1001/1301 with multiple coarse change-over selector (up to max. of 5 coarse tap con-nections) ........................................................................................................................................... 27
4 Appendix ........................................................................................................................... 28
4.1 VACUTAP VRC/VRE type overview (727017) ............................................................................... 28
4.2 VACUTAP VRD/VRF/VRG, type overview (727016) ..................................................................... 30
4.3 VACUTAP VR, basic connection diagrams, designation of tap selector connection contacts accord-ing to MR standard (719037) ............................................................................................................ 32
4.4 VACUTAP VRF I 1001, VRD/VRF I 1301, VRF I 1001 HD, VRD/VRF I HD 1301, dimensionaldrawing (899805) .............................................................................................................................. 34
4.5 VACUTAP VRF I 1001/1301 (Um 362 kV), VRF I HD 1001/1301 (Um 362 kV), dimensional draw-ing (899806) ...................................................................................................................................... 364.6 VACUTAP VRG I 1001/1301, VRG I HD 1001/1301, dimensional drawing (899810) ................... 38
4.7 VACUTAP VRG I 1001/1301 (Um 362 kV), VRG I HD 1001/1301 (Um 362 kV), dimensional draw-ing (899811) ...................................................................................................................................... 40
4.8 VACUTAP VRF I 1601, 72.5...300 kV, dimensional drawing (786915) .......................................... 42
4.9 VACUTAP VRF I 1601, 362 kV, dimensional drawing (786916) .................................................... 44
4.10 VACUTAP VRG I 1601, 72.5...300 kV, dimensional drawing (786917) ......................................... 46
4.11 VACUTAP VRG I 1601, 362 kV, dimensional drawing (786918) ................................................... 48
4.12 VACUTAP VRF I 2602, dimensional drawing (727033) ................................................................. 50
Table of contents
-
8/10/2019 2188029_02en
4/136
Table of contents
Maschinenfabrik Reinhausen 20134 2188029/02 ENVACUTAP VR I II III/VR I HD
4.13 VACUTAP VRF I 2602 (Um 362 kV), dimensional drawing (727034) ............................................ 52
4.14 VACUTAP VRG I 2602, dimensional drawing (727035) ................................................................ 54
4.15 VACUTAP VRG I 2602 (Um 362 kV), dimensional drawing (727036) ........................................... 56
4.16 VACUTAP VRC I 401/551/701-0/W/G, VRC I HD 401/551/701-0/W/G, dimensional drawing(899990)............................................................................................................................................ 58
4.17 VACUTAP VRE I 701-0/W/G, VRE I HD 701-0/W/G, dimensional drawing (899991) ................... 59
4.18 VACUTAP VRC I 1001-0/W/G, VRC I HD 1001-0/W/G, dimensional drawing (718306) ............... 60
4.19 VACUTAP VRE I 1001-0/W/G, VRE I HD 1001-0/W/G, dimensional drawing (718307) ............... 61
4.20 VACUTAP VRC I 1301-0/W/G, VRC I HD 1301-0/W/G, dimensional drawing (718308) ............... 62
4.21 VACUTAP VRE I 1301-0/W/G, VRE I HD 1301-0/W/G, dimensional drawing (727040) ............... 63
4.22 VACUTAP VRC I 701/VRC I HD 701 with multiple coarse change-over selector, dimensional draw-ing (718316) ...................................................................................................................................... 64
4.23 VACUTAP VRC I 1001/VRC I HD 1001 with multiple coarse change-over selector, dimensionaldrawing (718318) .............................................................................................................................. 65
4.24 VACUTAP VRC I 1301/VRC I HD 1301 with multiple coarse change-over selector, dimensionaldrawing (718321) .............................................................................................................................. 66
4.25 VACUTAP VRF II 1302, dimensional drawing (899814) ................................................................ 67
4.26 VACUTAP VRF II 1302 (Um 362 kV), dimensional drawing (899815) ........................................... 69
4.27 VACUTAP VRG II 1302, dimensional drawing (899816) ............................................................... 71
4.28 VACUTAP VRG II 1302 (Um 362 kV), dimensional drawing (899817) .......................................... 73
4.29 VACUTAP VRC III 400/550/700 Y-0/W/G, dimensional drawing (899981) .................................... 75
4.30 VACUTAP VRE III 700 Y-0/W/G, dimensional drawing (899982) .................................................. 76
4.31 VACUTAP VRD/VRF III 1000/1300 Y, dimensional drawing (899803) .......................................... 774.32 VACUTAP VRG III 1000/1300 Y, dimensional drawing (899804) .................................................. 79
4.33 VACUTAP VRC II 402/552/702-0/W/G, dimensional drawing (899989) ........................................ 81
4.34 VACUTAP VRC III 700 Y with multiple coarse change-over selector, dimensional drawing (718314)........................................................................................................................................................... 82
4.35 VACUTAP VRC III 400/550/700 Y-10191W, detailed connection diagram (ZS030355) ................ 83
4.36 VACUTAP VRE III 700 Y-10193W, detailed connection diagram (ZS030356) .............................. 84
4.37 VACUTAP VRD III 1300 Y-C/D-10191W, detailed connection diagram (ZS030201) .................... 85
4.38 VACUTAP VRG III 1300 Y-E-14271G, detailed connection diagram (ZS030202) ........................ 86
4.39 VACUTAP VRC/VRE, installation drawing (899992) ..................................................................... 87
4.40 VACUTAP VRD/VRF, installation drawing (899898) ...................................................................... 884.41 VACUTAP VRG, installation drawing (899945) .............................................................................. 89
4.42 VACUTAP VRC/VRE, connecting leads 3W, 1G, 3G, dimensional drawing (723590) .................. 90
4.43 VACUTAP VR, on-load tap-changer head (720847) ...................................................................... 91
4.44 VACUTAP VR, on-load tap-changer head with flange for pressure relief device (899946) ........... 92
4.45 VACUTAP VR, special design for bell-type tank installation (720781)........................................... 93
4.46 VACUTAP VRC/VRE, arrangement of contacts on tap selector, tap selector division 1022(899993)............................................................................................................................................ 94
4.47 VACUTAP VRC/VRE I 1001/1301, VRC/VRE I HD 1001/1301, bridges to parallel connection of tapselector connection contacts (727025) ............................................................................................. 95
-
8/10/2019 2188029_02en
5/136
Table of contents
Maschinenfabrik Reinhausen 2013 52188029/02 EN VACUTAP VR I II III/VR I HD
4.48 VACUTAP VR, installation position of tap selector connection contacts (727042) ........................ 96
4.49 VACUTAP VR installation position of tap selector connection contacts (743603) ......................... 97
4.50 VACUTAP VRC III 400/550/700 Y, VRE III 700 Y, arrangement of tap selector (899994) ............ 98
4.51 VACUTAP VRC I 401/551/701, VRC I HD 401/551/701, VRE I 701, VRE I HD 701, arrangement oftap selector (899995) ........................................................................................................................ 99
4.52 VACUTAP VRC/VRE I 1001, VRC/VRE I HD 1001, arrangement of tap selector (899996) ........ 100
4.53 VACUTAP VRC/VRE I 1301, VRC/VRE I HD 1301, arrangement of tap selector (727043) ........ 101
4.54 VACUTAP VR, variants of the on-load tap-changer head, gear unit swivel range and drive direction(721216).......................................................................................................................................... 102
4.55 VACUTAP VR, swivel range of gear unit (728474) ...................................................................... 103
4.56 VACUTAP VR, horizontal drive shaft (899958) ............................................................................ 104
4.57 VACUTAP VRG, horizontal drive shaft, tap selector size (899959) ............................................. 105
4.58 VACUTAP VRC/VRE III, tie-in resistors with or without potential switch (899972) ...................... 106
4.59 VACUTAP VRC II, tie-in resistors with or without potential switch (899986) ............................... 107
4.60 VACUTAP VRC/VRE I, VRC/VRE I HD, tie-in resistors with or without potential switch (718447) .... 108
4.61 VACUTAP VRC/VRE, tie-in resistor cylinder with potential switch without tie-in resistors (899973)......................................................................................................................................................... 109
4.62 VACUTAP VRD/VRF/VRG, fine tap selector connection contact and change-over selector connec-tion contact (899941) ...................................................................................................................... 110
4.63 VACUTAP VRF, bridges to parallel connection of tap selector connection contacts (786919) ... 111
4.64 VACUTAP VRG, bridges to parallel connection of tap selector connection contacts (786920) ... 112
4.65 VACUTAP VRD/VRF, tap selector size C/D, tap selector bottom depiction of the lowest live parts
(899968).......................................................................................................................................... 1134.66 VACUTAP VRG, tap selector size E, tap selector bottom depiction of the lowest live parts (899969)
......................................................................................................................................................... 1144.67 VACUTAP VRD/VRF, arrangement of potential switches/tie-in resistors (899950) ..................... 115
4.68 VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder andpotential switch (899951) ................................................................................................................ 116
4.69 VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder(899955).......................................................................................................................................... 117
4.70 VACUTAP VRD/VRF III WP, tap selector size C/D, tie-in resistor cylinder and potential switch(899962).......................................................................................................................................... 118
4.71 VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in resistor cylinder (899964) .................. 119
4.72 VACUTAP VRD/VRF I/III WS, VRD/VRF I HD WS, tap selector size C/D, potential switch (899966)
......................................................................................................................................................... 1204.73 VACUTAP VRG I/III WS, VRG I HD WS, tap selector size E, potential switch (899967)............. 121
4.74 VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder andpotential switch (899952) ................................................................................................................ 122
4.75 VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder andpotential switch (899953) ................................................................................................................ 123
4.76 VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder andpotential switch (899954) ................................................................................................................ 124
4.77 VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder(899960).......................................................................................................................................... 125
4.78 VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder(899956).......................................................................................................................................... 126
-
8/10/2019 2188029_02en
6/136
Table of contents
Maschinenfabrik Reinhausen 20136 2188029/02 ENVACUTAP VR I II III/VR I HD
4.79 VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder(899961).......................................................................................................................................... 127
4.80 VACUTAP VRD/VRF III WP, tap selector size C/D, tie-in resistor cylinder and potential switch(899963).......................................................................................................................................... 128
4.81 VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in resistor cylinder and potential switch(899965).......................................................................................................................................... 129
4.82 VACUTAP VRF II 1302 WP, tap selector size C/D, tie-in resistor cylinder (728691) ................... 130
4.83 VACUTAP VRF II 1302 WR, tap selector size C/D, tie-in resistor cylinder (728690)................... 131
4.84 VACUTAP VRF I 2602 WP, tap selector size C/D, tie-in resistor cylinder (729538) .................... 132
4.85 VACUTAP VRF I 2602 WR, tap selector size C/D, tie-in resistor cylinder (729537).................... 133
-
8/10/2019 2188029_02en
7/136
1 General
Maschinenfabrik Reinhausen 2013 72188029/02 EN VACUTAP VR I II III/VR I HD
General
On-load tap-changer designations
Example: VRF I 1301 Y245 / C10 19 1W R
VRF = Type VACUTAP VRC VRC
VACUTAP VRE VRE
VACUTAP VRD VRD
VACUTAP VRF VRF
VACUTAP VRG VRG
I = Number of phases 1 phase I
2 phases II
3 phases III
1301 = Ium[A] VRC 400
VRC 550
VRC, VRE 700
VRC, VRE, VRD, VRF, VRG 1000
VRC, VRE, VRD, VRF, VRG 1300
VRF, VRG 1600
VRF, VRG 2600
1301 = Number of parallel main switching con-tacts
1 (3-phase Y) 0
1 (1-phase) 1
2 (1-phase) 2
3 (1-phase) 3
Y = Applications For use with neutral point only Y
245 = Um[kV] VRC, VRE, VRD, VRF, VRG 72.5
VRC, VRE, VRD, VRF, VRG 123
VRC, VRE, VRD, VRF, VRG 170
VRC, VRE, VRD, VRF, VRG 245
VRC, VRE, VRD, VRF, VRG 300
VRF, VRG 362
C = Tap selector size VRC, VRE B
VRC VRE, VRD, VRF CVRC, VRE, VRD, VRF D
VRC, VRE DE
VRG E
10 = Maximum number of operating posi-tions without change-over selector
10 10
12 12
14 14
16 16
18 18
1
1.1
-
8/10/2019 2188029_02en
8/136
1 General
Maschinenfabrik Reinhausen 20138 2188029/02 ENVACUTAP VR I II III/VR I HD
19 = Maximum number of operating posi-tions with change-over selector
19 19
23 23
27 27
31 31
35 35
1W = Mid-positions 0 mid-positions (without change-over selector)
0
1 mid-position 1
3 mid-positions 3
1W = Change-over selector Reversing change-over selector W
Coarse tap connection G
R = Tie-in measures Tie-in resistor R
Potential switch SPotential switch with tie-in resistor P
Table 1: Explanation of type designation
If intended to be used in applications with increased number of tap-changeoperations, the on-load tap-changer is also available as VACU-TAP VR I HD.
-
8/10/2019 2188029_02en
9/136
1 General
Maschinenfabrik Reinhausen 2013 92188029/02 EN VACUTAP VR I II III/VR I HD
Summary of the technical data
VACUTAP VRC/VRD I
On-load tap-changer VRC I 401 VRC I 551 VRC I 701 VRC I 1001 VRC I 1301
VRD I 1301
Number of phasesand application
1 1 1 1 1
Maximum ratedthrough current Ium(inA)
400 550 700 1000 1300
Rated short-time cur-rent (kA)
6 8 10 12 15
Rated duration ofshort-circuits (s)
3 3 3 3 3
Rated peak withstandcurrent (kA)
15 20 25 30 37.5
Maximum rated stepvoltage Vin(V)
1)
3300 3300 3300 3300 3300
Step capacity (PStN)(kVA)
1320 1500 1500 1500 1500
Table 2: Technical data for VACUTAP VRC/VRD I
1)The maximum rated step voltage may be exceeded by 10 % due to over-excitation of the transformer if the step capacity is limited to its rated value.
1.2
-
8/10/2019 2188029_02en
10/136
1 General
Maschinenfabrik Reinhausen 201310 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRE/VRF/VRG I
On-load tap-changer VRE I 701 VRE I 1001VRF I 1001
VRG I 1001
VRE I 1301VRF I 1301
VRG I 1301
VRF I 1601VRG I 1601
VRF I 2602
1)
VRG I 26021)
Number of phasesand application
1 1 1 1 1
Maximum ratedthrough current Ium(inA)
700 1000 1300 1600 2600
Rated short-time cur-rent (kA)
10 12 15 19 26
Rated duration ofshort-circuits (s)
3 3 3 3 3
Rated peak withstandcurrent (kA)
25 30 37.5 47.5 65
Maximum rated stepvoltage Vin(V)
2)
4000 4000 4000 4000 4000
Step capacity (PStN)(kVA)
2800 3750 3750 3750 6000
Table 3: Technical data for VACUTAP VRE/VRF/VRG I
1)Forced current splitting by two parallel winding branches required (notavailable for VR I HD).
2)The maximum rated step voltage may be exceeded by 10 % due to over-
excitation of the transformer if the step capacity is limited to its rated value.
-
8/10/2019 2188029_02en
11/136
1 General
Maschinenfabrik Reinhausen 2013 112188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC/VRF/VRG II
On-load tap-changer VRC II 402 VRC II 552 VRC II 702 VRF II 1302VRG II 1302
Number of phases and application 2 2 2 2
Maximum rated through current Ium(inA)
400 550 700 1300
Rated short-time current (kA) 6 8 10 15
Rated duration of short-circuits (s) 3 3 3 3
Rated peak withstand current (kA) 15 20 25 37.5
Maximum rated step voltage Vin(V)1) 3300 3300 3300 4000
Step capacity (PStN) (kVA) 1320 1500 1500 3000
Table 4: Technical data for VACUTAP VRC/VRF/VRG II
1)The maximum rated step voltage may be exceeded by 10 % due to over-excitation of the transformer if the step capacity is limited to its rated value.
-
8/10/2019 2188029_02en
12/136
1 General
Maschinenfabrik Reinhausen 201312 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE III
On-load tap-changer VRC III 400 Y VRC III 550 Y VRC III 700 Y VRE III 700 YNumber of phases and application 31) 31) 31) 31)
Maximum rated through current Ium(inA)
400 550 700 700
Rated short-time current (kA) 6 8 10 10
Rated duration of short-circuits (s) 3 3 3 3
Rated peak withstand current (kA) 15 20 25 25
Maximum rated step voltage Vin(V)2) 3300 3300 3300 4000
Step capacity (PStN) (kVA) 1320 1500 1500 2800
Table 5: Technical data for VACUTAP VRC/VRE III
1)
neutral point2)The maximum rated step voltage may be exceeded by 10 % due to over-excitation of the transformer if the step capacity is limited to its rated value.
-
8/10/2019 2188029_02en
13/136
1 General
Maschinenfabrik Reinhausen 2013 132188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF/VRG III
On-load tap-changer VRD III 1000 Y VRD III 1300 Y VRF III 1000 YVRG III 1000 Y
VRF III 1300 YVRG III 1300 Y
Number of phases and appli-cation
31) 31) 31) 31)
Maximum rated through cur-rent Ium(in A)
1000 1300 1000 1300
Rated short-time current (kA) 12 15 12 15
Rated duration of short-cir-cuits (s)
3 3 3 3
Rated peak withstand current(kA)
30 37.5 30 37.5
Maximum rated step voltageVin(V)2) 3300 3300 4000 4000
Step capacity (PStN) (kVA) 1500 1500 3000 3000
Table 6: Technical data for VACUTAP VRD/VRF/VRG III
1)neutral point
2)The maximum rated step voltage may be exceeded by 10 % due to over-excitation of the transformer if the step capacity is limited to its rated value.
-
8/10/2019 2188029_02en
14/136
1 General
Maschinenfabrik Reinhausen 201314 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC I HD
On-load tap-changer VRC I HD401 VRC I HD551 VRC I HD701 VRC I HD1001 VRC I HD1301
Number of phasesand application
1 1 1 1 1
Maximum ratedthrough current Ium(inA)
400 550 700 1000 1300
Rated short-time cur-rent (kA)
6 8 10 12 15
Rated duration ofshort-circuits (s)
3 3 3 3 3
Rated peak withstand
current (kA)
15 20 25 30 37.5
Maximum rated stepvoltage Vin(V)
1)
3300 3300 3300 3300 3300
Step capacity (PStN)(kVA)
1320 1500 1500 1500 1500
Table 7: Technical data for VACUTAP VRC I HD
1)The maximum rated step voltage may be exceeded by 10 % due to over-excitation of the transformer if the step capacity is limited to its rated value.
-
8/10/2019 2188029_02en
15/136
1 General
Maschinenfabrik Reinhausen 2013 152188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRE/VRD/VRF/VRG I HD
On-load tap-changer VRE I HD 701 VRE I HD 1001VRF I HD 1001
VRG I HD 1001
VRD I HD 1301 VRE I HD 1301VRF I HD 1301
VRG I HD 1301
Number of phases and appli-cation
1 1 1 1
Maximum rated through cur-rent Ium(in A)
700 1000 1300 1300
Rated short-time current (kA) 10 12 15 15
Rated duration of short-cir-cuits (s)
3 3 3 3
Rated peak withstand current
(kA)
25 30 37.5 37.5
Maximum rated step voltageVin(V)
1)
4000 4000 3300 4000
Step capacity (PStN) (kVA) 2800 3750 1500 3750
Table 8: Technical data for VACUTAP VRE/VRD/VRF/VRG I HD
1)The maximum rated step voltage may be exceeded by 10 % due to over-excitation of the transformer if the step capacity is limited to its rated value.
For all on-load tap-changer variants
Rated frequency (in Hz) 50...60
Operating positions without change-over selector: maximum of 181)with change-over se-lector: maximum of 351)
Oil compartment Pressure-tight up to 0.3 bar permanent differential pressure (test pres-sure 0.6 bar), head and cover of the on-load tap-changer are vacuum-proof
Temperature range The on-load tap-changer VACUTAP VR can be operated in the ratedload range at oil temperatures of between 25 C and + 105 C andoverload up to + 115 C according to IEC 60214-1.
Dimensions Weight, displacement volume and oil content of the diverter switch oilcompartment are shown in the relevant dimension drawings.
Table 9: Technical data for VACUTAP VR
1)For more operating positions, see chapter "Special designs [26]"
-
8/10/2019 2188029_02en
16/136
1 General
Maschinenfabrik Reinhausen 201316 2188029/02 ENVACUTAP VR I II III/VR I HD
Rated insulation level
Rated insulation level On-load tap-changer 72.5 kV362 kV VRF/VRG I 1001; VRF/VRG I HD 1001
VRF/VRG I 1301; VRF/VRG I HD 1301VRF/VRG II 1302VRF/VRG I 1601VRF/VRG I 2602
72.5 kV300 kV VRC I 401/551/701; VRC I HD 401/551/701VRC I 1001; VRC I HD 1001VRC I 1301; VRC I HD 1301VRE I 1001; VRE I HD 1001VRE I 1301; VRE I HD 1301VRD I 1301; VRD I HD 1301
VRE I 701; VRE I HD 701VRC II 402/552/702
72.5 kV245 kV VRC III 400/550/700 YVRD III 1000 Y; VRD III 1300 YVRE III 700 Y; VRF/VRG III 1000 YVRF/VRG III 1300 Y
Highest voltage for equipment Vm(kV)1) 72.5 123 170 245 300 362
Rated lightning impulse withstand voltage (kV,1.2/50 s)
350 550 750 1050 1050 1175
Rated switching impulse voltage (kV) 850 850 950
Rated short-duration power frequency withstandvoltage (kV, 50 Hz, 1 min)
140 230 325 460 460 510
1)According to IEC 60214-1, chapter 3.57: highest effective value for phase-to-phase voltage in a three-phase system for which a on-load tap-changer isdesigned with respect to its insulation.
1.3
-
8/10/2019 2188029_02en
17/136
2 Technical data
Maschinenfabrik Reinhausen 2013 172188029/02 EN VACUTAP VR I II III/VR I HD
Technical data
Step capacity diagram VRC and VRE
Figure 1: Step capacities (rated voltage V i, rated through current Iu)
Step capacity diagram VRD, VRF, VRG*
* VRG: Versions identical to VRF but with tap selector size "E"
Figure 2: Step capacities (rated step voltages V i, rated through current Iu)
2
2.1
2.2
-
8/10/2019 2188029_02en
18/136
2 Technical data
Maschinenfabrik Reinhausen 201318 2188029/02 ENVACUTAP VR I II III/VR I HD
Step capacity diagram VRC, VRE electrical arc furnace op-eration)*
* Please contact MR
Figure 3: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),(rated step voltages Vi, rated through current Iu)
Step capacity diagram VRD, VRF, VRG* (electrical arc fur-nace operation)**
* VRG: Versions identical to VRF but with tap selector size "E"
** Please contact MR
Figure 4: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),(rated step voltages Vi, rated through current Iu)
2.3
2.4
-
8/10/2019 2188029_02en
19/136
2 Technical data
Maschinenfabrik Reinhausen 2013 192188029/02 EN VACUTAP VR I II III/VR I HD
Step capacity diagram VRC/VRE I HD
Figure 5: Step capacities (rated step voltages V i, rated through current Iu)
Step capacity diagram VRD/VRF/VRG* I HD
* VRG: Versions identical to VRF but with tap selector size "E"
Figure 6: Step capacities (rated step voltage Vi, rated through current Iu)
2.5
2.6
-
8/10/2019 2188029_02en
20/136
2 Technical data
Maschinenfabrik Reinhausen 201320 2188029/02 ENVACUTAP VR I II III/VR I HD
Step capacity diagram VRC/VRE I HD (electrical arc furnaceoperation)*
* Please contact MR
Figure 7: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),(rated step voltage Vi, rated through current Iu)
Step capacity diagram VRD/VRF/VRG* I HD (electrical arcfurnace operation)**
* Please contact MR
** VRG: Versions identical to VRF but with tap selector size "E"
Figure 8: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),(rated step voltage Vi, rated through current Iu)
2.7
2.8
-
8/10/2019 2188029_02en
21/136
2 Technical data
Maschinenfabrik Reinhausen 2013 212188029/02 EN VACUTAP VR I II III/VR I HD
Rated withstand voltages of the internal insulation
The following diagrams show the voltage stress present on the tap windingof the three primary basic connections of three-pole on-load tap-changersand single-pole on-load tap-changers.
When selecting the on-load tap-changer, you must check that the higheststress on the tap selector does not exceed the related rated withstand vol-tages.
without change-over selector with reversing change-over selector
with coarse change-over selector in (+) posi-tion
with coarse change-over selector in (-) position1* Notice: Observe maximum rated lightning impulse withstand voltage stress at a0 in mid-position!
a0 = between selected and preselected tap on the diverter switch
a1 = between fine tap selector contacts of the winding of one tap position (connected or not connected)
2.9
-
8/10/2019 2188029_02en
22/136
2 Technical data
Maschinenfabrik Reinhausen 201322 2188029/02 ENVACUTAP VR I II III/VR I HD
a = between start and end of a tapped winding and, in version with coarse winding, between start andend of a coarse winding
Note for coarse tap selector connection (-) position of the change-over selector: When loading withimpulse voltage, note the permissible withstand voltage "a" between the end of a coarse windingconnected with the K fine tap selector contact and the fine tap selector contact at the end of thetapped winding of the same phase.
b = between the fine tap selector contacts of different phases and between change-over selector con-tacts of different phases, which are connected with the beginning/end of a tapped winding or with afine tap selector contact
f = between diverter switch output terminal and ground
Additionally for coarse tap selector connection in (+) position of the change-over selector:
c1 = from one (-) change-over selector contact to take-off lead of the same phase
c2 = between (-) change-over selector contacts of different phases
Insulation distances Tap selector size C Tap selector size D1) Tap selector size E
kV1.2/50 s
kV50 Hz1 min
kV1.2/50 s
kV50 Hz1 min
kV1.2/50 s
kV50 Hz1 min
a0 Maximum1502)
20 Maximum1502)
20 Maximum1502)
20
a1 150 30 150 30 150 30
a 400 85 5003) 110 670 180
b4) 400 100 5003) 150 670 180
c1 550 180 590 210 820 250
c24) 550 195 590 225 820 280
Table 10: On-load tap-changer VRD, VRF, VRG, rated withstand voltages of the internal on-load tap-changer insulation
1)Tap selectors according to basic connection diagram 10 09 1 W, 12 111W, 14 13 1 W are designed as 18 09 1 W, 18 11 1 W, 18 13 1 W. Tap se-lectors according to basic connection diagram 16 15 1 W and 18 17 1 W arenot available.
2)Varistor response voltage at 1.2/50 s lightning impulse: as of 55 kV (U100%(t)standardized U75%(t)standardized, residual voltage at 3 kA peak current: 70 kV
3)Higher values up to 550 kV on request
4)Insulation distance omitted for single-pole on-load tap-changers
Insulation distan-ces
Tap selector sizeB
Tap selector sizeC
Tap selector sizeD
Tap selector sizeDE
kV1.2/50
s
kV50 Hz1 min
kV1.2/50
s
kV50 Hz1 min
kV1.2/50
s
kV50 Hz1 min
kV1.2/50
s
kV50 Hz1 min
a0 Maxi-mum1501)
20 Maxi-mum1501)
20 Maxi-mum1501)
20 Maxi-mum1501)
20
a1 150 30 150 30 150 30 150 30
a 265 50 350 82 490 105 550 120
-
8/10/2019 2188029_02en
23/136
2 Technical data
Maschinenfabrik Reinhausen 2013 232188029/02 EN VACUTAP VR I II III/VR I HD
Insulation distan-ces
Tap selector sizeB
Tap selector sizeC
Tap selector sizeD
Tap selector sizeDE
b2) 265 50 350 82 490 146 550 160
c1 485 143 545 178 590 208 660 230
c22) 495 150 550 182 590 225 660 250
Table 11: On-load tap-changer VRC, VRE, rated withstand voltages of the internal on-load tap-changer insulation
1)Varistor response voltage at 1.2/50 s lightning impulse: as of 55 kV (U100%(t)standardized U75%(t)standardized, residual voltage at 3 kA peak current: 70 kV
2)Insulation distance omitted for single-pole on-load tap-changers
The tap selector size (ID letters B, C, D, DE, E) characterizes the internal in-sulation of the tap selector, whose rated withstand voltages must be match-
ed to the requirements of the transformer winding.
The admissible maximum operating voltage on the individual tap selectordistances corresponds to half the value of the above mentioned rated short-duration power frequency withstand voltages.
without change-over selector with reversing change-over se-lector
with coarse change-over selec-tor
Tap-changeoperation
Tap selector size Tap-changeoperation
Tap selector size Tap-changeoperation
Tap selector size
10050 B/C/D/DE 10071W B/C/D/DE 10071G B/C/D/DE
10060 B/C/D/DE 10081W B/C/D/DE 10081G B/C/D/DE
10070 B/C/D/DE 10091W B/C/D/DE 10091G B/C/D/DE
10080 B/C/D/DE 12101W B/C/D/DE 12101G B/C/D/DE
10090 B/C/D/DE 12111W B/C 12111G B/C
10100 B/C/D/DE 14111W D/DE 14111G D/DE
12110 B/C/D/DE 14121W B/C 14121G B/C
12120 B/C/D/DE 14131W B/C 14131G B/C
14130 B/C/D/DE 16121W D/DE 16121G D/DE
14140 B/C/D/DE 16131W D/DE 16131G D/DE
16150 B/C/D/DE 16141W B/C/D/DE 16141G B/C/D/DE
16160 B/C/D/DE 16151W B/C 16151G B/C
18170 B/C/D/DE 18151W D/DE 18151G D/DE
18180 B/C/D/DE 18161W B/C 18161G B/C
22190 B/C/D/DE 18171W B/C 18171G B/C
22200 B/C/D/DE 10191W B/C/D/DE 10191G B/C/D/DE
22210 B/C 12231W B/C/D/DE 12231G B/C/D/DE
22220 B/C 14271W B/C/D/DE 14271G B/C/D/DE
16311W B/C/D/DE 16311G B/C/D/DE
18351W B/C/D/DE 18351G B/C/D/DE
Table 12: Available connections (also available as 3 W, 3 G)
-
8/10/2019 2188029_02en
24/136
2 Technical data
Maschinenfabrik Reinhausen 201324 2188029/02 ENVACUTAP VR I II III/VR I HD
On-load tap-changer VACUTAP VRC with multiple coarsechange-over selector
Extremely fine voltage adjustment requires a great number of operating posi-tions which sometimes can only be achieved with a multiple coarse tappingarrangement.
The multiple coarse change-over selector is attached to both sides of thefine tap selector.
Multiple coarse change-over selector
Figure 9: Designation and definition of insulation distances
a0 = between selected and preselected tap on the diverter switch
a1 = between fine tap selector contacts of the winding of one tap posi-tion (connected or not connected)
a = between beginning and end of a tapped winding and between theconnected K contact and any points of the tapped winding of thesame phase
b = between the fine tap selector contacts of different phases and be-tween the connected K contact of one phase and any points of thetapped winding of another phase
c1 = between any coarse tappings of one phase to the diverter switchoutput terminal of the same phase
c2 = between identically-named, unconnected coarse tappings of differ-ent phases
d1 = between connected and adjacent coarse tap contacts in onephase
d2 = between unconnected, adjacent coarse tap contacts in one phase
d3 = between beginning and end of all coarse tap connections of onephase
f = between diverter switch output terminal and ground
2.10
-
8/10/2019 2188029_02en
25/136
2 Technical data
Maschinenfabrik Reinhausen 2013 252188029/02 EN VACUTAP VR I II III/VR I HD
Insulation distan-ces
Tap selector size B Tap selector size C Tap selector size D
kV1.2/50 s
kV50 Hz1 min.
kV1.2/50 s
kV50 Hz1 min.
kV1.2/50 s
kV50 Hz1 min.
a0 Maximum1501)
20 Maximum1501)
20 Maximum1501)
20
a1 150 30 150 30 150 30
a 265 50 350 82 450 105
B2) 265 50 350 82 450 146
c1 455 127 525 165 590 210
c22) 455 127 525 165 590 215
d1 265 50 350 82 450 105
d2 350 82 450 105 450 105
d3 350 82 450 105 490 120
Table 13: On-load tap-changer VACUTAP VRC with multiple coarse change-over selector, rated withstand voltages ofthe internal on-load tap-changer insulation
1)Varistor response voltage at 1.2/50 s lightning impulse: as of 55 kV (U100%(t)standardized U75%(t)standardized, residual voltage at 3 kA peak current: 70 kV
2)Insulation distance omitted for single-pole on-load tap-changers
The admissible maximum operating voltage on the individual tap selectordistances corresponds to half the value of the above mentioned rated short-duration power frequency withstand voltages.
-
8/10/2019 2188029_02en
26/136
3 Special designs
Maschinenfabrik Reinhausen 201326 2188029/02 ENVACUTAP VR I II III/VR I HD
Special designs
Parallel bridges for parallel connections
Current division on the connection contacts of 2 tap selector planes only foron-load tap-changers VACUTAP VR I 1001 [95], VACUTAP VR I1601 [111] and of 3 tap selector planes only for on-load tap-changersVACUTAP VR I 1301 [95].
Parallel bridges on the tap selector connection contacts are then mandatoryif the tap winding has been wound in two or more branches and each ofthese branch taps is connected to the contacts of the tap selector.
This measure reliably prevents the following:
Introduction of circulating currents into the current paths of tap selectorand diverter switch
Commutating arc on movable tap selector contact bridges
Overvoltage between adjacent tap selector connection contacts con-nected in parallel
On-load tap-changer combination VACUTAP VRC I/VR II /VRF I/VRF II for delta connection
The on-load tap-changers VRC II 402, VRF II 1302 and VRG II 1302 can al-so be used with the single-pole on-load tap-changers VRC I 401, VRF I 1301and VRG I 1301 as two-column on-load tap-changer combinationsVRC I 401/VRC II 402, VRF I 1301/VRF II 1302 and VRG I 1301/VRG II 1302 to set the voltage for transformer windings in delta connections(the same is true with VRC I 551/VRC II 552 und VRC I 701/VRC II 702).
The tap developments for this should be provided as shown below.
3
3.1
3.2
-
8/10/2019 2188029_02en
27/136
3 Special designs
Maschinenfabrik Reinhausen 2013 272188029/02 EN VACUTAP VR I II III/VR I HD
Figure 10: On-load tap-changer combination VRC I 401 and VRC II 402 for delta con-nection
a VRC I 401 b VRC II 402
On-load tap-changer VACUTAP VRC III 700 Y,
VRC I 701/1001/1301 und VRC I HD 701/1001/1301 with mul-tiple coarse change-over selector (up to max. of 5 coarsetap connections)
Extremely fine voltage adjustment requires a great number of operating posi-tions which sometimes can only be achieved with a multiple coarse tappingarrangement.
For instance, 107 operating positions can be obtained by using a coarse 5-tap winding and a tapped winding with 18 taps.
The multiple coarse change-over selector is attached to both sides of thefine tap selector.
The on-load tap-changers are available (on request) for Vm= 72.5 up to max.300 kV and for 2...5 coarse tap connections (tap selector sizes B, C) or 2and 3 coarse tap connections (tap selector size D).
3.3
-
8/10/2019 2188029_02en
28/136
4 Appendix
Maschinenfabrik Reinhausen 201328 2188029/02 ENVACUTAP VR I II III/VR I HD
Appendix
VACUTAP VRC/VRE type overview (727017)
4
4.1
-
8/10/2019 2188029_02en
29/136
4 Appendix
Maschinenfabrik Reinhausen 2013 292188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
30/136
4 Appendix
Maschinenfabrik Reinhausen 201330 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF/VRG, type overview (727016)4.2
-
8/10/2019 2188029_02en
31/136
4 Appendix
Maschinenfabrik Reinhausen 2013 312188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
32/136
4 Appendix
Maschinenfabrik Reinhausen 201332 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VR, basic connection diagrams, designation oftap selector connection contacts according to MR standard(719037)
4.3
-
8/10/2019 2188029_02en
33/136
4 Appendix
Maschinenfabrik Reinhausen 2013 332188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
34/136
4 Appendix
Maschinenfabrik Reinhausen 201334 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF I 1001, VRD/VRF I 1301, VRF I 1001 HD,VRD/VRF I HD 1301, dimensional drawing (899805)
4.4
-
8/10/2019 2188029_02en
35/136
4 Appendix
Maschinenfabrik Reinhausen 2013 352188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
36/136
4 Appendix
Maschinenfabrik Reinhausen 201336 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF I 1001/1301 (Um 362 kV),VRF I HD 1001/1301 (Um 362 kV), dimensional drawing(899806)
4.5
-
8/10/2019 2188029_02en
37/136
4 Appendix
Maschinenfabrik Reinhausen 2013 372188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
38/136
4 Appendix
Maschinenfabrik Reinhausen 201338 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG I 1001/1301, VRG I HD 1001/1301, dimen-sional drawing (899810)
4.6
-
8/10/2019 2188029_02en
39/136
4 Appendix
Maschinenfabrik Reinhausen 2013 392188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
40/136
4 Appendix
Maschinenfabrik Reinhausen 201340 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG I 1001/1301 (Um 362 kV),VRG I HD 1001/1301 (Um 362 kV), dimensional drawing(899811)
4.7
-
8/10/2019 2188029_02en
41/136
4 Appendix
Maschinenfabrik Reinhausen 2013 412188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
42/136
4 Appendix
Maschinenfabrik Reinhausen 201342 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF I 1601, 72.5...300 kV, dimensional drawing(786915)
4.8
-
8/10/2019 2188029_02en
43/136
4 Appendix
Maschinenfabrik Reinhausen 2013 432188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
44/136
4 Appendix
Maschinenfabrik Reinhausen 201344 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF I 1601, 362 kV, dimensional drawing(786916)
4.9
-
8/10/2019 2188029_02en
45/136
4 Appendix
Maschinenfabrik Reinhausen 2013 452188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
46/136
4 Appendix
Maschinenfabrik Reinhausen 201346 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG I 1601, 72.5...300 kV, dimensional drawing(786917)
4.10
-
8/10/2019 2188029_02en
47/136
4 Appendix
Maschinenfabrik Reinhausen 2013 472188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
48/136
4 Appendix
Maschinenfabrik Reinhausen 201348 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG I 1601, 362 kV, dimensional drawing(786918)
4.11
-
8/10/2019 2188029_02en
49/136
4 Appendix
Maschinenfabrik Reinhausen 2013 492188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
50/136
4 Appendix
Maschinenfabrik Reinhausen 201350 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF I 2602, dimensional drawing (727033)4.12
-
8/10/2019 2188029_02en
51/136
4 Appendix
Maschinenfabrik Reinhausen 2013 512188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
52/136
4 Appendix
Maschinenfabrik Reinhausen 201352 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF I 2602 (Um 362 kV), dimensional drawing(727034)
4.13
-
8/10/2019 2188029_02en
53/136
4 Appendix
Maschinenfabrik Reinhausen 2013 532188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
54/136
4 Appendix
Maschinenfabrik Reinhausen 201354 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG I 2602, dimensional drawing (727035)4.14
-
8/10/2019 2188029_02en
55/136
4 Appendix
Maschinenfabrik Reinhausen 2013 552188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
56/136
4 Appendix
Maschinenfabrik Reinhausen 201356 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG I 2602 (Um 362 kV), dimensional drawing(727036)
4.15
-
8/10/2019 2188029_02en
57/136
4 Appendix
Maschinenfabrik Reinhausen 2013 572188029/02 EN VACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
58/136
4 Appendix
Maschinenfabrik Reinhausen 201358 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC I 401/551/701-0/W/G,VRC I HD 401/551/701-0/W/G, dimensional drawing (899990)
4.16
-
8/10/2019 2188029_02en
59/136
4 Appendix
Maschinenfabrik Reinhausen 2013 592188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRE I 701-0/W/G, VRE I HD 701-0/W/G, dimen-sional drawing (899991)
4.17
-
8/10/2019 2188029_02en
60/136
4 Appendix
Maschinenfabrik Reinhausen 201360 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC I 1001-0/W/G, VRC I HD 1001-0/W/G, di-mensional drawing (718306)
4.18
-
8/10/2019 2188029_02en
61/136
4 Appendix
Maschinenfabrik Reinhausen 2013 612188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRE I 1001-0/W/G, VRE I HD 1001-0/W/G, di-mensional drawing (718307)
4.19
-
8/10/2019 2188029_02en
62/136
4 Appendix
Maschinenfabrik Reinhausen 201362 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC I 1301-0/W/G, VRC I HD 1301-0/W/G, di-mensional drawing (718308)
4.20
-
8/10/2019 2188029_02en
63/136
4 Appendix
Maschinenfabrik Reinhausen 2013 632188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRE I 1301-0/W/G, VRE I HD 1301-0/W/G, di-mensional drawing (727040)
4.21
-
8/10/2019 2188029_02en
64/136
4 Appendix
Maschinenfabrik Reinhausen 201364 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC I 701/VRC I HD 701 with multiple coarsechange-over selector, dimensional drawing (718316)
4.22
-
8/10/2019 2188029_02en
65/136
4 Appendix
Maschinenfabrik Reinhausen 2013 652188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC I 1001/VRC I HD 1001 with multiple coarsechange-over selector, dimensional drawing (718318)
4.23
-
8/10/2019 2188029_02en
66/136
4 Appendix
Maschinenfabrik Reinhausen 201366 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC I 1301/VRC I HD 1301 with multiple coarsechange-over selector, dimensional drawing (718321)
4.24
-
8/10/2019 2188029_02en
67/136
4 Appendix
Maschinenfabrik Reinhausen 2013 672188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRF II 1302, dimensional drawing (899814)4.25
-
8/10/2019 2188029_02en
68/136
4 Appendix
Maschinenfabrik Reinhausen 201368 2188029/02 ENVACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
69/136
4 Appendix
Maschinenfabrik Reinhausen 2013 692188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRF II 1302 (Um 362 kV), dimensional drawing(899815)
4.26
-
8/10/2019 2188029_02en
70/136
4 Appendix
Maschinenfabrik Reinhausen 201370 2188029/02 ENVACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
71/136
4 Appendix
Maschinenfabrik Reinhausen 2013 712188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRG II 1302, dimensional drawing (899816)4.27
-
8/10/2019 2188029_02en
72/136
4 Appendix
Maschinenfabrik Reinhausen 201372 2188029/02 ENVACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
73/136
4 Appendix
Maschinenfabrik Reinhausen 2013 732188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRG II 1302 (Um 362 kV), dimensional drawing(899817)
4.28
-
8/10/2019 2188029_02en
74/136
4 Appendix
Maschinenfabrik Reinhausen 201374 2188029/02 ENVACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
75/136
-
8/10/2019 2188029_02en
76/136
4 Appendix
Maschinenfabrik Reinhausen 201376 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRE III 700 Y-0/W/G, dimensional drawing(899982)
4.30
-
8/10/2019 2188029_02en
77/136
4 Appendix
Maschinenfabrik Reinhausen 2013 772188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF III 1000/1300 Y, dimensional drawing(899803)
4.31
-
8/10/2019 2188029_02en
78/136
4 Appendix
Maschinenfabrik Reinhausen 201378 2188029/02 ENVACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
79/136
4 Appendix
Maschinenfabrik Reinhausen 2013 792188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRG III 1000/1300 Y, dimensional drawing(899804)
4.32
-
8/10/2019 2188029_02en
80/136
4 Appendix
Maschinenfabrik Reinhausen 201380 2188029/02 ENVACUTAP VR I II III/VR I HD
-
8/10/2019 2188029_02en
81/136
4 Appendix
Maschinenfabrik Reinhausen 2013 812188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC II 402/552/702-0/W/G, dimensional drawing(899989)
4.33
-
8/10/2019 2188029_02en
82/136
4 Appendix
Maschinenfabrik Reinhausen 201382 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC III 700 Y with multiple coarse change-overselector, dimensional drawing (718314)
4.34
-
8/10/2019 2188029_02en
83/136
4 Appendix
Maschinenfabrik Reinhausen 2013 832188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC III 400/550/700 Y-10191W, detailed con-nection diagram (ZS030355)
4.35
-
8/10/2019 2188029_02en
84/136
4 Appendix
Maschinenfabrik Reinhausen 201384 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRE III 700 Y-10193W, detailed connection dia-gram (ZS030356)
4.36
-
8/10/2019 2188029_02en
85/136
4 Appendix
Maschinenfabrik Reinhausen 2013 852188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD III 1300 Y-C/D-10191W, detailed connec-tion diagram (ZS030201)
4.37
-
8/10/2019 2188029_02en
86/136
4 Appendix
Maschinenfabrik Reinhausen 201386 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG III 1300 Y-E-14271G, detailed connectiondiagram (ZS030202)
4.38
-
8/10/2019 2188029_02en
87/136
4 Appendix
Maschinenfabrik Reinhausen 2013 872188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE, installation drawing (899992)
4.39
-
8/10/2019 2188029_02en
88/136
4 Appendix
Maschinenfabrik Reinhausen 201388 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF, installation drawing (899898)
4.40
-
8/10/2019 2188029_02en
89/136
4 Appendix
Maschinenfabrik Reinhausen 2013 892188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRG, installation drawing (899945)
4.41
-
8/10/2019 2188029_02en
90/136
4 Appendix
Maschinenfabrik Reinhausen 201390 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE, connecting leads 3W, 1G, 3G, di-mensional drawing (723590)
4.42
-
8/10/2019 2188029_02en
91/136
4 Appendix
Maschinenfabrik Reinhausen 2013 912188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VR, on-load tap-changer head (720847)
4.43
-
8/10/2019 2188029_02en
92/136
4 Appendix
Maschinenfabrik Reinhausen 201392 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VR, on-load tap-changer head with flange forpressure relief device (899946)
4.44
-
8/10/2019 2188029_02en
93/136
4 Appendix
Maschinenfabrik Reinhausen 2013 932188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VR, special design for bell-type tank installa-tion (720781)
4.45
-
8/10/2019 2188029_02en
94/136
4 Appendix
Maschinenfabrik Reinhausen 201394 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE, arrangement of contacts on tap se-lector, tap selector division 1022 (899993)
4.46
-
8/10/2019 2188029_02en
95/136
4 Appendix
Maschinenfabrik Reinhausen 2013 952188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE I 1001/1301, VRC/VRE I HD 1001/1301, bridges to parallel connection of tapselector connection contacts (727025)
4.47
-
8/10/2019 2188029_02en
96/136
4 Appendix
Maschinenfabrik Reinhausen 201396 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VR, installation position of tap selector con-nection contacts (727042)
4.48
-
8/10/2019 2188029_02en
97/136
4 Appendix
Maschinenfabrik Reinhausen 2013 972188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VR installation position of tap selector connec-tion contacts (743603)
4.49
-
8/10/2019 2188029_02en
98/136
4 Appendix
Maschinenfabrik Reinhausen 201398 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC III 400/550/700 Y, VRE III 700 Y, arrange-ment of tap selector (899994)
4.50
-
8/10/2019 2188029_02en
99/136
4 Appendix
Maschinenfabrik Reinhausen 2013 992188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC I 401/551/701, VRC I HD 401/551/701,VRE I 701, VRE I HD 701, arrangement of tap selector(899995)
4.51
-
8/10/2019 2188029_02en
100/136
4 Appendix
Maschinenfabrik Reinhausen 2013100 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE I 1001, VRC/VRE I HD 1001, arrange-ment of tap selector (899996)
4.52
-
8/10/2019 2188029_02en
101/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1012188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE I 1301, VRC/VRE I HD 1301, arrange-ment of tap selector (727043)
4.53
-
8/10/2019 2188029_02en
102/136
4 Appendix
Maschinenfabrik Reinhausen 2013102 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VR, variants of the on-load tap-changer head,gear unit swivel range and drive direction (721216)
4.54
-
8/10/2019 2188029_02en
103/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1032188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VR, swivel range of gear unit (728474)
4.55
-
8/10/2019 2188029_02en
104/136
4 Appendix
Maschinenfabrik Reinhausen 2013104 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VR, horizontal drive shaft (899958)
4.56
-
8/10/2019 2188029_02en
105/136
-
8/10/2019 2188029_02en
106/136
-
8/10/2019 2188029_02en
107/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1072188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC II, tie-in resistors with or without potentialswitch (899986)
4.59
-
8/10/2019 2188029_02en
108/136
4 Appendix
Maschinenfabrik Reinhausen 2013108 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE I, VRC/VRE I HD, tie-in resistors withor without potential switch (718447)
4.60
-
8/10/2019 2188029_02en
109/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1092188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRC/VRE, tie-in resistor cylinder with potentialswitch without tie-in resistors (899973)
4.61
-
8/10/2019 2188029_02en
110/136
4 Appendix
Maschinenfabrik Reinhausen 2013110 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF/VRG, fine tap selector connectioncontact and change-over selector connection contact(899941)
4.62
-
8/10/2019 2188029_02en
111/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1112188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRF, bridges to parallel connection of tap se-lector connection contacts (786919)
4.63
-
8/10/2019 2188029_02en
112/136
4 Appendix
Maschinenfabrik Reinhausen 2013112 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG, bridges to parallel connection of tap se-lector connection contacts (786920)
4.64
-
8/10/2019 2188029_02en
113/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1132188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF, tap selector size C/D, tap selectorbottom depiction of the lowest live parts (899968)
4.65
-
8/10/2019 2188029_02en
114/136
4 Appendix
Maschinenfabrik Reinhausen 2013114 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRG, tap selector size E, tap selector bottomdepiction of the lowest live parts (899969)
4.66
-
8/10/2019 2188029_02en
115/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1152188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF, arrangement of potential switches/tie-in resistors (899950)
4.67
-
8/10/2019 2188029_02en
116/136
4 Appendix
Maschinenfabrik Reinhausen 2013116 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selectorsize C/D, tie-in resistor cylinder and potential switch(899951)
4.68
-
8/10/2019 2188029_02en
117/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1172188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selectorsize C/D, tie-in resistor cylinder (899955)
4.69
-
8/10/2019 2188029_02en
118/136
-
8/10/2019 2188029_02en
119/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1192188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in re-sistor cylinder (899964)
4.71
-
8/10/2019 2188029_02en
120/136
4 Appendix
Maschinenfabrik Reinhausen 2013120 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I/III WS, VRD/VRF I HD WS, tap selec-tor size C/D, potential switch (899966)
4.72
-
8/10/2019 2188029_02en
121/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1212188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRG I/III WS, VRG I HD WS, tap selector size E,potential switch (899967)
4.73
-
8/10/2019 2188029_02en
122/136
4 Appendix
Maschinenfabrik Reinhausen 2013122 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selectorsize C/D, tie-in resistor cylinder and potential switch(899952)
4.74
-
8/10/2019 2188029_02en
123/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1232188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selectorsize C/D, tie-in resistor cylinder and potential switch(899953)
4.75
-
8/10/2019 2188029_02en
124/136
4 Appendix
Maschinenfabrik Reinhausen 2013124 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selectorsize C/D, tie-in resistor cylinder and potential switch(899954)
4.76
-
8/10/2019 2188029_02en
125/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1252188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selectorsize C/D, tie-in resistor cylinder (899960)
4.77
-
8/10/2019 2188029_02en
126/136
4 Appendix
Maschinenfabrik Reinhausen 2013126 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selectorsize C/D, tie-in resistor cylinder (899956)
4.78
-
8/10/2019 2188029_02en
127/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1272188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selectorsize C/D, tie-in resistor cylinder (899961)
4.79
-
8/10/2019 2188029_02en
128/136
4 Appendix
Maschinenfabrik Reinhausen 2013128 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF III WP, tap selector size C/D, tie-in re-sistor cylinder and potential switch (899963)
4.80
-
8/10/2019 2188029_02en
129/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1292188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in re-sistor cylinder and potential switch (899965)
4.81
-
8/10/2019 2188029_02en
130/136
4 Appendix
Maschinenfabrik Reinhausen 2013130 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF II 1302 WP, tap selector size C/D, tie-in re-sistor cylinder (728691)
4.82
-
8/10/2019 2188029_02en
131/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1312188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRF II 1302 WR, tap selector size C/D, tie-in re-sistor cylinder (728690)
4.83
-
8/10/2019 2188029_02en
132/136
4 Appendix
Maschinenfabrik Reinhausen 2013132 2188029/02 ENVACUTAP VR I II III/VR I HD
VACUTAP VRF I 2602 WP, tap selector size C/D, tie-in re-sistor cylinder (729538)
4.84
-
8/10/2019 2188029_02en
133/136
4 Appendix
Maschinenfabrik Reinhausen 2013 1332188029/02 EN VACUTAP VR I II III/VR I HD
VACUTAP VRF I 2602 WR, tap selector size C/D, tie-in re-sistor cylinder (729537)
4.85
-
8/10/2019 2188029_02en
134/136
-
8/10/2019 2188029_02en
135/136
-
8/10/2019 2188029_02en
136/136
MR worldwide
Australia
Reinhausen Australia Pty. Ltd.
17/20-22 St Albans Road
Kingsgrove NSW 2208
Phone: +61 2 9502 2202
Fax: +61 2 9502 2224
E-Mail: [email protected]
Brazil
MR do Brasil Indstria Mecnica Ltda.
Av. Elias Yazbek, 465
CEP: 06803-000
Embu - So Paulo
Phone: +55 11 4785 2150
Fax: +55 11 4785 2185
E-Mail: [email protected]
Canada
Reinhausen Canada Inc.
3755, rue Java, Suite 180
Brossard, Qubec J4Y 0E4
Phone: +1 514 370 5377
Fax: +1 450 659 3092
E-Mail: [email protected]
India
Easun-MR Tap Changers Ltd.
612, CTH Road
Tiruninravur, Chennai 602 024
Phone: +91 44 26300883
Fax: +91 44 26390881
E-Mail: [email protected]
Indonesia
Pt. Reinhausen Indonesia
German Center, Suite 6310,
Jl. Kapt. Subijanto Dj.
BSD City, Tangerang
Phone: +62 21 5315-3183
Fax: +62 21 5315-3184
E-Mail: [email protected]
IranIran Transfo After Sales Services Co.
Zanjan, Industrial Township No. 1 (Aliabad)
Corner of Morad Str.
Postal Code 4533144551
Malaysia
Reinhausen Asia-Pacific Sdn. Bhd
Level 11 Chulan Tower
No. 3 Jalan Conlay
50450 Kuala Lumpur
Phone: +60 3 2142 6481
Fax: +60 3 2142 6422
E-Mail: [email protected]
P.R.C. (China)
MR China Ltd. (MRT)
360
4 E
200120
86 21 61634588
86 21 61634582
Russian Federation
OOO MR
Naberezhnaya Akademika Tupoleva
15, Bld. 2 ("Tupolev Plaza")
105005 MoscowPhone: +7 495 980 89 67
Fax: +7 495 980 89 67
E-Mail: [email protected]
South Africa
Reinhausen South Africa (Pty) Ltd.
No. 15, Third S treet, Booysens Reserve
Johannesburg
Phone: +27 11 8352077
Fax: +27 11 8353806
E-Mail: [email protected]
South Korea
Reinhausen Korea Ltd.
21st floor, Standard Chartered Bank Bldg.,
47, Chongro, Chongro-gu,
Seoul 110-702
Phone: +82 2 767 4909
Fax: +82 2 736 0049
E-Mail: [email protected]
U.S.A.
R i h M f t i I