    Electrical Safety Clearance (Part-1)

    AUGUST 8, 20129 COMMENTS

    Standard: Qatar General Electricity & Water Corporation

    Minimum Safety Clearance of Pipelines from Electrical Tower:

    DescriptionVoltage

    33KV/66KV/132KV 220KV/400KV

    The right of way(ROW) (widths oneither side of the

    center line of

    overheadtransmission lines

    )

    25 Meter 50 Meter

    Other than the

    roadways andboundary fences ofsecurityestablishmentsany temporary or

    permanentstructures /buildings, parapet

    walls,

    Not within 25 MeterNot within 50

    Meter

    With All

    Underground

    services crossing

    the way leave(from the nearest

    tower foundation)

    35 Meter (Min) 50 Meter (Min)

    The nearest side of

    the road

    reservation to thenearest towerfoundation

    25 Meter35 Meter,50

    Meter

    The pipelines(water, oil/gas

    etc.) crossing

    (respectively awayfrom the nearest

    base of tower leg).Pipe-lines shall not

    be laid parallel tothe overhead line

    within the limits of

    a way leave(ROW).

    25 Meter (Min)35 Meter(Min),50 Meter(Min)

    http://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#commentshttp://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#commentshttp://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#commentshttp://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#comments
  • 7/26/2019 204189355 Electrical Safety Clearance

    2/23

    Cables crossing

    the transmissionlines way leave(ROW)

    respectively away

    from the nearest

    base of tower leg.

    25 Meter35 Meter,50

    Meter

    Foundations andcivil structures(Temporary or

    permanent) will

    not be permittedin the close

    proximity to the

    cable circuit. Aminimum

    horizontal distancefrom such

    structures to thenearest edge of

    the cable trenchshall be observed

    Min 1.5 Meter Min 1.5 Meter

    Clearance among Electrical Line-Telephone- Water-Sewerage -Gas Line

    Service VerticalClearance(Min)

    Water Line (to cross below EHV cablelevel)

    0.5 Meter

    Sewerage Mains (to cross below EHV

    cable level)

    1.0 Meter

    Drainage Mains (to cross below EHVcable level)

    0.5 Meter

    Gas pipes 0.6 Meter

    Telephone lines 0.5 Meter

    LV / 11kV cables 0.5 Meter

    Safety Clearance for Excavation of Land :

    Type of Excavation Distance

    Use of heavy mechanical

    excavators (other than handoperated pneumatic jackhammers) or driving sheet piles

    Not less than 3 Meter from

    the edge of cable, cover,cable joint

    Heavy machinery engaged in the

    civil construction or road works

    operating load/thrust/weight will not be applied

    directly on the cable

    installation

    Trench excavations parallel to Minimum separation of 1

  • 7/26/2019 204189355 Electrical Safety Clearance

    3/23

    the cable installations Meter to the nearest edge

    of cable tile

    Laying of metal pipes over a long

    distance parallel to cable

    Not permitted unless the

    Step and Touch Potentials

    at any point of the pipe line

    do not exceed 65 Volts.(A) Inside Towns

    Distance between Towers foundation to Pipeline in parallel and intersections.

    Voltage Min Distance

    380/220V 0.5 Meter

    20KV 2 Meter

    63KV 7 Meter

    132KV 10 Meter

    230KV and Above 20 Meter

    Distance between underground power cables to wall of gas pipelines in parallelroutes.

    Voltage Min HorizontalDistance

    Min VerticalDistance

    380/220V 1 Meter 0.5 Meter

    20KV 2 Meter 1 Meter

    63KV 3 Meter 1.5 Meter

    (B) Outside of Towns:

    Distance between Towers foundation to Pipeline in parallel and intersections.

    KVMin Distance in

    Parallel Route (Up to5 Km)

    Min Distance inParallel Route(Above 5 Km)

    20KV 20 Meter 30 Meter

    63KV 30 Meter 40 Meter

    132KV 40 Meter 50 Meter

    230KV 50 Meter 60 Meter

    400KV 60 Meter 60 Meter

    Distance between overhead lines to gas pipelines at intersections.

    KV Min Distance

    20KV 8 Meter

    63KV 9 Meter

    132KV 10 Meter

    230KV 11 Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    4/23

    400KV 12 Meter

    Distance between Towers foundations to gas pipelines at intersections.

    KV Min Distance

    20KV 20 Meter

    63KV and Higher 30 Meter

    Right Of Way (R.O.W) From Roads:

    Highway Distance

    High Way : (38 meter from one side of Central

    Line of Highway)76 Meter

    First Class State Road=(22.5 meter from one

    side of Central Line of Highway)

    45 Meter

    Second Class State Road=(17.5 meter from oneside of Central Line of Highway)

    35 Meter

    Third Class State Road =(12.5 meter from oneside of Central Line of Highway)

    25 Meter

    Forth Class State Road=(7.5 meter from one

    side of Central Line of Highway)

    15 Meter

    General Electrical Safety Clearance:

    KV Description Distance

    Up to 11

    KV

    At points where thelines cross roads or

    railwaysMin 6 Meter Height

    Up to 11

    KVparallel to roads the Min 5.5 Meter Height

    Up to 11

    KV

    lines cross totallydesert regions whereno traffic is possible

    Min 5.5 Meter Height

    20 KV to66 KV

    All Location Min 6 Meter Height

    Up to 11KV

    Conductor JointNo joint shall be closer

    than 3 meters to apoint of support

    33 KV & 66

    KV

    Conductor Joint No tension joints shall

    be used unlessspecially approved.

  • 7/26/2019 204189355 Electrical Safety Clearance

    5/23

    Electrical Safety Clearance (Part-2)

    AUGUST 9, 201216 COMMENTS

    Code: Indian Electricity Rules/ Central Electricity Authority:

    Right of Way Clearance (As per GETCO Standard):

    KV Min ROW

    66 KV 18 Meter

    132 KV 27 Meter

    220 KV 35 Meter

    400KV 52 Meter (Single Circuit)

    400 KV 48 Meter (Double Circuit)

    Minimum clearances between Electrical Lines crossing each other:

    Voltage 66 KV132

    KV

    220

    KV

    400 KV

    66 KV2.4

    Meter3 Meter 4.5

    Meter5.4

    Meter

    132 KV 3 Meter3 Meter 4.5

    Meter

    5.4

    Meter

    220 KV4.5

    Meter

    4.5

    Meter

    4.5

    Meter

    5.4

    Meter

    400 KV4.5

    Meter

    5.4

    Meter

    5.4

    Meter

    5.4

    MeterPermissible Min ground Clearance of Electrical Line:

    KV Ground ClearanceOver National

    Highway

    66 KV 6.1 Meter 8.0 Meter

    132 KV 6.1 Meter 8.6 Meter

    220 KV 7.0 Meter 9.8 Meter

    400KV 8.8 Meter 10.8 Meter

    Clearance for Telephone line Crossings Power Line:

    KV Clearance (Min)

    66 KV 2.4 Meter

    132 KV 2.7 Meter

    220 KV 3.0 Meter

    Vertical Clearance between Electrical Line and railway tracks.

    KV Clearance (Min)

    http://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#commentshttp://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#commentshttp://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#commentshttp://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#comments
  • 7/26/2019 204189355 Electrical Safety Clearance

    6/23

    66 KV 14 Meter

    132 KV 14.6 Meter

    220 KV 15.4 Meter

    400 KV 17.9 Meter

    Clearance from Buildings to low, medium & high voltage lines:

    Voltage Description Distance

    Low &

    MediumVoltage

    Flat roof, open balcony,

    verandah roof ,When the linepasses above the building avertical clearance from the

    highest point

    2.5 Meter

    Low &Medium

    Voltage

    Line passes adjacent to thebuilding a horizontal

    clearance from the nearestpoint

    1.2 Meter

    Low &Medium

    Voltage

    Line passes above thebuilding a vertical clearance

    2.5 Meter

    Low &Medium

    Voltage

    Line passes adjacent thebuilding a Horizontal

    clearance

    1.2 Meter

    11 KV to 33

    KV

    Line passes above or

    adjacent to any building orpart of a building

    3.7 Meter

    Above 33

    KV

    Line passes above or

    adjacent to any building orpart of a building

    3.7+(0.3 for

    everyadditional 33KV )

    Up to 11 KV The horizontal clearance

    between the nearerconductor and any part of

    such building

    1.2 Meter

    11 KV to 33

    KV

    The horizontal clearance

    between the nearerconductor and any part of

    such building

    2.0 Meter

    Above 33 The horizontal clearancebetween the nearer

    2.0 + (0.3 forevery

  • 7/26/2019 204189355 Electrical Safety Clearance

    7/23

    KV conductor and any part

    ofsuch building

    additional 33

    KV )

    Clearance above ground at the lowest conductor:

    Voltage Description Distance

    Low & MediumVoltage

    Across a street 5.8 Meter

    High Voltage Across a street 6.1 Meter

    Low & Medium

    Voltage

    Along a street 5.5 Meter

    High Voltage Along a street 5.8 Meter

    Low & MediumVoltage Elsewhere than alongor across any street 4.0 Meter

    High Voltage Elsewhere than alongor across any street

    5.2 Meter

    33 KV & EHV Clearance above

    ground(Add 0.3 Meter

    for every 33 KV Voltsin 5.2 Meter)

    Min 6.1

    Meter

    Vertical Clearance at Middle of Span:

    SpanVertical Clearance (At Middle of

    Span)

    200 Meter 4.0 Meter

    300 Meter 5.5 Meter

    400 Meter 7.0 Meter

    500 Meter 8.5 Meter

    Safety Clearance from Live Part in Outdoor Substation:

    KV Safety Working Clearance

    12 KV 2.6 Meter

    36 KV 2.8 Meter

    72.5 KV 3.1 Meter

    145 KV 3.7 Meter

    220 KV 4.3 Meter

    400KV 6.4 Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    8/23

    800 KV 10.3 Meter

    Lying of Telecommunication Cables with Power Cables (>33 kV).

    Cable Min. Distance

    Power cable of voltage exceeding

    33 kV shall be laid

    Min 1.2 Meter depth

    Underground telecommunicationcable shall be with underground

    power cable of voltage exceeding

    33 kV.

    Min 0.6 Meter Separatefrom Power Cable

    Safe approach limits for people:

    Voltage

    214V

    to

    415KV

    11KV 33KV 66KV 132KV 275KV

    Person

    usingmanually

    operated

    tool

    1.3

    Meter

    2.0

    Meter

    3.0

    Meter

    4.0

    Meter

    5.0

    Meter

    6.0

    Meter

    Personusing

    poweroperated

    tool

    3.0Meter

    3.0Meter

    3.0Meter

    4.0Meter

    5.0Meter

    6.0Meter

    Electrical Safety Clearance (Part-3)

    AUGUST 10, 20128 COMMENTS

    Standard:Northern Ireland Electricity (NIE), 6/025 ENA

    Clearances of Electrical Line to Ground and Roads:

    Description

    ofClearance

    0.4KV

    11KV

    33KV 110KV220KV

    400KV

    Lineconductor toany point

    not over

    road

    5.2Meter

    6.1Meter

    6.4Meter

    6.4Meter

    7.0Meter

    7.0Meter

    Line

    conductor toroad surface

    5.8

    Meter

    6.1

    Meter

    6.4

    Meter

    6.4

    Meter

    7.4

    Meter

    8.1

    Meter

    http://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#commentshttp://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#commentshttp://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#commentshttp://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#comments
  • 7/26/2019 204189355 Electrical Safety Clearance

    9/23

    Line

    conductor toroad surfaceof high load

    routes

    6.9

    Meter

    6.9

    Meter

    6.9

    Meter

    7.2

    Meter

    8.5

    Meter

    9.2

    Meter

    Bare livemetalwork (

    transformerterminals,jumper

    connections,

    etc)

    4.6Meter

    4.6Meter

    4.6Meter

    - - -

    Clearances of Electrical Line to Other Objects:

    Description

    of

    Clearance

  • 7/26/2019 204189355 Electrical Safety Clearance

    10/23

    Line

    conductorsto irrigates,slurry guns

    and high-

    pressure

    hoses

    30

    Meter

    30

    Meter

    30

    Meter

    30

    Meter

    30

    Meter

    Lineconductorsto playing

    fields

    8.5Meter

    8.5Meter

    8.5Meter

    8.5Meter

    8.5Meter

    Lineconductors

    to CaravanSites

    9.0Meter

    9.0Meter

    9.0Meter

    9.0Meter

    9.0Meter

    Horizontal

    clearancesto wells

    15.0

    Meter

    15.0

    Meter

    15.0

    Meter

    15.0

    Meter

    15.0

    Meter

    Clearances of Electrical Line to Trees and Hedges:

    Description

    ofClearance

  • 7/26/2019 204189355 Electrical Safety Clearance

    11/23

    metalwork

    to treesfallingtowards the

    overhead

    line with the

    lineconductors

    hangingvertically.

    Line

    conductorsto trees in

    Orchards

    3.0

    Meter

    3.0

    Meter

    3.4

    Meter

    4.6

    Meter

    5.3

    Meter

    Clearances of Electrical Line to Street Lighting:

    Descriptionof

    Clearance

    0.4

    KV

    11

    KV33KV 110KV

    220

    KV400KV

    Lineconductor toLantern on

    same pole

    1.0Meter

    - - - - -

    Bare line

    conductor tolantern or

    columnbelow.

    1.5

    Meter

    - - - - -

    Insulatedline

    conductor to

    column

    0.3Meter

    - - - - -

    Insulatedline

    conductor tolantern

    1.0Meter

    - - - - -

    Column to

    nearest LV

    pole

    1.5

    Meter

    - - - - -

    Lineconductor to

    street

    lightingcolumn with

    (i) Column

    in normalupright

    - 1.7

    Meter

    1.7

    Meter

    2.3

    Meter

    3.3

    Meter

    4.0

    Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    12/23

    position.

    (ii) Columnfalling

    towards line

    with line

    conductorhanging

    verticallyonly

    - 1.7Meter

    1.7Meter

    2.3Meter

    3.3Meter

    4.0Meter

    (iii)Column

    fallingtowards line

    - 0.4

    Meter

    0.4

    Meter

    0.8

    Meter

    1.4

    Meter

    1.9

    Meter

    Clearances of Electrical Line to Waterways:

    Description

    of Clearance0.4

    KV

    11

    KV33KV 110KV

    220

    KV400KV

    NavigableWaters:Lowerbank to

    conductor or

    earth wire

    10.5Meter

    10.5Meter

    10.5Meter

    10.5Meter

    10.5Meter

    10.5Meter

    MinorWatercourses

    :Lower bank toconductor or

    earth wire

    7.6Meter

    7.6Meter

    7.6Meter

    7.6Meter

    7.6Meter

    7.6Meter

    Clearances to Railways:

    Descriptionof

    Clearance

    0.4

    KV

    11

    KV33KV 110KV

    220

    KV400KV

    Lineconductor toground level

    6.1Meter

    6.1Meter

    6.1Meter

    6.7Meter

    7.0Meter

    7.6Meter

    Lineconductor to

    ground level

    on or acrossvehicle

    parks

    7.6Meter

    8.5Meter

    8.5Meter

    9.1Meter

    9.4Meter

    10.1Meter

    Lineconductor to

    ground level

    at roads andyards,where road

    mobile

    10.7Meter

    10.7Meter

    10.7Meter

    11.2Meter

    11.5Meter

    12.2Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    13/23

    cranes are

    likely to beemployed

    Line

    conductor to

    Rail level

    7.3

    Meter

    7.3

    Meter

    7.3

    Meter

    8.0

    Meter

    8.2

    Meter

    8.8

    Meter

    Lineconductor tothe level of

    buildings,

    gantries orotherstructures

    (includingthose

    carryingtraction

    wires) onwhich a man

    may be

    3.0Meter

    3.0Meter

    3.0Meter

    3.7Meter

    4.6Meter

    6.1Meter

    Lineconductor to

    poles and

    otherprojections.

    2.4Meter

    2.7Meter

    2.7Meter

    3.0Meter

    3.7Meter

    5.5Meter

    Lineconductor to

    any otherwire other

    thantraction

    wires.

    1.8Meter

    1.8Meter

    1.8Meter

    2.4Meter

    3.0Meter

    3.7Meter

    Clearances of Electrical Line to Fuel Tanks:

    Descriptionof

    Clearance

    0.4

    KV

    11

    KV33KV 110KV

    220

    KV400KV

    Horizontalclearance

    from line

    conductors

    to petroltanks andvents

    15

    Meter

    15

    Meter

    15

    Meter

    15

    Meter

    15

    Meter

    15

    Meter

    Horizontal

    clearance

    from lineconductorsto liquid gas

  • 7/26/2019 204189355 Electrical Safety Clearance

    14/23

    tanks

    (1) 459 to2273 litre

    capacity

    3.0Meter

    3.0Meter

    3.0Meter

    3.4Meter

    4.6Meter

    5.3Meter

    (2) 2274 to

    9092 litre

    capacity

    7.6Meter

    7.6Meter

    7.6Meter

    7.6Meter

    7.6Meter

    7.6Meter

    (3) More

    than 9093litre.

    15

    Meter

    15

    Meter

    15

    Meter

    15

    Meter

    15

    Meter

    15

    Meter

    Vertical

    clearancefrom lineconductors

    to fuel oiltanks

    Please refer Clearances to Objects

    Clearances of Electrical Lines to other Electrical Lines:

    Descriptionof

    Clearance

    0.4

    KV

    11

    KV33KV 110KV

    220

    KV400KV

    Lowest line

    conductor or

    earth wireof upper line

    to highest

    lineconductor of

    lower line.

    1.0

    Meter

    1.8

    Meter

    2.0

    Meter

    2.5

    Meter

    3.7

    Meter

    4.4

    Meter

    Lowest lineconductor orearth wire

    of upper lineto earthwire of

    lower linewhereerected.

    0.7

    Meter

    1.4

    Meter

    1.6

    Meter

    2.5

    Meter

    3.7

    Meter

    4.4

    Meter

    Lowest lineconductor orearth wire

    of upper lineto any pointon a support

    of the lower

    line onwhich aperson may

    2.7Meter

    2.8Meter

    3.0Meter

    3.4Meter

    4.6Meter

    5.3Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    15/23

    stand.

    Support ofupper line

    and any

    conductor of

    lower line.

    7.5

    Meter

    7.5

    Meter

    7.5

    Meter

    15

    Meter

    15

    Meter

    15

    Meter

    Vertical Passing Clearance (sites where vehicles will pass below the lines):

    Description of

    Clearance 1 KV 2.0 Meter

    Above 110 KV All 2.5 Meter

    Vertical Distance between Conductors of different Circuit (On Different Support):

    Higher Voltage of either

    Circuit Distance between Circuits

    < 1 KV 0.6 Meter

    1 KV to 33 KV 1.2 Meter

    33 KV to 66 KV 1.8 Meter

    110 KV 2.4 Meter

    220 KV 2.8 Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    16/23

    Distance between Conductors (Taken down from Pole to other Support, on

    Transformer):

    Voltage Distance between Circuits

    11 KV & LV Line 0.60 Meter

    22 KV & LV Line 0.75 Meter

    33 KV & LV Line 0.90 Meter

    Horizontal Distance of Telecommunication Line & Overhead Line:

    Description of Clearance Distance

    Telecommunication Line(Not insulated) to HVLine

    Min 1.6 Meter

    Telecommunication Line (Bare) to LV (Bare)Line

    Min 1.2 Meter

    Telecommunication Line (Covered) to LV (Bare)Line Min 0.6 Meter

    Telecommunication Line (Bare) to Stay (Bare)

    Wire

    Min 0.3 Meter

    Passage Way for Metal clad Switchgear:

    Description of Clearance Distance

    Clean &unobstructed Passages at the front of

    any Low/High Voltage Switchgear.

    1.0 Meter wide

    & 2.5 Meter

    high

    Clean &unobstructed Passages at side or

    under any earthed enclosure containing BareConductor

    0.8 Meter wide

    & 2.2 Meterhigh

    Safe approach distance for Person from Exposed Live Parts:

    Circuit Voltage Distance

    < 1 KV 0.5 Meter

    11 KV 1.5 Meter

    22 KV 2.0 Meter

    33 KV 2.5 Meter

    66 KV 3.0 Meter

    110 KV 4.0 Meter

    >220 KV 6.0 Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    17/23

    Electrical Safety Clearance (Part-4)

    AUGUST 11, 201210 COMMENTS

    Standard: ETSA Utilities

    Vertical Clearances between Services:

    Service LV Cable HV Cable

    Common Pipe 0.100 Meter 0.100 Meter

    Gas Pipe 0.200 Meter 0.200Meter

    Sewer Pipe 0.300 Meter 0.300 Meter

    Water Pipe 0.600 Meter 0.600 Meter

    Horizontal Clearances between Services:Service LV Cable HV Cable

    Common Pipe 0.100 Meter 0.100 Meter

    Gas Pipe 0.200 Meter 0.200 Meter

    Sewer Pipe 1.0 Meter 1.0 Meter

    Water Pipe 0.600 Meter 0.600 Meter

    Standard: UK Power Networks EI 02-0019

    Cable Installation Depths:

    Voltage AreaDepth(min)

    LowVoltage

    Footways, grass verges or private

    property

    0.450

    Meter

    Carriageways (including road

    crossings)

    0.600

    Meter

    Normal agricultural land (not deepploughing)

    1.0 Meter

    Agricultural land subject to deep

    ploughing1.2 Meter

    11 KV to20 KV

    Footways, grass verges or privateproperty

    0.600Meter

    Carriageways (including roadcrossings)

    0.750Meter

    Normal agricultural land (not deep

    ploughing)1.0 Meter

    http://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#commentshttp://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#commentshttp://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#commentshttp://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#comments
  • 7/26/2019 204189355 Electrical Safety Clearance

    18/23

    Agricultural land subject to deep

    ploughing1.2 Meter

    33 KV to132 KV

    Footways, grass verges or private

    property

    0.900

    Meter

    Carriageways (including road

    crossings)

    0.900

    Meter

    Normal agricultural land (not deepploughing)

    1.0 Meter

    Agricultural land subject to deepploughing

    1.2 Meter

    AuxiliaryMulti-

    core &Multi-

    pairCables

    Footways, grass verges or privateproperty

    0.450Meter

    Carriageways (including roadcrossings)

    0.600Meter

    Normal agricultural land (not deepploughing) 1.0 Meter

    Agricultural land subject to deep

    ploughing1.2 Meter

    OnCable

    Ladderfor LV to

    HV

    The Horizontal clearance betweencables on cable ladders

    2X Dia of

    Cable of

    LargestCable ormin 150

    mm

    The clearance from a supporting wall 20 mm

    The vertical clearance between cablesis greater

    150 mm

    If the number of cables > 4, they areto be installed in a horizontal

    Minimum Approach Distance of Crane or Moving Part from Live Conductor:

    Voltage

    Without Safety ObservationFor

    ordinaryPerson

    Un

    insulated

    portions

    Insulatedportions

    Upto1KV 2 Meter 1.0 Meter 3.0 Meter

    11 KV 2 Meter 1.4 Meter 3.0 Meter

    22 KV 2.4 Meter 2 Meter 3.0 Meter

    33 KV 2.4 Meter 2 Meter 3.0 Meter

    66 KV 2.8 Meter 2 Meter 3.0 Meter

    132 KV 3.0 Meter 3.0 Meter 3.0 Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    19/23

    220 KV 4.8 Meter 4.8 Meter 6.0 Meter

    330 KV 6.0 Meter 6.0 Meter 6.0 Meter

    500 KV 8.0 Meter 8.0 Meter 8.0 Meter

    Minimum Fixed Clearances for Electrical Apparatus (Isolation Points):

    Voltage Fixed Clearance

    Up to 11Kv 0.320 Meter

    11KV to 33KV 0.320 Meter

    33KV to 66KV 0.630 Meter

    66KV to 132KV 1.1 Meter

    Electrical Safety Clearance (Part-5)

    AUGUST 18, 20125 COMMENTS

    Standard: New Zealand Electrical Code:

    Min Safe Distance between Buildings and Overhead Line:

    Voltage Pole Tower

    11 kV to 33 kV 2 Meter 2 Meter

    33 kV to 66 kV 6 Meter 6 Meter

    66 kV and Above 8 Meter 8 Meter

    Min Safe Distance for excavation near Overhead Line:

    Description of ClearanceFromPole

    (Min)

    FromTower

    (min)

    Excavation in land more than 750mm

    depth8 Meter

    12

    Meter

    Excavation in land up to750mmdepth

    2.2 to 5Meter

    6 to12Meter

    Excavation in land up to300mmdepth 2.2 Meter 6 Meter

    Construction near 11KV to 33KV Line 2.2 Meter 6 Meter

    Construction near 33KV to 66KV Line 6 Meter 9 Meter

    Construction near 66KV and more8 Meter

    12Meter

    Wire Fence near 1KV to 66KV Line 2.2 Meter 2.2

    http://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#commentshttp://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#commentshttp://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#commentshttp://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#comments
  • 7/26/2019 204189355 Electrical Safety Clearance

    20/23

    Meter

    Wire Fence near 66KV and more 5 Meter 5 Meter

    Min Safe Distance for Tower Carin near Electrical Tower:

    Description of Clearance Distance (Min)

    Mobile Carin movement 4.0 Meter

    Tower Carin movement 4.0 Meter

    Carin movement 4.0 Meter

    Moving Activity above height of Tower 4.0 Meter

    Hedge Cutter movement 4.0 Meter

    Min Safe Vertical Distance above Railway Track:

    Description of Clearance Distance (Min)

    Earthed conductors 5.5 Meter

    Stay wires 5.5 Meter

    Conductors up to 33 kV 6.5 Meter

    Conductors above 33 kV to 220 kV 7.5 Meter

    Conductors above 220 kV. 8 Meter

    Min Distance between two Conductors on Same Supports:

    High VoltageCircuit

    High VoltageCircuit

    Distance betweencircuits(min)

    Up to 33 KV Up to 1KV 1.0 Meter

    Up to 33 KV

    More than

    1KV 1.2 Meter

    33 KV to 110 KV Up to 1KV 1.5 Meter

    33 KV to 110 KVMore than

    1KV2.0 Meter

    More than 110 KV All 2.5 Meter

    Min Distance between two Conductors on Different Supports:

    High Voltage Circuit Distance (min)

    Up to 1 KV 0.6 Meter

    1 KV to 33 KV 1.2 Meter

    33 KV to 66 KV 1.8 Meter

    110 KV 2.4 Meter

    More than 220 KV 2.8 Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    21/23

    Min Safety Distance from Electrical Apparatuses:

    Description of Clearance Distance (min)

    Passage In front of Metal Clad Switchgear(UP to HV)

    1.0 Meter wide2.5 Height

    Passage In rear or side of Metal CladSwitchgear (UP to HV)

    1.0 Meter wide2.2 Height

    Passage at any side of Metal Clad Switchgear containing Bare conductor (UP to HV)

    0.8 Meter wide2.2 Height

    Min Approach Distance for Non-Competent Person near exposed Live Parts:

    Voltage Distance (min)

    Below 110 kV 4.0 Meter

    220 kV and above 6.0 Meter

    Min Approach Distance for Competent Person near exposed Live Parts:

    Voltage Distance (min)

    Below 1 kV 0.5 Meter

    11 kV 1.5 Meter

    22 kV 2.0 Meter

    33 kV 2.5 Meter

    66 kV 3.0 Meter

    110 kV 4.0 Meter

    220 kV and above 6.0 Meter

  • 7/26/2019 204189355 Electrical Safety Clearance

    22/23

    Electrical Safety Clearance (Part-6)

    AUGUST 22, 20121 COMMENT

    Standard: Western Power Company.

    Water Safely Clearance on Electrical Fires:

    Voltage

    Minimum distances between a nozzle

    producing a fog stream of freshwater and a live conductor

    Up to 750 V 1.5 Meter

    750 V to 15 KV 4.0 Meter

    15 KV to 230 KV 5.0 Meter

    Minimum Approach Distance for Authorized Person:

    This is the minimum distance that must be maintained by a person, vehicle or mobile plant.

    Voltage Distance (min)

    Up to 1 KV 0.7 Meter

    1 V to 6.6 KV 0.7 Meter

    6.6 KV to 11 KV 0.7 Meter

    11 KV to 22 KV 0.7 Meter

    22 KV to 33 KV 1.0 Meter

    33 KV to 66 KV 1.0 Meter

    66 KV to 132 KV 1.2 Meter

    132 KV to 220 KV 1.8 Meter

    220 KV to 330 KV 3.0 Meter

    Minimum Approach Distance for Ordinary Person:

    Voltage Distance (min)

    Up to 1 KV 3.0 Meter

    1 V to 6.6 KV 3.0 Meter

    6.6 KV to 11 KV 3.0 Meter

    11 KV to 22 KV 3.0 Meter

    22 KV to 33 KV 3.0 Meter

    33 KV to 66 KV 3.0 Meter

    66 KV to 132 KV 3.0 Meter

    132 KV to 220 KV 4.5 Meter

    220 KV to 330 KV 6.0 Meter

    http://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#commentshttp://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#commentshttp://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#commentshttp://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#comments
  • 7/26/2019 204189355 Electrical Safety Clearance

    23/23

    Minimum Approach Distance for Vehicle & Plant for Ordinary Person:

    VoltageDistance (min)

    Mobile Plant Vehicle

    Up to 1 KV 3.0 Meter 0.6 Meter

    1 V to 6.6 KV 3.0 Meter 0.9Meter

    6.6 KV to 11 KV 3.0 Meter 0.9Meter

    11 KV to 22 KV 3.0 Meter 0.9Meter

    22 KV to 33 KV 3.0 Meter 0.9Meter

    33 KV to 66 KV 3.0 Meter 2.1 Meter

    66 KV to 132 KV 3.0 Meter 2.1 Meter

    132 KV to 220 KV 3.0 Meter 2.9 Meter

    220 KV to 330 KV 6.0 Meter 3.4 Meter