Electrical Safety Clearance (Part-1)
AUGUST 8, 20129 COMMENTS
Standard: Qatar General Electricity & Water Corporation
Minimum Safety Clearance of Pipelines from Electrical Tower:
DescriptionVoltage
33KV/66KV/132KV 220KV/400KV
The right of way(ROW) (widths oneither side of the
center line of
overheadtransmission lines
)
25 Meter 50 Meter
Other than the
roadways andboundary fences ofsecurityestablishmentsany temporary or
permanentstructures /buildings, parapet
walls,
Not within 25 MeterNot within 50
Meter
With All
Underground
services crossing
the way leave(from the nearest
tower foundation)
35 Meter (Min) 50 Meter (Min)
The nearest side of
the road
reservation to thenearest towerfoundation
25 Meter35 Meter,50
Meter
The pipelines(water, oil/gas
etc.) crossing
(respectively awayfrom the nearest
base of tower leg).Pipe-lines shall not
be laid parallel tothe overhead line
within the limits of
a way leave(ROW).
25 Meter (Min)35 Meter(Min),50 Meter(Min)
http://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#commentshttp://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#commentshttp://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#commentshttp://electricalnotes.wordpress.com/2012/08/08/electrical-safety-clearance-part-1/#comments -
7/26/2019 204189355 Electrical Safety Clearance
2/23
Cables crossing
the transmissionlines way leave(ROW)
respectively away
from the nearest
base of tower leg.
25 Meter35 Meter,50
Meter
Foundations andcivil structures(Temporary or
permanent) will
not be permittedin the close
proximity to the
cable circuit. Aminimum
horizontal distancefrom such
structures to thenearest edge of
the cable trenchshall be observed
Min 1.5 Meter Min 1.5 Meter
Clearance among Electrical Line-Telephone- Water-Sewerage -Gas Line
Service VerticalClearance(Min)
Water Line (to cross below EHV cablelevel)
0.5 Meter
Sewerage Mains (to cross below EHV
cable level)
1.0 Meter
Drainage Mains (to cross below EHVcable level)
0.5 Meter
Gas pipes 0.6 Meter
Telephone lines 0.5 Meter
LV / 11kV cables 0.5 Meter
Safety Clearance for Excavation of Land :
Type of Excavation Distance
Use of heavy mechanical
excavators (other than handoperated pneumatic jackhammers) or driving sheet piles
Not less than 3 Meter from
the edge of cable, cover,cable joint
Heavy machinery engaged in the
civil construction or road works
operating load/thrust/weight will not be applied
directly on the cable
installation
Trench excavations parallel to Minimum separation of 1
-
7/26/2019 204189355 Electrical Safety Clearance
3/23
the cable installations Meter to the nearest edge
of cable tile
Laying of metal pipes over a long
distance parallel to cable
Not permitted unless the
Step and Touch Potentials
at any point of the pipe line
do not exceed 65 Volts.(A) Inside Towns
Distance between Towers foundation to Pipeline in parallel and intersections.
Voltage Min Distance
380/220V 0.5 Meter
20KV 2 Meter
63KV 7 Meter
132KV 10 Meter
230KV and Above 20 Meter
Distance between underground power cables to wall of gas pipelines in parallelroutes.
Voltage Min HorizontalDistance
Min VerticalDistance
380/220V 1 Meter 0.5 Meter
20KV 2 Meter 1 Meter
63KV 3 Meter 1.5 Meter
(B) Outside of Towns:
Distance between Towers foundation to Pipeline in parallel and intersections.
KVMin Distance in
Parallel Route (Up to5 Km)
Min Distance inParallel Route(Above 5 Km)
20KV 20 Meter 30 Meter
63KV 30 Meter 40 Meter
132KV 40 Meter 50 Meter
230KV 50 Meter 60 Meter
400KV 60 Meter 60 Meter
Distance between overhead lines to gas pipelines at intersections.
KV Min Distance
20KV 8 Meter
63KV 9 Meter
132KV 10 Meter
230KV 11 Meter
-
7/26/2019 204189355 Electrical Safety Clearance
4/23
400KV 12 Meter
Distance between Towers foundations to gas pipelines at intersections.
KV Min Distance
20KV 20 Meter
63KV and Higher 30 Meter
Right Of Way (R.O.W) From Roads:
Highway Distance
High Way : (38 meter from one side of Central
Line of Highway)76 Meter
First Class State Road=(22.5 meter from one
side of Central Line of Highway)
45 Meter
Second Class State Road=(17.5 meter from oneside of Central Line of Highway)
35 Meter
Third Class State Road =(12.5 meter from oneside of Central Line of Highway)
25 Meter
Forth Class State Road=(7.5 meter from one
side of Central Line of Highway)
15 Meter
General Electrical Safety Clearance:
KV Description Distance
Up to 11
KV
At points where thelines cross roads or
railwaysMin 6 Meter Height
Up to 11
KVparallel to roads the Min 5.5 Meter Height
Up to 11
KV
lines cross totallydesert regions whereno traffic is possible
Min 5.5 Meter Height
20 KV to66 KV
All Location Min 6 Meter Height
Up to 11KV
Conductor JointNo joint shall be closer
than 3 meters to apoint of support
33 KV & 66
KV
Conductor Joint No tension joints shall
be used unlessspecially approved.
-
7/26/2019 204189355 Electrical Safety Clearance
5/23
Electrical Safety Clearance (Part-2)
AUGUST 9, 201216 COMMENTS
Code: Indian Electricity Rules/ Central Electricity Authority:
Right of Way Clearance (As per GETCO Standard):
KV Min ROW
66 KV 18 Meter
132 KV 27 Meter
220 KV 35 Meter
400KV 52 Meter (Single Circuit)
400 KV 48 Meter (Double Circuit)
Minimum clearances between Electrical Lines crossing each other:
Voltage 66 KV132
KV
220
KV
400 KV
66 KV2.4
Meter3 Meter 4.5
Meter5.4
Meter
132 KV 3 Meter3 Meter 4.5
Meter
5.4
Meter
220 KV4.5
Meter
4.5
Meter
4.5
Meter
5.4
Meter
400 KV4.5
Meter
5.4
Meter
5.4
Meter
5.4
MeterPermissible Min ground Clearance of Electrical Line:
KV Ground ClearanceOver National
Highway
66 KV 6.1 Meter 8.0 Meter
132 KV 6.1 Meter 8.6 Meter
220 KV 7.0 Meter 9.8 Meter
400KV 8.8 Meter 10.8 Meter
Clearance for Telephone line Crossings Power Line:
KV Clearance (Min)
66 KV 2.4 Meter
132 KV 2.7 Meter
220 KV 3.0 Meter
Vertical Clearance between Electrical Line and railway tracks.
KV Clearance (Min)
http://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#commentshttp://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#commentshttp://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#commentshttp://electricalnotes.wordpress.com/2012/08/09/electrical-safety-clearance-part-2/#comments -
7/26/2019 204189355 Electrical Safety Clearance
6/23
66 KV 14 Meter
132 KV 14.6 Meter
220 KV 15.4 Meter
400 KV 17.9 Meter
Clearance from Buildings to low, medium & high voltage lines:
Voltage Description Distance
Low &
MediumVoltage
Flat roof, open balcony,
verandah roof ,When the linepasses above the building avertical clearance from the
highest point
2.5 Meter
Low &Medium
Voltage
Line passes adjacent to thebuilding a horizontal
clearance from the nearestpoint
1.2 Meter
Low &Medium
Voltage
Line passes above thebuilding a vertical clearance
2.5 Meter
Low &Medium
Voltage
Line passes adjacent thebuilding a Horizontal
clearance
1.2 Meter
11 KV to 33
KV
Line passes above or
adjacent to any building orpart of a building
3.7 Meter
Above 33
KV
Line passes above or
adjacent to any building orpart of a building
3.7+(0.3 for
everyadditional 33KV )
Up to 11 KV The horizontal clearance
between the nearerconductor and any part of
such building
1.2 Meter
11 KV to 33
KV
The horizontal clearance
between the nearerconductor and any part of
such building
2.0 Meter
Above 33 The horizontal clearancebetween the nearer
2.0 + (0.3 forevery
-
7/26/2019 204189355 Electrical Safety Clearance
7/23
KV conductor and any part
ofsuch building
additional 33
KV )
Clearance above ground at the lowest conductor:
Voltage Description Distance
Low & MediumVoltage
Across a street 5.8 Meter
High Voltage Across a street 6.1 Meter
Low & Medium
Voltage
Along a street 5.5 Meter
High Voltage Along a street 5.8 Meter
Low & MediumVoltage Elsewhere than alongor across any street 4.0 Meter
High Voltage Elsewhere than alongor across any street
5.2 Meter
33 KV & EHV Clearance above
ground(Add 0.3 Meter
for every 33 KV Voltsin 5.2 Meter)
Min 6.1
Meter
Vertical Clearance at Middle of Span:
SpanVertical Clearance (At Middle of
Span)
200 Meter 4.0 Meter
300 Meter 5.5 Meter
400 Meter 7.0 Meter
500 Meter 8.5 Meter
Safety Clearance from Live Part in Outdoor Substation:
KV Safety Working Clearance
12 KV 2.6 Meter
36 KV 2.8 Meter
72.5 KV 3.1 Meter
145 KV 3.7 Meter
220 KV 4.3 Meter
400KV 6.4 Meter
-
7/26/2019 204189355 Electrical Safety Clearance
8/23
800 KV 10.3 Meter
Lying of Telecommunication Cables with Power Cables (>33 kV).
Cable Min. Distance
Power cable of voltage exceeding
33 kV shall be laid
Min 1.2 Meter depth
Underground telecommunicationcable shall be with underground
power cable of voltage exceeding
33 kV.
Min 0.6 Meter Separatefrom Power Cable
Safe approach limits for people:
Voltage
214V
to
415KV
11KV 33KV 66KV 132KV 275KV
Person
usingmanually
operated
tool
1.3
Meter
2.0
Meter
3.0
Meter
4.0
Meter
5.0
Meter
6.0
Meter
Personusing
poweroperated
tool
3.0Meter
3.0Meter
3.0Meter
4.0Meter
5.0Meter
6.0Meter
Electrical Safety Clearance (Part-3)
AUGUST 10, 20128 COMMENTS
Standard:Northern Ireland Electricity (NIE), 6/025 ENA
Clearances of Electrical Line to Ground and Roads:
Description
ofClearance
0.4KV
11KV
33KV 110KV220KV
400KV
Lineconductor toany point
not over
road
5.2Meter
6.1Meter
6.4Meter
6.4Meter
7.0Meter
7.0Meter
Line
conductor toroad surface
5.8
Meter
6.1
Meter
6.4
Meter
6.4
Meter
7.4
Meter
8.1
Meter
http://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#commentshttp://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#commentshttp://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#commentshttp://electricalnotes.wordpress.com/2012/08/10/electrical-safety-clearance-part-3/#comments -
7/26/2019 204189355 Electrical Safety Clearance
9/23
Line
conductor toroad surfaceof high load
routes
6.9
Meter
6.9
Meter
6.9
Meter
7.2
Meter
8.5
Meter
9.2
Meter
Bare livemetalwork (
transformerterminals,jumper
connections,
etc)
4.6Meter
4.6Meter
4.6Meter
- - -
Clearances of Electrical Line to Other Objects:
Description
of
Clearance
-
7/26/2019 204189355 Electrical Safety Clearance
10/23
Line
conductorsto irrigates,slurry guns
and high-
pressure
hoses
30
Meter
30
Meter
30
Meter
30
Meter
30
Meter
Lineconductorsto playing
fields
8.5Meter
8.5Meter
8.5Meter
8.5Meter
8.5Meter
Lineconductors
to CaravanSites
9.0Meter
9.0Meter
9.0Meter
9.0Meter
9.0Meter
Horizontal
clearancesto wells
15.0
Meter
15.0
Meter
15.0
Meter
15.0
Meter
15.0
Meter
Clearances of Electrical Line to Trees and Hedges:
Description
ofClearance
-
7/26/2019 204189355 Electrical Safety Clearance
11/23
metalwork
to treesfallingtowards the
overhead
line with the
lineconductors
hangingvertically.
Line
conductorsto trees in
Orchards
3.0
Meter
3.0
Meter
3.4
Meter
4.6
Meter
5.3
Meter
Clearances of Electrical Line to Street Lighting:
Descriptionof
Clearance
0.4
KV
11
KV33KV 110KV
220
KV400KV
Lineconductor toLantern on
same pole
1.0Meter
- - - - -
Bare line
conductor tolantern or
columnbelow.
1.5
Meter
- - - - -
Insulatedline
conductor to
column
0.3Meter
- - - - -
Insulatedline
conductor tolantern
1.0Meter
- - - - -
Column to
nearest LV
pole
1.5
Meter
- - - - -
Lineconductor to
street
lightingcolumn with
(i) Column
in normalupright
- 1.7
Meter
1.7
Meter
2.3
Meter
3.3
Meter
4.0
Meter
-
7/26/2019 204189355 Electrical Safety Clearance
12/23
position.
(ii) Columnfalling
towards line
with line
conductorhanging
verticallyonly
- 1.7Meter
1.7Meter
2.3Meter
3.3Meter
4.0Meter
(iii)Column
fallingtowards line
- 0.4
Meter
0.4
Meter
0.8
Meter
1.4
Meter
1.9
Meter
Clearances of Electrical Line to Waterways:
Description
of Clearance0.4
KV
11
KV33KV 110KV
220
KV400KV
NavigableWaters:Lowerbank to
conductor or
earth wire
10.5Meter
10.5Meter
10.5Meter
10.5Meter
10.5Meter
10.5Meter
MinorWatercourses
:Lower bank toconductor or
earth wire
7.6Meter
7.6Meter
7.6Meter
7.6Meter
7.6Meter
7.6Meter
Clearances to Railways:
Descriptionof
Clearance
0.4
KV
11
KV33KV 110KV
220
KV400KV
Lineconductor toground level
6.1Meter
6.1Meter
6.1Meter
6.7Meter
7.0Meter
7.6Meter
Lineconductor to
ground level
on or acrossvehicle
parks
7.6Meter
8.5Meter
8.5Meter
9.1Meter
9.4Meter
10.1Meter
Lineconductor to
ground level
at roads andyards,where road
mobile
10.7Meter
10.7Meter
10.7Meter
11.2Meter
11.5Meter
12.2Meter
-
7/26/2019 204189355 Electrical Safety Clearance
13/23
cranes are
likely to beemployed
Line
conductor to
Rail level
7.3
Meter
7.3
Meter
7.3
Meter
8.0
Meter
8.2
Meter
8.8
Meter
Lineconductor tothe level of
buildings,
gantries orotherstructures
(includingthose
carryingtraction
wires) onwhich a man
may be
3.0Meter
3.0Meter
3.0Meter
3.7Meter
4.6Meter
6.1Meter
Lineconductor to
poles and
otherprojections.
2.4Meter
2.7Meter
2.7Meter
3.0Meter
3.7Meter
5.5Meter
Lineconductor to
any otherwire other
thantraction
wires.
1.8Meter
1.8Meter
1.8Meter
2.4Meter
3.0Meter
3.7Meter
Clearances of Electrical Line to Fuel Tanks:
Descriptionof
Clearance
0.4
KV
11
KV33KV 110KV
220
KV400KV
Horizontalclearance
from line
conductors
to petroltanks andvents
15
Meter
15
Meter
15
Meter
15
Meter
15
Meter
15
Meter
Horizontal
clearance
from lineconductorsto liquid gas
-
7/26/2019 204189355 Electrical Safety Clearance
14/23
tanks
(1) 459 to2273 litre
capacity
3.0Meter
3.0Meter
3.0Meter
3.4Meter
4.6Meter
5.3Meter
(2) 2274 to
9092 litre
capacity
7.6Meter
7.6Meter
7.6Meter
7.6Meter
7.6Meter
7.6Meter
(3) More
than 9093litre.
15
Meter
15
Meter
15
Meter
15
Meter
15
Meter
15
Meter
Vertical
clearancefrom lineconductors
to fuel oiltanks
Please refer Clearances to Objects
Clearances of Electrical Lines to other Electrical Lines:
Descriptionof
Clearance
0.4
KV
11
KV33KV 110KV
220
KV400KV
Lowest line
conductor or
earth wireof upper line
to highest
lineconductor of
lower line.
1.0
Meter
1.8
Meter
2.0
Meter
2.5
Meter
3.7
Meter
4.4
Meter
Lowest lineconductor orearth wire
of upper lineto earthwire of
lower linewhereerected.
0.7
Meter
1.4
Meter
1.6
Meter
2.5
Meter
3.7
Meter
4.4
Meter
Lowest lineconductor orearth wire
of upper lineto any pointon a support
of the lower
line onwhich aperson may
2.7Meter
2.8Meter
3.0Meter
3.4Meter
4.6Meter
5.3Meter
-
7/26/2019 204189355 Electrical Safety Clearance
15/23
stand.
Support ofupper line
and any
conductor of
lower line.
7.5
Meter
7.5
Meter
7.5
Meter
15
Meter
15
Meter
15
Meter
Vertical Passing Clearance (sites where vehicles will pass below the lines):
Description of
Clearance 1 KV 2.0 Meter
Above 110 KV All 2.5 Meter
Vertical Distance between Conductors of different Circuit (On Different Support):
Higher Voltage of either
Circuit Distance between Circuits
< 1 KV 0.6 Meter
1 KV to 33 KV 1.2 Meter
33 KV to 66 KV 1.8 Meter
110 KV 2.4 Meter
220 KV 2.8 Meter
-
7/26/2019 204189355 Electrical Safety Clearance
16/23
Distance between Conductors (Taken down from Pole to other Support, on
Transformer):
Voltage Distance between Circuits
11 KV & LV Line 0.60 Meter
22 KV & LV Line 0.75 Meter
33 KV & LV Line 0.90 Meter
Horizontal Distance of Telecommunication Line & Overhead Line:
Description of Clearance Distance
Telecommunication Line(Not insulated) to HVLine
Min 1.6 Meter
Telecommunication Line (Bare) to LV (Bare)Line
Min 1.2 Meter
Telecommunication Line (Covered) to LV (Bare)Line Min 0.6 Meter
Telecommunication Line (Bare) to Stay (Bare)
Wire
Min 0.3 Meter
Passage Way for Metal clad Switchgear:
Description of Clearance Distance
Clean &unobstructed Passages at the front of
any Low/High Voltage Switchgear.
1.0 Meter wide
& 2.5 Meter
high
Clean &unobstructed Passages at side or
under any earthed enclosure containing BareConductor
0.8 Meter wide
& 2.2 Meterhigh
Safe approach distance for Person from Exposed Live Parts:
Circuit Voltage Distance
< 1 KV 0.5 Meter
11 KV 1.5 Meter
22 KV 2.0 Meter
33 KV 2.5 Meter
66 KV 3.0 Meter
110 KV 4.0 Meter
>220 KV 6.0 Meter
-
7/26/2019 204189355 Electrical Safety Clearance
17/23
Electrical Safety Clearance (Part-4)
AUGUST 11, 201210 COMMENTS
Standard: ETSA Utilities
Vertical Clearances between Services:
Service LV Cable HV Cable
Common Pipe 0.100 Meter 0.100 Meter
Gas Pipe 0.200 Meter 0.200Meter
Sewer Pipe 0.300 Meter 0.300 Meter
Water Pipe 0.600 Meter 0.600 Meter
Horizontal Clearances between Services:Service LV Cable HV Cable
Common Pipe 0.100 Meter 0.100 Meter
Gas Pipe 0.200 Meter 0.200 Meter
Sewer Pipe 1.0 Meter 1.0 Meter
Water Pipe 0.600 Meter 0.600 Meter
Standard: UK Power Networks EI 02-0019
Cable Installation Depths:
Voltage AreaDepth(min)
LowVoltage
Footways, grass verges or private
property
0.450
Meter
Carriageways (including road
crossings)
0.600
Meter
Normal agricultural land (not deepploughing)
1.0 Meter
Agricultural land subject to deep
ploughing1.2 Meter
11 KV to20 KV
Footways, grass verges or privateproperty
0.600Meter
Carriageways (including roadcrossings)
0.750Meter
Normal agricultural land (not deep
ploughing)1.0 Meter
http://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#commentshttp://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#commentshttp://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#commentshttp://electricalnotes.wordpress.com/2012/08/11/electrical-safety-clearance-part-4/#comments -
7/26/2019 204189355 Electrical Safety Clearance
18/23
Agricultural land subject to deep
ploughing1.2 Meter
33 KV to132 KV
Footways, grass verges or private
property
0.900
Meter
Carriageways (including road
crossings)
0.900
Meter
Normal agricultural land (not deepploughing)
1.0 Meter
Agricultural land subject to deepploughing
1.2 Meter
AuxiliaryMulti-
core &Multi-
pairCables
Footways, grass verges or privateproperty
0.450Meter
Carriageways (including roadcrossings)
0.600Meter
Normal agricultural land (not deepploughing) 1.0 Meter
Agricultural land subject to deep
ploughing1.2 Meter
OnCable
Ladderfor LV to
HV
The Horizontal clearance betweencables on cable ladders
2X Dia of
Cable of
LargestCable ormin 150
mm
The clearance from a supporting wall 20 mm
The vertical clearance between cablesis greater
150 mm
If the number of cables > 4, they areto be installed in a horizontal
Minimum Approach Distance of Crane or Moving Part from Live Conductor:
Voltage
Without Safety ObservationFor
ordinaryPerson
Un
insulated
portions
Insulatedportions
Upto1KV 2 Meter 1.0 Meter 3.0 Meter
11 KV 2 Meter 1.4 Meter 3.0 Meter
22 KV 2.4 Meter 2 Meter 3.0 Meter
33 KV 2.4 Meter 2 Meter 3.0 Meter
66 KV 2.8 Meter 2 Meter 3.0 Meter
132 KV 3.0 Meter 3.0 Meter 3.0 Meter
-
7/26/2019 204189355 Electrical Safety Clearance
19/23
220 KV 4.8 Meter 4.8 Meter 6.0 Meter
330 KV 6.0 Meter 6.0 Meter 6.0 Meter
500 KV 8.0 Meter 8.0 Meter 8.0 Meter
Minimum Fixed Clearances for Electrical Apparatus (Isolation Points):
Voltage Fixed Clearance
Up to 11Kv 0.320 Meter
11KV to 33KV 0.320 Meter
33KV to 66KV 0.630 Meter
66KV to 132KV 1.1 Meter
Electrical Safety Clearance (Part-5)
AUGUST 18, 20125 COMMENTS
Standard: New Zealand Electrical Code:
Min Safe Distance between Buildings and Overhead Line:
Voltage Pole Tower
11 kV to 33 kV 2 Meter 2 Meter
33 kV to 66 kV 6 Meter 6 Meter
66 kV and Above 8 Meter 8 Meter
Min Safe Distance for excavation near Overhead Line:
Description of ClearanceFromPole
(Min)
FromTower
(min)
Excavation in land more than 750mm
depth8 Meter
12
Meter
Excavation in land up to750mmdepth
2.2 to 5Meter
6 to12Meter
Excavation in land up to300mmdepth 2.2 Meter 6 Meter
Construction near 11KV to 33KV Line 2.2 Meter 6 Meter
Construction near 33KV to 66KV Line 6 Meter 9 Meter
Construction near 66KV and more8 Meter
12Meter
Wire Fence near 1KV to 66KV Line 2.2 Meter 2.2
http://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#commentshttp://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#commentshttp://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#commentshttp://electricalnotes.wordpress.com/2012/08/18/electrical-safety-clearance-part-5/#comments -
7/26/2019 204189355 Electrical Safety Clearance
20/23
Meter
Wire Fence near 66KV and more 5 Meter 5 Meter
Min Safe Distance for Tower Carin near Electrical Tower:
Description of Clearance Distance (Min)
Mobile Carin movement 4.0 Meter
Tower Carin movement 4.0 Meter
Carin movement 4.0 Meter
Moving Activity above height of Tower 4.0 Meter
Hedge Cutter movement 4.0 Meter
Min Safe Vertical Distance above Railway Track:
Description of Clearance Distance (Min)
Earthed conductors 5.5 Meter
Stay wires 5.5 Meter
Conductors up to 33 kV 6.5 Meter
Conductors above 33 kV to 220 kV 7.5 Meter
Conductors above 220 kV. 8 Meter
Min Distance between two Conductors on Same Supports:
High VoltageCircuit
High VoltageCircuit
Distance betweencircuits(min)
Up to 33 KV Up to 1KV 1.0 Meter
Up to 33 KV
More than
1KV 1.2 Meter
33 KV to 110 KV Up to 1KV 1.5 Meter
33 KV to 110 KVMore than
1KV2.0 Meter
More than 110 KV All 2.5 Meter
Min Distance between two Conductors on Different Supports:
High Voltage Circuit Distance (min)
Up to 1 KV 0.6 Meter
1 KV to 33 KV 1.2 Meter
33 KV to 66 KV 1.8 Meter
110 KV 2.4 Meter
More than 220 KV 2.8 Meter
-
7/26/2019 204189355 Electrical Safety Clearance
21/23
Min Safety Distance from Electrical Apparatuses:
Description of Clearance Distance (min)
Passage In front of Metal Clad Switchgear(UP to HV)
1.0 Meter wide2.5 Height
Passage In rear or side of Metal CladSwitchgear (UP to HV)
1.0 Meter wide2.2 Height
Passage at any side of Metal Clad Switchgear containing Bare conductor (UP to HV)
0.8 Meter wide2.2 Height
Min Approach Distance for Non-Competent Person near exposed Live Parts:
Voltage Distance (min)
Below 110 kV 4.0 Meter
220 kV and above 6.0 Meter
Min Approach Distance for Competent Person near exposed Live Parts:
Voltage Distance (min)
Below 1 kV 0.5 Meter
11 kV 1.5 Meter
22 kV 2.0 Meter
33 kV 2.5 Meter
66 kV 3.0 Meter
110 kV 4.0 Meter
220 kV and above 6.0 Meter
-
7/26/2019 204189355 Electrical Safety Clearance
22/23
Electrical Safety Clearance (Part-6)
AUGUST 22, 20121 COMMENT
Standard: Western Power Company.
Water Safely Clearance on Electrical Fires:
Voltage
Minimum distances between a nozzle
producing a fog stream of freshwater and a live conductor
Up to 750 V 1.5 Meter
750 V to 15 KV 4.0 Meter
15 KV to 230 KV 5.0 Meter
Minimum Approach Distance for Authorized Person:
This is the minimum distance that must be maintained by a person, vehicle or mobile plant.
Voltage Distance (min)
Up to 1 KV 0.7 Meter
1 V to 6.6 KV 0.7 Meter
6.6 KV to 11 KV 0.7 Meter
11 KV to 22 KV 0.7 Meter
22 KV to 33 KV 1.0 Meter
33 KV to 66 KV 1.0 Meter
66 KV to 132 KV 1.2 Meter
132 KV to 220 KV 1.8 Meter
220 KV to 330 KV 3.0 Meter
Minimum Approach Distance for Ordinary Person:
Voltage Distance (min)
Up to 1 KV 3.0 Meter
1 V to 6.6 KV 3.0 Meter
6.6 KV to 11 KV 3.0 Meter
11 KV to 22 KV 3.0 Meter
22 KV to 33 KV 3.0 Meter
33 KV to 66 KV 3.0 Meter
66 KV to 132 KV 3.0 Meter
132 KV to 220 KV 4.5 Meter
220 KV to 330 KV 6.0 Meter
http://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#commentshttp://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#commentshttp://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#commentshttp://electricalnotes.wordpress.com/2012/08/22/electrical-safety-clearance-part-6/#comments -
7/26/2019 204189355 Electrical Safety Clearance
23/23
Minimum Approach Distance for Vehicle & Plant for Ordinary Person:
VoltageDistance (min)
Mobile Plant Vehicle
Up to 1 KV 3.0 Meter 0.6 Meter
1 V to 6.6 KV 3.0 Meter 0.9Meter
6.6 KV to 11 KV 3.0 Meter 0.9Meter
11 KV to 22 KV 3.0 Meter 0.9Meter
22 KV to 33 KV 3.0 Meter 0.9Meter
33 KV to 66 KV 3.0 Meter 2.1 Meter
66 KV to 132 KV 3.0 Meter 2.1 Meter
132 KV to 220 KV 3.0 Meter 2.9 Meter
220 KV to 330 KV 6.0 Meter 3.4 Meter