gogreenchillers · 2017-03-16 · eer net 3,16 3,32 3,15 3,28 3,24 3,13 eseer 4,36 5,11 5,38 5,02...
TRANSCRIPT
GOGREENchillersthe new HFO1234ze ecorange
GOGREENs o l u t i o n s
rcgroupairconditioning
Let’s treat well the earth on which we live:it was not donated by our fathers , but we borrowed it from our children ...
(Masai Proverb)
OUR PLANETToday, environmental respect is the core value and guideline to develop new technologies.The environmental sustainability makes its appearance in every sector through research techniques for the renewal of the resources of our planet Earth. Mankind has the duty to defend and preserve the delicate balance of the Earth.Sustainability for RC Group is the commitment of the present generations to leave to future generations the same quantity and quality of resources especially.Since 1997 (from the Kyoto Protocol) to today, the first aspect is the reduction of global warming, gradually limiting the use of HFC refrigerants and, later, of F gases as well.
OUR MISSIONThe high efficiency of the products together with the study and design of tailored solution, translate into energy savings, and consequently in cost reduction.RC Group solutions arise from synergies between RC Group hardware and software, through analysis and energy management.Calculating it in advance and carefully, drive us to system design compatible with requirements and environment. At the same time, we can also determine which will be the return of the initial investment in terms of economies of exercise.
GOReliableEcologicEvolvedNatural
rcgroupairconditioning
X TYPE
SPECIAL TURBO HFO SPECTRUM SEQUENCER COOLNET
RC-CLOUD PLATFORM
RCWORLD
Types y s t e m
OUR SOLUTION: X TYPE SYSTEMA new concept of CRAH unit designed around a revolutionary thermal exchange coil using the state of the art in terms of high efficiency components optimized for the new operating conditions for the lowest PUE (1,14).
• Supply air temperature: minimum 20°C• In/Out CHW temperature: 18 / 28°C
THE SYSTEM
HFO1234ze
GOGREEN
EnvironmentallyEnergy Saving
Ecosustainability
LIGHT WEIGHT SOLUTIONS FOR ENVIRONMENT
RC Group makes use of refrigerants innocuous to the atmosphere, first of all the HFO1234ze that, thanks to its high environmental compatibility joined to a high energy efficiency, results to be an excellent SOLUTION for replacement of R134a.Another point in its favor is the much higher critical temperature which allows to operate at much higher condensation temperatures retaining a good thermodynamic efficiency.
HFO1234ze
NOODP
LOWTEWI
LOWGWP
R134a HFO1234 ze
R134a
HFO1234 ze -37%
2018
-69%
2024 2030
-79%
CFCs1900s
HCFCs1990s
HFCsmid 1990s 2006
HFOs
CFC Phase-out
HCFC Phase-out F-Gas Regulation
rcgroupairconditioning
1900 1990 mid1990 2006
13 YEARS
18 DAYS
The GWP (Global Warming Potential) expresses the contribution to the greenhouse effect of a gas relatively to the effect of CO2, whose reference potential is equal to 1. Each GWP value is calculated for a specific time interval.
The ODP (Ozone Depletion Potential) index refers to a chemical compound and it is the relative value of degradation of the ozone layer that this compound may cause.
The TEWI (Total Equivalent Warming Impact) index allows to quantify the impact that the equipment have on global warming considering both the emission of greenhouse gases during operation and disposal of the fluids operating at the end of the l ife cycle.
UE GOALS
GREENHOUSE GASES REDUCTION
MONTREAL PROTOCOLEU LEGISLATIONKYOTO PROTOCOL
Ozone depletingVery high GWP
No-Ozone depletingHigh GWP
No-Ozone depletingVery low GWP
GWP 1430 6
ODP 0 0
NON-Toxicity level A Class A Class
Inflammability NO NO
Efficiency + ++
Critical Temperature (°C) 101 110
-20%CO2
+20%Renewable
Energy-20%
PrimaryEnergy
ConsumptionEmission
LIFE TIME IN ATMOSPHERE
±0,3°C
310 kW
+ 3%
NEWPRODUCT
3 new High Efficiency series36 models for a wide selection opportunity
Design excellence by RC GroupGren refrigerant HFO1234ze
Microchannel condensing coilsHigh EER and ESEER
Wide range of accessories
OUR ECO-RANGE SELECTION
UNICO TURBO FLGAir cooled liquid chillers in A class energy efficiency equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel condensing coils.
UNICO TURBO FLG FREE Air cooled liquid chillers with Free-Cooling system in A class energy efficiency equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel condensing coils.
FRIGO TURBO FLGWater cooled liquid chillers in A class energy efficiency equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and shall and tube condenser.
Cooling Capacity, Range 310-65 kW
Accurate Cooling
Energy Efficiency increase compared to R134a
COMPRESSOR TG310
INVERTER
HIGHEFFICIENCY
AB
C
LOWNOISE HFO1234ze
UNICO TURBO FLG
rcgroupairconditioning
OUR ECO-RANGE SELECTION
Model 200 T1 VT2 260 T1 VT2 310 T1E VT3 400 T2 VT4 520 T2E VT5 620 T2E VT6Cooling Capacity (kW) 200 260 310 400 520 620
EER net 3,16 3,32 3,15 3,28 3,24 3,13ESEER 4,36 5,11 5,38 5,02 5,07 5,49A (mm) 2410 3530 3530 4650 5770 6890B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370
Net weight (Kg) 2429 2680 3433 3720 4285 5141
Model 700 T3 VT7 780 T3E VT7 900 T3E VT8 1040 T4E VT10 1200 T4E VT11 1300 T4E VT12Cooling Capacity (kW) 700 780 900 1040 1200 1260
EER net 3,28 3,16 3,15 3,20 3,15 3,17ESEER 5,15 5,09 5,59 5,07 5,46 5,71A (mm) 8010 8010 9130 10250 12490 13610B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370
Net weight (Kg) 5518 5647 5296 5913 6945 8196
Model Sound Pressure Level (Lp1m)[dB(A)]
Sound Power Level(Lw)[dB(A)]
200 T1 VT2 73,4 92,3260 T1 VT2 73,9 93,4
310 T1E VT3 73,9 93,4400 T2 VT4 74,8 94,8
520 T2E VT5 75,1 95,6620 T2E VT6 75,4 96,4700 T3 VT7 75,7 97,1
780 T3E VT7 75,7 97,1900 T3E VT8 76,1 97,8
1040 T4E VT10 76,1 98,21200 T4E VT11 76,4 99,11300 T4E VT12 76,5 99,5
Cooling Capacity: 200 ÷ 1260 kW
Referred to water temperature 12/7°C and 35°C ambient air temperature according to Eurovent standard
EER up to 3,28ESEER up to 5,71
Sound pressure ISO3744Sound power ISO9614-2
FREECOOLING
INVERTERHIGHEFFICIENCY
LOWNOISEHFO1234ze
AB
C
UNICO TURBO FLG FREE
Model 200 T1 VT2 260 T1 VT3 310 T1E VT3 400 T2 VT4 520 T2E VT5 620 T2E VT6Cooling Capacity (kW) 200 260 310 400 520 620
Free-Cooling (kW) 243 364 364 485 607 728EER net 3,09 3,33 3,46 3,22 3,51 3,46ESEER 3,92 4,60 4,84 4,52 4,56 4,94A (mm) 2410 3530 3530 4650 5770 6890B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370
Net weight (Kg) 2706 3091 3844 4280 4983 6000
Model 700 T3 VT7 780 T3E VT7 900 T3E VT8 1040 T4E VT10 1200 T4E VT11 1300 T4E VT12Cooling Capacity (kW) 700 780 900 1040 1200 1260
Free-Cooling (kW) 849 849 970 1092 1334 1456EER net 3,29 3,48 3,46 3,47 3,48 3,43ESEER 4,64 4,58 5,03 4,56 4,91 5,14A (mm) 8010 8010 9130 10250 12490 13610B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370
Net weight (Kg) 6519 6648 6438 7197 8512 9904
Model Sound Pressure Level (Lp1m)[dB(A)]
Sound Power Level(Lw)[dB(A)]
200 T1 VT2 73,4 92,3260 T1 VT2 73,9 93,4
310 T1E VT3 73,9 93,4400 T2 VT4 74,8 94,8
520 T2E VT5 75,1 95,6620 T2E VT6 75,4 96,4700 T3 VT7 75,7 97,1
780 T3E VT7 75,7 97,1900 T3E VT8 76,1 97,8
1040 T4E VT10 76,1 98,21200 T4E VT11 76,4 99,11300 T4E VT12 76,5 99,5
Cooling Capacity: 200 ÷ 1260 kWFree-Cooling Capacity: 243 ÷ 1456 kW
Referred to water temperature 12/7°C and 35°C ambient air temperature according to Eurovent standard
EER up to 3,51ESEER up to 5,03EER up to 3,51ESEER up to 5,03
Sound pressure ISO3744Sound power ISO9614-2
INVERTER
HIGHEFFICIENCY
LOWNOISEHFO1234ze
AB
C
FRIGO TURBO FLG
rcgroupairconditioning
Model K 270 T1 250 T1 P4 280 T1 310 T1E 400 T2 400 T2 P4 500 T2 P4Cooling Capacity (kW) 270 250 280 310 400 400 500
EER net 4,55 5,23 5,05 5,24 5,21 5,23 5,24ESEER 7,45 8,09 8,24 8,27 8,33 8,37 8,63A (mm) 1000 3620 3620 3620 3620 3620 3805B (mm) 1300 1360 1360 1360 1360 1360 1360C (mm) 1850 1770 1770 1770 1770 1770 1929
Net weight (Kg) 1200 1921 1918 2031 2108 2208 2704
Model 560 T2 620 T2E 750 T3 P4 840 T3 930 T3E 1000 T4 P4 1120 T4 1240 T4ECooling Capacity (kW) 560 620 750 840 930 1000 1120 1240
EER net 5,05 5,25 5,26 5,08 5,28 5,26 5,08 5,30ESEER 8,61 8,68 8,99 8,87 8,76 8,55 8,67 8,80A (mm) 3805 3097 3870 3870 3870 4640 4640 4640B (mm) 1360 1360 1400 1400 1400 1400 1400 1400C (mm) 1929 1929 2059 2059 2059 2090 2090 2090
Net weight (Kg) 2703 2763 3912 3912 4094 5289 5291 5468
Model Sound Pressure Level (Lp1m)[dB(A)]
Sound Power Level(Lw)[dB(A)]
K 270 T1 69,4 86,0250 T1 P4 69,5 87,5
280 T1 69,5 87,5310 T1E 69,9 87,9400 T2 71,7 89,7
400 T2 P4 71,7 89,7500 T2 P4 71,5 89,7
560 T2 71,5 89,7620 T2E 71,7 89,9
750 T3 P4 71,6 90,7840 T3 71,6 90,7
930 T3E 72,1 91,21000 T4 P4 72,7 92,1
1120 T4 72,7 92,11240 T4E 72,9 92,3
Cooling Capacity: 270 ÷ 1240 kW
Referred to water temperature 12/7°C and condenser water temperature 30/35°C according to Eurovent standard
EER up to 5,30ESEER up to 8,99EER up to 5,30ESEER up to 8,99
Sound pressure ISO3744Sound power ISO9614-2
X TYPE AIR CONDITIONERS
GOGREEN
CHILLEDWATER
NEWPRODUCT
ECFAN
XCOILS
BAGFILTERS
The new chil led water air conditioners range designed for a perfect synergy with TURBO FLG liquid chil lers.3 models: from 100 to 190 kW EER up to 52,63 cabinets2 stage CHW coil and 2-way CHW valveEC plug fansReturn air bag filterIn/Out CHW connections from the bottom
UNDER PATENT
rcgroupairconditioning
TIER II TIER IVPotenza Frigorifera (kW) 140 101Portata Aria (m3/h) 31000 22000Potenza Assorbita Ventilatori (kW) 4,5 1,92EER (kW / kW) 31,1 52,6
FILTER SECTIONwith low pressure drop G4 efficiency bag type return air filters for once a year replacement
INNOVATIVE X COIL SECTIONLower pressure drop on air sideLower turbulenceCorrect water side pressure dropPossibility to have two independent separate CHW coils complying with TIER IV without modifications
FANS SECTIONwith nr. 2, 3 or 4 x Plug Fan EC “radical” type with:large diameter, 630 mm very high energy efficiency (wing profile).
TWO OPERATING COOLING LOGICS FOR A PERFECT REDUNDANCY
COOLING LOGIC 1
Single CHW source with:nr. 1 x TWO STAGE COOLING PROCESS FOR FULL CAPACITY
COOLING LOGIC 2
Double CHW source with:nr. 2 x SINGLE STAGE COOLING PROCESS FOR HALF CAPACITY EACH TO MEET THE TIER IV REQUIREMENTS
More uniform air/CHW temperature
Correct air path crossing the unit
Fans in symmetrical position on the vertical axes
Lower power input and noise
GOReliableEcologicEvolvedNatural
RC GROUP S.p.A Via Roma 5, 27010 Valle Salimbene (PV) Italy +39 0382 433811 www.rcgroup.it [email protected]
RC Group isa company of
Technicaldataanddimensionsarepreliminaryandnotbinding.RCGROUPS.p.A.reservestherightforchangesand/ormodificationswithoutnotice