2 CREEK TECHNICAL SERVICES, LLC EVALUATION REPORT Manufacturer: Manufacturing: Quality Assurance: SCOPE Category: Subcategory: Code Sections: Properties: REFERENCES GLOBAL INNOVATION, LLC 496 SW Ring Court Lake City, FL 32025 (877) 784-2824 www.endureed.com Lake City, FL Certificate of Authorization No. 29824 17520 Edinburgh Dr Tampa, FL 33647 (813) 480-3421 FLORIDA BUILDING CODE, 5H EDITION (2014) PRI Construction Materials Technologies (QUA9110) Issued September 26, 2016 Roofing Roofing Accessories that are an Integral Part of the Roofing System 1504.3.1 Wind Resistance Entitv PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) TrinityIERD PRODUCT DESCRIPTION Endureed - Regions Profile: Description: Material: : Report No. CCR-008-02-01 CCR-009-02-01A CCR-009-02-01 B CCR-010-02-01A CCR-010-02-01 B CCR-011-02-01 CCR-012-02-01 S35000.12.10-R16 Standard ASTM D 3161 TAS 107 UL 1897 UL 1897 TAS 100 TAS 100 ASTM 3161 TAS 107 ASTM D 3462 ASTM D 882 ASTM D 6163 Year 2009 1995 2004 2004 1995 1995 2009 1995 2009 2012 2000(2008) Synthetic thatch shingle; 42 in. width x 14 to 15 in. tall, 6.5 to 8 in. headlap; Panels abutted end-to-end PVC reeds bound by 23 ga. grade 304 stainless steel binder strip Sol STAINLESS STEEL 5/32· ATTAC#*ENT HOLES n BII[PER 304 STAINLESS STm- BINDER 1 , 504 STAINLESS STEEL i'*1/4· LOCKINS STRIP </: 4 4.. 1111]- 111111 PVC REEM 1 1 1-, ' MCIESS J FL21047 GIE16001 Page 1 of 5 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein.

Upload: others

Post on 28-Jul-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2 CREEK Certificate of Authorization No. 29824...Certificate of Authorization No. 29824 17520 Edinburgh Dr Tampa, FL 33647 (813) 480-3421 FLORIDA BUILDING CODE, 5H EDITION (2014) PRI

2 CREEK TECHNICAL SERVICES, LLC

EVALUATION REPORT

Manufacturer:

Manufacturing:

Quality Assurance:

SCOPE

Category:

Subcategory:Code Sections:

Properties:

REFERENCES

GLOBAL INNOVATION, LLC

496 SW Ring Court

Lake City, FL 32025

(877) 784-2824www.endureed.com

Lake City, FL

Certificate of Authorization No. 29824

17520 Edinburgh Dr

Tampa, FL 33647

(813) 480-3421

FLORIDA BUILDING CODE, 5H EDITION (2014)

PRI Construction Materials Technologies (QUA9110)

Issued September 26, 2016

Roofing

Roofing Accessories that are an Integral Part of the Roofing System1504.3.1

Wind Resistance

Entitv

PRI Construction Materials Technologies (TST5878)

PRI Construction Materials Technologies (TST5878)PRI Construction Materials Technologies (TST5878)

PRI Construction Materials Technologies (TST5878)

PRI Construction Materials Technologies (TST5878)PRI Construction Materials Technologies (TST5878)

PRI Construction Materials Technologies (TST5878)

TrinityIERD

PRODUCT DESCRIPTION

Endureed - Regions

Profile:

Description:Material:

:

Report No.

CCR-008-02-01

CCR-009-02-01A

CCR-009-02-01 B

CCR-010-02-01A

CCR-010-02-01 B

CCR-011-02-01

CCR-012-02-01

S35000.12.10-R16

Standard

ASTM D 3161

TAS 107

UL 1897

UL 1897

TAS 100

TAS 100

ASTM 3161

TAS 107

ASTM D 3462

ASTM D 882

ASTM D 6163

Year

2009

1995

2004

2004

1995

1995

2009

1995

2009

2012

2000(2008)

Synthetic thatch shingle;

42 in. width x 14 to 15 in. tall, 6.5 to 8 in. headlap; Panels abutted end-to-end

PVC reeds bound by 23 ga. grade 304 stainless steel binder strip

Sol STAINLESS STEEL

5/32· ATTAC#*ENT HOLES n BII[PER

304 STAINLESS STm- BINDER 1 , 504 STAINLESS STEELi'*1/4· LOCKINS STRIP </:4 4..1111]- 111111

PVC REEM 1

1 1-, '

MCIESS J

FL21047GIE16001 Page 1 of 5

This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEKTechnical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are notspecifically addressed herein.

Page 2: 2 CREEK Certificate of Authorization No. 29824...Certificate of Authorization No. 29824 17520 Edinburgh Dr Tampa, FL 33647 (813) 480-3421 FLORIDA BUILDING CODE, 5H EDITION (2014) PRI

Z CREEKTECHNICAL SERVICES, LLC

Endureed - Viva

Profile:

Description:Material:

0

a

1-*

\

\

\

LIMITATIONS

1.

2.

3.

4.

5.

6.

Synthetic thatch shingle

36 in. width x 27-25 in. tall, 7.5 in. headlap; Minimum 2.5 in. side lap;

Synthetic palm thatch comprised of composite HDPE

36"

Field Shingle

1 lili 1 -]

End yielD

\

=

rC.1

GLOBAL INNOVATION LLC

Endureed

Fastner Location

WDPE Shingle.043" Nom. Thickness (+/-.003)

Fire classification is not within the scope of this evaluation.The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loadsestablished for components and cladding and in accordance with FBC requirements.The roof system shall not be installed over an existing roof.Installation of the evaluated products shall comply with this report, the FBC, and the manufacturer'spublished application instructions. Where discrepancies exist between these sources, the more restrictiveand FBC compliant installation detail shall prevail.Quality Assurance for SOPREMA modified bituminous roofing products is provided under FL3915.All products listed in this report shall be manufactured under a quality assurance program in compliance withRule 61 G20-3.

GIE16001 FL21047 Page 2 of 5

This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK

Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are notspecifically addressed herein.

Page 3: 2 CREEK Certificate of Authorization No. 29824...Certificate of Authorization No. 29824 17520 Edinburgh Dr Tampa, FL 33647 (813) 480-3421 FLORIDA BUILDING CODE, 5H EDITION (2014) PRI

Roof Deck:

B

C

D

-CREEK-U TECHNICAL SERVICES, LLC

APPROVED ASSEMBLIES

System 1 - Endureed - Regions

Slope: 2:12 or greater

Roof Covering:

Surfacing:

B

C

D

B

C

D

Maximum DesignPressures:

Exposure

Notes:

120

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

30 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

30 ft

15 ft

60 ft

20 ft

NA

GLOBAL INNOVATION LLC

Endureed

Solid or closely fitted min. 15/32 in. plywood sheathing for new and existing construction atmax. 24 in. span; Designed by others in accordance with FBC requirements.

SOPREMA Elastophene Stick HR FR GR shall be applied direct to plywood deck inaccordance with the manufacturer's installation instructions.

Endureed "Region" synthetic thatch shingles shall be installed by fastening with four (4) toseven (7) 11 ga. x 1.75 in. stainless steel ring shank roofing nails per panel. The nailsshall be placed in the predrilled holes at either end of each binder and spaced between theend nails as evenly as possible.

-82.5 psfPressure calculated using 2:1 margin of safety per 1504.9

Maximum Mean Roof Heights for Gable/Hip RoofsSlopes 2:12-6.1:12

9Basic Wind Speed (mph)130 140 150 160 170

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

Zone 1 - Field

60 ft 60 ft

60 ft 60 ft

60 ft 60 ft

Zone 2 - Perimeter

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

Zone 3 -

60 ft

30 R

Corner

60 ft

15 ft

180 190

60 ft 60 ft 60 ft 40 ft 30 ft NA

60 ft 60 ft 60 ft NA NA NA

60 ft 60 ft 30 ft NA NA NA NA NA

1) Exposure category for the structure location shall be as defined in the Florida Building Code2) Limitations are based on the exposed area of 10ff or less3) Topographic factors such as escarpments or hills are not included in the above assessment4) Applicable for Enclosed Buildings without overhangs

5) NA = "Not Allowed"6) %4 = 0.857) Projects with mean roof heights of greater than 60 ft shall be evaluated by a licensed design professional

8) See page 5 for details for dimensions and locales of Zone 1, 2, and 39) Vult is shown in the above table. Design pressures are calculated using Vasd = Vu,NO.6 per 1609.3.1.10) For Hip roofs between 2:12 and 5.6:12, Zone 3 shall be treated as Zone 2.

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

200

50 ft

NA

NA

NA

NA

NA

GIE16001 FL21047 Page 3 of 5

This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK

Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are notspecifically addressed herein.

Page 4: 2 CREEK Certificate of Authorization No. 29824...Certificate of Authorization No. 29824 17520 Edinburgh Dr Tampa, FL 33647 (813) 480-3421 FLORIDA BUILDING CODE, 5H EDITION (2014) PRI

Notes:

B

C

D

-CREEK-U TECHNICAL SERVICES, LLC

System 2

Slope:

Roof Deck:

Roof Covering:

Surfacing

Maximum DesignPressures:

B

C

D

B

C

D

Exposure

Endureed - Viva

120

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

2:12 or greater

60 ft

25 ft

NA

60 ft

60 ft

60 ft

50 ft

NA

NA

60 ft

60 ft

60 ft

40 ft

NA

NA

GLOBAL INNOVATION LLC

Endureed

Solid or closely fitted min. 15/32 in. plywood sheathing for new and existing construction atmax. 24 in. span; Designed by others in accordance with FBC requirements.

SOPREMA Elastophene Stick HR FR GR shall be applied direct to plywood deck inaccordance with the manufacturer's installation instructions.

Endureed "Viva" synthetic thatch shingles shall be installed by fastening with seven (7) 11ga. x 1.25 in. stainless steel ring shank roofing nails per panel. The nails shall be placedin the premolded nail locations.

-67.5 psfPressure calculated using 2:1 margin of safety per 1504.9

· Maximum Mean Roof Heights for Gable/Hip Roofs cSlopes 2:12-6.1:12

9Basic Wind Speed (mph)130 140 150 160 170 180

60 ft

60 ft

60 ft

60 ft

60 ft

60 ft

Zone 1 - Field

60 ft 60 ft

60 ft 60 ft

60 ft 60 ft

Zone 2 - Perimeter

60 ft 60 ft

60 ft 40 ft

40 ft 15 ft

Zone 3 - Corner

190

60 ft 60 ft 60 ft 50 ft 30 ft NA NA NA

60 ft 50 ft 25 ft NA NA NA NA NA

50 ft 20 ft NA NA NA NA NA NA

1) Exposure category for the structure location shall be as defined in the Florida Building Code2) Limitations are based on the exposed area of 100 or less3) Topographic factors such as escarpments or hills are not included in the above assessment4) Applicable for Enclosed Buildings without overhangs

5) NA = "Not Allowed" 6) K,i = 0.857) Projects with mean roof heights of greater than 60 ft shall be evaluated by a licensed design professional

8) See page 5 for details for dimensions and locales of Zone 1, 2, and 39) Vuit is shown in the above table. Design pressures are calculated using Vasd = VuiNO.6 per 1609.3.1.10) For Hip roofs between 2:12 and 5.6:12, Zone 3 shall be treated as Zone 2.

60 ft

60 ft

60 ft

200

NA

NA

NA

60 ft

60 ft

30 ft

NA

NA

NA

GIE16001 FL21047 Page 4 of 5

This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK

Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are notspecifically addressed herein.

Page 5: 2 CREEK Certificate of Authorization No. 29824...Certificate of Authorization No. 29824 17520 Edinburgh Dr Tampa, FL 33647 (813) 480-3421 FLORIDA BUILDING CODE, 5H EDITION (2014) PRI

ZGable

a

CREEKTECHNICAL SERVICES, LLC

3

3

2

2

2

1

a

3

2

3

a a

a

a

Hip

43

2

Ial

1 2

2

Ial

a

a

GLOBAL INNOVATION LLC

Endureed

Zones 1,2, and 3 shall be defined as shown above. Dimension "a" shall be 10% of the least horizontal dimension or

(0.4 x Mean Roof Height), whichever is smaller, but not less than either 4% of the least horizontal dimension or 3ft.

COMPLIANCE STATEMENT

The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida BuildingCode, 0 Edition (2014) as evidenced in the referenced documents submitted by the named manufacturer.

...0,1,11'11"i'...

6§5:·SWN 2:2*%,0 .. M 5

:+ : No 74021 S2* S

-..-*.

-

,-0: : tr-

Ste; STATE OF ./,4 2Ave

":1***22*89"/"il,11 lii",0

CERTIFICATION OF INDEPENDENCE

2016.09.26. .' Se rvice

6-&- 15:04:36-04'00'

Zachary R. Priest, P.E.Florida Registration No. 74021Organization No. ANE9641

CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributingproducts under this evaluation.

CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products underthis evaluation.

Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing productsunder this evaluation.

Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the

product.

END OF REPORT

GIE16001 FL21047 Page 5 of 5

This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEKTechnical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are notspecifically addressed herein.