1mac502624-dr a single line diagram … 2014 all rights reserved relay order code:nafccbc3ffxxxax1xx...
TRANSCRIPT
SHEET 1 OF 10
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
NAFCCBC3FFxxxAx1xxRELAY ORDER CODE:
SINGLE LINE DIAGRAM (TYPICAL)
1MAC502624-DRA
PO1
PO3
INPUT 4
OR
52-1_EXE_CL
79-1_CLOSE_CB
CLOSE
TRIP
INPUT 5
CB1_POSITION_CLOSE
CB1_POSITION_OPEN
STATUS
52-1
REF620 V2.0 ANSI Functional Application C(CB)
REF620_NAFCCBC3FFxxxAx1xx
SO1
BREAKER
FAIL
50BF-1_TRBU
OR
52-1_EXE_OP
86/94-1_TRIP
HSO1
86/94-1_TRIP
46-1_TRIP
46-2_TRIP
46PD_TRIP
49F_TRIP
50P-1_TRIP
50P-2_TRIP
50P-3_TRIP
50N-1_TRIP
50N-2_TRIP
Breaker
Trip(1)
50N-3_TRIP
51LT_TRIP
51P-1_TRIP
51N-1_TRIP
HIZ_TRIP
AFD-1_TRIP
67_50P-1_TRIP
67_50P-2_TRIP
67_51P_TRIP
67_50N-1_TRIP
67_50N-2_TRIP
67-51N_TRIP
81LSH-1_TRIP
81LSH-2_TRIP
AFD-3_TRIP
HSO3
ARC FLASH
TRIP(3)
SO2
BREAKER
FAIL
50BF-2_TRBU
46-1_TRIP
46-2_TRIP
46PD_TRIP
49F_TRIP
50P-1_TRIP
50P-2_TRIP
50P-3_TRIP
50N-1_TRIP
50N-2_TRIP
Breaker
Trip(2)
50N-3_TRIP
51LT_TRIP
51P-1_TRIP
51N-1_TRIP
HIZ_TRIP
AFD-2_TRIP
67_50P-1_TRIP
67_50P-2_TRIP
67_51P_TRIP
67_50N-1_TRIP
67_50N-2_TRIP
67-51N_TRIP
81LSH-1_TRIP
81LSH-2_TRIP
PO2
PO4
INPUT 2
OR
52-2_EXE_CL
79-2_CLOSE_CB
CLOSE
TRIP
INPUT 3
CB2_POSITION_CLOSE
CB2_POSITION_OPEN
STATUS
52-2
OR
52-2_EXE_OP
86/94-2_TRIP
HSO2
86/94-2_TRIP
Bus 1
Bus 2
25-1
25-2 79-1
79-1
50BF-1 59N-
1(1)²
27-2(1) 47-1(1) 47-2(1) 59-1(1) 59-2(1)
(Open Delta)
Y or
2 or 3
(Open Delta)
Y or
2 or 3
60-1(1)27-1(1)
24-1 81LSH-
1
81LSH-
2
81-1 81-2
50P-1 50P-2 50P-3 51LT-1 51P-137-1 46-1 46-2 46PD-1 49F-1
21P-1 32P-1 67/50P
-1
Load
Prof.
PQ-1
50N-1 50N-2 50N-3 32N-1
67/50
N-1
67/50
N-2
67/51
N-1
Calculated Ground Functions
51N-1
50SEF HIZ
50BF-2
59N-
1(2)²
AFD-1 AFD-2 AFD-3
27-2
(2)
47-1
(2)
47-2
(2)
59-1
(2)
59-2
(2)
60-1
(2)
27-1
(2)
2
Calc V0
3
Neg Seq Volt
1
25-3
4
3
PB13
(KEY_13)
PB13
(KEY_14)
(1)
(2)
CT
SUMMATION
PT
50SEF_TRIP
(1)
REF620 V2.0 ANSI Functional Application C(CB)
(3)
67/50P
-2
67/51P
-1
50SEF_TRIP
(2)
General Notes:
1. Rotary switch emulates drop down menu for "Pol Signal Sel" parameter setting in PCM600.
Switch position shown for default setting (Calculated Vo).
2. "Pol Signal Sel" parameter setting Calc Vo, and 59N-1 functions not applicable for open delta connected VTs.
3. Default labels for programmable pushbuttons 13 and 14. Pushbuttons are shown latched and toggle to emulate flip-flop
bus selection logic in PCM600 ACT (Application Configuration Tool). Relay defaults to Bus 1 selection when energized.
SHEET 2 OF 10
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
A
RELAY ORDER CODE:
NAFCCBC3FFxxxAx1xx
General Notes:
1. Style and code numbers for FT-1 switches provide black covers and handles, screw terminals and standard depth. Poles selection follows arrangement
shown in this drawing set. For custom designs, different selection options can be made by using FT-1 configurator at ft1switch.com
2. Refer to 620 series ANSI Installation Manual for relay and cutout dimensions ( Document ID: 1MAC457436-iB, Revision: A, Product version 2.0)
REF620_NAFCCBC3FFxxxAx1xx
FRONT PANEL ELEVATION- RELAY & SWITCHES
1MAC502624-DR
SHEET 3 OF 10
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
A
RELAY ORDER CODE:
FRONT PANEL ELEVATION - SWITCH LABELS
NAFCCBC3FFxxxAx1xx
JIHGFEDCBA
2 1816141210864
19
20
1715131197531
PH
AS
E C
UR
RE
NT
IA
(1)
PH
AS
E C
UR
RE
NT
IB
(1)
PH
AS
E C
UR
RE
NT
IC
(1)
(BUS 1 POTENTIALS AND CB 52-1 BINARY I/O)
JIHGFEDCBA
2 1816141210864
19
20
1715131197531
(CT (1) CURRENTS AND RELAY POWER SUPPLY)
GR
OU
ND
C
UR
RE
NT
RE
LA
Y P
OS
. V
DC
IG
RE
LA
Y N
EG
. V
DC
52-1_E
XE
_C
L/79-1_C
LO
SE
_C
B(P
O1)
86/94-1_T
RIP
/52-1_E
XE
_O
P(P
O3)
50B
F-1_T
RB
U(S
O1)
86/94-1_T
RIP
(H
SO
1)
CB
1_P
OS
IT
IO
N_C
LO
SE
(IN
4)
CB
1_P
OS
IT
IO
N_O
PE
N(IN
5)
PH
AS
E C
UR
RE
NT
V
A(1)
PH
AS
E C
UR
RE
NT
V
B(1)
PH
AS
E C
UR
RE
NT
V
C(1)
JIHGFEDCBA
2 1816141210864
19
20
1715131197531
PH
AS
E C
UR
RE
NT
IA
(2)
PH
AS
E C
UR
RE
NT
IB
(2)
PH
AS
E C
UR
RE
NT
IC
(2)
(BUS 2 POTENTIALS AND CB 52-2 BINARY I/O)
JIHGFEDCBA
2 1816141210864
19
20
1715131197531
(CT (2) CURRENTS AND LINE POTENTIAL)
AF
D-3_T
RIP
(H
SO
3)
SY
NC
H V
OL
TA
GE
V
S
52-2_E
XE
_C
L/79-2_C
LO
SE
_C
B(P
O2)
86/94-2_T
RIP
/52-2_E
XE
_O
P(P
O4)
50B
F-2_T
RB
U(S
O2)
86/94-2_T
RIP
(H
SO
2)
CB
2_P
OS
IT
IO
N_C
LO
SE
(IN
2)
CB
2_P
OS
IT
IO
N_O
PE
N(IN
3)
PH
AS
E C
UR
RE
NT
V
A(2)
PH
AS
E C
UR
RE
NT
V
B(2)
PH
AS
E C
UR
RE
NT
V
C(2)
REF620_NAFCCBC3FFxxxAx1xx
1MAC502624-DR
SHEET 4 OF 10
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
A
RELAY ORDER CODE:
NAFCCBC3FFxxxAx1xx
AC SCHEMATIC BUS 1, CB52-1 (TYPICAL)
52-1
Bus 1
X130
REF620FT-1/TS2
X120
FT-1/TS1
Open
Delta *
REF620_NAFCCBC3FFxxxAx1xx
Summation Point
WYE VT CONNECTION
'VT connection' setting = 'Wye')
* For relay voltage connections shown set Analog input Voltage 'VT connection' setting to Wye' for metering to work correctly.
Refer to application manual for alternate connections to relay for open delta connections using 'Delta' VT connection setting.
1MAC502624-DR
SHEET 5 OF 10
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
A
RELAY ORDER CODE:
NAFCCBC3FFxxxAx1xx
AC SCHEMATIC - FEEDER, CB52-2 (TYPICAL)
REF620_NAFCCBC3FFxxxAx1xx
52-2
Circuit Breaker 52-1
Bus 2
Feeder
FT-1/TS1
X120
FT-1/TS3
X130
REF620
1MAC502624-DR
SHEET 6 OF 10
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
A
RELAY ORDER CODE:
NAFCCBC3FFxxxAx1xx
AC SCHEMATIC FEEDER, CB52-2 (TYPICAL)
Bus 2
X130
FT-1/TS4
REF620FT-1/TS3
Open
Delta *
X120
Circuit Breaker 52-2
REF620_NAFCCBC3FFxxxAx1xx
1MAC502624-DR
WYE VT CONNECTION
'VT connection' setting = 'Wye')
* For relay voltage connections shown set Analog input Voltage 'VT connection' setting to Wye' for metering to work correctly.
Refer to application manual for alternate connections to relay for open delta connections using 'Delta' VT connection setting.
SHEET 7 OF 10
A
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
NAFCCBC3FFxxxAx1xxRELAY ORDER CODE:
DC SCHEMATIC - OUTPUTS, PS (TYPICAL)
52-1_EXE_CL
79-1_CLOSE_CB
52-2_EXE_CL
79-2_CLOSE_CB
SO1
50BF-1_TRBU
TRIP
CIRCUIT
RELAY NEG. VDC
BREAKER 52-1 NEG. VDC
BREAKER 52-2 NEG.VDC
86/94-1_TRIP
52-1_EXE_OP
RELAY POS. VDC
BREAKER 52-1 POS. VDC
BREAKER 52-2 POS. VDC
TRIP
CIRCUIT
FT-1/TS4
X110
50BF-1_TRIP
POS(+VDC)
86/94-1_TRIP 86/94-2_TRIP AFD_TRIP
FT-1/TS2 FT-1/TS4 FT-1/TS3
DC SCHEMATIC: INPUTS
SO2
50BF-2_TRBU
50BF-2_TRIP
CKT
CLOSE
CIRCUIT
CLOSE
CIRCUIT
50BF-1_TRIP
CKT
86_94-2_TRIP
52-2_EXE_OP
50BF-2_TRIP
POS(+VDC)
AFD-3_TRIP
POS(+VDC)
AFD-3_TRIP CKT
DC SCHEMATIC: INPUTS
1MAC502624-DR
SHEET 8 OF 10
A
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
RELAY ORDER CODE:
DC SCHEMATIC - INPUTS (TYPICAL)
RELAY NEG. VDC
BREAKER 52-1 NEG. VDC
RELAY POS. VDC
BREAKER 52-1 POS. VDC
BI2
CB2_POSITION
_CLOSE
DC SCHEMATIC: POWER
SUPPLY
AND OUTPUTS
NAFCCBC3FFxxxAx1xx
REF620_NAFCCBC3FFxxxAx1xx
BREAKER 52-2 POS. VDC
BREAKER 52-2 NEG. VDC
DC SCHEMATIC: POWER
SUPPLY
AND OUTPUTS
1MAC502624-DR
SHEET 9 OF 10
A
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
RELAY ORDER CODE:
CONNECTION DIAGRAM-RELAY
NAFCCBC3FFxxxAx1xx
REF620_NAFCCBC3FFxxxAx1xx
1MAC502624-DR
SHEET 10 of 10
A
ABB Protective Relays and Switches, Coral Springs Fl, U.S.A.
Copyright 2015 ABB
All rights reserved AUTOCAD 2014
RELAY ORDER CODE:
CONNECTION DIAGRAM-FT-1 SWITCHES
NAFCCBC3FFxxxAx1xx
REF620_NAFCCBC3FFxxxAx1xx
1MAC502624-DR