1.2 dc standards
DESCRIPTION
1.2 DC StandardsTRANSCRIPT
-
www.isaaktech.com
BICSI002/TIA942/UptimeWhichDataCenterStandard
ShouldIFollow
PhilIsaak,PE,P.Eng.,RCDD,DCDCPresident,MasterInstructor
IsaakTechnologiesInc.
-
www.isaaktech.com
Standards WhoarethesePeople PowerStandards
Distribution&Grounding NetworkStandards
Protocols ITHardwareManufacturers
MediaStandards CablingManufacturers
Design&InstallationStandards EndUsers,Contractors,Consultants,Manufacturers
-
www.isaaktech.com
Uptime TIA BICSI
OpenIndustryStandard NOT VendorNeutral
ANSI/TIA942A(2012)TelecommunicationsInfrastructureStandard
forDataCenters118pages
ANSI/BICSI0022011DataCenterDesignandImplementation
BestPractices392pages
UptimeInstitute(2010)DataCenterSiteInfrastructure
TierStandard:Topology12pages
OpenIndustryStandard VendorNeutral
ForProfitPrivatelyHeld NOT aStandard
-
www.isaaktech.com
ANSICertifiedStandardRequirements
Openness: Participationshallbeopentoallpersonswhoaredirectlyandmateriallyaffectedbytheactivityinquestion.
LackofDominance:Thestandardsdevelopmentprocessshallnotbedominatedbyanysingleinterestcategory,individualororganization.
Balance:Participantsfromdiverseinterestcategoriesshallbesoughtwiththeobjectiveofachievingbalance.
-
www.isaaktech.com
BICSISubjectMatterExpertsMorethan150subjectmatterexpertsfromaroundtheworldparticipatedindevelopingthestandard.
Perspectives: DataCenterManagers DataCenterOperators Consultants Contractors RiskAssessors Manufacturers CommissioningAgents
Expertise: FacilityEngineers/Architects ITEngineers/Architects SystemAdministrators Telecommunications Security FireProtection ProjectManagers
-
www.isaaktech.com
ANSI/BICSI0022011Providesareferenceofcommonterminologyanddesignpracticesaframeworkfordeterminingtherecommendedfacilityandtechnologyredundancytomeettheoperationalrequirements,achieveITobjectives
andtodevelopoptimumdesign&implementationsolutions
UptimeTiersOnlydatacenterbenchmarkingsystemdevelopedbyandfordatacenterowners,notachecklist,designmenu,orcookbook
Source:UptimeInstitute:TierClassificationSystem&OperationalSustainabilitypresentedbyDanaSmith,DirectorofDevelopment,UptimeInstituteatBICSIAndino 2012
DesignGuidevs Benchmarking
-
www.isaaktech.com
UptimeBenchmarks
UptimeInstitute TierI TierII TierIII TierIV
ScheduledOutages/Year 2x12hrs 1x12hrs None None
AveFailures/Year(4hrs/failure) 1.2 1.0 1.0 1.0
AveAnnualDowntimeHours 28.8 22 1.6 0.8
Availability 99.67% 99.75% 99.98% 99.99%
**Basisisontop10%ofsitesasdeterminedbyUptimeInstituteBenchmarking**
-
www.isaaktech.com
ComparingtheStandards TIA942Achapters (normative)
Datacenterdesignoverview Datacentercablingsysteminfrastructure Datacentertelecommunicationsspaces&relatedtopologies Datacentercablingsystems Datacentercablingpathways Datacenterredundancy
TIA942Aannexes (informative) Cablingdesignconsiderations Accessproviderinformation Coordinationofequipmentplanswithotherengineers Datacenterspaceconsiderations Datacentersiteselectionandbuildingdesignconsiderations Datacenterinfrastructuretiers Datacenterdesignexamples
-
www.isaaktech.com
Spaceplanning Siteselection Architectural Structural Electricalsystems Mechanical Fireprotection
BICSI002annexes Designprocess Reliabilityandavailability
Security Buildingautomationsystems Telecommunications Informationtechnology Commissioning Datacentermaintenance
BICSI002sections
ComparingtheStandards
-
www.isaaktech.com
ANSI/BICSI0022011
ComprehensiveDataCenterStandard
-
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
AnnualPlannedDowntime
OperationalLevel
> 400hrs 0
100 400hrs 1
50 99hrs 2
0 49hrs 3
0hrs 4
-
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
Minutes Numberof9s
>5,000 >99%
500 5,000 99% 99.9%
50 500 99.9% 99.99%
5 50 99.99% 99.999%
0.5 5 99.999% 99.9999%
DefineAvailabilityRequirements
-
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
Description ClassificationLocalinscope,affectingonlyasinglefunctionoroperation,resultinginaminordisruptionordelayinachievingnoncriticalorganizationalobjectives.
Isolated
Localinscope,affectingonlyasinglesite,orresultinginaminordisruptionordelayinachievingkeyorganizationalobjectives.
Minor
Regionalinscope,affectingaportionoftheenterpriseorresultinginamoderatedisruptionordelayinachievingkeyorganizationalobjectives.
Major
Multiregionalinscope,affectingamajorportionoftheenterpriseorresultinginamajordisruptionordelayinachievingkeyorganizationalobjectives.
Severe
Affectingthequalityofservicedeliveryacrosstheentireenterprise,orresultinginasignificantdisruptionordelayinachievingkeyorganizationalobjectives.
Catastrophic
DefineAvailabilityRequirements
DefineImpactofDowntime
-
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
DefineAvailabilityRequirements
DefineImpactofDowntime
RecommendedPerformanceIdentified
Class0Class1Class2Class3Class4
-
www.isaaktech.com
Class0/1SinglePath
BPSUAPSU
PowerCircuitA1
APOU
RPPA
NCRAHModules
NChiller,Pumps&Condenser
Pipingandvalveredundancynotrequired.
LargeFrame
Processing
WANCarrier
DiskArray
Core
EdgeInternet
AccessSwitch
Server n
Aggregation
Server 1
EdgeWAN
NASDiskArray
Transfer Switchgear
Electrical Distribution
Alternate Power Source
UPS
PDU
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Static Bypass
Maint.Bypass
Utility
2013IsaakTechnologiesInc.
-
www.isaaktech.com
Class2RedundantComponents
BPSUAPSU
PowerCircuitA1
APOU
BPOU
PowerCircuitA2
RPPA
+1CRAHModule
N+1Chillers,Pumps&Condensers
MorethanN+1redundancyisrecommendedasthenumberofmodulestomeetNincreases
NCRAHModules
Pipingandvalveredundancynotrequiredoutsidecomputerroom.
RefertoChillerPipingandValveRedundancysectionforcomputerroomrecommendations
LargeFrame
Processing
WANCarrier
DiskArray
NASDiskArray
Core
AccessSwitch
Server n
Aggregation
Server 1
EdgeWAN
EdgeInternet
Transfer Switchgear
Electrical Distribution
Alternate Power Source
Alternate Power Source
UPS UPS
PDU
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Static Bypass
Maint.Bypass
Utility
2013IsaakTechnologiesInc.
-
www.isaaktech.com
Class3ConcurrentMaintainability
BPSUAPSU
APOU
BPOU
STSA
STSB
PowerCircuit
RPPB12
PowerCircuit
RPPB11
RPPB1
PDUB1
PowerCircuit
RPPA12
PowerCircuit
RPPA11
RPPA1
PDUA1
+1CRAHModule
N+1Chillers,Pumps&Condensers
MorethanN+1redundancyisrecommendedasthenumberofmodulestomeetNincreases
NCRAHModules
Pipingandvalveredundancynotrequired,butrecommended,outsidecomputerroom.
RefertoChillerPipingandValveRedundancysectionforcomputerroomrecommendations
LargeFrame
Processing
WANCarrier 1
DiskArray n
SANSwitch2
DiskArray1
SANSwitch1
Core2Core1
Edge2Internet
Edge1Internet
AccessSwitch 1
Server n
Aggregation1
AccessSwitch 2
Server 1
WANCarrier 2
Aggregation2
Edge2WAN
Edge1WAN
Carrier 1 Carrier 2
NASDiskArray
SwitchgearUtility
Electrical Distribution
Switchgear
Alternate Power Source
Electrical Distribution
Alternate Power Source
UPS UPS
Output Distribution Switchboard
PDU
Mechanical Switchboard
CriticalFans/Pumps
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Alternate Switchboard
PDU
Mechanical Switchboard
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Static Bypass
Maint.Bypass
2013IsaakTechnologiesInc.
-
www.isaaktech.com
Class4FaultTolerant
BPSUAPSU
APOU
BPOU
STSA
STSB
PowerCircuit
RPP2B1
PowerCircuit
RPP2A1
PowerCircuit
RPP1B1
PowerCircuit
RPP1A1
PDUA1 PDUA2
PanelA PanelBRPP1
PDUB1 PDUB2
PanelA PanelBRPP2
NCRAHModules
+2CRAHModule
N+2Chillers,Pumps&Condensers
MorethanN+2redundancyisrecommendedasthenumberofmodulestomeetNincreases
Pipingandvalveredundancyrequiredoutsidecomputerroom.
RefertoChillerPipingandValveRedundancysectionforcomputerroomrecommendations
LargeFrame
Processing
WANCarrier 1
DiskArray n
SANSwitch2
DiskArray1
SANSwitch1
Core2Core1
Edge2Internet
Edge1Internet
AccessSwitch 1
Server n
Aggregation1
AccessSwitch 2
Server 1
WANCarrier 2
Aggregation2
Edge2WAN
Edge1WAN
Carrier 1 Carrier 2
NASDiskArray
SwitchgearUtility
Electrical Distribution
Switchgear
Alternate Power Source
Electrical Distribution
Alternate Power Source
UPS UPS
Output Distribution Switchboard
PDU
Mechanical Switchgear
CriticalFans/Pumps
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Output Distribution Switchboard
PDU
Mechanical Switchgear
Non-CriticalLoads
Mechanical Switchgear
Static Bypass Maint.
Bypass
UPS UPS
Static Bypass Maint.
Bypass
Utility
Alternate Power Source
Alternate Power Source
2013IsaakTechnologiesInc.
-
www.isaaktech.com
EndtoEndReliability
Applications Systems Network CablingInfrastructure Facility
Facility
CablingInfrastructure
Network
DataProcessing&StorageSystems
Applications
-
www.isaaktech.com
DC125DataCenterDesignCourse
4DayCourse InDepthReviewofStandard
PrepareforDCDCExamDataCenterDesignConsultant
ContactFiberOpto AsiaPte LtdforcoursedatesandlocationsavailableinSouthEastAsia
-
www.isaaktech.com
BICSIDataCenterDocumentsANSI/BICSI0022011DataCenterDesignandImplementationBestPractices
AvailablefromBICSIwww.bicsi.org/standards
BICSIInternationalStandardsSupplementalInformation001
MethodologyforSelectingDataCenterDesignClassUtilizingPerformanceCriteria