11kV MV Switch Board
Item Details / Description Unit Supplier data
1 11kV Switchboard Cubicle
Make ABB/AREVA/SIEMENSType VCB
Metal clad switchgear and control gear yes/no yes
Compartmented switchgear and control gear yes/no yes
- rated voltage kV 11
- operating voltage kV 11
Air insulated yes/no yes
Draw-out type yes/no yes
With automatic shutter ( for safety ) yes/no yes
Separate compartment for :
- circuit breaker yes/no yes
- busbars yes/no yes
- low voltage equipment yes/no yes- cable termination yes/no yes
Pressure relief covers / Flaps yes/no yes
Rear access necessary yes/no yes
Cable connection from bottom yes/no yes
Ample cabling space shall be provided for ease of
cable connection / Termination
yes/no yes
Lockable service position for circuit breaker yes/no yes
Lockable test position for circuit breaker yes/no yes
Lockable isolated position for circuit breaker yes/no yes
Circuit breaker floor mounted yes/no yes
Cable earthing by earthing switch yes/no no
Mechanical & Electrical safety interlocks for :- earthing switch yes/no no
- test position yes/no yes
- buscoupler & incomer * yes/no yes
Type of enclosure & degree of protection IP IP42
Thickness of sheet metal
a) load bearing members mm 2
b) Non load bearing members mm 2
Door arrangement ( enclose details ) During detailed Engg
Location of instruments & protection relays Metering chamber
above CB chamberMax.height of instruments & protection relays
from the round level
mm During detailed Engg
Overall dimension ( L x D x H ) & approx. weight mm / kg During detailed Engg
a) Double/Single bus board B/C
b) Double/Single bus board I/C
c) Single bus board O/G ( Trafo Feeder )
d) Single bus board O/G ( Motor Feeder )
GA drawings enclosed yes/no no
Space heaters with thermostat in all panels with
suitable interlocks
yes/no yes
DC source for each switchboard AH As per BOQ
2 Busbars
Busbar and T-off connections :
Page 1
-
8/13/2019 11 KV MV Board.
2/10
Technical Data sheets
11kV MV Switch Board
Item Details / Description Unit Supplier data
- Copper yes/no Yes
- Aluminium yes/no No
- insulated yes/no No
- Min clearance between
a) Phase to Phase mm As per IECb) Phase to Ground mm As per IEC
- Busbar size
4000 A sq.mm
2000A sq.mm
1250A sq.mm
500A sq.mm
-Current density - for copper busbars A/sq.mm 1.2A/sq.mm
Maximum temperature rise at rated full load
currentabove site ambient temperature ( 48 deg C ) deg C 42 deg C
Ground bus
-material
-one sec rating of ground bus KA 403 Current Transformers
- Make
-Type ( cast resin , bar primary ) yes/no yes
-Service Indoor
-Secondary current A 1
-Transformation ratio as per SLD yes/no yes
-Rated burden VA 15
-Accuracy class
a)Metering 0.5
b)Protection 5P20
suitable CTs to be provided to take care of
additional burden due to KW transducers
yes/no yes
- Class of insulation
-Power frequency & Impulse withstand KV 28/75
- short time thermal rating for 1 sec KA min. 31.5
4 Voltage Transformers
- Make
-Type
-Service
-Transformation ratio as per SLD yes/no yes
-Rated burden (for line PT's) VA 100
-Accuracy class 1.0/3P
-Power frequency & Impulse withstand KV 28/75
-Whether withdrawable type yes/no yes
-HT & LT fuses provided yes/no yes
5 Relays
Solid state relays equivalent to mentioned in SLD
with profibus communication facility
Yes/noYes
6 Meters
Ammeter
-Make
-Type
-Size mmxmm 90 x 90
-Range
During detailed Engg
Page 2
-
8/13/2019 11 KV MV Board.
3/10
Technical Data sheets
11kV MV Switch Board
Item Details / Description Unit Supplier data
-Reference standard
Voltmeter
-Make
-Type
-Size mmxmm 90 x 90-Range
-Reference standard
MW meter
-Make
-Type
-Size mmxmm 90 x 90
-Range
-Reference standard
KWH meter
-Make
-Type
-Size mmxmm 90 x 90
-Range-Reference standard
Power factor meter
-Make
-Type
-Size mmxmm During detailed Engg
-Range
-Reference standard
KW Transducer
-Make
-Type
-Size mmxmm During detailed Engg
-Range-Reference standard
Page 3
-
8/13/2019 11 KV MV Board.
4/10
Technical Data sheets
11kV MV Switch Board
Item Details/Description Unit Supplier
General Make As per Make listType Vacuum
Rated voltage kV 11
Operating voltage kV 11
Frequency Hz 50
Rated short circuit breaking current KA 40kA
Rated short time current (1 sec) KA 40kA
Total interrupting time ( measured in cycles
from trip coil energisation ) cycles
-
8/13/2019 11 KV MV Board.
5/10
Technical Data sheets
11kV MV Switch Board
Item Details/Description Unit Supplier
Circuit Breaker
measures
No-voltage release (control voltage) yes/no No Volt Coil shall be
considered for only HT
motor feeders.
Interlocks to :- prevent moving of C.B. in closed position yes/no yes
- allow closing of C.B. in defined position yes/no yes
Maintanence C.B. operation in racked-out/test/isolated
position yes/no yes
Additional Switching status indicator yes/no yesaccessories Operation counter yes/no yes
No. of auxiliary contacts
a) Normally closed nos. 6
b) Normally open nos. 6
c) Whether convertible type yes/no No
5
-
8/13/2019 11 KV MV Board.
6/10
Technical Data sheets
11kV MV Switch Board
Item Details/Description Unit Supplier
General Location : Main Sub-station
& Load Sub-station
Feeder Totally enclosed metal clad cubicle yes/no yes
cubicle (separate technical data sheet)
rated current of busbars considering deration due
to site conditions- for Double bus I/C A Not applicable
- for Single bus I/C A As per SLD- rated voltage KV 11
- operating voltage KV 11
- short circuit capacity at operating voltage for 3 KA 40kA
Switchgear Circuit breaker yes/no yes
(separate technical data sheet)
for single bus I/C
- for Double bus I/C A Not applicable
- for Single bus I/C A As per SLD
Whether suitable for voltage and frequency
variations as iven in s ecifications
yes/no yes
Surge diverter Surge diverter with counter yes/no No
Earthing Earthing switch yes/no No
Protection , Current transformers qty. As per SLD
metering, Voltage transformers qty. As per SLD
& Indications
Protections: As per the spec
Indications: yes/no yes
( Enclose detailed list of indications provided )
Energy / PowerAmmeters with selector switch qty. 1
Metering Voltmeter with selector switch qty. 1
Power factor meter yes/no
kWh meter yes/no
kW - tranducer with isolated 4-20 mA yes/no No
Incoming Feeder
On MFM
6
-
8/13/2019 11 KV MV Board.
7/10
Technical Data sheets
11kV MV Switch Board
Item Details/Description Unit Supplier
GeneralLocation : Crusher, RM, Kiln & Cement Mill
SubstationFeeders
: Single bus board
Feeder Totally enclosed metal clad cubicle yes/no yes
cubicle (separate technical data sheet)
rated current (Contactor feeder) A Not Applicable
- rated voltage KV -- operating voltage KV -
short circuit capacity at operating voltage for 1
sec
KA -
Switchgear Contactor feeder with fuses yes/no VCB Offered
(separate technical data sheet)
- rated current A As per the
requirement
- rated voltage KV 11
- operating voltage KV 11
short circuit capacity at operating voltage for KA 40kAWhether suitable for voltage and frequency
variations as iven in s ecifications
yes/no yes
Earthing Earthing switch yes/no no
Protection, Current transformers, output side qty. As per SLD
metering, & Indicatio Protections: As per the spec
Indications: yes/no yes
( Enclose detailed list of indications including
transformer faults provided, Annunciator
be for transformer faults )
Ammeters with selector switch qty. 1
Energy / Power kWh-meter yes/no MFM
Metering Metering: - unbalanced load yes/no no
- accuracy class % -
kW-transmitter with 4-20 mA output yes/no applicable for
motor feeder
Transformer Feeder
7
-
8/13/2019 11 KV MV Board.
8/10
Technical Data sheets
11kV MV Switch Board
Item Details/Description Unit Supplier
MakeABB/AREVA/SIEME
NS
General Location : Main Sub-station
Feed to : 11kV/MV motors
Feeders
: Single bus board
Feeder Totally enclosed metal clad cubicle yes/no yes
cubicle (separate technical data sheet)
rated current (Contactor feeder) A Not Applicable
Derated current (Contactor feeder) A Not Applicablerated current (Breaker feeder) A As per Tender
Derated current (Breaker feeder) A As per Tender
- rated voltage KV 11
- operating voltage KV 11
- short circuit capacity at operating voltage for KA 40kA
Switchgear Contactor and VCB/SF6 Breakers VCB
(separate technical data sheet) yes/no yes
- rated current A As per Tender
- derated current at site conditions A As per Tender
- rated current A -
- derated current at site conditions A -
Whether suitable for voltage and frequency variations
as given in Specifications yes/no yes
Surge divert Surge diverter with counter yes/no without counter
Earthing Earthing switch yes/no no
Protection , Current transformers, output side qty. As per Requirement
metering, Current transformers for capacitor line current qty. As per Requirement
& Indications
Protections:
Motor protection (microprocessor based) yes/no As per Requirement
Trip circuit supervision yes/no As per Requirement
High speed lock out Relay yes/no As per Requirement
Antipumping protection yes/no As per Requirement
Others :
Indications: yes/no As per Requirement
( Enclose detailed list of indications provided )
Energy / Po Ammeters qty. 1
Metering Ammeters with selector switch Confirmed
( for capacitor line currents) qty. 1
MFM Yes/no Yes
Motor feeder
8
-
8/13/2019 11 KV MV Board.
9/10
Technical Data sheets
11kV MV Switch Board
Item Details/Description Unit Supplier
Motor feeder
9
-
8/13/2019 11 KV MV Board.
10/10
Technical Data sheets
11kV MV Switch Board
Item Details/Description Unit Supplier
General Location : Main Sub-station
Feeder Totally enclosed metal clad cubicle yes/no yes
Cubicle (separate technical data sheet)
rated current A As pe the requirement
Derated current A As pe the requirement
- rated voltage KV 11
- operating voltage KV 11
- short circuit capacity at operating voltage for KA 40
Switchgear Circuit breaker yes/no yes
(separate technical data sheet)
- rated current A As pe the requirement
-derated current at site conditions A 2500
Whether suitable for voltage and frequency variations
as given in Specifications yes/no yes
Earthing Earthing switch yes/no no
Protection , Voltage transformers qty. 3
metering, ( one for each bus section)
& Indications
Protections: As per SLD
O/C (Low set & high set) yes/no yes
E/F (Low set & high set) yes/no yes
Under voltage Protection yes/no yes
Trip circuit supervision yes/no yes
DC fail protection yes/no yes
High speed lock out Relay yes/no yes
Others :Indications: yes/no yes
( Enclose detailed list of indications provided )
Energy/pow Voltmeters with selector switch qty. 1
metering
Buscoupler
10