11 kv mv board

Upload: costea0028

Post on 04-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 11 KV MV Board.

    1/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details / Description Unit Supplier data

    1 11kV Switchboard Cubicle

    Make ABB/AREVA/SIEMENSType VCB

    Metal clad switchgear and control gear yes/no yes

    Compartmented switchgear and control gear yes/no yes

    - rated voltage kV 11

    - operating voltage kV 11

    Air insulated yes/no yes

    Draw-out type yes/no yes

    With automatic shutter ( for safety ) yes/no yes

    Separate compartment for :

    - circuit breaker yes/no yes

    - busbars yes/no yes

    - low voltage equipment yes/no yes- cable termination yes/no yes

    Pressure relief covers / Flaps yes/no yes

    Rear access necessary yes/no yes

    Cable connection from bottom yes/no yes

    Ample cabling space shall be provided for ease of

    cable connection / Termination

    yes/no yes

    Lockable service position for circuit breaker yes/no yes

    Lockable test position for circuit breaker yes/no yes

    Lockable isolated position for circuit breaker yes/no yes

    Circuit breaker floor mounted yes/no yes

    Cable earthing by earthing switch yes/no no

    Mechanical & Electrical safety interlocks for :- earthing switch yes/no no

    - test position yes/no yes

    - buscoupler & incomer * yes/no yes

    Type of enclosure & degree of protection IP IP42

    Thickness of sheet metal

    a) load bearing members mm 2

    b) Non load bearing members mm 2

    Door arrangement ( enclose details ) During detailed Engg

    Location of instruments & protection relays Metering chamber

    above CB chamberMax.height of instruments & protection relays

    from the round level

    mm During detailed Engg

    Overall dimension ( L x D x H ) & approx. weight mm / kg During detailed Engg

    a) Double/Single bus board B/C

    b) Double/Single bus board I/C

    c) Single bus board O/G ( Trafo Feeder )

    d) Single bus board O/G ( Motor Feeder )

    GA drawings enclosed yes/no no

    Space heaters with thermostat in all panels with

    suitable interlocks

    yes/no yes

    DC source for each switchboard AH As per BOQ

    2 Busbars

    Busbar and T-off connections :

    Page 1

  • 8/13/2019 11 KV MV Board.

    2/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details / Description Unit Supplier data

    - Copper yes/no Yes

    - Aluminium yes/no No

    - insulated yes/no No

    - Min clearance between

    a) Phase to Phase mm As per IECb) Phase to Ground mm As per IEC

    - Busbar size

    4000 A sq.mm

    2000A sq.mm

    1250A sq.mm

    500A sq.mm

    -Current density - for copper busbars A/sq.mm 1.2A/sq.mm

    Maximum temperature rise at rated full load

    currentabove site ambient temperature ( 48 deg C ) deg C 42 deg C

    Ground bus

    -material

    -one sec rating of ground bus KA 403 Current Transformers

    - Make

    -Type ( cast resin , bar primary ) yes/no yes

    -Service Indoor

    -Secondary current A 1

    -Transformation ratio as per SLD yes/no yes

    -Rated burden VA 15

    -Accuracy class

    a)Metering 0.5

    b)Protection 5P20

    suitable CTs to be provided to take care of

    additional burden due to KW transducers

    yes/no yes

    - Class of insulation

    -Power frequency & Impulse withstand KV 28/75

    - short time thermal rating for 1 sec KA min. 31.5

    4 Voltage Transformers

    - Make

    -Type

    -Service

    -Transformation ratio as per SLD yes/no yes

    -Rated burden (for line PT's) VA 100

    -Accuracy class 1.0/3P

    -Power frequency & Impulse withstand KV 28/75

    -Whether withdrawable type yes/no yes

    -HT & LT fuses provided yes/no yes

    5 Relays

    Solid state relays equivalent to mentioned in SLD

    with profibus communication facility

    Yes/noYes

    6 Meters

    Ammeter

    -Make

    -Type

    -Size mmxmm 90 x 90

    -Range

    During detailed Engg

    Page 2

  • 8/13/2019 11 KV MV Board.

    3/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details / Description Unit Supplier data

    -Reference standard

    Voltmeter

    -Make

    -Type

    -Size mmxmm 90 x 90-Range

    -Reference standard

    MW meter

    -Make

    -Type

    -Size mmxmm 90 x 90

    -Range

    -Reference standard

    KWH meter

    -Make

    -Type

    -Size mmxmm 90 x 90

    -Range-Reference standard

    Power factor meter

    -Make

    -Type

    -Size mmxmm During detailed Engg

    -Range

    -Reference standard

    KW Transducer

    -Make

    -Type

    -Size mmxmm During detailed Engg

    -Range-Reference standard

    Page 3

  • 8/13/2019 11 KV MV Board.

    4/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details/Description Unit Supplier

    General Make As per Make listType Vacuum

    Rated voltage kV 11

    Operating voltage kV 11

    Frequency Hz 50

    Rated short circuit breaking current KA 40kA

    Rated short time current (1 sec) KA 40kA

    Total interrupting time ( measured in cycles

    from trip coil energisation ) cycles

  • 8/13/2019 11 KV MV Board.

    5/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details/Description Unit Supplier

    Circuit Breaker

    measures

    No-voltage release (control voltage) yes/no No Volt Coil shall be

    considered for only HT

    motor feeders.

    Interlocks to :- prevent moving of C.B. in closed position yes/no yes

    - allow closing of C.B. in defined position yes/no yes

    Maintanence C.B. operation in racked-out/test/isolated

    position yes/no yes

    Additional Switching status indicator yes/no yesaccessories Operation counter yes/no yes

    No. of auxiliary contacts

    a) Normally closed nos. 6

    b) Normally open nos. 6

    c) Whether convertible type yes/no No

    5

  • 8/13/2019 11 KV MV Board.

    6/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details/Description Unit Supplier

    General Location : Main Sub-station

    & Load Sub-station

    Feeder Totally enclosed metal clad cubicle yes/no yes

    cubicle (separate technical data sheet)

    rated current of busbars considering deration due

    to site conditions- for Double bus I/C A Not applicable

    - for Single bus I/C A As per SLD- rated voltage KV 11

    - operating voltage KV 11

    - short circuit capacity at operating voltage for 3 KA 40kA

    Switchgear Circuit breaker yes/no yes

    (separate technical data sheet)

    for single bus I/C

    - for Double bus I/C A Not applicable

    - for Single bus I/C A As per SLD

    Whether suitable for voltage and frequency

    variations as iven in s ecifications

    yes/no yes

    Surge diverter Surge diverter with counter yes/no No

    Earthing Earthing switch yes/no No

    Protection , Current transformers qty. As per SLD

    metering, Voltage transformers qty. As per SLD

    & Indications

    Protections: As per the spec

    Indications: yes/no yes

    ( Enclose detailed list of indications provided )

    Energy / PowerAmmeters with selector switch qty. 1

    Metering Voltmeter with selector switch qty. 1

    Power factor meter yes/no

    kWh meter yes/no

    kW - tranducer with isolated 4-20 mA yes/no No

    Incoming Feeder

    On MFM

    6

  • 8/13/2019 11 KV MV Board.

    7/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details/Description Unit Supplier

    GeneralLocation : Crusher, RM, Kiln & Cement Mill

    SubstationFeeders

    : Single bus board

    Feeder Totally enclosed metal clad cubicle yes/no yes

    cubicle (separate technical data sheet)

    rated current (Contactor feeder) A Not Applicable

    - rated voltage KV -- operating voltage KV -

    short circuit capacity at operating voltage for 1

    sec

    KA -

    Switchgear Contactor feeder with fuses yes/no VCB Offered

    (separate technical data sheet)

    - rated current A As per the

    requirement

    - rated voltage KV 11

    - operating voltage KV 11

    short circuit capacity at operating voltage for KA 40kAWhether suitable for voltage and frequency

    variations as iven in s ecifications

    yes/no yes

    Earthing Earthing switch yes/no no

    Protection, Current transformers, output side qty. As per SLD

    metering, & Indicatio Protections: As per the spec

    Indications: yes/no yes

    ( Enclose detailed list of indications including

    transformer faults provided, Annunciator

    be for transformer faults )

    Ammeters with selector switch qty. 1

    Energy / Power kWh-meter yes/no MFM

    Metering Metering: - unbalanced load yes/no no

    - accuracy class % -

    kW-transmitter with 4-20 mA output yes/no applicable for

    motor feeder

    Transformer Feeder

    7

  • 8/13/2019 11 KV MV Board.

    8/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details/Description Unit Supplier

    MakeABB/AREVA/SIEME

    NS

    General Location : Main Sub-station

    Feed to : 11kV/MV motors

    Feeders

    : Single bus board

    Feeder Totally enclosed metal clad cubicle yes/no yes

    cubicle (separate technical data sheet)

    rated current (Contactor feeder) A Not Applicable

    Derated current (Contactor feeder) A Not Applicablerated current (Breaker feeder) A As per Tender

    Derated current (Breaker feeder) A As per Tender

    - rated voltage KV 11

    - operating voltage KV 11

    - short circuit capacity at operating voltage for KA 40kA

    Switchgear Contactor and VCB/SF6 Breakers VCB

    (separate technical data sheet) yes/no yes

    - rated current A As per Tender

    - derated current at site conditions A As per Tender

    - rated current A -

    - derated current at site conditions A -

    Whether suitable for voltage and frequency variations

    as given in Specifications yes/no yes

    Surge divert Surge diverter with counter yes/no without counter

    Earthing Earthing switch yes/no no

    Protection , Current transformers, output side qty. As per Requirement

    metering, Current transformers for capacitor line current qty. As per Requirement

    & Indications

    Protections:

    Motor protection (microprocessor based) yes/no As per Requirement

    Trip circuit supervision yes/no As per Requirement

    High speed lock out Relay yes/no As per Requirement

    Antipumping protection yes/no As per Requirement

    Others :

    Indications: yes/no As per Requirement

    ( Enclose detailed list of indications provided )

    Energy / Po Ammeters qty. 1

    Metering Ammeters with selector switch Confirmed

    ( for capacitor line currents) qty. 1

    MFM Yes/no Yes

    Motor feeder

    8

  • 8/13/2019 11 KV MV Board.

    9/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details/Description Unit Supplier

    Motor feeder

    9

  • 8/13/2019 11 KV MV Board.

    10/10

    Technical Data sheets

    11kV MV Switch Board

    Item Details/Description Unit Supplier

    General Location : Main Sub-station

    Feeder Totally enclosed metal clad cubicle yes/no yes

    Cubicle (separate technical data sheet)

    rated current A As pe the requirement

    Derated current A As pe the requirement

    - rated voltage KV 11

    - operating voltage KV 11

    - short circuit capacity at operating voltage for KA 40

    Switchgear Circuit breaker yes/no yes

    (separate technical data sheet)

    - rated current A As pe the requirement

    -derated current at site conditions A 2500

    Whether suitable for voltage and frequency variations

    as given in Specifications yes/no yes

    Earthing Earthing switch yes/no no

    Protection , Voltage transformers qty. 3

    metering, ( one for each bus section)

    & Indications

    Protections: As per SLD

    O/C (Low set & high set) yes/no yes

    E/F (Low set & high set) yes/no yes

    Under voltage Protection yes/no yes

    Trip circuit supervision yes/no yes

    DC fail protection yes/no yes

    High speed lock out Relay yes/no yes

    Others :Indications: yes/no yes

    ( Enclose detailed list of indications provided )

    Energy/pow Voltmeters with selector switch qty. 1

    metering

    Buscoupler

    10