    LAHMEYER INTERNATIONAL

    GOVERNMENT OF THE REPUBLIC OF THE SUDANMINISTRY OF IRRIGATION AND WATER RESOURCES

    MEROWE DAM PROJECT IMPLEMENTATION UNIT 

    MEROWE DAM PROJECT 10 x 140MVA

    CONTRACTS 3A, 3B, 3C, 3E

    ENGINEER:CONTRACTOR: 

    OPERATING & MAINTENANCE MANUAL

    SANITARY WASTE WATER TREATMENT SYSTEMCONTROLLER CABINET, TECHNICAL LEAFLETS, UPS & UNIT DISPLAY -SEO-

    (92SEOW01DL, 92SEO001AR)

    SCALE1/1

    Subcontractor:

    INTERNAL USE

    Power EnvironmentHydro

    REV

     ASH/SH END

    1/

    N of SH AHS MRW00SEO.OM.109.06 

    Ce document propriété de ALSTOM ne doit pas être utilisé, copié ou communiqué à des tiers sans son autorisation

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 1 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    2/415

    CHAPTER

    B) List of Illustrations 4

    C) Introduction: 5

    C1)   General Description of Equipment ………… 6

    C2)   Brief Description of Equipment Use ………… 7

    C3)   Definitions and Technical Terms Used ………… 9

    C4)   List of items used ………… 10

    D) Detailed Description of Equipment

    E) Operating Principles and Characteristics

      ● UNINTERRUPTABLE POWER SUPPLY  (UPS)   …………   12

      ‐ SAFETY STANDARDS   …………   15

      ‐GENERAL DESCRIPTION / OPERATION   …………   16

      ‐UNPACKING & INSTALLATION   …………   18

      ‐ CONFIGURATION & START UP   …………   21

      ‐ DISPLAYS & CONTROLS   …………   22

      ‐USE OF SIGNAL RELAY   …………   26

      ‐ TECHNICAL DATA   …………   27 

      ‐ TROUBLESHOOTING   …………   28

      ● CONTROL CUBICLE EQUIPMENT DRAWING ‐ SANITARY WASTE WATER TREATMENT SYS.   …………   29

      ● ELECTRICAL DIAGRAM ‐ SANITARY WASTE WATER TREATMENT SYS.   …………   39

      ● TECHNICAL LEAFLETS   …………   65

      ‐ CIRCUIT BREAKERS   …………   66

      ‐ CONTROL & SIGNALLING UNITS   …………   88

      ‐ POWER DISTRIBUTION  …………   138

      ‐ CURRENT TRANSFORMER   …………   140

      ‐MOTOR STARTERS   …………   153

      ‐ CONTACTOR CONTROL UNITS   …………   169

      ‐ BEACONS   …………   176

      ‐ RELAYS   …………   183

      ‐MISCELLANEOUS COMPONENTS   …………   194

    F) Operating Instructions

    G) Testing and Adjustment  ● UNIT DISPLAY OPERATOR'S MANUAL ‐ MEGALIS XBT  R410   …………   209

      ● UNIT DISPLAY USER MANUAL  …………   216

    PAGE

    ……………

    ……………

    ……… 11

    ……… 208

    OPERATION & MAINTENANCE MANUAL

      AHS-MRW00SEO.OM.109.06 

     REVISION: A Rev. Date: 18.04.2011

      page: 2 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    3/415

    CHAPTER

    H) Maintenance Instructions: 407

    H1)   Preventive Maintenance ………… 408

    H2)   Repair and Adjustment ………… 409

      ● MAINTENANCE INSTRUCTIONS:  UPS SYSTEM …………   410 

    H3)   Spare Parts Lists ………… 412

    H4)   Special Tools Lists ………… 414

    H5)   List of Suppliers ………… 415

    J)  As Built Drawings ………… 416

    ……………

    OPERATION & MAINTENANCE MANUAL

    PAGE

      AHS-MRW00SEO.OM.109.06 

     REVISION: A Rev. Date: 18.04.2011

      page: 3 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    4/415

     

    B) LIST OF ILLUSTRATIONS

    SITE TEST REPORTSSEO – DOMESTIC SEWAGE – SANITARY

    WASTEWATER TREATMENT SYSTEM

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 4 of 416 

    http://seo_site%20test%20reports/00_00SEO_TABLE%20OF%20CONTENTS.xlshttp://seo_site%20test%20reports/00_00SEO_TABLE%20OF%20CONTENTS.xls

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    5/415

     

    C) INTRODUCTION

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 5 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    6/415

     

    C1) BRIEF DESCRIPTION OF EQUIPMENT

    CONTROLLER CABINET ,UNINTERRUPTED POWER SUPPLY,DISPLAY UNIT

    LIST OF MAIN EQUIPMENT:

    REFERENCE DESCRIPTION MODEL SUPPLIER

    92SEOW01DLUINTERREUPTED POWER SUPPLY

    (UPS)ENT-TW15

    (800-2000VA)MANUF: SOCOMECSICONSUPPLIER: HYTEC

    --- UNIT DISPLAY XBTR410  MANUF: MAGELIS(SCHNEIDER)SUPPLIER: HYTEC

    92SEO001AR CABINET CONTROLLER --- SUPPLIER: HYTEC

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 6 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    7/415

     

    C2) DESCRIPTION OF USE OF EQUIPMENT

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 7 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    8/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 8 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    9/415

     

    C3) DEFINITION OF TECHNICAL TERMS

    UPS: The main purpose of the UPS is to protect sensitive and critical equipment items fromthe electrical disturbances that can compromise operation. Black-outs, brown-outs,variations of voltage and frequency, lightening, electrostatic discharges and rapidovervoltages are phenomena found in all office and industrial environments and which causehardware damage and data losses.

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 9 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    10/415

     C4) List of Items Used

    UNIT SYS. NUM TYPE DESIGNATION SUPP. ROOM

    92 SEO 001 AR CABINET CONTROLER AHS STP

    92 SEO 001 DL UNINTERRUPTIBLE POWER SUPPLY AHS STP

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 10 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    11/415

     

    D) DETAILED DESCRIPTION&

    E) OPERATING PRINCIPLES ANDCHARACTERISTICS

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 11 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    12/415

     

    UNINTERRUPTIBLE POWERSUPPLY

    UPS - 92SEO001DL

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 12 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    13/415

     

    992-11803.11. 180/201 /A 

    5. MISCELLANEOUS

    5.1. Uninterruptible power supply 92SEOW01DL

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 13 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    14/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    15/415

     

    992-11803.11. 182/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 15 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    16/415

     

    992-11803.11. 183/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 16 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    17/415

     

    992-11803.11. 184/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 17 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    18/415

     

    992-11803.11. 185/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 18 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    19/415

     

    992-11803.11. 186/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 19 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    20/415

     

    992-11803.11. 187/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 20 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    21/415

     

    992-11803.11. 188/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 21 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    22/415

     

    992-11803.11. 189/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 22 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    23/415

     

    992-11803.11. 190/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 23 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    24/415

     

    992-11803.11. 191/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 24 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    25/415

     

    992-11803.11. 192/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 25 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    26/415

     

    992-11803.11. 193/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 26 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    27/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    28/415

     

    992-11803.11. 195/201 /A  AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 28 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    29/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    30/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    31/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    32/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    33/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    34/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    35/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    36/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    37/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    38/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    39/415

     

    SANITARY WASTE WATER TREATMENT SYSTEM

    ELECTRICAL DIAGRAM

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 39 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    40/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    41/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    42/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    43/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    44/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    45/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    46/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    47/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    48/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    49/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    50/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    51/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    52/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    53/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    54/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    55/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    56/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    57/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    58/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    59/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    60/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    61/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    62/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    63/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    64/415

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    65/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    66/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    67/415

       T   h  e

       i  n   f  o  r  m  a

       t   i  o  n  p  r  o  v

       i   d  e

       d   i  n

       t   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n  c  o  n

       t  a   i  n  s  g  e  n  e  r  a

       l   d  e  s  c  r   i  p

       t   i  o  n  s  a  n

       d   /  o  r

       t  e  c

       h  n

       i  c  a

       l  c

       h  a  r  a  c

       t  e  r   i  s

       t   i  c  s  o

       f   t   h  e  p  e  r   f  o  r  m  a  n  c  e  o

       f   t   h  e  p  r  o

       d

      u  c

       t  s  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

       T   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n

       i  s  n  o

       t   i  n

       t  e  n

       d  e

       d  a  s  a  s  u

       b  s

       t   i   t  u   t  e   f  o  r  a  n

       d   i  s  n  o

       t   t  o   b  e  u  s  e

       d   f  o  r

       d  e

       t  e  r  m

       i  n   i  n  g  s  u

       i   t  a

       b   i   l   i   t  y  o  r  r  e

       l   i  a

       b   i   l   i   t  y  o

       f   t   h  e  s  e  p  r  o

       d  u  c

       t  s   f  o  r  s  p  e  c

       i   f   i  c  u  s  e  r  a  p  p

       l   i  c  a

       t   i  o  n  s .

       I   t   i  s   t   h  e

       d  u

       t  y  o

       f  a  n  y  s  u  c

       h  u  s  e  r  o  r

       i  n   t  e  g  r  a

       t  o  r

       t  o  p  e  r   f  o  r  m

        t   h  e  a  p  p  r  o  p  r   i  a

       t  e  a  n

       d  c  o  m  p

       l  e   t  e

      r   i  s

       k  a  n  a

       l  y  s

       i  s ,

      e  v  a

       l  u  a

       t   i  o  n  a  n

       d   t  e  s

       t   i  n  g  o

       f   t   h  e  p  r  o

       d  u  c

       t  s  w

       i   t   h

      r  e  s  p  e  c

       t   t  o   t   h  e  r  e

       l  e  v  a  n

       t  s  p  e  c

       i   f   i  c  a  p  p

       l   i  c  a

       t   i  o  n  o  r  u  s  e

       t   h  e  r  e  o

       f .

       N  e

       i   t   h  e  r

       S  c

       h  n  e

       i   d  e  r

       E   l  e  c

       t  r   i  c   I  n

       d  u  s

       t  r   i  e  s

       S   A   S  n  o  r  a  n  y  o

       f   i   t  s  a

       f   f   i   l   i  a   t  e  s  o  r  s  u

       b  s

       i   d   i  a  r   i  e  s  s

       h  a

       l   l   b  e  r  e  s  p  o  n  s

       i   b   l  e  o  r

       l   i  a

       b   l  e   f  o  r  m

       i  s  u  s  e  o

       f   t   h  e

       i  n   f  o  r  m  a

       t   i  o  n  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

    Mon Oct 11 10:03:43 EDT 2010

    1

    Product data sheetCharacteristics

    24186miniature circuit breaker Multi 9 - C60N - 1 pole

    + N - 4 A - C curve

    Certifications and standards

    Standards EN 60898

    IEC 60947-2

    Compatibility

    Comb busbar distribution block compatibility NO

    Earth-leakage protection Separate block

    Product compatibility C60 accessories

    C60 auxiliary

    Connections

    Connections - terminals Tunnel type terminals 25 mm² rigid

    Tunnel type terminals 16 mm² flexible

    Electrical

    [In] rated current 4 A 30 °C

    [Ue] rated operational voltage 12...440 V AC 50/60 Hz

    [Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2

    [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2

    Breaking capacity 20 kA Icu IEC 60947-2 130 V AC 50/60 Hz

    10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz

    3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz

    15 kA Icu IEC 60947-2 60 V DC 1P

    6 kA Icn EN 60898 230/400 V AC 50/60 Hz

    Magnetic tripping limit 5...10 x In

    Network frequency 50/60 Hz

    Environment

     Ambient air temperature for operation -25...60 °C

     Ambient air temperature for storage -40...70 °C

    Operating altitude 2000 m

    Relative humidity 95 % 55 °C

    Tropicalisation 2 IEC 60068-1

    RoHS EUR conformity date 0643

    RoHS EUR status Compliant

    Functional

    Contact position indicator Yes

    Control type Toggle

    Limitation class 3 IEC 60947-2

    Local signalling ON/OFF indication 

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 67 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    68/415

    2

    Installation

    Mounting mode Fixed

    Mounting support 35 mm symmetrical DIN rail

    Performance

    [Ics] rated service breaking capacity 2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz

    6 kA EN 60898 230/400 V AC 50/60 Hz

    7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz15 kA IEC 60947-2 130 V AC 50/60 Hz

    Mechanical durability 20000 cycles

    Physical characteristics

    9 mm pitches 4

    Depth 73 mm

    Height 81 mm

    Product weight 0,12 kg

    Tightening torque 2 N.m upside power circuit

    2 N.m downside

    Width 36 mm

    Poles descriptions

    Neutral position Left

    Number of protected poles 1

    Poles description 1P + N

    Product identification

    Device short name C60N

    Range of product C60

    Usage / Application

    Circuit breaker application Distribution

    Curve code C

    Network type AC

    DC

    Suitability for isolation Yes IEC 60947-2

    Trip unit technology Thermal-magnetic

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 68 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    69/415

       T   h  e

       i  n   f  o  r  m  a

       t   i  o  n  p  r  o  v

       i   d  e

       d   i  n

       t   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n  c  o  n

       t  a   i  n  s  g  e  n  e  r  a

       l   d  e  s  c  r   i  p

       t   i  o  n  s  a  n

       d   /  o  r

       t  e  c

       h  n

       i  c  a

       l  c

       h  a  r  a  c

       t  e  r   i  s

       t   i  c  s  o

       f   t   h  e  p  e  r   f  o  r  m  a  n  c  e  o

       f   t   h  e  p  r  o

       d

      u  c

       t  s  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

       T   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n

       i  s  n  o

       t   i  n

       t  e  n

       d  e

       d  a  s  a  s  u

       b  s

       t   i   t  u   t  e   f  o  r  a  n

       d   i  s  n  o

       t   t  o   b  e  u  s  e

       d   f  o  r

       d  e

       t  e  r  m

       i  n   i  n  g  s  u

       i   t  a

       b   i   l   i   t  y  o  r  r  e

       l   i  a

       b   i   l   i   t  y  o

       f   t   h  e  s  e  p  r  o

       d  u  c

       t  s   f  o  r  s  p  e  c

       i   f   i  c  u  s  e  r  a  p  p

       l   i  c  a

       t   i  o  n  s .

       I   t   i  s   t   h  e

       d  u

       t  y  o

       f  a  n  y  s  u  c

       h  u  s  e  r  o  r

       i  n   t  e  g  r  a

       t  o  r

       t  o  p  e  r   f  o  r  m

        t   h  e  a  p  p  r  o  p  r   i  a

       t  e  a  n

       d  c  o  m  p

       l  e   t  e

      r   i  s

       k  a  n  a

       l  y  s

       i  s ,

      e  v  a

       l  u  a

       t   i  o  n  a  n

       d   t  e  s

       t   i  n  g  o

       f   t   h  e  p  r  o

       d  u  c

       t  s  w

       i   t   h

      r  e  s  p  e  c

       t   t  o   t   h  e  r  e

       l  e  v  a  n

       t  s  p  e  c

       i   f   i  c  a  p  p

       l   i  c  a

       t   i  o  n  o  r  u  s  e

       t   h  e  r  e  o

       f .

       N  e

       i   t   h  e  r

       S  c

       h  n  e

       i   d  e  r

       E   l  e  c

       t  r   i  c   I  n

       d  u  s

       t  r   i  e  s

       S   A   S  n  o  r  a  n  y  o

       f   i   t  s  a

       f   f   i   l   i  a   t  e  s  o  r  s  u

       b  s

       i   d   i  a  r   i  e  s  s

       h  a

       l   l   b  e  r  e  s  p  o  n  s

       i   b   l  e  o  r

       l   i  a

       b   l  e   f  o  r  m

       i  s  u  s  e  o

       f   t   h  e

       i  n   f  o  r  m  a

       t   i  o  n  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

    Mon Oct 11 10:09:27 EDT 2010

    1

    Product data sheetCharacteristics

    24187miniature circuit breaker Multi 9 - C60N - 1 pole

    + N - 6 A - C curve

    Certifications and standards

    Standards EN 60898

    IEC 60947-2

    Compatibility

    Comb busbar distribution block compatibility NO

    Earth-leakage protection Separate block

    Product compatibility C60 accessories

    C60 auxiliary

    Connections

    Connections - terminals Tunnel type terminals 16 mm² flexible

    Tunnel type terminals 25 mm² rigid

    Electrical

    [In] rated current 6 A 30 °C

    [Ue] rated operational voltage 12...440 V AC 50/60 Hz

    [Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2

    [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2

    Breaking capacity 20 kA Icu IEC 60947-2 130 V AC 50/60 Hz

    10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz

    3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz

    15 kA Icu IEC 60947-2 60 V DC 1P

    6 kA Icn EN 60898 230/400 V AC 50/60 Hz

    Magnetic tripping limit 5...10 x In

    Network frequency 50/60 Hz

    Environment

     Ambient air temperature for operation -25...60 °C

     Ambient air temperature for storage -40...70 °C

    Operating altitude 2000 m

    Relative humidity 95 % 55 °C

    Tropicalisation 2 IEC 60068-1

    RoHS EUR conformity date 0643

    RoHS EUR status Compliant

    Functional

    Contact position indicator Yes

    Control type Toggle

    Limitation class 3 IEC 60947-2

    Local signalling ON/OFF indication 

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 69 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    70/415

    2

    Installation

    Mounting mode Fixed

    Mounting support 35 mm symmetrical DIN rail

    Performance

    [Ics] rated service breaking capacity 15 kA IEC 60947-2 130 V AC 50/60 Hz

    7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz

    2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz6 kA EN 60898 230/400 V AC 50/60 Hz

    Mechanical durability 20000 cycles

    Physical characteristics

    9 mm pitches 4

    Depth 73 mm

    Height 81 mm

    Product weight 0,12 kg

    Tightening torque 2 N.m upside power circuit

    2 N.m downside

    Width 36 mm

    Poles descriptions

    Neutral position Left

    Number of protected poles 1

    Poles description 1P + N

    Product identification

    Device short name C60N

    Range of product C60

    Usage / Application

    Circuit breaker application Distribution

    Curve code C

    Network type AC

    DC

    Suitability for isolation Yes IEC 60947-2

    Trip unit technology Thermal-magnetic

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 70 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    71/415

       T   h  e

       i  n   f  o  r  m  a

       t   i  o  n  p  r  o  v

       i   d  e

       d   i  n

       t   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n  c  o  n

       t  a   i  n  s  g  e  n  e  r  a

       l   d  e  s  c  r   i  p

       t   i  o  n  s  a  n

       d   /  o  r

       t  e  c

       h  n

       i  c  a

       l  c

       h  a  r  a  c

       t  e  r   i  s

       t   i  c  s  o

       f   t   h  e  p  e  r   f  o  r  m  a  n  c  e  o

       f   t   h  e  p  r  o

       d

      u  c

       t  s  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

       T   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n

       i  s  n  o

       t   i  n

       t  e  n

       d  e

       d  a  s  a  s  u

       b  s

       t   i   t  u   t  e   f  o  r  a  n

       d   i  s  n  o

       t   t  o   b  e  u  s  e

       d   f  o  r

       d  e

       t  e  r  m

       i  n   i  n  g  s  u

       i   t  a

       b   i   l   i   t  y  o  r  r  e

       l   i  a

       b   i   l   i   t  y  o

       f   t   h  e  s  e  p  r  o

       d  u  c

       t  s   f  o  r  s  p  e  c

       i   f   i  c  u  s  e  r  a  p  p

       l   i  c  a

       t   i  o  n  s .

       I   t   i  s   t   h  e

       d  u

       t  y  o

       f  a  n  y  s  u  c

       h  u  s  e  r  o  r

       i  n   t  e  g  r  a

       t  o  r

       t  o  p  e  r   f  o  r  m

        t   h  e  a  p  p  r  o  p  r   i  a

       t  e  a  n

       d  c  o  m  p

       l  e   t  e

      r   i  s

       k  a  n  a

       l  y  s

       i  s ,

      e  v  a

       l  u  a

       t   i  o  n  a  n

       d   t  e  s

       t   i  n  g  o

       f   t   h  e  p  r  o

       d  u  c

       t  s  w

       i   t   h

      r  e  s  p  e  c

       t   t  o   t   h  e  r  e

       l  e  v  a  n

       t  s  p  e  c

       i   f   i  c  a  p  p

       l   i  c  a

       t   i  o  n  o  r  u  s  e

       t   h  e  r  e  o

       f .

       N  e

       i   t   h  e  r

       S  c

       h  n  e

       i   d  e  r

       E   l  e  c

       t  r   i  c   I  n

       d  u  s

       t  r   i  e  s

       S   A   S  n  o  r  a  n  y  o

       f   i   t  s  a

       f   f   i   l   i  a   t  e  s  o  r  s  u

       b  s

       i   d   i  a  r   i  e  s  s

       h  a

       l   l   b  e  r  e  s  p  o  n  s

       i   b   l  e  o  r

       l   i  a

       b   l  e   f  o  r  m

       i  s  u  s  e  o

       f   t   h  e

       i  n   f  o  r  m  a

       t   i  o  n  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

    Mon Oct 11 10:00:25 EDT 2010

    1

    Product data sheetCharacteristics

    24188miniature circuit breaker Multi 9 - C60N - 1 pole

    + N - 10 A - C curve

    Certifications and standards

    Standards EN 60898

    IEC 60947-2

    Compatibility

    Comb busbar distribution block compatibility NO

    Earth-leakage protection Separate block

    Product compatibility C60 accessories

    C60 auxiliary

    Connections

    Connections - terminals Tunnel type terminals 16 mm² flexible

    Tunnel type terminals 25 mm² rigid

    Electrical

    [In] rated current 10 A 30 °C

    [Ue] rated operational voltage 12...440 V AC 50/60 Hz

    [Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2

    [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2

    Breaking capacity 15 kA Icu IEC 60947-2 60 V DC 1P

    20 kA Icu IEC 60947-2 130 V AC 50/60 Hz

    6 kA Icn EN 60898 230/400 V AC 50/60 Hz

    10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz

    3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz

    Magnetic tripping limit 5...10 x In

    Network frequency 50/60 Hz

    Environment

     Ambient air temperature for operation -25...60 °C

     Ambient air temperature for storage -40...70 °C

    Operating altitude 2000 m

    Relative humidity 95 % 55 °C

    Tropicalisation 2 IEC 60068-1

    RoHS EUR conformity date 0651

    RoHS EUR status Compliant

    Functional

    Contact position indicator Yes

    Control type Toggle

    Limitation class 3 IEC 60947-2

    Local signalling ON/OFF indication 

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 71 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    72/415

    2

    Installation

    Mounting mode Fixed

    Mounting support 35 mm symmetrical DIN rail

    Performance

    [Ics] rated service breaking capacity 15 kA IEC 60947-2 130 V AC 50/60 Hz

    7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz

    2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz6 kA EN 60898 230/400 V AC 50/60 Hz

    Mechanical durability 20000 cycles

    Physical characteristics

    9 mm pitches 4

    Depth 73 mm

    Height 81 mm

    Product weight 0,12 kg

    Tightening torque 2 N.m upside power circuit

    2 N.m downside

    Width 36 mm

    Poles descriptions

    Neutral position Left

    Number of protected poles 1

    Poles description 1P + N

    Product identification

    Device short name C60N

    Range of product C60

    Usage / Application

    Circuit breaker application Distribution

    Curve code C

    Network type AC

    DC

    Suitability for isolation Yes IEC 60947-2

    Trip unit technology Thermal-magnetic

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 72 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    73/415

       T   h  e

       i  n   f  o  r  m  a

       t   i  o  n  p  r  o  v

       i   d  e

       d   i  n

       t   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n  c  o  n

       t  a   i  n  s  g  e  n  e  r  a

       l   d  e  s  c  r   i  p

       t   i  o  n  s  a  n

       d   /  o  r

       t  e  c

       h  n

       i  c  a

       l  c

       h  a  r  a  c

       t  e  r   i  s

       t   i  c  s  o

       f   t   h  e  p  e  r   f  o  r  m  a  n  c  e  o

       f   t   h  e  p  r  o

       d

      u  c

       t  s  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

       T   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n

       i  s  n  o

       t   i  n

       t  e  n

       d  e

       d  a  s  a  s  u

       b  s

       t   i   t  u   t  e   f  o  r  a  n

       d   i  s  n  o

       t   t  o   b  e  u  s  e

       d   f  o  r

       d  e

       t  e  r  m

       i  n   i  n  g  s  u

       i   t  a

       b   i   l   i   t  y  o  r  r  e

       l   i  a

       b   i   l   i   t  y  o

       f   t   h  e  s  e  p  r  o

       d  u  c

       t  s   f  o  r  s  p  e  c

       i   f   i  c  u  s  e  r  a  p  p

       l   i  c  a

       t   i  o  n  s .

       I   t   i  s   t   h  e

       d  u

       t  y  o

       f  a  n  y  s  u  c

       h  u  s  e  r  o  r

       i  n   t  e  g  r  a

       t  o  r

       t  o  p  e  r   f  o  r  m

        t   h  e  a  p  p  r  o  p  r   i  a

       t  e  a  n

       d  c  o  m  p

       l  e   t  e

      r   i  s

       k  a  n  a

       l  y  s

       i  s ,

      e  v  a

       l  u  a

       t   i  o  n  a  n

       d   t  e  s

       t   i  n  g  o

       f   t   h  e  p  r  o

       d  u  c

       t  s  w

       i   t   h

      r  e  s  p  e  c

       t   t  o   t   h  e  r  e

       l  e  v  a  n

       t  s  p  e  c

       i   f   i  c  a  p  p

       l   i  c  a

       t   i  o  n  o  r  u  s  e

       t   h  e  r  e  o

       f .

       N  e

       i   t   h  e  r

       S  c

       h  n  e

       i   d  e  r

       E   l  e  c

       t  r   i  c   I  n

       d  u  s

       t  r   i  e  s

       S   A   S  n  o  r  a  n  y  o

       f   i   t  s  a

       f   f   i   l   i  a   t  e  s  o  r  s  u

       b  s

       i   d   i  a  r   i  e  s  s

       h  a

       l   l   b  e  r  e  s  p  o  n  s

       i   b   l  e  o  r

       l   i  a

       b   l  e   f  o  r  m

       i  s  u  s  e  o

       f   t   h  e

       i  n   f  o  r  m  a

       t   i  o  n  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

    Mon Oct 11 10:02:23 EDT 2010

    1

    Product data sheetCharacteristics

    24189miniature circuit breaker Multi 9 - C60N - 1 pole

    + N - 16 A - C curve

    Certifications and standards

    Standards EN 60898

    IEC 60947-2

    Compatibility

    Comb busbar distribution block compatibility NO

    Earth-leakage protection Separate block

    Product compatibility C60 accessories

    C60 auxiliary

    Connections

    Connections - terminals Tunnel type terminals 16 mm² flexible

    Tunnel type terminals 25 mm² rigid

    Electrical

    [In] rated current 16 A 30 °C

    [Ue] rated operational voltage 12...440 V AC 50/60 Hz

    [Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2

    [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2

    Breaking capacity 20 kA Icu IEC 60947-2 130 V AC 50/60 Hz

    10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz

    3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz

    15 kA Icu IEC 60947-2 60 V DC 1P

    6 kA Icn EN 60898 230/400 V AC 50/60 Hz

    Magnetic tripping limit 5...10 x In

    Network frequency 50/60 Hz

    Environment

     Ambient air temperature for operation -25...60 °C

     Ambient air temperature for storage -40...70 °C

    Operating altitude 2000 m

    Relative humidity 95 % 55 °C

    Tropicalisation 2 IEC 60068-1

    RoHS EUR conformity date 0651

    RoHS EUR status Compliant

    Functional

    Contact position indicator Yes

    Control type Toggle

    Limitation class 3 IEC 60947-2

    Local signalling ON/OFF indication 

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 73 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    74/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    75/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    76/415

    2

    Installation

    Mounting mode Fixed

    Mounting support 35 mm symmetrical DIN rail

    Performance

    [Ics] rated service breaking capacity 15 kA IEC 60947-2 130 V AC 50/60 Hz

    7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz

    2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz6 kA EN 60898 230/400 V AC 50/60 Hz

    Mechanical durability 20000 cycles

    Physical characteristics

    9 mm pitches 4

    Depth 73 mm

    Height 81 mm

    Product weight 0,12 kg

    Tightening torque 3,5 N.m upside power circuit

    3,5 N.m downside

    Width 36 mm

    Poles descriptions

    Neutral position Left

    Number of protected poles 1

    Poles description 1P + N

    Product identification

    Device short name C60N

    Range of product C60

    Usage / Application

    Circuit breaker application Distribution

    Curve code C

    Network type AC

    DC

    Suitability for isolation Yes IEC 60947-2

    Trip unit technology Thermal-magnetic

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 76 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    77/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    78/415

    2

    Functional

    Contact position indicator Yes

    Control type Toggle

    Limitation class 3 IEC 60947-2

    Local signalling ON/OFF indication

    Installation

    Mounting mode Fixed

    Mounting support 35 mm symmetrical DIN rail

    Performance

    [Ics] rated service breaking capacity 7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz

    3,75 kA IEC 60947-2 400...415 V AC 50/60 Hz

    2,25 kA IEC 60947-2 440 V AC 50/60 Hz

    6 kA EN 60898 230/400 V AC 50/60 Hz

    Mechanical durability 20000 cycles

    Physical characteristics

    9 mm pitches 6

    Depth 73 mm

    Height 81 mm

    Product weight 0,36 kg

    Tightening torque 2 N.m upside power circuit

    2 N.m downside

    Width 54 mm

    Poles descriptions

    Number of protected poles 3

    Poles description 3P

    Product identification

    Device short name C60N

    Range of product C60

    Usage / Application

    Circuit breaker application Distribution

    Curve code C

    Network type AC

    DC

    Suitability for isolation Yes IEC 60947-2

    Trip unit technology Thermal-magnetic

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 78 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    79/415

       T   h  e

       i  n   f  o  r  m  a

       t   i  o  n  p  r  o  v

       i   d  e

       d   i  n

       t   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n  c  o  n

       t  a   i  n  s  g  e  n  e  r  a

       l   d  e  s  c  r   i  p

       t   i  o  n  s  a  n

       d   /  o  r

       t  e  c

       h  n

       i  c  a

       l  c

       h  a  r  a  c

       t  e  r   i  s

       t   i  c  s  o

       f   t   h  e  p  e  r   f  o  r  m  a  n  c  e  o

       f   t   h  e  p  r  o

       d

      u  c

       t  s  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

       T   h   i  s   d  o  c  u  m  e  n

       t  a   t   i  o  n

       i  s  n  o

       t   i  n

       t  e  n

       d  e

       d  a  s  a  s  u

       b  s

       t   i   t  u   t  e   f  o  r  a  n

       d   i  s  n  o

       t   t  o   b  e  u  s  e

       d   f  o  r

       d  e

       t  e  r  m

       i  n   i  n  g  s  u

       i   t  a

       b   i   l   i   t  y  o  r  r  e

       l   i  a

       b   i   l   i   t  y  o

       f   t   h  e  s  e  p  r  o

       d  u  c

       t  s   f  o  r  s  p  e  c

       i   f   i  c  u  s  e  r  a  p  p

       l   i  c  a

       t   i  o  n  s .

       I   t   i  s   t   h  e

       d  u

       t  y  o

       f  a  n  y  s  u  c

       h  u  s  e  r  o  r

       i  n   t  e  g  r  a

       t  o  r

       t  o  p  e  r   f  o  r  m

        t   h  e  a  p  p  r  o  p  r   i  a

       t  e  a  n

       d  c  o  m  p

       l  e   t  e

      r   i  s

       k  a  n  a

       l  y  s

       i  s ,

      e  v  a

       l  u  a

       t   i  o  n  a  n

       d   t  e  s

       t   i  n  g  o

       f   t   h  e  p  r  o

       d  u  c

       t  s  w

       i   t   h

      r  e  s  p  e  c

       t   t  o   t   h  e  r  e

       l  e  v  a  n

       t  s  p  e  c

       i   f   i  c  a  p  p

       l   i  c  a

       t   i  o  n  o  r  u  s  e

       t   h  e  r  e  o

       f .

       N  e

       i   t   h  e  r

       S  c

       h  n  e

       i   d  e  r

       E   l  e  c

       t  r   i  c   I  n

       d  u  s

       t  r   i  e  s

       S   A   S  n  o  r  a  n  y  o

       f   i   t  s  a

       f   f   i   l   i  a   t  e  s  o  r  s  u

       b  s

       i   d   i  a  r   i  e  s  s

       h  a

       l   l   b  e  r  e  s  p  o  n  s

       i   b   l  e  o  r

       l   i  a

       b   l  e   f  o  r  m

       i  s  u  s  e  o

       f   t   h  e

       i  n   f  o  r  m  a

       t   i  o  n  c  o  n

       t  a   i  n  e

       d   h  e  r  e

       i  n .

    Mon Oct 11 10:08:04 EDT 2010

    1

    Product data sheetCharacteristics

    24214miniature circuit breaker Multi 9 - C60N - 3

    poles - 10 A - C curve

    Certifications and standards

    Standards EN 60898

    IEC 60947-2

    Compatibility

    Comb busbar distribution block compatibility NO

    Earth-leakage protection Separate block

    Product compatibility C60 accessories

    C60 auxiliary

    Connections

    Connections - terminals Tunnel type terminals 16 mm² flexible

    Tunnel type terminals 25 mm² rigid

    Electrical

    [In] rated current 10 A 30 °C

    [Ue] rated operational voltage 12...440 V AC 50/60 Hz

    [Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2

    [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2

    Breaking capacity 10 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz

    30 kA Icu IEC 60947-2 125 V DC 3P

    20 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz

    40 kA Icu IEC 60947-2 250 V DC 4P

    6 kA Icn EN 60898 230/400 V AC 50/60 Hz

    20 kA Icu IEC 60947-2 125 V DC 2P

    6 kA Icu IEC 60947-2 440 V AC 50/60 Hz

    Magnetic tripping limit 5...10 x In

    Network frequency 50/60 Hz

    Environment

     Ambient air temperature for operation -25...60 °C

     Ambient air temperature for storage -40...70 °C

    Operating altitude 2000 m

    Relative humidity 95 % 55 °C

    Tropicalisation 2 IEC 60068-1

    RoHS EUR conformity date 0651

    RoHS EUR status Compliant

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 79 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    80/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    81/415

    Page 11

    trippingVisualisation of tripping by means of the redindicator on front face.

    MX + OF shunt tripRemote tripping of a circuit-breaker:c equipped with an OF changeover switch:- to indicate the circuit-breaker’s position- to carry out self-breaking allowing thecontrol circuit to remain energized.Undervoltage releases(MN, MN sssss)Controls the tripping of a circuit-breaker when its supply voltage drops(threshold between 70 and 35 % of Un)It allows for manual closing of thecircuit-breaker if its voltage exceeds 85 % of the rated voltagedelayed MN sssss release0.2 second time-delay: prevents tripping dueto brownouts or momentary voltage

    decreases.MNx release for opening pushbuttonCompletely unaffected by power supplycircuit cuts, it is recommended for fail-safeemergency stopping. Replaces the MX“voluntary“ release equipped with its NO/NCindicator lights.MSU overvoltageMSU voltage threshold releaseSpecially designed to monitor voltagebetween the neutral and phase(s)conductors, it cuts power supply by openingthe circuit-breaker in event of an overvoltage.For overvoltages lasting for more than a fewseconds.

    technical dataComplance with standard: AS 3947-2

    v release consumption type voltage power  

    (V AC or DC) (W or VA)

    MX+OF 415 V AC inrush 120

    220...240 V AC inrush 50

    110...130 V AC inrush 200

    DC inrush 10

    48 V AC inrush 22

    DC inrush 12

    24 V AC inrush 120

    DC inrush 120

    12 V AC inrush 20

    DC inrush 20

    MN 220...240 V AC holding 4.1

    48 V AC holding 4.3

    DC holding 2.0

    MNs 220...240 V AC holding 4.1MNx 230 AC inrush 50

    400 AC inrush 120

    MSU 230 AC inrush 50

    400 AC inrush 120

    remote indication

    OF auxiliary switchv changeover switch that indicates the

    “open” or “closed” position of thecircuit-breaker.v test button on the front face that allows for the indication circuit to be verified withoutoperating the circuit-breaker SD fault indicating switchv changeover switch that indicates the ”faulttrip” position of the circuit-breaker v visualisation of the fault (SD) by means of a mechanical indicator on front face.OF+SD/OF selector switchv double changeover switch that indicates:v the “open” or “closed” position of thecircuit-breaker (OF)v the “fault trip” position of the circuit-breaker (SD).v 2 circuits:

    - upper: OF- lower: SD or OF.v function is selected using rotary selector switch on the right-hand sidev the selected function is indicated on thefront facev visualisation of the fault (SD) by means of a red mechanical indicator on front face.

    technical dataComplies with standard: AS 3947-2

    v rated current of auxiliary contacts voltage rated current

     (V AC or DC) (A)

    415 V AC 3

    ≤ 240 V AC 6

    130 V DC 1

    ≤ 48 V DC 2≤ 24 V DC 6

    connectionc using screw clamp terminals for 1 or 2cables (max. 2.5 mm2)c visible markers near terminals.

    protection 

    electrical auxiliariesfor C60 and C120 circuit-breakers

     AHSMRW00LAA-OM100.159/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 81 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    82/415

    Page 12 Schneider Electric Help Centre: 1300 369 233

     type control voltage catalogue width

    (V AC) (V DC) number in mod.

    of 9 mm

    MX + OF shunt release

    220...415 110...130 26946 2

    48...130 48 26947 2

    24 24 26948 2

    12 12 26949 2

    MSU overvoltage release

    1P + N 220...240 26979 4

    3P + N 380...415 26980 4

    MN undervoltage release

    instantaneous 220...240 26960 2

    48 26961 2

    48 26962 2

    delayed s 220...240 26963 4

    MNx release for opening pushbutton

    Ph + N 220...240 26969 4

    Ph to Ph 380...415 26971 4

    references

    26946

    26963

    26979

    26969

    C1C21214

    U >

    E2 NE1 L

    U <

    N L

    U >>

    D2D1

    U <

    E2 L1E1 L2

    U <

    L3L2N   L1

    U >>

    protection 

    electrical auxiliariesfor C60 and C120 circuit-breakers

     AHSMRW00LAA-OM100.160/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 82 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    83/415

    Page 13

     type control voltage catalogue width

    (V AC) (V DC) number in mod.

    of 9 mm

    SD fault indicating switch

    26927 1

    OF auxiliary contact

    26924 1

    OF+SD/OF selector switch

    26929 1

    26927

    26924

    26929

    14 12 11

    2191

    2294

    2492

    919294

    111214

    protection 

    electrical auxiliariesfor C60 and C120 circuit-breakers

     AHSMRW00LAA-OM100.161/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 83 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    84/415

    2

    PresentationGB2 thermal-magnetic circuit-breakers protect and isolate the control circuits of

    industrial equipment with contactor coils, transformers.…

    They protect and isolate single-phase auxiliary circuits such as solenoid valves,

    electro-brakes, battery chargers, supplied from the control circuit voltage.

     

    GB2 CB, GB2 CD, GB2 DB12 ratings are available, from 0.5 to 20 A, in single-pole (GB2 CB), single-pole +

    neutral (GB2 CD) and 2-pole (GB2 DB) versions.

    They have a magnetic tripping threshold set at between 12 and 16 In to withstand the

    current peaks generated by many industrial components.

     

    GB2 CS2 ratings are available, 0.5 and 1 A, in single-pole version.

    The magnetic tripping threshold is set between 5 and 7 In.

     

    Functions, installationClip-on fixing onto all types of 35 mm 5 rails, on 4 rails and on Telequick

    mounting plates.Upstream and downstream marking by means of AB1 clip-in markers.

    Clear indication of “I” and “O” positions on the operator.

    Tamper-proof device which requires no special maintenance (fixed magnetic and

    thermal tripping thresholds).

     

    Selection for the protection of circuits supplied by transformersSingle-phase transformers.

    Magnetising peak: 20 In.

    Operation of magnetic trips: 13 In.

     

    Power Primary (1) Secondary

    VA 220/240 V 380/415 V 24 V 48 V 110 V 220 V

    40 GB2 DB05 GB2 DB05 GB2 CD07 GB2 CD06 GB2 CD05 GB2 CD05

    63 GB2 DB05 GB2 DB05 GB2 CD08 GB2 CD07 GB2 CD06 GB2 CD05

    100 GB2 DB06 GB2 DB05 GB2 CD10 GB2 CD07 GB2 CD06 GB2 CD05

    160 GB2 DB07 GB2 DB06 GB2 CD14 GB2 CD09 GB2 CD07 GB2 CD06

    250 GB2 DB07 GB2 DB06 GB2 CD16 GB2 CD12 GB2 CD08 GB2 CD07

    400 GB2 DB08 GB2 DB07 GB2 CD22 GB2 CD14 GB2 CD09 GB2 CD07

    630 GB2 DB10 GB2 DB08 – GB2 CD21 GB2 CD12 GB2 CD08

    1000 GB2 DB14 GB2 DB09 – – GB2 CD16 GB2 CD10

    1600 GB2 DB20 GB2 DB14 – – – GB2 CD14

    2000 GB2 DB21 GB2 DB14 – – GB2 CD22 GB2 CD16

    2500 GB2 DB22 GB2 DB20 – – – GB2 CD20

    3000 GB2 DB22 GB2 DB20 – – – GB2 CD21

    4000  – GB2 DB21 – – – GB2 CD22

    5000  – GB2 DB22 – – – – 

    (1) If the breaking capacity of the GB2 is insuf ficient, use a GV2 RT with 2 poles connected inseries, see page 24508/7.

     

    Characteristics :pages 21092/3 to 21092/5

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Characteristics :pages 21092/3 to 21092/5

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Characteristics :pages 21092/3 to 21092/5

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Characteristics :pages 21092/3 to 21092/5

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits

    Presentation, selection

    21092-EN_Ver5.0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 84 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    85/415

    3

    Circuit-breaker type GB2 CB GB2 CD GB2 DB GB2 CS

    EnvironmentConforming to standards IEC 60947-1, 947-2, EN 60947-1, 60947-2

    Product certifications CSA, NEMKO, UL NEMKO, UL – –  

    Protective treatment “TC”

    Degree of protection Conforming to IEC 60529 IP 20

    Shock resistance Conforming to IEC 60068-2-27 22 gn for 20 ms

    Vibration resistance Conforming to IEC 60068-2-6 5 gn (5…110 Hz)

     Ambien t air temperaturearound the device

    Storage °C - 40…+ 80

    Operation °C - 20…+ 60

    Flame resistance Conforming to IEC 60695-2-1 °C 960

    Maximum operating altitude m 3000

    Operating positi on In relation to normalvertical mounting plane

     

    GB2 CB,CD, CS GB2 DB

    Cabling Minimum c.s.a. Maximum c.s.a.

    Solid cable mm 2 1 x 0.75 1 x 6 or 2 x 4

    Flexible cable with cable end mm 2 1 x 0.75 1 x 4 or 2 x 2.5

    Tightening torque N.m 1.2

    Technical characteristicsUtilisation category Conforming to IEC 60947-2 A A A A

    Rated operational voltage(Ue)

    Conforming to IEC 60947-2 V 415 (1) 250 415 415 (1)

    Conforming to CSA C22-2 Nr 14and UL 1077

    V 277 – 277 –  

    Rated operational frequency Conforming to IEC 60947-2 Hz 50/60 50/60 50/60 50/60

    Rated impulse wi thstandvoltage (U imp)

    Conforming to IEC 60947-2 kV 4 4 4 4

    Total power dissipated per pole W 2 2 2 1.9

    Mechanical andelectrical durability

    C.O.: Closing - Opening C.O. 8000 8000 8000 8000

    Operational cu rrentcorrection coef ficient(a orc)

     According to the permissibleambient temperature

    °C - 20 - 10 0 + 10 + 20 + 30 + 40 + 50 + 60

    Correction coef ficient 1.2 1.15 1.1 1.05 1 0.95 0.90 0.85 0.80

    Tripping threshold Of the magnetic trips 12…16 In 12…16 In 12…16 In 5…7 In

    (1) One GB2 circuit-breaker on each live conductor.

    Tripping curves

     Average operat ing t ime at 20 °C withou t pri or cu rren t flow (cold state)

    GB2 CB, GB2 CD, GB2 DB GB2 CS

     

    1,05

    1,5

    2 3 4 5 6 8

    10

    1

    5

    2

    2010

    100

    50

    1

    5

    2

    2010

    1

    5

    2

    20

    10

    60

    120

    500

    200

    100 x In1,05

    1,5

    2 3 4 5 6 8

    10

    1

    5

    2

    2010

    100

    50

    1

    5

    2

    2010

    1

    5

    2

    20

    10

    60

    120

    500

    200

    100 x In

         M     i     l     l     i    s    e    c    o    n     d    s

         S    e    c    o    n     d    s

         M     i    n    u     t    e    s

    1,05

    1,5

    2 3 4 5 6 8

    10

    1

    5

    2

    2010

    100

    50

    1

    5

    2

    2010

    1

    5

    2

    20

    10

    60

    120

    500

    200

    100 x In1,05

    1,5

    2 3 4 5 6 8

    10

    1

    5

    2

    2010

    100

    50

    1

    5

    2

    2010

    1

    5

    2

    20

    10

    60

    120

    500

    200

    100 x In

         M     i     l     l     i    s    e    c    o    n     d    s

         S    e    c    o    n     d    s

         M     i    n    u     t    e    s

    1,05

    1,5

    2 3 4 56 8

    10

    1

    5

    2

    20

    10

    100

    50

    1

    5

    2

    20

    10

    1

    5

    2

    20

    10

    60

    120

    500

    200

    100 x In

         M     i     l     l     i    s    e    c    o    n     d    s

         S    e    c    o    n     d    s

         M     i    n    u     t    e    s

    1,05

    1,5

    2 3 4 56 8

    10

    1

    5

    2

    20

    10

    100

    50

    1

    5

    2

    20

    10

    1

    5

    2

    20

    10

    60

    120

    500

    200

    100 x In

         M     i     l     l     i    s    e    c    o    n     d    s

         S    e    c    o    n     d    s

         M     i    n    u     t    e    s

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits

    Characteristics

    21092-EN_Ver5.0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 85 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    86/415

    4

    Circuit-breaker type GB2

    CB 05 CB06 CB 07 CB08 CB09 CB10 CB12 CB 14 CB16 CB20 CB 21 CB 22

    Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20

    Breaking capacityconforming to IEC 60947-2a 50/60 Hz

    110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2

    Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75

    230/240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5

    Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

    400/415 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5

    Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

     Assoc iated f uses , if requi redif Isc > breaking capacity Icuconforming to IEC 60947-2

    110 V aM  A   g g 20 25 25 40 40 50 50 63 63 63

    gG  A   g g 25 32 32 50 50 63 63 80 80 80

    230/240 V aM  A   g g 16 20 20 32 32 40 40 50 50 50

    gG  A   g g 25 32 32 40 40 50 50 63 63 63

    400/415 V aM  A   g g 16 20 20 32 32 40 40 50 50 50

    gG  A   g g 25 32 32 40 40 50 50 63 63 63

    Circuit-breaker type GB2

    CD05 CD06 CD07 CD08 CD09 CD10 CD12 CD14 CD16 CD20 CD21 CD22

    Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20

    Breaking capacityconforming to IEC 60947-2a 50/60 Hz

    110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2

    Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75

    230/ 240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5

    Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

     Assoc iated fuses , if requi redif lsc > breaking capacity Icuconforming to IEC 60947-2

    110 V aM  A   g g 20 25 25 40 40 50 50 63 63 63

    gG  A   g g 25 32 32 50 50 63 63 80 80 80

    230/240 V aM  A   g g 16 20 20 32 32 40 40 50 50 50

    gG  A   g g 25 32 32 40 40 50 50 63 63 63

    Circuit-breaker type GB2

    DB05 DB06 DB 07 DB08 DB 09 DB10 DB12 DB14 DB16 DB20 DB21 DB 22

    Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20

    Breaking capacityconforming to IEC 60947-2a 50/60 Hz

    110 V lcu kA 50 50 15 10 6 3 3 3 2 2 2 2

    Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75

    230/240 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5

    Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

    400/415 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 75

    Ics % (1) 25 25 25 50 50 75 75 75 75 75 1.5 75

     Assoc iated fuses , if requi redif lsc > breaking capacity Icuconforming to IEC 60947-2

    110 V aM  A   g g 20 25 25 40 40 50 50 63 63 63

    gG  A   g g 25 32 32 50 50 63 63 80 80 80

    230/240 V aM  A   g g 16 20 20 32 32 40 40 50 50 50

    gG  A   g g 25 32 32 40 40 50 50 63 63 63

    400/415 V aM  A   g g 16 20 20 32 32 40 40 50 50 50

    gG  A   g g 25 32 32 40 40 50 50 63 63 63

    (1) As % of Icu.g  Fuse not required. Breaking capacity Icu > lsc.

     

    Presentation, selection :page 21092/2

    References :page 21093/2

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :page 21093/2

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :page 21093/2

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :page 21093/2

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits

    Characteristics (continued)

    21092-EN_Ver5.0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 86 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    87/415

    5

    Circuit-breaker type GB2

    pp05   pp06   pp07   pp08   pp09   pp10   pp12   pp14 pp16   pp20   pp21   pp22

    Breaking capacity (lcu)

    conforming to IEC 60947-2c

    24 V kA 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

    48 V kA 1 1 1 1 1 1 1 1 – – – –  

    Operational currentconforming to IEC 60947-5-1c

    DC-12 24 V  A 0.5 1 2 3 4 5 6 8 10 12 16 20

    48 V  A 0.5 1 2 3 4 5 6 8 10 12 16 20

    DC-13 24 V  A 0.5 1 2 3 4 5 6 8 10 12 16 20

    48 V  A 0.5 1 2 3 4 5 6 8 – – – –  

    Circuit-breaker type GB2

    CS05 CS06

    Rating A 0.5 1

    Breaking capacityconforming to IEC 60947-2a 50/60 Hz

    110 V lcu kA 50 50

    lcs % (1) 100 100

    230/240 V lcu kA 50 50

    lcs % (1) 25 25

    400/415 V(2)

    lcu kA 50 50

    lcs % (1) 25 25

    Breaking capacity (lcu) conforming to IEC 60947-2c

    24 V kA 1.5 1.5

    48 V kA 1 1

    Operational currentconforming to IEC 60947-5-1c

    DC-12 24 V  A 0.5 1

    48 V  A 0.5 1

    DC-13 24 V  A 0.5 1

    48 V  A 0.5 1

    Maximumpermissible

    line length forstar-delta starting(length of cablecontaining 2 ormore conductors)

    With contactorsLCp D09 …D18

    Operational voltage V 48 110 230 48 110 230

    C.s.a. 060 mm2 m (3) 31 365 6 85 230

    0.75 mm2 m (3) 39 460 8 110 290

    1 mm2 m (3) 52 610 10 145 380

    1.5 mm2 m (3) 78 910 15 220 570

    2.5 mm2 m (3) 130 1520 26 360 950

    4 mm2 m (3) 200 2400 41 580 1500

    With contactorsLCp D25…D32

    Operational voltage V 48 110 230 48 110 230

    C.s.a. 0.60 mm2 m (3) (3) 230 (3) 56 230

    0.75 mm2 m (3) (3) 290 (3) 70 290

    1 mm2 m (3) (3) 390 (3) 95 380

    1.5 mm2 m (3) (3) 580 (3) 140 570

    2.5 mm2 m (3) (3) 970 (3) 230 950

    4 mm2 m (3) (3) 1500 (3) 375 1500

    With contactorsLCp D40…D80

    Operational voltage V 48 110 230 48 110 230

    C.s.a. 0.60 mm2 m (3) (3) 46 (3) 13 100

    0.75 mm2 m (3) (3) 60 (3) 17 130

    1 mm2 m (3) (3) 80 (3) 22 170

    1.5 mm2 m (3) (3) 120 (3) 34 250

    2.5 mm2 m (3) (3) 190 (3) 56 420

    4 mm2 m (3) (3) 310 (3) 90 680

    (1) As % of Icu.(2) One GB2 CS circuit-breaker on each live conductor.(3) Use relays.

     

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Presentation, selection :page 21092/2

    References :pages 21093/2 and 21093/3

    Dimensions :page 21093/3

    Schemes :page 21093/3

    Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits

    Characteristics (continued)

    21092-EN_Ver5.0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 87 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    88/415

     

    CONTROL & SIGNALLING UNITS

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 88 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    89/415

    Control and signalling unitsThe essential guide

     AHSMRW00LAA-OM100.223/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 89 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    90/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    91/415

    2/1Schneider Electric

    2

     

    2121 0 21 021

    21

    IN 230 V

    6 V

    IN

    21

    230 V6 V

    IN

            1        3

            1        4

            2        4

            2        3

    IN250 V max

    BA 0 BA 0BA

    D

    C

    0 BA

    D

    C

    0 BA

    D

    C

    0

    Pushbuttons and Emergency stop pushbuttons

     

    Selector switches

     

    Selector switch - 2 position,spring return from right to left,key withdrawal LH positionN/O contact

    Pilot lights

     

    Illuminated pushbuttons and selector switches

     

    Pushbutton Pushbutton Mushroom head, Emergency stop latchingN/O contact N/C contact spring return mushroom head. Push-pull

    N/O contact N/C contact

    Emergency stop trigger Emergency stop trigger Emergency stop trigger Emergency stop triggeraction mushroom head action mushroom head action mushroom head action mushroom headPush-pullN/O + N/C contact

    Turn to release - N/C contact Key release - N/C contact Turn to releaseN/O + N/C contact

    Emergency stop triggeraction mushroom headKey release Double-headed pushbuttonN/O + N/C contact N/O + N/C contact

    Selector switch - 2 position, Selector switch - 3 position, Selector switch - 3 position, Selector switch - 2 position,stay put stay put 2 spring return to centre stay put, key withdrawal LHN/O contact N/O + N/O contact N/O + N/O contact position - N/O contact

    Pilot light with BA 9s Pilot light with integral transformer, 230 V  aa a a primary,incandescent bulb LED pilot light 6 V secondary. BA 9s incandescent bulb or LED

    Illuminated pushbutton Illuminated pushbutton Illuminated pushbutton Double-headed pushbuttonBA 9s incandescent bulb with LED with integral transformer, with LED pilot lightN/O + N/C contact N/O + N/C contact 230 V  aa a a 50/60 Hz primary, N/O + N/C contact

    6 V secondary.BA 9s incandescent bulb or LEDN/O + N/C contact

    Illuminated selector switchwith LED - 2 position stay putN/O + N/C contact

    Joystick controllers 4 direction

    2 direction

     Without With Without With springspring return spring return spring return return

    Control and signalling units Ø 22Harmony ®  style 5Pushbuttons, switches and pilot lights, with doubleinsulated bezel

    General 

    Schematic library

    Characteristics:pages 2/6 to 2/9

    References:pages 2/10 to 2/47

    Dimensions:pages 2/48 to 2/55

    LED LED

    LED

    LED

    LEDLED

     AHSMRW00LAA-OM100.225/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 91 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    92/415

    2/2 Schneider Electric

    2

     

    Non illuminated unitsfor user assembly

    Contact functions

    Body Headsub-assemblies sub-assemblies

    Pushbuttons, spring return,without marking

    Screw clamp terminalsZB5-AZ10pppp /AZ141see page 2/10 Flush push Flush push for Flush push

    insertion of legend

    ZB5-AA0/AA9 ZB5-AApppp ZB5-AApppp8 ZB5-CApppp

    see page 2/11 see page 2/11 see page 2/11 see page 2/11

    Plug-in connectorZB5-AZ10p4/AZ1414see page 2/10 Projecting push Recessed push Booted flush push Projecting push

    ZB5-ALpppp ZB5-AApppp4 ZB5-APpppp / APpppp8 ZB5-CLppppsee page 2/11 see page 2/11 see page 2/11 see page 2/11

    Pushbuttons, spring return,with marking

    Flush push Projecting push Flush pushZB5-AApppp3pppp/AApppp4pppp ZB5-AL ZB5-CApppp3/CApppp9see page 2/12 see page 2/12 see page 2/12

    “Push-turn” pushbuttons (1) Knob positions

    Lockable Knurled knob (1)ZB5-AFD ZB5-AFsee page 2/12 see page 2/12

    Double-headed pushbuttons,

    spring return

    Flush pushes (IP 40/IP 66) Flush push + Projecting push (IP 40/IP 66)Without/with markings Without/with markingsZB5-AA81/AA82 ZB5-AA91/AA92 ZB5-AL83/AL84 ZB5-AL93/AL94see page 2/13 see page 2/13 see page 2/13 see page 2/13

    “Push-push to release”pushbuttons

    Flush push Projecting push Flush pushZB5-AH0/CH0 ZB5-AHp ZB5-CH0psee page 2/13 see page 2/13 see page 2/13

     

    Control and signalling units Ø 22Harmony ®  style 5Pushbuttons, switches and pilot lights, with double insulated bezelSub-assemblies, ZB5-A 

    General (continued) 

    Characteristics:pages 2/6 to 2/9

    References:pages 2/10 to 2/47

    Dimensions:pages 2/48 to 2/55

     AHSMRW00LAA-OM100.226/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 92 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    93/415

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    94/415

    2/4 Schneider Electric

    2

     

    Pilot lightsfor user assembly

     Signalling functions

    Body sub-assemblies Head sub-assembliesIntegral LED

    With lens mountedZB5-AV0p3 ZB5-CV0p3see page 2/21 see page 2/21

    Screw clamp terminalsZB5-AVB/AVG/AVMsee page 2/20

    With 5 separate lensesZB5-AV003 ZB5-CV003see page 2/21 see page 2/21

    Plug-in connectorZB5-AVBp4/AVGp4/AVMp4see page 2/20

    Body sub-assemblies Head sub-assembliesfor BA 9s bulb

    With lens mountedZB5-AV0psee page 2/21

    Direct supplyScrew clamp terminalsZB5-AV6see page 2/21

    Via integral transformerScrew clamp terminalsZB5-AVp /AV3Dp(1) /AV5Dp(1)see page 2/21

    Control and signalling units Ø 22Harmony ®  style 5Pushbuttons, switches and pilot lights, with double insulated bezelSub-assemblies, ZB5-A 

    General (continued) 

    Characteristics:pages 2/6 to 2/9

    References:pages 2/10 to 2/47

    Dimensions:pages 2/48 to 2/55

     AHSMRW00LAA-OM100.228/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 94 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    95/415

    2/5Schneider Electric

    2

    Control and signalling units Ø 22Harmony ® style 5Pushbuttons, switches and pilot lights, with double insulated bezelSub-assemblies, ZB5-A 

    General 

    Characteristics:pages 2/6 to 2/9

    References:pages 2/10 to 2/47

    Dimensions:pages 2/48 to 2/55

     

    Illuminatedpushbuttonsand selector switches

    for user assembly

    Combined contact and signalling functions

    Body sub-assemblies Head sub-assembliesIntegral LED

    Illuminated pushbuttons,spring return

    Flush push with cap Flush push for Booted Flush pushmounted or not insertion of legend

    ZB5-AW3pppp3/AW9pppp3 ZB5-AApppp8 ZB5-AW5pppp3see page 2/29 see page 2/29 see page 2/29

    Screw clamp terminalsZB5-AW0B/AW0G/ AW0Msee page 2/24

    Projecting push Flush or projecting push

    ZB5-AW1pppp3/ALpppp8 ZB5-CW3pppp3/CW1pppp3see page 2/29 see page 2/29

    Double headed pushbuttons,spring return, with pilot light

    Plug-in connectorZB5-AW0Bpppppppp4/ AW0Gpppppppp4/AW0Mpppppppp4 Flush pushes Flush push + projecting pushsee page 2/26 Without/with markings Without/with markings

    ZB5-AW81pppppppppppp3, ZB5-AW82pppppppppppp3 ZB5-AW83pppppppppppp3, ZB5-AW84pppppppppppp3see page 2/30 see page 2/30 see page 2/30 see page 2/30

     Illuminated “push-push torelease” pushbuttons andilluminated selector switcheswith standard handle

    Flush or projecting Selector switches with“push-push to release” standard handleZB5-AH0i3/AHpppp3 ZB5-AK1ppppi3see page 2/30 see page 2/31

    Body sub-assemblies Head sub-assembliesFor BA 9s bulb

    Illuminated pushbuttons,spring return

    Flush pushZB5-AW3pppp

    Direct supply see page 2/29Screw clamp terminalsZB5-AW06ppppsee page 2/28

    Projecting pushZB5-AW1ppppsee page 2/29

    Via integral transformerScrew clamp terminalsZB5-AW03/4/5/3D/5Dsee page 2/28

     

     AHSMRW00LAA-OM100.229/A

     

     AHS-MRW00SEO.OM.109.06 

     

    REVISION: A Rev. Date: 18.04.2011

     

     page: 95 of 416 

  • 8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets

    96/415

    2/6 Schneider Electric

    2

    Control and signalling units Ø 22Harmony ®  style 5Pushbuttons, switches and pilot lights, with doubleinsulated bezel

    Environment

    Protective treatment  “TH”standard version

    Ambient air temperature Storage ˚C - 40…+ 70around the device

    Operation ˚C - 25…+ 70 unless otherwise stated

    Electric shock protection Conforming to IEC 536 Class II

    Degree of protection Conforming to IEC 529 IP 65, unless otherwise statedIP 66, for booted pushbutton heads

    Conforming to NEMA NEMA type 4X and 13, unless otherwise stated

    High pressure cleaning resistance Pa 70 x 105 (70 bar); distance: 0.1 m

    Temperature: 55˚C

    Mechanical shock protection Conforming to EN 50102 Non illuminated heads: IK 03

    Illuminated heads: IK 05

    Conforming to standards IEC/EN 60947-1, IEC/EN 60947-5-1, IEC/EN 60947-5-4,JIS C 4520,UL 508, CSA C22-2 n˚ 14

    Product certifications UL Listed, CSA Standard single contacts with screw clamp terminals: A600; Q600Double contacts with screw clamp terminals: A600; Q600Light blocks with screw clamp terminalsJoystick controllers XD5-PA/ZD5-PA: A600; R300

    UL Recognized, CSA Standard single contacts for plug-in connector: A300; R300Standard single contacts for printed circuit board: B300; R300

    BV, RINA, LROS, DNV, GL (pending) Standard single contacts and double contacts with screw clampterminals

    Terminal identification Conforming to EN 50005 & EN 50013

    Characteristics of contact blocks

    Mechanical characteristics

    Contact operation N/C or N/O Slow break

    Positive operation Conforming to IEC/EN 60947-5-1 All functions incorporating a N/C contact are positive openingAppendix K operation

    Operating travel Pushbutton mm Changing N/C state: 1.5(to change electrical state) mm Changing N/O state: 2.6

    mm Total travel: 4.3

    Operating force Pushbutton N Changing N/C state: 3.5N Changing N/O state: 3.8

    Additional contact N Single N/C contact: 2(extra to change state) N Single N/O contact: 2.3

    N Double contact N/C: 3.4N Double contact N/O: 5N Double contact N/C + N/O: 4.6

    Emergency stop with N/C + N/O N Standard push-pull: 45

    N Trigger action push-pull: 50

    N Standard turn to release and key release: 40N Trigger action turn to release and key release: 44

    Characteristics�