1. i am adding an scr to my plant. should i upgrade my ......should i upgrade my existing fans, add...
TRANSCRIPT
![Page 1: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/1.jpg)
1. I am adding an SCR to my plant. Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide?Considerations:
Pressure required: High pressure requires high tipspeed High wheel stress, Low specific speed (possibly lower efficiency) noisierSpace availableTime available for change-overControl – One fan easier than 2 in seriesIs current foundation OK for upgraded fan?Ductwork connections
![Page 2: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/2.jpg)
3. What are the suggested maintenance operations and frequency to maintain fan efficiency and lengthen the life?
Efficiency: Dampers/VIV’s clean and operational, Rotors clean and not worn, wheel to inlet cone clearanceLife: Lubrication, alignment, monitor bearing temperature and vibrationConsult the fan supplier’s O&M Manual!
![Page 3: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/3.jpg)
4. Which is the best type of fan for each application in a power plant (centrifugal, variable pitch or axial) and why?
Specific speed – axials typically higher (high flow/low pressure)efficiencyturn-down rangeparticulate load – erosion/build-upRef. AMCA Publication 801, Specification Guidelines
![Page 4: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/4.jpg)
5. My flue gas has a high particulate load. What is the best way to improve the life in a highly abrasive environment?Velocity related – exponentiallyDWDI vs. SWSILow speed vs. High speedBlade profileLiners: AR plate/ Chromium carbide/tungsten carbide/ceramic
Wheel, Casing, Inlet boxes, Inlet cones
![Page 5: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/5.jpg)
6. How can I decide whether a fixed speed fan with dampers or a fan with a variable speed motor for fan control is best for my application?
Initial cost vs operational costAmount of turn-down
![Page 6: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/6.jpg)
Example: Inlet Louvered Damper Control:Turndown condition requires 880 BHP
Volume (CFM x 1000)
3002752502252001751501251007550250
Pressure (in
. H
20)
50
45
40
35
30
25
20
15
10
5
0
BH
P
4000
3600
3200
2800
2400
2000
1600
1200
800
400
0
20
Robinson Industries, Inc.Fan : 83" x 14.38" FRD SWSIFor : Basic Fan Laws I
Fan Speed : 1180 RPMTemperature : 70°FDensity : 0.075 LB/FT³
Date : 02/02/1999Quote Number : 123456RII FO # : 123456
EF :1SE :1TF :1
Note: Louvered damperedcurves are approximate
SP
20° 40°60°
BHP20°
40°60°
Note: InletP(s) Ratio = 0
880 BHP
105000 CFM
20 in. H20
![Page 7: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/7.jpg)
Volume (CFM) x 100025020015010050
P
ress
ure
(In
H2
0)
25
20
15
10
5
0
BH
P
1000
800
600
400
200
20” SP
450 BHP
ROBINSON INDUSTRIES, INC.
FAN : 83" x 14.38" FRD
FOR : Basic Fan Laws I
FAN SPEED : 840
TEMP. : 70
DENSITY : 0.075
SP
BHP
SYSTEM RESISTANCE
105,000 CFM
Example: Speed Control:Same turndown condition requires 450 BHP
![Page 8: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/8.jpg)
7. How can I optimize the performance of my fans to improve efficiency?
Field test – Establish baseline current performanceControl range requiredConsider rotor retrofit – Performance must be confirmed via lab model prototype testDon’t neglect mechanical and other operational concerns
![Page 9: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/9.jpg)
8. What speed should I specify? Why?High speed: smallerlower costhigher Ns, higher efficiency(?)higher velocitieshigher wearhigher bearing peripheral speed
![Page 10: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/10.jpg)
9. Do I need to specify an overspeed test for the fan rotor?The end user can feel more comfortable knowing that the rotors have
been tested at speeds in excess of the actual maximum operating speed.
Inspection of the rotor welded joints before and after testing (using non-
destructive inspection techniques) provides further proof that the rotor
can tolerate such high stress levels without any cracks developing.
![Page 11: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/11.jpg)
What balance quality grade should I specify?ANSI S2.19 Grade G2.5 is appropriate for most fan applications in the power industry. Ref. AMCA/ANSI 204
![Page 12: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/12.jpg)
11. What source would you recommend for learning about basic fan performance parameters and definitions?AMCA International (Air Movement and Control Association) 801, 99, etc.
![Page 13: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/13.jpg)
12. What happens if I throttle my fan too much with the inlet control dampers?
![Page 14: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/14.jpg)
Boiler FD Fan: Squeeze Points – OUCH!
![Page 15: 1. I am adding an SCR to my plant. Should I upgrade my ......Should I upgrade my existing fans, add a booster fan or install a new fan? How can I decide? Considerations: Pressure required:](https://reader034.vdocuments.mx/reader034/viewer/2022042016/5e747cf2596abb1a6368dea0/html5/thumbnails/15.jpg)
13. What factory testing and analyses should be specified?Options include:Wheel stress FEAFatigue analysisWheel modal analysisTorsionalLateralshop balanceImpeller overspeed testCFD