1 harmonic mitigation installation of mirus harmonic filters in tps fields prepared by ahmed...
TRANSCRIPT
1
HARMONIC MITIGATION
Installation of Mirus harmonic filters in TPS fields
Prepared by Ahmed BOUJELBENElectrical & Instrumentation Engineer
Thyna Petroleum Services7, Avenue Abderahmen EL GHAFIKI
BP. 069 - 3069 Sfax HachedSFAX TUNISIA
2
Objectives
Reduce voltage and current harmonic distortion
Reduce Energy losses
Protect electrical equipment against the harmful effects of
harmonics
Avoid failure of equipment ( VFDs, motors, etc.) and
especially on offshore fields (Generator, battery charge, …).
Reduce maintenance cost
Realize energy saving
Abstract- Electric drives, both DC SCR and AC variable frequency drives (VFDs), are
commonplace on drilling rigs and offshore installations.
- Their operation can significantly degrade the quality of electric power, resulting in loss of operational capability, equipment failure with subsequent down-time in addition to presenting safety concerns.
- Marine classification bodies have rules to limit harmonic voltage distortion but these are rarely policed.
- The quality and security of electric power are absolutely crucial to the operational integrity of any drilling rig or offshore installation, irrespective of type or class.
- Any failure or malfunction of equipment due to poor power quality can result in severe or disastrous consequences.
-
• Power Quality Offshore is often taken for granted
• Poor Power Quality on drilling rigs is due to the use of large AC and DC adjustable speed drives
• Poor Power Quality results in: - Lost production - Equipment disruption and failure - Safety concerns
- ‘Harmonics’, a serious and growing problem worldwide, are due to conventional power conversion technologies (e.g. AC to DC conversion) which draw non-sinusoidal currents which interact with the system impedance(s) to produce voltage distortion up to the highest transmission levels.
- Most countries have national standards (or adopt international standards such as the North American IEEE 519 (1992) in order to protect their electricity networks from excessive harmonic ‘pollution’ exported into the network by consumers.
- In some parts of London it is now very difficult to get approval for large non-linear loads such AC variable frequency drives due to the Uthd (total harmonic voltage distortion) being very close to the limits set by Engineering Recommendation G5/4-1 (2001); the UK’s Electricity Associations ‘rules’ for harmonics.
- Adjustable speed drives have many applications in the offshore sector including main propulsion, thrusters, ‘drilling packages’ (i.e. mud pumps , draw-work and top drives), compressors, fans, pumps (especially electrical submersible types), leg racking drives on jack-up rigs, cranes, etc.
- For installations which rely on generator derived power (i.e. the vast majority of drilling rigs) the resulting harmonic voltage distortion can be up to 3 to 4 times that of transformer based power supplies of the same given adjustable speed drive load.
- This is due largely to difference in source impedance between transformers (e.g. 5-6%) and generators (e.g. 12-25%)
The numerous negative effects of harmonics are widely acknowledged that they generally fall into two basic categories :
a) Excessive heating caused by additional RI² losses, skin effect et al in cables and in equipment (e.g. generators, transformers, motors, etc).
b) Voltage distortion due to the harmonic currents ability to produce voltage drops in the various feeder impedances and leakage inductances of the system. In addition, line notching due to DC SCR drives can also be problematic.
Consequently, marine classification societies and other bodies have rules and recommendations to limit the harmonic voltage distortion to 5% Uthd (total harmonic voltage distortion).
The result is a considerable number of installations have significantly more harmonic voltage distortion than permitted.
It is not uncommon to measure up to FIVE to SIX times the permitted limit on some installations
Any failure or malfunction of equipment due to poor power quality can result in loss of production or an incident with possible severe or disastrous consequences.
The problem has been further compounded by offshore Health& Safety bodies across the world not policing the high levelsof voltage distortion either; instead this is currently left to theoil companies to police themselves
Quick Harmonic Refresher
An ‘ideal’ single phase current and voltage waveforms associated with linear
Typical current waveform of a computer switched mode power supply (SMPS) unit (and a single phase AC variable frequency drive (VFD).
Fig 1 – Single phase linear load voltage and current waveforms
Fig2-Single phase non-linear waveforms for computer or VFD
Non-Linear loads
When all harmonic voltages and currents are added to the fundamental a waveform known as a ‘complex wave’ is
formed
Fourier components
An example of complex wave consisting of the fundamental (1st harmonic) + 5th harmonic + 7th harmonic is illustrated as follows
5th harmonic current is 250 Hz (5 x 50 Hz)7th harmonic current is 350 Hz (7 x 50 Hz)
11th harmonic current is 550 Hz (11 x 50 Hz)
Complex waveMost VFD’s incorporate a 3-phase, 6-pulse diode bridge rectifier which generates current harmonics in the 5th, 7th, 11th, 13th, etc…….
Single - phase loads Three- phase loads
Harmonic Spectrum and Current Waveform
The effects of harmonics● Voltage distortion: - Excessive temperature rise in motors, cables - Electrical noises - Sensitive electronic equipment malfunction
● Increase in the apparent power and over-sizing of sources (UPS, Genset, etc.), capacitors, cables... - Derating of electrical equipment or over-sizing - Accelerated ageing of equipment
● Flow of current in the neutral conductor and consequently in the PEN: - Excessive temperature rise in transformer - Tripping of circuit breakers
The additional heating due to harmonics degrades optimal operation because equipment can run at a higher temperature than designed.
If a cable or a motor stator winding gets too hot as a result of harmonics, insulation can melt. Failure is usually the result; in extreme cases FIRES can occur. In hazardous areas, overheating of explosion motors can create a source of ignition with potentially catastrophic consequences.
If voltages are distorted due to harmonics then that too can cause other equipment to MALFUNCTION.
These are the key reasons why harmonics are
Not to be ignored !!!
Harmonic Distortion
THD (Total Harmonic Distortion) for currents, and voltages is one popular measure of Power Quality
The THD of a voltage or current waveform is really a ratio of power dissipation due to harmonics, to power dissipation due to the fundamental
This ratio allows one to predict how much “hotter” (i.e the temperature rise) the wiring or equipment will run, compared to the rated nameplate “design” temperature
Examples of equipment draw harmonic currents from the network
Essentially, the list (which is not exhaustive) is based mainly on equipment which
converts AC power to DC power for internal use and includes the following :
Single phase loads:• Computers• Printers• TVs• Fax machines• Lighting dimmers• Microwave ovens• Fluorescent light ballasts• Medical equipment• Ultrasonic equipment• AC and DC variable speed drives
Three phase loads:
• AC variable frequency drives• DC drives• UPS systems• Induction furnaces• Process and other rectifiers• Medical equipment
Main problems associated with poor power quality:
- Excessive harmonic voltage distortion - Line notching (SCR drives)
- Voltage spikes attributed to SCR drives
These are all traditional ‘harmonics problems’.
Harmonic voltage distortion
.
During the conversion process from AC to DC, both DC SCR drives and from AC VFDs draw unwanted harmonic currents which are multiples of the supply frequency (e.g. 5th harmonic current is 5 x 50Hz = 250Hz) are drawn from the source.
The individual harmonic currents then interact with the system impedance at their respective frequencies to produce voltage distortion at those frequencies.
HARMONIC VOLTAGE DISTORSION
Most conventional adjustable speed drives fed with sinusoidal voltages draw non-sinusoidal or ‘non linear’ current
This Figure illustrates an example line voltages distorted due to excessive harmonics currents
Example of line voltages distorted by AC VFDs (8.8% Uthd) .
Harmonic voltage distorsionExample of 3 x 800HP DC drives voltage waveforms - Uthd 12.2%
AC Variable Frequency Drives (VFDs)VFDs are increasingly popular on drilling rigs/ships
Simplified 6 pulse AC VFD schematic
Both AC and DC adjustable speed drives draw nonlinear current but AC variable frequency drives (VFDs) tend to produce higher levels of harmonic voltage distortion
The nonlinear phase currents drawn by a 1500HP/1100kW VFD at moderate load
Typical 6-pulse (3-phase) VFD Harmonic current spectrum
DC SCR drives DC SCR drives are not as complex as VFDs and are essentially sophisticated DC voltage controllers where the output voltage largely determines the DC motor speed whilst the output DC current determines the motor torque
DC SCR drives draw nonlinear current:
Serious Cause for Concern – high order harmonics - The figure shows the Uthd (total harmonic voltage distortion) captured instantaneously on a 690V drilling package with a DC SCR drilling package.
- The average Uthd was 25.61% of which 19.3% was >21st harmonic due mainly to large number of 24 pulse VFDs for submersible pumps connected to MV supplies.
- The recommended limit for harmonic voltage for the installation was 5%.
Serious Cause for Concern – high order harmonics
Why Cause for Concern ?
Common types of harmonic mitigation
1- Passive Wide Spectrum FiltersOver the last 5-6 years the passive ‘wide spectrum filter’ has gained popularity within the drilling and marine sectors.
The filter is connected in series with the drive load(s).
These devices have been installed in sizes to 3500HP/2650kW for both AC VFD and for DC drives and are now being developed for MV (i.e. medium voltage) VFDs.
Fig shows 2 x 2300HP/1800kW D type (AC) wide spectrum filters :
These units were connected to an AC VFD common DC bus system for three mud pumps. The Uthd was reduced to below 5% to meet requirements.
2- Active Harmonic FilterParallel active filters are similar in technology to VFDs, they treat the harmonic currents (not the main rms current), which are typically around 30-40% of the full rms source current value.In a correctly dimensioned system the vast majority of the harmonic currents are drawn from the active filter and only the fundamental current is drawn from the generator or transformer
Parallel active filter current waveforms
The effects (Ithd and Uthd) of 1500A of harmonic filters on a DC SCRdrilling package comprising 3x 900HP/630kW DC SCR drives
retrofitted with 3% AC line reactors.
Uthd on 3 x 600kW DC drives without/with/without harmonic filter.
Uthd reduced from 11.2% to 3.2%.
Ithd on 3 x 630kW DC SCR drives without/with/without Harmonic Filter.
Ithd reduced from 35% to 3.7%
Without harmonic filter
With Harmonic filter With Harmonic filter
Line notching‘Line notching’ is usually associated with phase controlled semi-conductors such as SCRs
(i.e. silicon controlled rectifiers or thyristors).
Line notching can also be seen in high powered AC drives with diode rectifiers under certaincircumstances.
Severe line notching on due to fully controlled SCR rectifiers on DC drilling package
Reduction of line notching
3 x 900HP DC drives voltage waveforms with 3% AC line reactors only
Without Harmonic filter
3 x 900HP DC drives voltage waveforms with active harmonic filter and 3% AC line reactors.
With harmonic filter
Voltage spikes
Fig. illustrates a typical example of voltage spikes
Damage due to voltage spikes on small to medium powered VFDs.
Failure of rectifier devices and DC bus capacitors
Attenuation of voltage spikesUsing Wide Spectrum Filter
The input (upper trace) and output (lower trace) to/from a wide spectrum filter on a DC drilling package.
Fig above illustrates how effect this wide spectrum filter type of solution can be. These are now being promoted throughout the drilling industry.
Wide Spectrum FilterThe Lineator
(Advanced Universal Harmonic Filter)
Treats all major harmonics generated by Variable Speed Drives and other 3-phase rectifier loads (5th, 7th, 11th, 13th …)
A relatively low cost and very effective solution is to install a suitable wide spectrum harmonic filter between the sensitive VFDs and the voltage notches.
The wide spectrum filter treats the harmonic currents drawn from the supply as design but also acts as a ‘blocking filter’ and effectively isolates the VFDs from overvoltage and other disturbances
Compatible with engine generators
Mirus Lineator Passive filters solution was selected for all TPS fields
The Lineator™ (AUHF) Advanced Universal Harmonic Filter
The LINEATOR ™ is a purely passive device consisting of a revolutionary new inductor combined with a relatively small capacitor bank.
It's innovative design achieves cancellation of all the major harmonic currents (including AM Band RFI) generated by VSD's and other similar 3- phase, 6-pulse rectifier loads.
The resulting Ithd is reduced to < 8% and often as low as 5%.
Features• Treats all major harmonics generated by Variable Speed Drives and other 3-phase rectifier
loads (5th, 7th, 11th, 13th …)• Exceeds 18-pulse performance in a smaller footprint, at lower cost and without sacrificing
energy efficiency• Easily applied to input of a single VSD• No need to phase shift against other VSD’s• Will meet IEEE 519 standard for both current and voltage distortion• Input current demand distortion < 8% over entire operating range• Power factor 0.98 lagging to 0.95 leading over the normal operating range• Compatible with engine generators since capacitive reactance is < 15% of rated kVA even
under light loads• Will not resonate with other power system components • Will not be overloaded by other line side harmonic sources• Suppresses over voltages caused by capacitor switching and other fast changing loads• Eliminates need for drive isolation transformers, AC line reactors and DC link chokes• Removal of harmonics improves overall system power factor• Saves energy by reducing upstream harmonic losses • Reduces DC bus ripple and increases ride-through capability of the load
.TPS experience
As a first step:
TPS selected 4 sites Mirus was selected as suitable filter technology for all TPS
locationsTPS has purchased and installed 4 Lineator filters (2 filters
onshore + 2 filters offshore)Acceptable performances was achieved despite of using
filter at light load, Performance will be presented
As second step:
Mirus Lineator filters solution was generalized for all TPS
fields.38
39
Waveforms
Before filter installation After filter installation
Lineator (Advanced Universal Harmonic Filter)
Performance measurement (Load rate at 62%)
Before Harmonic Mitigation
AfterHarmonic Mitigation Reductions
I rms (A) 442,3 (A) 351,2 (A) - 20,5 %
Uthd 6,3 % 1,2 % - 81 %
Ithd 72,2 % 10,3 % - 87%
DPF 0,98 1,00
TPF 0,79 1,00 + 21 %
KVA 317,4 252,2 - 20 %
KVAR 196,0 24,4 - 88 %
Transformer losses 11,4 kw 5,7 kw - 50 %40
Before Harmonic Mitigation
AfterHarmonic Mitigation Reductions
I rms (A) 442,3 (A) 351,2 (A) - 20,5 %
Uthd 6,3 % 1,2 % - 81 %
Ithd 72,2 % 10,3 % - 87%
DPF 0,98 1,00
TPF 0,79 1,00 + 21 %
KVA 317,4 252,2 - 20 %
KVAR 196,0 24,4 - 88 %
Transformer losses 11,4 kw 5,7 kw - 50 %
BEFORE Harmonic Mitigation:Waveforms and harmonics Spectrums
41
Voltage Current
Uthd = 6,3%
Ithd = 72,2 %
AFTER Harmonic Mitigation:Formes des ondes et spectres harmoniques
42
Voltage Current
Uthd = 2,2 %
Ithd = 7,2 %
BEFORE MITIGATIONSummary Compliance with IEEE std 519 - 1992
Measurement
IEEE 519LIMITS
Voltage total Harmonic Distorsion
(uthd)
6,3 % 5 % Fail
Maximum individual voltage harmonic 4,4 % (5) 3 % Fail
Current total Demand Distorsion
(Itdd)
72,2 % 12,0 % Fail
Max individual current harmonic < 11 61,2 %
(5 )
10 % Fail
11
to 16
7,5 %
(13)
4,5 % Fail
17
to 22
3,4 %
(17)
4,0 % Fail
23
to 34
2,0 %
(23 )
1,5 % Fail
> 35
1,0 %
(35)
0,7 % Fail
43
AFTER MITIGATIONSummary Compliance with IEEE std 519 – (1992)
Measurement
IEEE 519LIMITS
Voltage total Harmonic Distorsion
(uthd)
2,2 % 5 % Pass
Maximum individual voltage harmonic 0,8 % (5)
3 % Pass
Current total Demand Distorsion (Itdd) 7,2% 12% Pass
Max individual current harmonic < 11 8,4 (7) 10 % Pass
11 to 16
2,4(11) 4,5 % Pass
17 to 22
1,5(17) 4 % Pass
23 to 34
0,7(23) 1,5 % Pass
> 35
0,3 (35) 0,7% Pass 44
RESULTS
• Reduction of voltage and current harmonic distortion
• Reduction of Energy losses• 20% KVA Reduction & 80% KVAR Reduction• Realization of saving energy• Protection of electrical equipment against the harmful effects of harmonics• Reduction of maintenance cost •
45
46
Investing in power quality will improve both
your operations and profits
Contact for advice or assistance in Tunisia
Green PlanetAmélioration de la qualité de puissance et
traitement des courants harmoniquesRésidence Dorret Carthage - Les Jardins de Carthage
Tél : 22 323 499 / 53 715 500Fax : 71 265 140
Email : [email protected] : Fethi Ben Bouzid