1 aspirating systems training e-series. 2 overview e-series model range asd software nettracer ...

31
1 ASPIRATING SYSTEMS TRAINING e-series

Upload: aleesha-burke

Post on 18-Dec-2015

220 views

Category:

Documents


3 download

TRANSCRIPT

1

ASPIRATINGSYSTEMS TRAINING

e-series

2

Overview

e-series model range ASD Software

NetTracerDetector MonitorPipeTracer

3

Pico

4

Pico

The Pico provides the earliest warning to a potential fire condition within localised areas or where space is limited.

Air is drawn from the protected area through a 25mm o.d sampling channel.

The Pico continually monitors the samples from areas up to 850m2

5

The aspirator has a static pressure of 800Pa providing superior detection times in high air low environments

The Pico employs a very high sensitivity smoke detector, with a range of 0.005% to 20% obscuration/metre with four alarm levels.

This wide dynamic range allows early warning detection and the ability to trigger suppression systems.

6

FT1

7

FT1 Single channel large bore aspirated early warning

smoke detection system Uses a high-sensitivity laser smoke detector combined

with a high static pressure centrifugal blower to achieve the earliest warning to a fire condition

The large bore pipes are normally 20mm / 25mm o.d. and are sited so that sampling holes along their length provide wide area detection coverage

The system has four input pipes with individual flow monitoring, each of which can be up to 100metres in length

This unit also comes with a display

8

FT4

9

FT4

Four channel large bore aspirated early warning smoke detection system

The system monitors all four input pipes simultaneously and when a trace level of smoke is detected the system raises an initial alert and then performs a rapid scan of each pipe to locate the source of the incident

10

FT6

11

FT6

Six channel aspirated early warning smoke detection system

The system monitors all six input pipes simultaneously and when a trace level of smoke is detected the system raises an initial alert and then performs a rapid scan of each pipe to locate the source of the incident

12

FT6 Enviro

13

RSU Enviro option

Enviro. offers an integrated fire, security and environmental monitoring system in a single package

Sensor inputs monitor changes in room temperature and humidity, and provide flood detection

Gas detection is integrated for toxic hazards or to supplement the early warning smoke detection where a known emission such as CO is present

14

FT15

15

FT15

High performance rotary pump enables 50m pipe runs using microbore tubing

15 different sectors can be simultaneously monitored

Small-bore pipes enable concealed installation

16

ASD

17

ASD - High Performance Aspirator The ASD allows the use of simple point

detectors within an aspirated system The system incorporates two analogue

addressable point detectors providing the ability for failsafe redundancy or mixed detection strategies

The ASD utilises a high performance aspirator and flow monitoring circuit

18

The flow level is displayed on a 10 element bargraph with adjustments for high and low flow thresholds

Flow failure is reported to the central panel as a device fault on the primary detector

The ASD incorporates an in-line air filter to remove dust particles from the air sample

19

Filter is housed in a removable transparent cartridge enabling rapid inspection and maintenance

The ASD provides closed loop sampling whereby the exhausted air can be completely returned to the sampled area making it particularly suitable for prison cells, hospitals and duct sampling

20

Software

WinTracer

Detector Monitor

PipeTracer

NetTracer

21

WinTracer WinTracer software

provides a central monitoring service for smoke and gas detection systems

22

Central monitoring, calibration and control of all functions.

Fully Accessible anywhere across the globe

Graphical interface enables fast review of the situation, improving reaction times

It has barcharts/spreadsheets of current data

23

Front panel representations of the attached units

Data is logged to disk for future requirements and can be displayed in trend graphs

If an alarm occurs, the user is notified clearly with site maps and sound sequences, along with user definable action and hazard lists

24

Detector Monitor

The Detector Monitor (DetMon) software allows the detector to be programmed from a PC

Displays current smoke levels and diagnostics for the Laser Smoke Detector

25

Download/display of rolling data log stored with SRAM inside the Laser Smoke Detector

Displays show current smoke & flow levels, along with the detector status

With this software, the engineer can inspect, diagnose and tune the Laser Smoke Detector to suit the environment of each site

26

The Main Screen showing Diagnostics, Numerical Values, Bar Graph and Strip Chart

27

PipeTracer

Calculates system response times

Models wide-bore systems

Straightforward interface

All factors taken into account Setting initial parameters

28

Details on holes, bends, segments and risers is entered

29

Graphical representations of the system are shown

30

Performance is given for each pipe and the entire system

All data is shown in spreadsheet form

The entered data can then be altered to minimise response time

31

NetTracer - WEB based central monitoring software Supports multiple ASDs – multiple observers Utilises IBM Websphere middle layer 3D graphics for stacked multi-storey floor plans Nationwide site at top layer All site hazards, alarms and faults seen at

nationwide level Stores logged data and flags exceptions Full access control management integrated