1 aspirating systems training e-series. 2 overview e-series model range asd software nettracer ...
TRANSCRIPT
4
Pico
The Pico provides the earliest warning to a potential fire condition within localised areas or where space is limited.
Air is drawn from the protected area through a 25mm o.d sampling channel.
The Pico continually monitors the samples from areas up to 850m2
5
The aspirator has a static pressure of 800Pa providing superior detection times in high air low environments
The Pico employs a very high sensitivity smoke detector, with a range of 0.005% to 20% obscuration/metre with four alarm levels.
This wide dynamic range allows early warning detection and the ability to trigger suppression systems.
7
FT1 Single channel large bore aspirated early warning
smoke detection system Uses a high-sensitivity laser smoke detector combined
with a high static pressure centrifugal blower to achieve the earliest warning to a fire condition
The large bore pipes are normally 20mm / 25mm o.d. and are sited so that sampling holes along their length provide wide area detection coverage
The system has four input pipes with individual flow monitoring, each of which can be up to 100metres in length
This unit also comes with a display
9
FT4
Four channel large bore aspirated early warning smoke detection system
The system monitors all four input pipes simultaneously and when a trace level of smoke is detected the system raises an initial alert and then performs a rapid scan of each pipe to locate the source of the incident
11
FT6
Six channel aspirated early warning smoke detection system
The system monitors all six input pipes simultaneously and when a trace level of smoke is detected the system raises an initial alert and then performs a rapid scan of each pipe to locate the source of the incident
13
RSU Enviro option
Enviro. offers an integrated fire, security and environmental monitoring system in a single package
Sensor inputs monitor changes in room temperature and humidity, and provide flood detection
Gas detection is integrated for toxic hazards or to supplement the early warning smoke detection where a known emission such as CO is present
15
FT15
High performance rotary pump enables 50m pipe runs using microbore tubing
15 different sectors can be simultaneously monitored
Small-bore pipes enable concealed installation
17
ASD - High Performance Aspirator The ASD allows the use of simple point
detectors within an aspirated system The system incorporates two analogue
addressable point detectors providing the ability for failsafe redundancy or mixed detection strategies
The ASD utilises a high performance aspirator and flow monitoring circuit
18
The flow level is displayed on a 10 element bargraph with adjustments for high and low flow thresholds
Flow failure is reported to the central panel as a device fault on the primary detector
The ASD incorporates an in-line air filter to remove dust particles from the air sample
19
Filter is housed in a removable transparent cartridge enabling rapid inspection and maintenance
The ASD provides closed loop sampling whereby the exhausted air can be completely returned to the sampled area making it particularly suitable for prison cells, hospitals and duct sampling
21
WinTracer WinTracer software
provides a central monitoring service for smoke and gas detection systems
22
Central monitoring, calibration and control of all functions.
Fully Accessible anywhere across the globe
Graphical interface enables fast review of the situation, improving reaction times
It has barcharts/spreadsheets of current data
23
Front panel representations of the attached units
Data is logged to disk for future requirements and can be displayed in trend graphs
If an alarm occurs, the user is notified clearly with site maps and sound sequences, along with user definable action and hazard lists
24
Detector Monitor
The Detector Monitor (DetMon) software allows the detector to be programmed from a PC
Displays current smoke levels and diagnostics for the Laser Smoke Detector
25
Download/display of rolling data log stored with SRAM inside the Laser Smoke Detector
Displays show current smoke & flow levels, along with the detector status
With this software, the engineer can inspect, diagnose and tune the Laser Smoke Detector to suit the environment of each site
27
PipeTracer
Calculates system response times
Models wide-bore systems
Straightforward interface
All factors taken into account Setting initial parameters
30
Performance is given for each pipe and the entire system
All data is shown in spreadsheet form
The entered data can then be altered to minimise response time
31
NetTracer - WEB based central monitoring software Supports multiple ASDs – multiple observers Utilises IBM Websphere middle layer 3D graphics for stacked multi-storey floor plans Nationwide site at top layer All site hazards, alarms and faults seen at
nationwide level Stores logged data and flags exceptions Full access control management integrated