Single Shot and Work Tag
On the ADVC Controller
With the flexVUE Operator Interface
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
2/18
Schneider Electric 2 < AUTHOR >
Single Shot Mode
Single Shot Mode is used to
provide an appropriate protection
curve when non-reclosingoperation is required.
For example:
When Auto Reclose is OFF
When closing onto a fault.
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
3/18
Schneider Electric 3 < AUTHOR >
Single Shot Operation
In Single Shot Mode the controllergoes directly to lockout after one
trip and will not Auto-Reclose.
Single Shot Mode is activatedwhen:
-Auto-Reclose is turned off andWork Tag is not applied.
-The circuit breaker is closed byoperator command irrespective ofthe state of Auto-Reclose.
Single Shot is de-activated when:
-Auto-Reclose is turned back on.
-Work Tag is not active, and theSingle Shot Timer expires without a
protection pickup occurring.
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
4/18
Schneider Electric 4 < AUTHOR >
Single Shot Timer
This may be disabled by setting
the Single Shot reset time to zero.
When set to zero, auto-reclosing
will always be enabled while Auto
Reclose is ON.
The Single Shot timer starts when
the switchgear is manually closed
and runs for the preset number ofseconds.
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
5/18
Schneider Electric 5 < AUTHOR >
Single Shot Timer Indication
OPERATOR CONTROLS
Lockout
Single Shot Active
LOCAL CONTROL ON
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
6/18
Schneider Electric 6 < AUTHOR >
Single Shot Timer initiated by Operator Close
SS Timer
CB Status
t
Single Shot
Timer Expires
OPEN CLOSED
Single Shot
Timer Setting
Single Shot Mode Auto Reclose Mode
Operator
Close
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
7/18Schneider Electric 7 < AUTHOR >
Protection Pickup during Single Shot Timing
CB Status
Pickup
t
SS Timer
Operator
Close
OPEN OPEN
Protection
Pickup
Single
Shot
Protection
Trip
CLOSED
Time to Trip
Single Shot
Timer Setting
Single Shot Mode
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
8/18Schneider Electric 8 < AUTHOR >
Protection Reset during Single Shot Timing
CB Status
Pickup
t
SS Timer
OPEN CLOSED
Single Shot
Timer Setting
Protection
Reset
Single Shot Mode
Single Shot
Timer Expires
Operator
Close
Protection
Pickup
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
9/18Schneider Electric 9 < AUTHOR >
Single Shot Protection Settings in WSOS
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
10/18Schneider Electric 10 < AUTHOR >
GLOBAL CONTROL
Global control
(Display, Copy, Trips to
lockout, Seq reset time,
Max time, Auto restore,Auto reclose)
Global pickup
(Current & mult for Phase,
Earth, SEF, NPS)
Fault reset
(FR time, Reset Threshold
Mult for Phase, Earth and
NPS, Start at RstThresh/Pickup)
PROT TRIP SETTINGS
Trip 1, 2, 3, 4
(Reclose time, Protection &
reset curve for P, E, SEF,
NPS)Single Shot
(SS reset time, Protection
& reset curve for P, E, SEF,
NPS)
Work Tag
(Protection & reset curve
for P, E, SEF, NPS)
Under Over Frequency(Under, Over, Normal
Close, Low V inhibit,
Bushing)
Under Over Voltage
(Under, Over, Config)
Loss of Phase
(On/Off/Alarm, Voltage,
Timeout)
PROTECTION CONTROL
Cold Load Pickup
(On/Off, Time, Multiplier)
Inrush Restraint
(On/Off, Time, Multiplier)
High Current Lockout
(On/Off, Current, Trip)
Dead Lockout On/Off
Live Load Blocking On/Off
Sequence Control On/Off
DIRECTIONAL ELEMENT
Directional Blocking
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)Directional Protection
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)
PROTECTION MENU
PROT TRIP SETTINGS
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
11/18
Schneider Electric 11 < AUTHOR >
Single Shot - Summary
An ACR will always go directly to
Lockout following a protection trip
if it is in Single Shot mode.
Providing the Work Tag has not
been applied, an ACR will be in
Single Shot mode if:
Auto Reclose is OFF
An operator has closed onto afault. Providing:
-The Single Shot Timer has not
been set to zero.
The timing of a trip that occurswhen the ACR is in Single Shot
mode is determined by dedicated
Single Shot settings for the
particular type of fault.
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
12/18
Schneider Electric 12 < AUTHOR >
Work Tag
Applying the Work Tag ensuresthat closing cannot take place at
all, either by a local operator, aremote operator or automatically.
The switchgear cannot closewhile the Work Tag is applied but
Work Tag can be applied whenthe switchgear is closed providingnothing is inhibiting tripping.
If a protection trip occurs while theWork Tag is applied, theswitchgear will always go tolockout even if Auto Reclose isON.
The protection pickup and time to
trip will be determined by theWork Tag protection settings andWork Tag Trip will be recorded in
the Event Log.
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
13/18
Schneider Electric 13 < AUTHOR >
Selecting Work Tag ON in WSOS
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
14/18
Schneider Electric 14 < AUTHOR >
OPERATOR CONTROLS
Local/Remote
Autoreclose ON/OFF
Earth SEF ON/OFF
NPS Alarm/Trip/OFF
Protection Group Active
APGS Off/Auto
Work Tag On/OFF
Cold LoadBattery health test manual
start
Radio supply On/Off
Low Gas Inhibit on/off
Demand Period
Sequence
SWITCHGEAR STATUS
Switchgear Info
(Function, Type, Serial #,
Rating, Software version)
Switchgear Data
(Pressure, Status,
Operations Count, Contact
Wear)
MEASUREMENTS
System Measurements
(AVG Current, Voltage,
Frequency, Power Factor,
3 PH Power P and Q)
Current
(Phase, Earth Magnitude &
Angle)
Bushing Indication
(Source and Load side
Live/Dead)
Maximum Demand Ind
(Phase Max & time, Reset)
INDICATIONS
Flags
(O/C, E/F, SEF, LOP, UOV,
NPS, EXT, FRQ)
Operations Count
OPERATOR MENU
OPERATOR CONTROLS
OPERATOR CONTROLS
Work Tag OFFWork Tag Applied
1 Alerts Active
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
15/18
Schneider Electric 15 < AUTHOR >
Work Tag Protection Settings in WSOS
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
16/18
Schneider Electric 16 < AUTHOR >
GLOBAL CONTROL
Global control
(Display, Copy, Trips to
lockout, Seq reset time,
Max time, Auto restore,Auto reclose)
Global pickup
(Current & mult for Phase,
Earth, SEF, NPS)
Fault reset
(FR time, Reset Threshold
Mult for Phase, Earth and
NPS, Start at RstThresh/Pickup)
PROT TRIP SETTINGS
Trip 1, 2, 3, 4
(Reclose time, Protection &
reset curve for P, E, SEF,
NPS)Single Shot
(SS reset time, Protection
& reset curve for P, E, SEF,
NPS)
Work Tag
(Protection & reset curve
for P, E, SEF, NPS)
Under Over Frequency(Under, Over, Normal
Close, Low V inhibit,
Bushing)
Under Over Voltage
(Under, Over, Config)
Loss of Phase
(On/Off/Alarm, Voltage,
Timeout)
PROTECTION CONTROL
Cold Load Pickup
(On/Off, Time, Multiplier)
Inrush Restraint
(On/Off, Time, Multiplier)
High Current Lockout
(On/Off, Current, Trip)
Dead Lockout On/Off
Live Load Blocking On/Off
Sequence Control On/Off
DIRECTIONAL ELEMENT
Directional Blocking
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)Directional Protection
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)
PROTECTION MENU
PROT TRIP SETTINGS
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
17/18
Schneider Electric 17 < AUTHOR >
Work Tag and Controller Mode
The controller is always in either
Local or Remote mode.
Only a local operator can
apply/remove the Work Tag when
the controller is in Local Mode.
Only a remote operator can
apply/remove the Work Tag when
the controller is in Remote Mode.
This means that for a local
operator to remove the Work Tag
which was applied by a remote
operator, they must first put the
controller into Local mode. OPERATOR CONTROLSWork Tag AppliedWORK TAG DENIED- CHANGE TO LOCALSELECT to continue
-
7/28/2019 06 ADVC_206J_FV Single Shot and Work Tag
18/18
Schneider Electric 18 < AUTHOR >
Single Shot and Work Tag Modes
Single Shot and Work Tag modeswill both cause an ACR to go
directly to Lockout if a protectiontrip occurs.
i.e.
-They both prevent automatic
reclosing.
Work Tag mode prevents manualclosing as well.
Single Shot and Work Tag tripsoccur according to their own
respective settings.
i.e.
-In Single Shot mode the ACRwill trip according to the Single
Shot settings.
-In Work Tag mode the ACR willtrip according to the Work Tagsettings.
An ACR will always be in WorkTag mode if the Work Tag isapplied regardless of the SingleShot status.