HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 2
The connection between EMU and BTS
DB9
RJ45
MON1 UEIU (RJ45)
![Page 3: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/3.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 3
Cable Power
Connect to SPARE1
![Page 4: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/4.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 4
DIP Switch on DEMU
SW_RST
SW1 - SW8
SW9 – SW16
SW17 – SW24
SW25 – SW32
![Page 5: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/5.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 5
Water Immersed Sensor
Temperature and Humidity Sensor
Smog
Door Sensor----> Move to switch 9 (SW9)
Special Alarm
Extend Alarm
![Page 6: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/6.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 6
Special Alarm
Temp & Humi Smog
Water
![Page 7: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/7.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 7
External Alarm
![Page 8: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/8.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 8
How to find main fail, module rectifier fail and
Battery low voltage ??
Hold until alarm appear, check all cable output by
Multimeter, which cable short/open because this alarm give
label “Module rectifier fail”
Return it back to normal:
Turn off one MCB AC Main
Turn off one MCB AC Main, check all cable output by
Multimeter, which cable short/open because this alarm,
will be have 2 alarm appear:
1st “Main fail “
2nd “Module rectifier fail” (already give label before)
Check load current, go to
“configuration low load” and set low
load limit higher than load current,
check all cable output by Multimeter,
which cable short/open because this
alarm give label “Battery low
voltage”
![Page 9: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/9.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 9
Configuration in LMT
Add DEMU board in subrack 2 slot 1
![Page 10: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/10.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 10
Configure DEMU board attributes
- Gate Magnetism disabled because gate sensor move to Switch 9
- Water Immersed in low level because sensor output NO (Normaly Open)
![Page 11: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/11.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 11
32 Switch can used
If sensor output NC (Normally Close), switch valid level High level
If sensor output NO (Normally Open), switch valid level Low level
![Page 12: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/12.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 12
Alarm auto clear permit
![Page 13: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/13.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 13
How to rename alarm ID in LMT base on alarm ID in IM2000 (1)
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=1, SW=OPEN, AID=65384, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=19, SW=OPEN, AID=65420, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=20, SW=OPEN, AID=65422, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=21, SW=OPEN, AID=65424, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=2, SW=OPEN, AID=65386, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=3, SW=OPEN, AID=65388, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=4, SW=OPEN, AID=65390, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=5, SW=OPEN, AID=65392, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=6, SW=OPEN, AID=65394, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=7, SW=OPEN, AID=65396, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=8, SW=OPEN, AID=65398, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=9, SW=OPEN, AID=65400, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=10, SW=OPEN, AID=65402, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=11, SW=OPEN, AID=65404, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=12, SW=OPEN, AID=65406, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=13, SW=OPEN, AID=65408, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=14, SW=OPEN, AID=65410, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=15, SW=OPEN, AID=65412, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=16, SW=OPEN, AID=65414, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=17, SW=OPEN, AID=65416, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=18, SW=OPEN, AID=65418, PT=BOOL;
Use MML and run this command;
![Page 14: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/14.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 14
How to rename alarm ID in LMT base on alarm ID in IM2000 (2)
In LMT open “Alarm Maintenance”, click “Query Alarm Configuration”
Start Alarm ID from: 65384
Start Alarm ID from: 65424
![Page 15: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/15.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 15
How to rename alarm ID in LMT base on alarm ID in IM2000 (3)
Right click an alarm name and then “Set Environment Alarm Configuration”
After Query Alarm Configuration
![Page 16: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/16.jpg)
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential Page 16
How to rename alarm ID in LMT base on alarm ID in IM2000 (4)
Alarm name and alarm saverity after config;
![Page 17: 05 EMU Installation](https://reader031.vdocuments.mx/reader031/viewer/2022012309/55cf8f0e550346703b987f6f/html5/thumbnails/17.jpg)