2007-10-03 Substation Automation and Protection Training
REL 670 Line DistanceProtection IED
Substation Automation andProtection Training
2
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Main application
Line distance protectionterminal for:
Directly earthed networks
Isolated or impedance earthed
networksOH-lines and Cables
Series Compensated Lines
Double circuit lines
Single-, two- or three pole trip
Quadrilateral (IEC) or MHO(ANSI) characteristics
-
8/10/2019 02A SEP-602A_ Line Distance Protection REL_670_1.1
2/18
3
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Main characteristics
Line IED for protection,monitoring and control
Building block in Substation Automation Systems
Completely full scheme
Functional flexibility
Configuration flexibility
Extensive self- supervision
4
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Main features in REL 670
Typical operate time: One cycle
Simultaneous measurement ineach loop and advanced phase
selectionVery low requirement of time tosaturation for CTs includingmaximum remanence
Complete software library for allapplications
Full Bay control functionalityavailable.
-
8/10/2019 02A SEP-602A_ Line Distance Protection REL_670_1.1
3/18
-
8/10/2019 02A SEP-602A_ Line Distance Protection REL_670_1.1
4/18
7
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Single Breaker (A31, A32)
UN
3I>
1/3phO->I
79
SC/VC25/27
A BIload
Z59
3UBF50BF
52PDPD
Contr Interl
86/94I->O
TripBus
Single-Breaker application3 ph trip1/3 ph trip
60FF
*)
*) Only 1/3 ph trip alternative
DR
DR
8
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Multi-Breaker alternative (B31, B32)
Multi-Breaker application3 ph trip1/3 ph trip
DR
UN
3I>
1/3phO->I
79
SC/VC25/27
ABIload
Z59
3UBF50BF
52PDPD
3I>BF50BF
94PDPD
1/3phO->I
79
SC/VC25/27
3I>STUB
50STUB
Multi-Breaker add-on:50STUB3I>BFO->ISCPDTRIPFUSE FAIL
Contr Interl
86/94I->O
86/94I->O60
FF
60FF
*)
*) Only 1/3 ph trip alternative
*)DR
-
8/10/2019 02A SEP-602A_ Line Distance Protection REL_670_1.1
5/18
9
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Functionality Pre-configured IEDs (IEC)
10
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Measuring algorithm
u = i . R + X. di
o. dt
I
UXS XL RL
Same reliablealgorithm as REL5xx
Distance Protection algorithm
-
8/10/2019 02A SEP-602A_ Line Distance Protection REL_670_1.1
6/18
11
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Remote back-up Load encroachment
The green area represents theload encroachment area and cuts any impedanceprotection that might enter in it(in the example ZM03 andZM04).
ZM03
ZM02
ZM01
ZM04
12
A B B A B
, 2 0 0 7
2007-10-03 Substation Automation and Protection Training
Export and import of load
ZL
Z