MEP Sample Set - The TJX Companies, Inc.AutoCAD SHX Text
E1 LIGHTING PLAN LIGHTING PLAN E2 POWER PLAN POWER PLAN E2a POWER PLAN - SUPPLEMENTAL POWER PLAN - SUPPLEMENTAL E3 PANEL SCHEDULES AND ONE-LINE DIAGRAM PANEL SCHEDULES AND ONE-LINE DIAGRAM E4 ELECTRICAL DETAILS ELECTRICAL DETAILS M0 MECHANICAL NOTES & SCHEDULES MECHANICAL NOTES & SCHEDULES M1 MECHANICAL PLAN MECHANICAL PLAN M2 MECHANICAL DETAILS MECHANICAL DETAILS P0 PLUMBING NOTES & SCHEDULES PLUMBING NOTES & SCHEDULES P1 PLUMBING PLAN PLUMBING PLAN P2 PLUMBING PLANS AND RISER DIAGRAMS PLUMBING PLANS AND RISER DIAGRAMS P3 PLUMBING GENERAL DETAILSPLUMBING GENERAL DETAILS
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST LANDLORD CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT, INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE APPLICABLE TJX GUIDE SPECIFICATIONS REFERENCED IN THE LEASE.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTES ARE INCLUDED THROUGHOUT THE SAMPLE MEP SET TO ASSIST THE SITE ADAPT CONSULTANT IN UNDERSTANDING THE TENANT'S DESIGN INTENT. DESIGNER NOTES DO NOT COVER EVERY SITUATION THAT MAY BE ENCOUNTERED BY THE SITE ADAPT CONSULTANT. THE SITE ADAPT CONSULTANT IS COMPLETELY RESPONSIBLE FOR THE DESIGN OF THE SITE ADAPTED PROJECT, INCLUDING SITE SPECIFIC LOAD CALCULATIONS, AND COMPLIANCE WITH ALL REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. PROJECT SPECIFIC SITE ADAPTED MEP DRAWINGS SHALL BE PREPARED UNDER THE SUPERVISION OF PROFESSIONAL ENGINEERS LICENSED IN THE JURISDICTION HAVING AUTHORITY OVER THE PROJECT. ALL SITE ADAPT CONSULTANTS SHALL PERFORM ALL NECESSARY DUE DILIGENCE. THIS INCLUDES COORDINATION WITH THE AUTHORITY HAVING JURISDICTION, THE FIRE DEPARTMENT, AND ALL SERVING UTILITY COMPANIES. DETAILS INCLUDED IN THE SAMPLE MEP SET SHALL BE MODIFIED BY THE SITE ADAPT CONSULTANT TO COMPLY WITH SPECIFIC REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION FOR THE SITE ADAPTED PROJECT. ITEMS THAT SHALL BE COORDINATED INCLUDE, BUT ARE NOT LIMITED TO: ELECTRICAL METER/CT CONFIGURATION, AVAILABLE FAULT CURRENT, FIRE ALARM SYSTEM NOTIFICATION REQUIREMENTS, EMERGENCY LIGHTING REQUIREMENTS, EXIT SIGNAGE REQUIREMENTS, HVAC LOAD CALCULATIONS, HVAC CONDENSATE DISPOSAL REQUIREMENTS, DOMESTIC WATER PRESSURE AND WATER QUALITY, AVAILABLE NATURAL GAS PRESSURE (WHEN APPLICABLE), AND SANITARY SEWER INVERT AND CONNECTION REQUIREMENTS.
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING; THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS. NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND SIGNATURE
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: COORDINATE SALES FLOOR LIGHT FIXTURE TYPES FOR PROJECTS WITH ACT CEILINGS WITH PROJECT SPECIFIC TJX C-SET.
AutoCAD SHX Text
DESIGNER NOTE: ONLY USE LIGHTING ZONE "c" and "d" IF REQUIRED BY APPLICABLE LOCAL LOCAL CODE.
AutoCAD SHX Text
AutoCAD SHX Text
ENSURE THAT ALL ROWS OF LIGHT FIXTURES ARE STRAIGHT AND LEVEL PRIOR TO OPENING OF STORE. SUPPLY ALL APPURTENANCES NEEDED TO PROVIDE A COMPLETE AND OPERATION INSTALLATION. PAINT ALL CONDUITS, CHANNEL, RODS, AND APPURTENANCES TO MATCH STRUCTURE. PROVIDE AND INSTALL ALL MATERIALS NECESSARY TO ENSURE PROPER SEISMIC BRACING AS REQUIRED PER CODES.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONDUIT AND BOX SUPPORTED AS REQUIRED BY FIELD CONDITIONS TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
BEAM CLAMP TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SUPPORT RESTRAINT CLIP MINIMUM (4) PER LIGHT FIXTURE, SECURELY ATTACHED TO CIELING GRID PER N.E.C. 410.36(B)
AutoCAD SHX Text
#12 SAFETY WIRE TIED TO SAFETY WIRE SUPPORT HOLES & FASTENED TO BLDG. STRUCTURE. MINIMUM (2) SAFETY WIRES PER LIGHT FIXTURE PLACED AT DIAGONAL CORNERS. IF CEILING SYSTEM IS FIRE RATED, WIRES ARE TO BE DISTINGUISHABLE BY COLOR OR TAGGING PER NEC 300.11(2)
AutoCAD SHX Text
AutoCAD SHX Text
EXPOSED T-BAR CEILING
AutoCAD SHX Text
NOTE: ALL WIRES ARE TO BE TAUT WITH A MINIMUM OF 3 TIGHT TURNS AROUND SELF - TYPICAL. FIXTURE INSTALLATION TO COMPLY WITH ASTM C636-96 AND U.B.C. SECTION 25.213
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
EMERGENCY REMOTE LIGHT HEADS AND EXIT SIGN, WALL MOUNTED, SEE SPECS.
AutoCAD SHX Text
CEILING MOUNTED SINGLE OCCUPANCY SENSOR SWITCH (PIR) (REFER TO TJX SPECIFICATIONS FOR PRODUCT INFORMATION.)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SINGLE OCCUPANCY SENSOR SWITCH (PIR) (REFER TO TJX SPECIFICATIONS FOR PRODUCT INFORMATION.) +46" OR AS NOTED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SUPPORT MOUNTING DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
1. ZONE 'a' - EMPLOYEE LIGHTING = INTERLOCK W/BURGLAR ALARM SYSTEM ZONE 'a' - EMPLOYEE LIGHTING = INTERLOCK W/BURGLAR ALARM SYSTEM SUCH THAT WHEN THE SYSTEM IS DISARMED THE EMPLOYEE LIGHTING TURNS ON. WHEN BURGLAR ALARM IS ARMED THE EMPLOYEE LIGHTING SHALL TURN OFF. ZONE 'a' SHALL CONTROL THE FOLLOWING LOADS: 50% OF SALES GENERAL LIGHTING (ALTERNATING ROWS) PROCESSING ROOM LIGHTING EMPLOYEE SUPPORT AREAS FITTING ROOM GENERAL LIGHTING UH-1, BB-1, EH-1 EF-1, EF-2, EF-3 2. ZONE 'b' - CUSTOMER LIGHTING = CONTROLLED BY NOVAR TIME SCHEDULE & ZONE 'b' - CUSTOMER LIGHTING = CONTROLLED BY NOVAR TIME SCHEDULE & SHALL BE CAPABLE OF MANUALLY REDUCING THE GENERAL SALES LIGHTING BY 50%. ZONE 'b' SHALL CONTROL THE FOLLOWING LOADS: 50% OF SALES GENERAL LIGHTING (ALTERNATING ROWS) FITTING ROOM MIRROR LIGHTING SALES PERIMETER TRACK LIGHTING JEWELRY CASE LIGHTING 3. ZONE 's' - SIGN & CANOPY LIGHTING = CONTROLLED BY NOVAR PHOTOCELL ZONE 's' - SIGN & CANOPY LIGHTING = CONTROLLED BY NOVAR PHOTOCELL & TIME SCHEDULE. ZONE 'e' SHALL CONTROL THE FOLLOWING LOADS: STOREFRONT SIGNS EXTERIOR CANOPY LIGHTING 4. ZONE 'e' - EXTERIOR WALLPACK LIGHTING = CONTROLLED ONLY BY NOVAR ZONE 'e' - EXTERIOR WALLPACK LIGHTING = CONTROLLED ONLY BY NOVAR PHOTOCELL. ZONE 'e' SHALL CONTROL THE FOLLOWING LOADS: EXTERIOR WALLPACK LIGHTING 5. ZONE 'c' - DAYLIGHT AREA LIGHTING = CONTROLLED BY NOVAR PHOTOCELL ZONE 'c' - DAYLIGHT AREA LIGHTING = CONTROLLED BY NOVAR PHOTOCELL & SHALL BE CAPABLE OF MANUALLY TURNING OFF THE LIGHTS IN DAYLIGHT AREAS. ZONE 'c' SHALL CONTROL THE FOLLOWING LOADS: DAYLIGHT AREAS 6. ZONE 'd' - DISPLAY LIGHTING = CONTROLLED BY NOVAR TIME SCHEDULE. ZONE 'd' - DISPLAY LIGHTING = CONTROLLED BY NOVAR TIME SCHEDULE. ZONE 'd' SHALL CONTROL THE FOLLOWING LOADS: SALE PERIMETER TRACK LIGHTING
AutoCAD SHX Text
NOTE: LIGHTING PATTERN MUST REMAIN AS DRAWN AND : LIGHTING PATTERN MUST REMAIN AS DRAWN AND ADHERE TO THIS PLAN. ALL LIGHT FIXTURES IN SALES AREA WILL BE MOUNTED @ 12'-0"
AutoCAD SHX Text
A.F.F. TO THE UNDERSIDE OF THE FIXTURE. (SEE EXCEPTIONS). G.C. MUST COORDINATE ALL M.E.P. TRADES TO ENSURE. PLEASE CONTACT TJX PROJECT MANAGER AND M.O.D. IMMEDIATELY IF THERE ARE ANY FIXTURE SPACING OR MOUNTING HEIGHT CONFLICTS. TJX WILL NOT BE RESPONSIBLE FOR COSTS INCURRED FOR INCORRECT INSTALLATION AND MOUNTING OF LIGHT FIXTURES WITHOUT PRIOR NOTIFICATION TO TJX P.M. OR M.O.D..
AutoCAD SHX Text
LIGHTING PLAN NOTES
AutoCAD SHX Text
SEE SHEET E2 FOR POWER REQUIREMENTS FOR MIRROR LIGHTS (TYPICAL).
AutoCAD SHX Text
AutoCAD SHX Text
MOUNT DOCK LIGHT @ 6'-6". SEE POWER PLAN SHEET E2 FOR POWER REQUIREMENTS.
AutoCAD SHX Text
A. EXIT SIGNS, EMERGENCY AND NIGHT LIGHTS SHALL BE CONNECTED TO AN UNSWITCHED LIGHTING CIRCUIT, NOT CONTROLLED BY OCCUPANCY SENSORS, SWITCHES, CONTRACTORS, OR RELAY PANEL.
AutoCAD SHX Text
GENERAL LIGHTING NOTES
AutoCAD SHX Text
B. REFER TO "RECESSED LIGHTING FIXTURE SUPPORT DETAIL", SHEET E1, FOR INFORMATION ON SUPPORT OF ALL 2' X 4' RECESSED LIGHT FIXTURES.
AutoCAD SHX Text
C. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND DETAILS FOR EXACT LOCATION OF ALL LIGHTING FIXTURES AND OTHER EQUIPMENT INSTALLED IN THE CEILING SYSTEM. VERIFY EXACT MOUNTING HEIGHTS AND FINISHES WITH ARCHITECT PRIOR TO ROUGH-IN.
AutoCAD SHX Text
D. REFER TO POWER PLANS FOR LOCATIONS OF ELECTRICAL EQUIPMENT.
AutoCAD SHX Text
E. ELECTRICAL J-BOX FOR ALL OVERHEAD TYPE LIGHTS TO BE WITHIN 4' OF EACH ACTUAL LIGHT FIXTURE.
AutoCAD SHX Text
F. SALES FLOOR LIGHTING SHALL BE CIRCUITED EVER OTHER ROW TO OPERATE WITH BUILDING MANAGEMENT SYSTEM (SEE E4 SHEET).
AutoCAD SHX Text
G. SALE FLOOR LIGHTS (NON-EMERGENCY) TO BE MOUNTED AT 12'-0" A.F.F. (UNLESS NOTED OTHERWISE ON TJX C-SET). MECHANICAL, ELECTRICAL, AND PLUMBING TO BE MOUNTED WITH ADEQUATE CLEARANCE BETWEEN TOP OF LIGHTING FIXTURES AND ROOF DECK.
AutoCAD SHX Text
AutoCAD SHX Text
1. STORE LIGHTING (SALES & SUPPORT) SHALL INCORPORATE QUANTUM ELM2 TYPE FIXTURES TO ACT AS EMERGENCY LIGHTS. NUMBER OF FIXTURES TO BE DETERMINED BY CODE.
AutoCAD SHX Text
2. NL-FIXTURES WILL BE WIRED BEFORE A SWITCH OR CONTACTOR. (FIXTURES WILL RUN 24 HOURS)
AutoCAD SHX Text
3. PROCESSING ROOM LIGHTING TO BE MOUNTED AT 13' AFF. (LIGHTING TO BE COORDINATED WITH HVAC & STRUCTURAL STEEL)
AutoCAD SHX Text
AutoCAD SHX Text
4. TYPE A4 PENDANT LIGHTING FITTED WITH LOCKING PLUG. NEMA L5-20P 20A, 125V NEMA L7-20P 20A, 277V E.C. TO FURNISH AND INSTALL APPROVED LOCKING RECEPTACLE AT OPEN DECK CEILING, PER REQUIRED VOLTAGE. NEMA L5-20R 20A, 125V NEMA L7-20R 20A, 277V
AutoCAD SHX Text
5. SECURE EXCESS CORD WITH TIE STRAP ABOVE LIGHT FIXTURE. COORDINATE WITH TJX PROJECT MANAGER.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
POSITION TRACK HEADS 2, 5 AND 8 TO ILLUMINATE GRAPHICS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
CONNECT SALES AREA EM FIXTURES 'R' & EXIT SIGNS 'E' TO CIRCUIT 'HA-29'.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP830 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP830 CS16WL20 (120 V)
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP830 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP830 CS16WL20 (120 V)
AutoCAD SHX Text
E.C. TO FURNISH LOCKING RECEPTACLE AT OPEN DECK CEILING (SEE NOTE 4)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP835 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP835 CS16WL20 (120 V)
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP835 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP835 CS16WL20 (120 V)
AutoCAD SHX Text
E.C. TO FURNISH LOCKING RECEPTACLE AT OPEN DECK CEILING (SEE NOTE 4)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PRSTP16LEDLX100L35KEX/LDW/HC240P277(L7-20) PR16DR16CNFRPT (277V) PRSTP16LEDLX100L35KEX/LDW/HC240P120(L5-21) PR16DR16CNFRPT (120V)
AutoCAD SHX Text
PRSTP16LEDLX100L35KEX/LDW/HC240P277(L7-20) PR16DR16CNFRPT (277V) PRSTP16LEDLX100L35KEX/LDW/HC240P120(L5-21) PR16DR16CNFRPT (120V)
AutoCAD SHX Text
E.C. TO FURNISH LOCKING RECEPTACLE AT OPEN DECK CEILING (SEE NOTE 4)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CAN USE ELM6-LED, ELM-LT, or other Emergency lights in the Acuity ELM family
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: USE DAYLIGHT LIGHTING ZONE "c" AS REQUIRED BY APPLICABLE CODE.
AutoCAD SHX Text
DESIGNER NOTE: PROVIDE EXTERIOR EMERGENCY LIGHTING AS REQUIRED BY LOCAL CODE. WHERE REQUIRED, ADD EM OPTION TO 'K3' FIXTURE(S). IF LOCAL AUTHORITY REQUIRES SEPARATE EMERGENCY LIGHT EOR SHALL CHOOSE FROM ACUITY'S LITHONIA LINE.
AutoCAD SHX Text
HA-6 ZONE 's'
AutoCAD SHX Text
HA-4 ZONE 'e'
AutoCAD SHX Text
H. ALL TRACK IS TO BE MOUNTED ON UNISTRUT. ALL UNISTRUT TO BE PAINTED WHITE & HUNG AS REQUIRED FROM STRUCTURE ABOVE. ALL TRACK USED IN THE STORE IS TO BE WIRED FROM 120V PANEL.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LA-9 ZONE 'b'
AutoCAD SHX Text
LA-1 ZONE 'b'
AutoCAD SHX Text
LA-3 ZONE 'b'
AutoCAD SHX Text
LA-5 ZONE 'b'
AutoCAD SHX Text
LA-7 ZONE 'b'
AutoCAD SHX Text
DESIGNER NOTE: TRACK LIGHTING CIRCUITS SHOWN FOR REFERENCE ONLY. EOR SHALL PROVIDE CIRCUITING AS REQUIRED PER NEC TRACK LIGHTING CALCULATIONS OR PROVIDE CURRENT LIMITING DEVICES AS REQUIRED TO MEET ENERGY CODE REQUIREMENTS. ALL TRACK LIGHTING TO BE 120V.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: NOT ALL LIGHT FIXTURES SHOWN ARE USED ON THIS SAMPLE SET. CURRENT PROTOTYPICAL FIXTURES SHOWN FOR REFERENCE ONLY. MODIFY LIGHT FIXTURE SCHEDULE PER TJX MASTER SCHEDULE TO MATCH ACTUAL PROJECT REQUIREMENTS OF THE SPECIFIC BRAND. REFER TO PROJECT SPECIFIC C-SET. EOR SHALL VERIFY LIGHT FIXTURE SPECIFICATION NUMBERS ARE CORRECT & LIGHT FIXTURE WATTAGES ARE ACCURATE WITH MANUFACTURER OR VENDOR.
AutoCAD SHX Text
DESIGNER NOTE: SALES AREA LIGHTING CIRCUITS SHOWN FOR REFERENCE ONLY. EOR SHALL PROVIDE CIRCUITING AS REQUIRED AND PROVIDE PROPER CALCULATIONS. SALES AREA MUST BE CIRCUITED WITH ZONES EVERY OTHER ROW AS SHOWN.
AutoCAD SHX Text
DESIGNER NOTE: FITTING ROOM, PROCESSING ROOM, OFFICES, RESTROOM & ADDITIONAL EMPLOYEE USED AREAS LIGHTING CIRCUITS SHOWN FOR REFERENCE ONLY. EOR SHALL PROVIDE CIRCUITING AS REQUIRED AND PROVIDE PROPER CALCULATIONS. THESE AREAS MUST BE ON EMPLOYEE CONTROL ZONE AS SHOWN.
AutoCAD SHX Text
DESIGNER NOTE: LIGHT FIXTURE 'L' IS EQUIPPED WITH EMERGENCY LIGHTING FEATURE FOR EMERGENCY EGRESS AT EXTERIOR DOORS. IF LOCAL AUTHORITY REQUIRES SEPARATE EMERGENCY LIGHT EOR SHALL CHOOSE FROM ACUITY'S LITHONIA LINE.
AutoCAD SHX Text
DESIGNER NOTE: EMERGENCY LIGHTING SHOWN FOR REFERENCE AND IS ONLY INTENDED TO BE MINIMUM REQ'D PER TYPICAL C-SET. FINAL QUANTITY AND LOCATIONS OF EMERGENCY LIGHTING SHALL BE PROVIDED BY EOR AND SHALL SATISFY LOCAL CODE REQUIREMENTS.
AutoCAD SHX Text
DESIGNER NOTE: EXTERIOR LIGHTING SHOWN FOR REFERENCE ONLY. EOR SHALL PROVIDE EXTERIOR LIGHTING AS REQUIRED SPECIFIC TO EACH STORE.
AutoCAD SHX Text
DESIGNER NOTE: EXTERIOR LIGHT FIXTURES MUST BE TJX PROTOTYPICAL FIXTURES UNLESS THERE IS A REQUIREMENT TO MATCH EXISTING SHOPPING CENTER FIXTURES.
AutoCAD SHX Text
ALL TRACK IS TO BE MOUNTED TO UNISTRUT. ALL UNISTRUT TO BE FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR, PAINTED WHITE & HUNG WITH AC CABLE AS REQUIRED FROM STRUCTURE ABOVE. ALL TRACK USED IN THE STORE IS TO BE WIRED FROM 120V PANEL.
AutoCAD SHX Text
DESIGNER NOTE: MOUNTING HEIGHT SHALL BE DETERMINED AND COORDINATED WITH SITE SPECIFIC TJX C-SET. CONDITIONS SUBJECT TO CHANGE PER LOCATION AND CHAIN.
AutoCAD SHX Text
AutoCAD SHX Text
J. LIGHT FIXTURES SHALL BE PURCHASED BY CONTRACTOR THRU TENANT'S NATIONAL ACCOUNT. NO SUBSTITUTIONS ALLOWED. REFER TO APPROVED VENDOR LIST IN TJX CRITERIA SET.
AutoCAD SHX Text
K. WIRING CONNECTIONS TO EXTERIOR WALL MOUNTED FIXTURES SHALL BE WEATHER TIGHT. USE WEATHERPROOF JUNCTION BOXES, FITTINGS, COVER PLATES, ETC. AS REQUIRED TO PREVENT ENTRY OF WATER INTO WIRING BOXES.
AutoCAD SHX Text
DESIGNER NOTE: TYPE H3, H4 & H5 USED IN HOMEGOODS STORE FORMAT FOR PERIMETER VALANCE LIGHTING.
AutoCAD SHX Text
DESIGNER NOTE: TYPE Q USED IN COMBO STORE FORMAT OVER SINGLE QUE.
AutoCAD SHX Text
DESIGNER NOTE: TYPE O5 USED TJ MAXX STORES WITH ACT FOR WALL WASHERS AROUND PERIMETER OF STORE
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT, INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
LIGHTING CONTROLS - ALL SWITCHES, OCCUPANCY SENSORS, RELAY PANEL CONTROLS, ETC.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: ALL SUSPENDED LIGHTS, WITH-IN 15' OF CONCENTRIC DIFFUSERS SHALL BE HUNG WITH THREADED ROD. SAME FOR HANGING SIGNS. REFER TO TJX SPECIFICATION SECTION 16A.18 FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING; THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS. NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND SIGNATURE
AutoCAD SHX Text
AutoCAD SHX Text
RESTROOM, LOUNGE, JANITOR, & DRESSING ROOM (WHEN APPLICABLE) EXHAUST FANS, WILL BE A CONTROLLED/SWITCHED CIRCUIT, RUN THROUGH THE GE LIGHTING RELAY PANEL ON THE "EMPLOYEE" CIRCUIT. WHEN REQUIRED, ELECTRIC ROOM AND/OR SYSTEMS ROOM EXHAUST FANS WILL BE A 24 HOUR LIVE CIRCUIT CONTROLLED BY IN LINE THERMOSTAT SET AT 80° DEGREES. SEE SPEC.BOOK FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COMMUNICATIONS GENERAL NOTES
AutoCAD SHX Text
1. CONDUIT ENDS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLE CONDUIT ENDS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLE FROM DAMAGE. BUSHINGS SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR. 2. AT TELEPHONE OUTLETS, PROVIDE 2 " DEEP, SINGLE GANG WALL BOX & " AT TELEPHONE OUTLETS, PROVIDE 2 " DEEP, SINGLE GANG WALL BOX & " 12" DEEP, SINGLE GANG WALL BOX & " 12" CONDUIT WITH PULL STRING STUBBED OUT TO ABOVE ACCESSIBLE CEILING. 3. AT DATA & CABLE OUTLETS, PROVIDE 2 " DEEP, SINGLE GANG WALL BOX & " AT DATA & CABLE OUTLETS, PROVIDE 2 " DEEP, SINGLE GANG WALL BOX & " 12" DEEP, SINGLE GANG WALL BOX & " 34" CONDUIT WITH PULL STRING STUBBED OUT TO ABOVE ACCESSIBLE CEILING. 4. AT TELEPHONE/DATA & TECHNOLOGY OUTLETS, PROVIDE 3" DEEP, 2-GANG WALL AT TELEPHONE/DATA & TECHNOLOGY OUTLETS, PROVIDE 3" DEEP, 2-GANG WALL BOX WITH 2-GANG PLASTIC RING & 1" CONDUIT WITH PULL STRING STUBBED OUT TO ABOVE ACCESSIBLE CEILING. 5. PUBLIC ADDRESS & CLOCK SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT. PUBLIC ADDRESS & CLOCK SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT. 6. ELECTRICAL CONTRACTOR TO PROVIDE & INSTALL WIREMOLD EXTENSION ELECTRICAL CONTRACTOR TO PROVIDE & INSTALL WIREMOLD EXTENSION ADAPTERS #5751 FLUSH TYPE FOR COLUMN MOUNTED PHONES (PHONES BY TENANT).
AutoCAD SHX Text
ELECTRICAL SYMBOLS LEGEND
AutoCAD SHX Text
HOME RUN TO PANEL, CIRCUIT NUMBERS, PHASE, NEUTRAL & GROUND CONDUCTORS INDICATED ALONG WITH ISOLATED GROUND CONDUCTOR IF APPLICABLE CONDUIT INSTALLED CONCEALED ABOVE CEILING OR IN WALL OR AT ROOF STRUCTURE, PAINT TO MATCH STRUCTURE AS APPLICABLE CONDUIT INSTALLED CONCEALED BELOW FLOOR SLAB OR UNDERGROUND AC OR DC CONTROL VOLTAGE WIRING SIMPLEX RECEPTACLE, +18" OR AS NOTED DUPLEX RECEPTACLE, +18" OR AS NOTED ISOLATED GROUND DUPLEX RECEPTACLE, +18" OR AS NOTED, ORANGE COLOR QUADRUPLEX RECEPTACLE, +18" OR AS NOTED ISOLATED GROUND QUADRUPLEX RECEPTACLE, +18" OR AS NOTED, ORANGE COLOR MULTI-RECEPTACLE SYSTEM (PLUGMOLD), INSTALL AS NOTED POWER POLE JUNCTION BOX JUNCTION BOX WITH BLANK COVER PLATE (FOR FUTURE USE) & " CONDUIT WITH PULL STRING STUBBED 34" CONDUIT WITH PULL STRING STUBBED ABOVE CEILING (OR AS INDICATED BY TJX PROJECT MANAGER FOR AREAS WITH OPEN STRUCTURE ABOVE), +18" OR AS NOTED DISCONNECT SWITCH, MOUNT AS NOTED, VERIFY REQUIREMENTS WITH EQUIPMENT SERVED EXHAUST FAN MOTOR CONNECTION, COORDINATE WITH MECHANICAL CONTRACTOR PUSH BUTTON, MOUNT AS NOTED DOOR BELL CHIME OR BUZZER, MOUNT AS NOTED CONTROL TRANSFORMER, INSTALL AS NOTED HVAC SENSING DEVICE @ +60", VERIFY LOCATIONS W/NOVAR, PROVIDE BACK-BOX & " CONDUIT TO UNIT 34" CONDUIT TO UNIT INDICATED TELEPHONE BOX-WALL HUNG, INSTALL AS NOTED WITH " CONDUIT WITH PULL STRING STUBBED ABOVE 34" CONDUIT WITH PULL STRING STUBBED ABOVE CEILING (OR AS INDICATED BY TJX PROJECT MANAGER FOR AREAS WITH OPEN STRUCTURE ABOVE) TELEPHONE BOX-DESK SET, INSTALL AS NOTED WITH " CONDUIT WITH PULL STRING STUBBED ABOVE 34" CONDUIT WITH PULL STRING STUBBED ABOVE CEILING (OR AS INDICATED BY TJX PROJECT MANAGER FOR AREAS WITH OPEN STRUCTURE ABOVE) TELEPHONE/DATA BOX, INSTALL AS NOTED WITH 1" CONDUIT WITH PULL STRING STUBBED ABOVE CEILING (OR AS INDICATED BY TJX PROJECT MANAGER FOR AREAS WITH OPEN STRUCTURE ABOVE) WIREMOLD ALA4800B SURFACE MOUNTED RACEWAY ELECTRIC DOOR STRIKE, SEE SPECS. PUSH BUTTON, HEIGHT AS NOTED. LOW VOLTAGE WIRING CONDUIT & JUNCTION BOX BY G.C. W/PULL WIRE. (WIRING BY OTHERS)
AutoCAD SHX Text
AutoCAD SHX Text
NOTES: REFER TO LIGHT FIXTURE SCHEDULE & SYMBOL LIST FOR SPECIFICATION & INFORMATION ON ALL LUMINAIRES. REFER TO SPECIFICATIONS & PLAN NOTES FOR DETAILED DESCRIPTION OF ALL DEVICES SHOWN IN THIS SCHEDULE, PROVIDED BY THIS CONTRACTOR. MOUNTING HEIGHTS INDICATED ARE MEASURED FROM FINISHED FLOOR TO THE CENTERLINE OF THE DEVICE UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
G.C./E.C. TO PROVIDE A 110VAC, CONTINUOUSLY ELECTRIFIED & NOT CONTROLLED BY A SWITCH, DUPLEX OUTLET AT THE CONDUIT TERMINATION POINT ABOVE THE VESTIBULE CEILING. G.C./E.C. TO PROVIDE AN 18"x18" (MINIMUM) ACCESS PANEL AT THIS LOCATION IN THE EVENT THE VESTIBULE IS A HARD CEILING.
AutoCAD SHX Text
G.C. RESPONSIBLE TO CONTRACT "STANLEY ACCESS TECHNOLOGIES" TO PROVIDE & INSTALL VESTIBULE SLIDING DOORS.
AutoCAD SHX Text
G.C. ELECTRICIAN RESPONSIBLE FOR ALL FINAL CONNECTIONS TO SLIDING DOORS.
AutoCAD SHX Text
DUPLEX OUTLET FOR FUTURE CART CONTAINMENT SYSTEM. (LOCATE 6" ABOVE VESTIBULE FINISHED CEILING) CENTERED BETWEEN INTERIOR DOORS. CONTINUOUSLY ELECTRIFIED AND NOT CONTROLLED BY A SWITCH.
AutoCAD SHX Text
G.C. ELECTRICIAN TO PROVIDE (1) 120 V. 20 AMP DEDICATED CIRCUIT FOR THE INTERIOR SET OF DOORS AND (1) 120 V. 20 AMP DEDICATED CIRCUIT FOR THE EXTERIOR SET OF DOORS. ( LOCATE 6"ABOVE FINISHED CEILING) (1) 10 AMP LINE TO EACH DOOR OPERATOR. ELECTRICAL TERMINATIONS BY E.C.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
1. VERIFY EXACT LOCATIONS OF HVAC EQUIPMENT, CONDUIT STUB-UPS & POWER VERIFY EXACT LOCATIONS OF HVAC EQUIPMENT, CONDUIT STUB-UPS & POWER CONNECTIONS PRIOR TO ROUGH-IN. 2. VERIFY EXACT LOCATION, MOUNTING HEIGHTS & CONDUIT ROUTING FOR ALL VERIFY EXACT LOCATION, MOUNTING HEIGHTS & CONDUIT ROUTING FOR ALL THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS & CO2 SENSORS WITH TEMPERATURE CONTROLS CONTRACTOR PRIOR TO ROUGH-IN. 3. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL ELECTRICAL REQUIREMENTS. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL ELECTRICAL REQUIREMENTS. COORDINATE PROVISIONS FOR ALL CONTROL CONDUIT & WIRING AS REQUIRED FOR INTERLOCKING OF FANS, MOTORS, ETC. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 4. ALL DEVICES INSTALLED ON HVAC EQUIPMENT SHALL BE MOUNTED ON A ALL DEVICES INSTALLED ON HVAC EQUIPMENT SHALL BE MOUNTED ON A NON-REMOVABLE PANEL OF THE EQUIPMENT. THIS LOCATION SHALL BE COORDINATED WITH THE MECHANICAL AND/OR PLUMBING CONTRACTOR PRIOR TO COMMENCING ANY ROUGH-IN WORK.
AutoCAD SHX Text
AutoCAD SHX Text
1. FIRE ALARM CABLING SHALL BE INSTALLED IN CONDUIT. FIRE ALARM CABLING SHALL BE INSTALLED IN CONDUIT. 2. DUCT TYPE SMOKE DETECTORS SHALL BE FURNISHED, INSTALLED & WIRED BY DUCT TYPE SMOKE DETECTORS SHALL BE FURNISHED, INSTALLED & WIRED BY MECHANICAL CONTRACTOR. SEE DETAIL THIS DRAWING. 3. FIRE ALARM SYSTEM HVAC SHUT DOWN RELAYS SHALL BE PROVIDED & WIRED FIRE ALARM SYSTEM HVAC SHUT DOWN RELAYS SHALL BE PROVIDED & WIRED TO FIRE ALARM CONTROL PANEL BY FIRE ALARM CONTRACTOR. E.C. SHALL PROVIDE CONDUIT WITH PULL STRING FROM RELAY TO HVAC UNIT. UNIT SHUT DOWN CONTROL WIRING SHALL BE PROVIDED BY MECHANICAL CONTRACTOR.
AutoCAD SHX Text
AutoCAD SHX Text
J-BOX FOR CUSTOMER COUNTER. INSTALL 6" ABOVE BOTTOM OF LIGHT FIXTURE HEIGHT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COORDINATE WALL MOUNTED ELECTRICAL WITH CASH CABINET LOCATION. IF STOREFRONT GLASS EXISTS BEHIND CABINET, FIELD VERIFY MOUNTING HEIGHT OF ELECTRICAL WITH TJX PROJECT MANAGER. MOUNT FIRE ALARM ANNUNCIATOR PANEL IN A VISIBLE LOCATION BEHIND CASHWRAP OR AS DIRECTED BY AUTHORITY HAVING JURISDICTION. COORDINATE W/TJX CONSTRUCTION MANAGER. DUPLEX RECEPTACLES FOR 'EAS' SECURITY SHALL BE CONNECTED TO THE SAME CIRCUIT THROUGHOUT CASH REGISTER AREA. MOUNT HORIZONTALLY AT 49" AFF. DEDICATED SIMPLEX RECETACLE TO BE MOUNTED TO END CHECKOUT UNIT. SEE DETAIL SHEET E4 FOR ADDITIONAL INFORMATION. (3) 2 " CONDUITS TO BE CONCEALED IN FLOOR & WALL ON SALES AREA SIDE. 12" CONDUITS TO BE CONCEALED IN FLOOR & WALL ON SALES AREA SIDE. CONDUIT TERMINATION POINT LOCATED UNDER CASH REGISTER COUNTER. FIELD VERIFY AND COORDINATE EXACT LOCATION. METAL "PANCAKE" MOLDING #1500 1 " x " x 10'-0" (A) AT FLOOR FOR WIRING TO DISPLAY CASE 12" x " x 10'-0" (A) AT FLOOR FOR WIRING TO DISPLAY CASE 12" x 10'-0" (A) AT FLOOR FOR WIRING TO DISPLAY CASE LIGHTING FIXTURES. ELECTRICAL CONTRACTOR TO FURNISH & INSTALL A MASTER ON/OFF SWITCH MOUNTED AT REGISTER WELL CABINET TO CONTROL ON/OFF OF CASE LIGHTING. CASES TO BE LEFT IN THE "ON" POSITION. SEE SHEET E4 FOR POWER POLE REQUIREMENTS. MAKE FINAL CONNECTION TO JEWELRY CASE LIGHTING. FOR EACH EXTERIOR SIGN, ELECT. CONTRACTOR SHALL PROVIDE (3) 20A, 120V CIRCUITS TO (3) 3-GANG JUNCTION BOXES. MIDDLE JUNCTION BOX SHALL BE CENTERED ON SIGN FIELD, REMAINING JUNCTION BOXES @ 10'-0" TO CENTERLINE, EITHER SIDE. CONTROLLED BY B.M.S. CONTACTOR. COORDINATE EXACT LOCATION OF CIRCUITS WITH TJX SIGN VENDOR & TJX PROJECT MANAGER. SEE SPEC. 16A. PROVIDE 30A, 3P, 480V, NEMA 3R, FUSED DISCONNECT SWITCH MOUNTED ON THE EXTERIOR WALL FOR TRASH COMPACTOR. DISCONNECT SWITCH SHALL BE WITHIN SIGHT OF COMPACTOR. COORDINATE REQUIREMENTS WITH COMPACTOR INSTALLER & PROVIDE FINAL CONNECTION, INCLUDING COMPACTOR CONTROL PANEL. (3) #8 & (1) #8 GROUND IN 1" CONDUIT. PROVIDE 20A, 120A CIRCUIT TO POWER SUPPLY FOR CASH OFFICE MANTRAP SYSTEM & EDWARDS SIGNALING BUILDERS CHIME KIT (C212 SERIES, FURNISHED BY CONTRACTOR). PROVIDE ALL REQUIRED WIRING, CONDUIT, ACCESSORIES & CONNECTIONS. VERIFY LOCATIONS OF ALL DEVICES WITH TJX PROJECT MANAGER. SEE DETAIL 5/E4 FOR ADDITIONAL INFORMATION. PROVIDE (1) PLUGMOLD AT LP DESK & (2) QUADRUPLEX RECEPTACLES BELOW LP DESK. SEE DETAIL SHEET E4 FOR ADDITIONAL INFORMATION. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER. PROVIDE QUADRUPLEX RECEPTACLE ABOVE CEILING FOR LOSS PREVENTION EQUIPMENT& TRANSFORMERS. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER. PROVIDE 2" CONDUIT SLEEVE & GOOSENECK THROUGH ROOF FOR SATELLITE CABLES. CONDUIT SHALL PENETRATE ROOF OUTSIDE OF ROOM BUT WITHIN 5'-0" OF IT'S PERIMETER. SEE SPEC. BOOK & COORDINATE EXACT LOCATION WITH TJX PROJECT MANAGER PRIOR TO INSTALLATION. FURNISH & INSTALL REAR DOOR ALARM CONTROL SYSTEM AT THE STOCKROOM MAN DOOR. PROVIDE 120 VOLT CIRCUIT (UNSWITCHED) AND A LOW VOLTAGE TRANSFORMER (24V/50 VA) U.L. APPROVED (AS REQUIRED), ABOVE THE HEAD OF THE DOOR (WITHIN 10'-0"). ALARM SHALL BE ACTIVATED BY DOOR CONTACTORS WHEN DOOR IS OPEN POSITION AND SHALL PRODUCE A CONTINUOUS CHIME TONE. WHEELOCK 38GV29 FROM GRAINGER MODEL #CH121092 & REQUIRED ACCESSORIES. VERIFY W/TJX P.M. PRIOR TO INSTALLATION. PROVIDE CONNECTION FOR HAND DRYER. COORDINATE HEIGHT & LOCATION FOR ELECTRIC DRYER WITH TJX PROJECT MANAGER. PROVIDE REQUIRED SIZED CONDUIT & (2) JUNCTION BOXES WITH BLANK PLATES AT LOCATION OF FIRE ALARM PANEL. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER & LOCAL AUTHORITY HAVING JURISDICTION PRIOR TO INSTALLATION. COORDINATE ALL INTEGRATION WITH EXISTING FIRE ALARM SYSTEM AS REQUIRED. PROVIDE 30A, 2P TOGGLE SWITCH WITH (2) #10 & (1) #10 GROUND FOR WATER HEATER. COORDINATE REQUIREMENTS WITH PLUMBING CONTRACTOR. PROVIDE JUNCTION BOX FOR COAXIAL CABLE @ 7'-6" AFF. INSTALL HORIZONTALLY ADJACENT TO DUPLEX RECEPTACLE. INSTALL CONDUIT WITH PULL-STRING TO 6" ABOVE FINISHED CEILING. MOUNT DUPLEX RECEPTACLE FOR STORE SECURITY SYSTEM ABOVE CEILING, NEAR DOOR. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER PRIOR TO INSTALLATION. ROOFTOP UNIT SMOKE DETECTOR. PROVIDE REMOTE TEST MOUNTED IN LOCATION DICTATED BY LOCAL FIRE AUTHORITY. IF MOUNTED TO NEAREST COLUMN, PLACE ON TELEPHONE SIDE OF COLUMN AND HIGHER THAN SLAT WALL FINISH. CIRCUIT 'LB-34'. (TYPICAL FOR ALL ROOFTOP UNITS). COORDINATE WITH GENERAL CONTRACTOR. . MOUNT DUPLEX RECEPTACLE ABOVE FINISHED CEILING FOR FUTURE P.V.M. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER PRIOR TO INSTALLATION. PROVIDE POWER POLE FOR JEWELRY COUNTER POWER & DATA. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER. SEE DETAIL SHEET E4 FOR ADDITIONAL INFORMATION. VIBRATING BELL & WEATHERPROOF PUSH BUTTON. PROVIDE 120V CIRCUIT (UNSWITCHED). VERIFY W/TJX P.M. PRIOR TO INSTALLATION. JUNCTION BOX MOUNTED AT 48" A.F.F. FOR DRESSING ROOM MIRROR LIGHT CONNECTION. MAKE FINAL CONNECTION. LOCATE FOR EMPLOYEE TIME CLOCK. MOUNT AT 54" A.F.F. COORDINATE EXACT LOCATION OF MANAGER'S OFFICE DEVICES W/TJX PROJECT MANAGER PRIOR TO ROUGH-IN. MOUNT DEVICES IN THIS ROOM @ 41" A.F.F. UNLESS NOTED OTHERWISE. PROVIDE POWER POLE FOR POP COOLER RECEPTACLE. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER. PROVIDE MATCHING RECEPTACLE. PROVIDE 20-AMP DEDICATED DUPLEX RECEPTACLE @ 7'-6" AFF. INSTALL HORIZONTALLY CENTERED ON WALL. WEATHER PROOF GFCI RECEPTACLE SHIPPED LOOSE W/ROOF TOP UNIT. FINAL INSTALLATION & CONNECTION BY ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: : JEWELRY COUNTERS ARE SUPPLIED BY TJX. FINAL CONNECTION BY ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
DESIGNER NOTE: VERIFY TRASH COMPACTOR VOLTAGE. 480V/3P = 30A DISCONNECT 208V/3P = 60A DISCONNECT
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT, INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
G.C. TO COORDINATE ELECTRIFIED STORE FIXTURES WITH DEPARTMENT LAYOUTS FROM THE FINAL FIXTURE PLAN.
AutoCAD SHX Text
DESIGNER NOTE: PROVIDE ADDITIONAL JUNCTION BOX FOR CANOPY BLADE SIGN AS NEEDED. VERIFY WITH TJX PROJECT MANAGER.
AutoCAD SHX Text
DESIGNER NOTE: POWER POLE FOR BEVERAGE COOLER SHOWN FOR REFERENCE ONLY. IF BEVERAGE COOLER IS LOCATED ON THE WALL, NO POWER POLE IS REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: EXHAUST FAN EF-4 ONLY REQUIRED WHEN PARTITION CONSTRUCTION IS FULL HEIGHT. REFER TO MECHANICAL DRAWINGS.
AutoCAD SHX Text
AutoCAD SHX Text
HA-18 ZONE 'a'
AutoCAD SHX Text
DESIGNER NOTE: ALL MECHANICAL INFO SHOWN FOR REFERENCE ONLY. ACTUAL DESIGN & LOCATIONS SHALL BE BASED ON MECHANICAL ENGINEER'S CONSTRUCTION DOCUMENTS.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: HVAC CONTROL DEVICES SHOWN FOR REFERENCE ONLY. ACTUAL LOCATIONS SHALL BE DETERMINED BY NOVAR.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: FIRE ALARM PANEL LOCATION SHOWN FOR REFERENCE ONLY. EOR SHALL VERIFY EXACT LOCATION WITH LOCAL AHJ.
AutoCAD SHX Text
DESIGNER NOTE: ELECTRIC ROOM LAYOUT SHOWN FOR REFERENCE ONLY. EOR SHALL LAYOUT ELECTRIC BASED ON C-SET AND/OR EXISTING CONDITIONS.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: NOTES #8, 11, 16, 19, 22, 23, 25 & 30 DO NOT APPLY TO HOMEGOODS & HOMESENSE STORES.
AutoCAD SHX Text
DESIGNER NOTE: VESTIBULE DETAIL SHOWN FOR REFERENCE ONLY. ACTUAL LAYOUT SHALL BE PER TJX C-SET.
AutoCAD SHX Text
DESIGNER NOTE: COMMUNICATION NOTES, FIRE ALARM NOTES & HVAC NOTES SHOWN FOR REFERENCE ONLY. NOTES SHALL BE REVISED AS NEEDED TO MEET PROJECT & CODE REQUIREMENTS.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: RTU-6 LOCATION IS NOT ACTUAL. SHOWN HERE FOR CLARITY. REFER TO HVAC FOR RTU LOCATIONS, SHALL BE LOCATED OVER THE AREA SERVED.
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING; THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS. NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND SIGNATURE
AutoCAD SHX Text
NOTE: GENERAL CONTRACTOR'S ELECTRICAL ENGINEER/ELECTRICIAN RESPONSIBLE FOR ALL HUBBELL PLUGTRAK SYSTEM (WALL AND GONDOLA) CIRCUITRY CALCULATIONS PER THE NATIONAL ELECTRIC CODE. (PLUGTRAK RECEPTACLES 6" ON CENTER.) ALL PLUGTRAK CIRCUITS CONTROLLED BY NOVAR ENERGY MANAGEMENT SYSTEM. (4) FOUR CIRCUITS PER GONDOLA (MIN.) (1) ONE REQUIRED AT EACH SIDE AT CENTER SPLINE & AT BOTH ENDS.
AutoCAD SHX Text
GONDOLA PLUGTRAK = POWER POLE LOCATED AT THE REAR OF = POWER POLE LOCATED AT THE REAR OF THE GONDOLA TO WIRE TWO ROWS OF PLUGTRAK. CENTERLINE OF PLUGTRAK SET @ 8" & 39" FROM THE TOP OF THE GONDOLA BASE DECK (14" & 43 1/2" A.F.F.). (SEE PROFILE IN THE HOMEGOODS FIXTURE INSTALLATION MANUAL)
AutoCAD SHX Text
WALL "LAMPS" PLUGTRAK = INSTALL WIRE PLUGTRAK WHERE = INSTALL WIRE PLUGTRAK WHERE LAMPS INDICATED ON THE WALL. CENTERLINE OF PLUGTRAK SET @ 8" & 39" ABOVE THE BASE DECK (14" & 43 1/2" A.F.F.).
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Box - B2432 - B2432 Cover - S3825 (x2) - S3825 (x2) Flange - SB3084- SB3084
AutoCAD SHX Text
NOTE: ALL CIRCUITS CONTROLLED BY NOVAR ENERGY MGMNT SYSTEM, ON CUSTOMER LIGHTING.
AutoCAD SHX Text
NOTE: ALL CIRCUITS CONTROLLED BY NOVAR ENERGY MGMNT SYSTEM, ON CUSTOMER LIGHTING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: MAXIMUM OF 5 FANS PER CIRCUIT. EACH FAN CONTROLED BY A TIMER SWITCH. SWITCH MOUNTED AT 4'-0" AFF. FAN SPEC: TPI CACU-24W TIMER SWITCH SPEC: TORK C506H FAN AND TIMER SWITCH PURCHASED BY G.C.
AutoCAD SHX Text
AutoCAD SHX Text
LOCATE FOR WALL-MOUNTED FAN. FAN TO BE CONTROLLED VIA TORK A506H 6-HOUR SPRING WOUND WALL MOUNTED TIMER & BE ON ZONE 'a'. SEE DETAIL 3/E2.
AutoCAD SHX Text
DESIGNER NOTE: DETAILS AND KEYED NOTES ARE ASSOCIATED WITH CHAIN DIFFERENCES RELATED TO HOMEGOODS OR HOMESENSE STORES ONLY. DETAILS INCLUDED FOR REFERENCE, REFER TO SITE SPECIFIC C-SET FOR DETAILS AND DIRECTION.
AutoCAD SHX Text
AutoCAD SHX Text
PLUG TRACK (FED VIA POWER POLE): 22':LA-30, 22':LA-32, 22':LA-34, 22':LA-36 (ALL ZONE 'b')
AutoCAD SHX Text
AutoCAD SHX Text
PLUG TRACK (FED VIA POWER POLE): 22':LA-22, 22':LA-24, 22':LA-26, 22':LA-28 (ALL ZONE 'b')
AutoCAD SHX Text
PLUG TRACK (FED VIA POWER POLE): 22':LA-38, 22':LA-40, 22':LA-41, 22':LA-42 (ALL ZONE 'b')
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: PLUGTRAK LAYOUT & CIRCUITING SHOWN FOR REFERENCE ONLY. PLUGTRAK LAYOUT SHALL BE DICTATED BY TJX C-SET. EOR SHALL PROVIDE CIRCUITING & LOAD CALCULATIONS @ 75W/FOOT PER NEC. EACH GRAPHIC ROW OF PLUGTRAK IS ACTUALLY (2) ROWS OF PLUGTRAK.
AutoCAD SHX Text
DESIGNER NOTE: DISPLAY LIGHTING FLOOR RECEPTACLES SHALL BE (2) DUPLEX RECEPTACLES PER CIRCUIT MAX.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXTERIOR J-BOX MOUNTED 6" ABOVE OVERHEAD DOOR COIL. RIGHT/LEFT OF ANY EXTERIOR LIGHT FIXTURE. PENETRATION TO BE WEATHERTIGHT.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: REFER TO SPECIFICATION SECTION 1B FOR CHAINS REQUIRING COMMERCIAL CIRCULATING FANS.
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT, INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING; THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS. NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND SIGNATURE
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
SYSTEM LIGHTING CONTROL ZONE INDICATED.
(3) POWER FEEDS FOR BUILDING MANAGEMENT SYSTEM MUST BE
FED FROM THE SAME PANELBOARD AND PHASE.
GROUND FAULT CIRCUIT INTERRUPTING BREAKER
HANDLE LOCK "ON" CLAMP DEVICE
PROVIDE "HACR" TYPE BREAKER FOR ROOF TOP EQUIPMENT
GENERAL NOTES:
CIRCUIT KEY NOTES:
65,000 A.I.C.
N L Y
SWITCHBOARD 'MDP'. THREE SELF-CONTAINED SPLIT-CORE
KWH TRANSDUCER METERS (PULSE OUTPUT) AROUND SERVICE
WIRES TO PANEL WITH BUILT-IN FUSE HOLDERS AND WIRE
LEADS FOR CONNECTION TO PANEL BUS OR LUGS. PROVIDE
EMPTY 3/4"C TO NOVAR EXECUTIVE CONTROLLER. COORDINATE
ALL REQUIREMENTS WITH NOVAR SYSTEM MANUFACTURER.
PANEL
'LA'
1
1
4
N L Y
N L Y
COPPER ONLY
ADDITIONAL INFORMATION.
N L Y
COPPER ONLY
N L Y
UTILITY COMPANY REQUIREMENTS.
N L Y
N L Y
1 " C W
N L Y
N L Y
1 " C W
N L Y
1 " C W
N L Y
N L Y
N L Y
N L Y
AutoCAD SHX Text
DESIGNER NOTE: ELECTRICAL SERVICE AND ONE-LINE DIAGRAM SHALL BE COORDINATED WITH LOCAL UTILITY AND ALL AUTHORITIES HAVING JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT, INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
AutoCAD SHX Text
THE WORK INCLUDES PROVIDING NEW MATERIALS, FIXTURES, DEVICES AND ACCESSORIES NECESSARY FOR A COMPLETE FUNCTIONING ELECTRICAL SYSTEM. THE WORK ALSO INCLUDES FINAL CONNECTIONS TO MECHANICAL EQUIPMENT ITEMS PROVIDED BY OTHERS. ALL WORK SHALL BE IN ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION, OR ORDINANCES AND SUBJECT TO INSPECTION.
AutoCAD SHX Text
AutoCAD SHX Text
THE INTENT OF THE DRAWINGS IS TO INDICATE THE GENERAL EXTENT OF WORK REQUIRED FOR THE PROJECT. THE DRAWINGS FOR ELECTRICAL WORK ARE DIAGRAMMATIC, SHOWING THE LOCATION, TYPE, DEVICES AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT MEASUREMENTS. PROVIDE ALL FIXTURES, DEVICES ACCESSORIES, OFFSETS, AND MATERIALS NECESSARY TO FACILITATE THE SYSTEM'S FUNCTIONING AS INDICATED BY THE DESIGN AND THE EQUIPMENT FURNISHED BY OTHERS.
AutoCAD SHX Text
COORDINATE WITH WORK OF OTHER SECTIONS, AND WITH THE CONSTRAINTS OF THE EXISTING CONDITIONS OF THE PROJECT SITE. VERIFY EXISTING CONDITIONS BEFORE BIDDING. REFER TO ARCHITECTURAL/EQUIPMENT DRAWINGS FOR ADDITIONAL INFORMATION REGARDING EQUIPMENT AND CASEWORK, AND ELECTRICAL CONNECTIONS REQUIRED.
AutoCAD SHX Text
COMPLY WITH ALL LAWS APPLYING TO ELECTRICAL INSTALLATIONS IN EFFECT, AND WITH THE MOST RECENT EDITION OF THE ADOPTED ELECTRICAL CODE. ALL MATERIALS USED SHALL BE NEW AND SHALL CONFIRM TO THE STANDARDS ESTABLISHED BY UNDERWRITERS LABORATORIES INC.
AutoCAD SHX Text
VERIFY SIZE OF ELECTRICAL SYSTEM BREAKERS, CONDUIT ETC. FOR EQUIPMENT CONNECTIONS.
AutoCAD SHX Text
PANEL BOARDS SHALL BE AS MANUFACTURED BY GENERAL ELECTRIC, MEETING UL STANDARDS 50 AND 67 WITH UL LABEL.
AutoCAD SHX Text
ALL PANELBOARDS, SWITCHBOARDS, AND LINE VOLTAGE CONTROL EQUIPMENT SHALL BE FIELD MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. MARKING SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTING, SERVICING OR MAINTENANCE OF EQUIPMENT. MARKING SHALL BE SELF ADHESIVE, COMMERCIAL LABEL CONFORMING TO NEC 110.16 AND ANSI Z535.4 AS MANUFACTURED BY IDEAL OR APPROVED EQUAL.
AutoCAD SHX Text
BREAKERS: THERMAL MAGNETIC TYPE, QUICK-MAKE, QUICK-BREAK, BOLT-IN TYPE OF SINGLE UNIT CONSTRUCTION. TWO AND THREE POLE BREAKERS SHALL BE SINGLE UNIT COMMON TRIP TYPE. BREAKERS USED AS SWITCHES FOR 120V LIGHTING CIRCUITS SHALL BE APPROVED FOR THAT USE AND MARKED "SWD". WHEN NEW BREAKERS ARE INSTALLED INTO EXISTING PANELS, NEW BREAKERS SHALL BE OF SAME MANUFACTURER AS EXISTING PANEL AND BE OF EQUAL OR GREATER AIC RATING AS EXISTING PANEL
AutoCAD SHX Text
CABINETS SHALL BE ONE PIECE CODE GAGE GALVANIZED STEEL WITH MOUNTING STUDS, WIRING GUTTERS OF AMPLE SIZE AND KNOCKOUTS FOR CONDUIT CONNECTIONS AS REQUIRED. BUS BARS SHALL BE THW, THHN, THWW COPPER. BRANCH CIRCUIT WIRING SHALL BE TYPE TW COPPER. FRONTS SHALL BE ONE PIECE CODE GAGE FURNITURE STEEL WITH ADJUSTABLE FASTENERS. PROVIDE SURFACE MOUNT UNITS UNLESS OTHERWISE INDICATED. PROVIDE PLASTIC COVERED TYPEWRITTEN SCHEDULE IDENTIFYING ALL BRANCH CIRCUITS INSIDE EACH CABINET.
AutoCAD SHX Text
PROVIDE DRY-TYPE ENERGY EFFICIENT TRANSFORMER WHICH SHALL BE NEMA TP-1 TYPE, ENCLOSED AND VENTILATED WITH KVA AND VOLTAGE RATINGS AS CALLED FOR ON THE DRAWINGS, WITH (150) DEGREE CLASS "H" INSULATION AND MINIMUM OF SIX 2-1/2% TAPS. SOUND LEVEL SHALL BE LOW AND INSTALLATION SHALL INCLUDE KORFUND OR EQUAL VIBRATION DAMPENING MOUNTS AND FLEXIBLE STEEL CONDUIT FOR PRIMARY AND SECONDARY CONNECTIONS TO MINIMIZE SOUND TRANSMISSION.
AutoCAD SHX Text
GROUNDING SYSTEM: PERMANENTLY AND EFFECTIVELY GROUND ALL METALLIC CONDUIT, SUPPORTS, CABINETS, PANEL BOARDS AND SYSTEM NEUTRAL CONDUCTORS. MAINTAIN CONTINUITY OF EQUIPMENT GROUND THROUGHOUT THE SYSTEM. GROUND CLAMPS SHALL BE APPROVED TYPE, SPECIFICALLY DESIGNED FOR GROUNDING. WHERE GROUNDING CONDUCTORS ARE ENCLOSED IN CONDUIT, GROUND CLAMP SHALL BE OF TYPE WHICH GROUNDS BOTH CONDUCTOR AND CONDUIT. ALL CIRCUITS IN FLEXIBLE METAL CONDUIT (6'-0" MAXIMUM LENGTH) SHALL INCLUDE A GROUND WIRE SIZED IN ACCORDANCE WITH NEC TABLE 250-95.
AutoCAD SHX Text
SIZE CONDUIT TO COMPLY WITH ELECTRICAL CODE FOR NUMBER AND SIZE OF CONDUCTORS INSTALLED, MINIMUM " ABOVE GRADE. ALL CONDUIT INSTALLED 12" ABOVE GRADE. ALL CONDUIT INSTALLED HORIZONTALLY ABOVE CEILING SHALL BE SUPPORTED FROM BUILDING STRUCTURE. NO NO CONDUIT SHALL BE SUPPORTS FROM CEILING GRID OR GRID WIRES. PROVIDE RIGID STEEL PROVIDE RIGID STEEL CONDUIT OR PVC BELOW GRADE, MINIMUM ". PROVIDE ELECTRICAL METAL TUBING (EMT) 34". PROVIDE ELECTRICAL METAL TUBING (EMT) OR "MC" CABLE FOR INTERIOR LOCATIONS. INTERIOR CONNECTORS AND COUPLINGS SHALL BE SET-SCREW TYPE. CLAMP CONDUIT TO BOXES WITH BUSHING INSIDE AND LOCKNUT OUTSIDE. FLEXIBLE METAL CONDUIT MAY BE USED IN LENGTHS 6' OR LESS.
AutoCAD SHX Text
CONDUCTORS: INSULATED SOFT ANNEALED 98% PURE COPPER WITH COLOR CODING, B AND S GAGE, #10 AND SMALLER TO BE SOLID, #8 AND LARGER TO BE STRANDED, MINIMUM #12 UNLESS OTHERWISE INDICATED.
AutoCAD SHX Text
DEVICES SHALL BE MANUFACTURED BY LEVITON OR EQUAL. ALL DEVICES SHALL BE WHITE COLOR WITH BRUSHED ALUMINUM COVER PLATES. STANDARD DUPLEX RECEPTACLES SHALL BE GROUNDING TYPE, 20A, NEMA WD-2 STANDARD 5-20R, BACK AND SIDE WIRED. ISOLATED GROUND RECEPTACLES SHALL BE LEVITON 5262-IG AND ORANGE IN COLOR. OTHER DEVICES SHALL BE INDICATED ON THE DRAWINGS, OR AS REQUIRED BY THE EQUIPMENT ITEM INTENDED TO BE SERVED. WHERE SWITCHES ARE GROUPED, PROVIDE GANGPLATES. NO RESIDENTIAL GRADE DEVICES ALLOWED.
AutoCAD SHX Text
LAYOUT BRANCH CIRCUIT WIRING AND ARRANGEMENT OF HOME RUNS FOR MAXIMUM ECONOMY AND EFFICIENCY. INCREASE WIRE SIZE IF VOLTAGE DROP EXCEEDS 3% OR CIRCUIT LENGTH EXCEEDS 100 FEET.
AutoCAD SHX Text
CONCEAL WIRING SYSTEM ABOVE SUSPENDED CEILINGS OR IN WALL WHERE POSSIBLE. INSTALL CONDUIT AND MC CABLE PARALLEL TO BUILDING LINES, AND TO CLEAR ALL OPENING, DEPRESSIONS, PIPES, DUCTS, STRUCTURE, ETC. SUPPORT PER NEC.
AutoCAD SHX Text
INSTALL CONDUIT CONTINUOUS BETWEEN BOXES AND CABINETS WITH NO MORE THAN FOUR (4) 90 DEGREE BENDS. SECURELY FASTEN IN PLACE WITH STRAPS, HANGERS AND STEEL SUPPORTS AS REQUIRED. REAM CONDUIT ENDS BEFORE INSTALLATION AND THOROUGHLY CLEAN BEFORE INSTALLATION. OPENINGS SHALL BE PLUGGED OR COVERED TO KEEP CONDUIT CLEAN. TERMINALS ON SWITCHES AND OUTLETS SHALL NOT BE USED TO "FEED THRU" TO THE NEXT SWITCH OR OUTLET. THE DISCONNECTION OR REMOVAL OF A RECEPTACLE, FIXTURE, OR OTHER DEVICE FED FROM A BOX SHALL NOT INTERFERE WITH OR INTERRUPT THE CONDUCTOR CONTINUITY.
AutoCAD SHX Text
ADJUSTING AND TESTING: ALL ELECTRICAL EQUIPMENT SHALL BE ADJUSTED AND TESTED FOR PROPER OPERATION. COMPLETED WIRING SYSTEM SHALL BE FREE FROM SHORT CIRCUITS.
AutoCAD SHX Text
TOUCHUP AND CLEANING: TOUCHUP OR REFINISH DAMAGED SURFACES OF FIXTURES AND EQUIPMENT EXPOSED TO VIEW. CLEAN FIXTURES, GLASSWARE AND LAMPS BY APPROVED METHODS, READY FOR USE.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: USE THIS SPACE TO PROVIDE LIGHTING COMPLIANCE FORMS AS REQUIRED BY LOCAL CODE AUTHORITY.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: G.E. RELAY PANEL SCHEDULE ZONES & CIRCUITS SHOWN AS REFERENCE ONLY. SCHEDULE SHALL BE COMPLETED BASED EACH PROJECT. ALL CONTROLLED CIRCUITS MUST BE SHOWN IN SCHEDULE. G.E. RELAY PANEL SCHEDULE IS REQUIRED FOR EACH PROJECT FOR FINAL APPROVAL. PROVIDE (2) RELAY PANELS WHEN MORE THAN 48 CIRCUITS ARE REQUIRED TO BE CONTROLLED (ONLY HOMEGOODS & HOMESENS). ALL RELAY PANELS WILL HAVE 48 SPACES.
AutoCAD SHX Text
DESIGNER NOTE: MECHANICAL CONNECTIONS ARE FOR REFERENCE ONLY. ALL MECHANICAL INFO SHALL BE BASED ON MECHANICAL ENGINEER'S CONSTRUCTION DOCUMENTS.
AutoCAD SHX Text
DESIGNER NOTE: ADDITIONAL PANEL(S) MAY BE REQUIRED FOR HOMEGOODS & HOMESENSE STORES.
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING; THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS. NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND SIGNATURE
AutoCAD SHX Text
MC-4 DPS
2 COND
NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM. BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE.
Components
Description Electric Strike Power Supply w/Dual Interlock Circuit Board Momentary SPDT - Push Button Switches Magnetic DPS Switches
Part Number 55-A24U 631RFA x UR2A 15-2 X SPDT x MOM MC-4
Manufacturer SDC SDC SDC SDC
Method of Operation
The above layout is identified as a Mantrap "B". Both openings have mechanical locks that are latched & unlatched by electric strikes. Access / Egress: Entering is accomplished by either mechanical key or push button control from inside a cash room. Egress is free at all times.
55-A
ELECTRIC
STRIKE
A5 A6 A7 A8 A9 A10 B5 B6 B7 B8 B9 B10
STATION A OUTPUT
STATION B OUTPUT
R EL
AY R
EL AY
R EL
AY R
EL AY
R EL
AY R
EL AY
E1 E2 E3 E4 E5 E7 E8E6A1 A2 A3 A4 B4B2 B3B1
STATION A OUTPUT
STATION B OUTPUT
DIP SWITCH 1 2 3 4 5 6 7 8
ON
- +
24 VDC OUTPUT
STANDBY BATTERY CONNECTION
A
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
SENS/SW
SENS/SW
SENS/SW
SENS/SW
SW/SENS
SW/SENS
SW/SENS
SW/SENS
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
SENS/SW
SENS/SW
SENS/SW
SENS/SW
SW/SENS
SW/SENS
SW/SENS
SW/SENS
AutoCAD SHX Text
MASTER ON/OFF SWITCH TO CONTROL ON/OFF CASE LIGHTING. SWITCH TO BE LOCATED 6" FROM FRONT FACE OF CABINET.
AutoCAD SHX Text
AutoCAD SHX Text
NOVAR INTERFACE SUMMARY (REFER TO TJX SPECIFICATIONS FOR DETAIL INFORMATION) 1) GENERAL CONTRACTOR A) PROVIDE AND INSTALL A 4'X8' PLYWOOD BACKBOARD IN THE ELECTRIC ROOM FOR NOVAR TO MOUNT THEIR PROVIDE AND INSTALL A 4'X8' PLYWOOD BACKBOARD IN THE ELECTRIC ROOM FOR NOVAR TO MOUNT THEIR EQUIPMENT. PHONE AND ETHERNET JACKS FOR THE NOVAR SAVVY CONTROLLER WILL ALSO BE LOCATED ON THIS BOARD BY A SEPARATE TJX VENDOR. 2) MECHANICAL CONTRACTOR A) HORIZONTALLY MOUNT A 2X4 J-BOX WITH CONDUIT (WIREMOLD IF EXPOSED IN FINISHED AREAS) AT THE LOCATIONS HORIZONTALLY MOUNT A 2X4 J-BOX WITH CONDUIT (WIREMOLD IF EXPOSED IN FINISHED AREAS) AT THE LOCATIONS DESIGNATED ON THE NOVAR CONTROLS SITE SPECIFIC PLANS. THE J-BOXES ARE TO BE MOUNTED AT 60" A.F.F. EXCEPT IN FITTING ROOM LOCATIONS WHERE THE J-BOXES ARE TO BE MOUNTED AT 84" A.F.F.. ON THE SALES FLOOR, THE J-BOXES ARE TO BE MOUNTED ON BACK SIDE OF THE COLUMNS WHEN VIEWED FROM FRONT OF STORE. B) PROVIDE AND INSTALL A PERMANENT STRANDED 18/2 AWG NON SHIELDED CABLE (18/8 IF THE RTU IS EQUIPPED WITH A PROVIDE AND INSTALL A PERMANENT STRANDED 18/2 AWG NON SHIELDED CABLE (18/8 IF THE RTU IS EQUIPPED WITH A C02 SENSOR WITH THE UNIT) FROM EACH ROOFTOP UNIT TO THE NOVAR ETM (T-STAT) LOCATION SHOWN ON THE NOVAR PLAN THAT SUPERSEDES ANY MECHANICAL PLAN LOCATIONS. C) TEMPORARY THERMOSTATS ARE TO BE INSTALLED AT THE ROOFTOP UNITS. TEMPORARY THERMOSTATS ARE TO BE INSTALLED AT THE ROOFTOP UNITS. D) HVAC EQUIPMENT ARE TO HAVE HAD A MANUFACTURER'S RECOMMENDED STARTUP PROCEDURE PERFORMED AND BE HVAC EQUIPMENT ARE TO HAVE HAD A MANUFACTURER'S RECOMMENDED STARTUP PROCEDURE PERFORMED AND BE OPERATIONAL IN ALL MODES BEFORE THE ARRIVAL OF THE NOVAR CONTROLS REPRESENTATIVE FOR THE FINAL NOVAR INSTALLATION. 3) ELECTRICAL CONTRACTOR A) PROVIDE AND INSTALL A THREE PHASE CIRCUIT BREAKER (20 AMPS) FOR THE PHASE MONITOR. THIS BREAKER PROVIDE AND INSTALL A THREE PHASE CIRCUIT BREAKER (20 AMPS) FOR THE PHASE MONITOR. THIS BREAKER MAY BE INSTALLED IN A LIGHTING DISTRIBUTION PANEL IF THE PANEL IS OF THE SAME VOLTAGE AS THE MAIN DISTRIBUTION PANEL. B) INSTALL THE NOVAR PROVIDED CURRENT TRANSFORMERS (CTS). INSTALL THE NOVAR PROVIDED CURRENT TRANSFORMERS (CTS). C) CONNECT ALL CT WIRING TO THE PHASE MONITOR. CONNECT ALL CT WIRING TO THE PHASE MONITOR. D) MOUNT AND POWER THE PHASE MONITOR. MOUNT AND POWER THE PHASE MONITOR. E) PROVIDE AND INSTALL BMS#1 (20 AMP, 1 POLE BREAKER), BMS#2 (20 AMP, 1 POLE BREAKER), AND BMS #3 (20 AMP, 1 POLE PROVIDE AND INSTALL BMS#1 (20 AMP, 1 POLE BREAKER), BMS#2 (20 AMP, 1 POLE BREAKER), AND BMS #3 (20 AMP, 1 POLE BREAKER) POWER SUPPLY. THESE BREAKERS MUST ORIGINATE FROM THE SAME PHASE. BMS BREAKERS REQ'D ON TJE CP PANEL. F) THE INSTALLATION, PROGRAMMING, AND LABELING OF THE GE SOFTWIRE PANEL IS THE RESPONSIBILITY OF THE ELECTRICAL THE INSTALLATION, PROGRAMMING, AND LABELING OF THE GE SOFTWIRE PANEL IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
LIGHTING SUMMARY (REFER TO TJX SPECIFICATIONS FOR DETAIL INFORMATION) 1) NIGHT LIGHTING: NIGHT LIGHTING: A) NIGHT LIGHTS ARE TO BE ON 24 HOURS A DAY AND ONLY IN THE SALES AREA. NIGHT LIGHTS ARE TO BE ON 24 HOURS A DAY AND ONLY IN THE SALES AREA. A) THE CIRCUIT FOR NIGHT LIGHTING IS NOT TO BE CONNECTED TO THE GE RELAY PANEL, OR EMERGENCY LIGHTING. THE THE CIRCUIT FOR NIGHT LIGHTING IS NOT TO BE CONNECTED TO THE GE RELAY PANEL, OR EMERGENCY LIGHTING. THE NOT TO BE CONNECTED TO THE GE RELAY PANEL, OR EMERGENCY LIGHTING. THE TO BE CONNECTED TO THE GE RELAY PANEL, OR EMERGENCY LIGHTING. THE NL SHOULD BE ONLY (1) CIRCUIT IN MOST SITUATIONS. B) NIGHT LIGHTING "RULE OF THUMB" IS (1) NIGHT LIGHT FOR EVERY 3,500 SQUARE FEET OF SALES AREA (ROUND UP), AND NIGHT LIGHTING "RULE OF THUMB" IS (1) NIGHT LIGHT FOR EVERY 3,500 SQUARE FEET OF SALES AREA (ROUND UP), AND SHOULD BE EVENLY DISTRIBUTED. (REFER TO TJX CRITERIA PLAN SHEET (C5) FOR EXACT QUANTITIES & LOCATIONS). 2) EMERGENCY LIGHTING: EMERGENCY LIGHTING: A) EMERGENCY LIGHTING IS TO BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES AND AT THE DIRECTION OF EMERGENCY LIGHTING IS TO BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES AND AT THE DIRECTION OF THE GOVERNING AUTHORITIES. B) AT A MINIMUM, THE EMERGENCY LIGHTING IS TO BE AS FOLLOWS: AT A MINIMUM, THE EMERGENCY LIGHTING IS TO BE AS FOLLOWS: 1) ALL ROOMS AND SPACES ARE TO HAVE AT LEAST (1) EMERGENCY LIGHT. ALL ROOMS AND SPACES ARE TO HAVE AT LEAST (1) EMERGENCY LIGHT. 2) THE SALES AREA IS TO HAVE (1) EMERGENCY LIGHT PER 2,000 SQUARE FEET OF FLOOR AREA, AND SHOULD BE THE SALES AREA IS TO HAVE (1) EMERGENCY LIGHT PER 2,000 SQUARE FEET OF FLOOR AREA, AND SHOULD BE EVENLY DISTRIBUTED THROUGHOUT THE SPACE. PATHS OF EGRESS SHOULD BE OF PRIMARY COVERAGE. 3) THE STOCK ROOM SHOULD HAVE A MINIMUM OF (4) EMERGENCY LIGHTS. THE STOCK ROOM SHOULD HAVE A MINIMUM OF (4) EMERGENCY LIGHTS. C) THE EMERGENCY LIGHTING SYSTEM AND CIRCUITS ARE NOT TO BE CONNECTED TO THE GE RELAY PANEL AND THE THE EMERGENCY LIGHTING SYSTEM AND CIRCUITS ARE NOT TO BE CONNECTED TO THE GE RELAY PANEL AND THE NOT TO BE CONNECTED TO THE GE RELAY PANEL AND THE TO BE CONNECTED TO THE GE RELAY PANEL AND THE CIRCUITS ARE TO BE DEDICATED WITH BREAKER LOCKS INSTALLED AT THE PANEL. D) THE EMERGENCY LIGHTS ARE TO BE LITHONIA LIGHTING, MODEL #ELM2, SELF CONTAINED BATTERY UNITS. THE EMERGENCY LIGHTS ARE TO BE LITHONIA LIGHTING, MODEL #ELM2, SELF CONTAINED BATTERY UNITS. 3) SECURITY LIGHTING: SECURITY LIGHTING: A) EXTERIOR SECURITY LIGHTING INCLUDES EXTERIOR WALL LIGHT PACKS ATTACHED TO THE BUILDING AS NOTED ON THE EXTERIOR SECURITY LIGHTING INCLUDES EXTERIOR WALL LIGHT PACKS ATTACHED TO THE BUILDING AS NOTED ON THE PLANS. THESE ARE GENERALLY MOUNTED ABOVE ALL EGRESS DOORS FROM THE STORE. B) THE CIRCUITING FOR THIS IS THROUGH THE GE RELAY PANEL. THE CIRCUITING FOR THIS IS THROUGH THE GE RELAY PANEL. C) NOVAR WILL CONTROL THIS LIGHTING BY A SEPARATE CHANNEL IN THE RELAY PANEL. THIS LIGHTING IS OVERRIDDEN NOVAR WILL CONTROL THIS LIGHTING BY A SEPARATE CHANNEL IN THE RELAY PANEL. THIS LIGHTING IS OVERRIDDEN BY A LIGHT SENSOR SUPPLIED AND INSTALLED BY NOVAR. 4) SIGNS AND CANOPY LIGHTS: SIGNS AND CANOPY LIGHTS: A) THIS INCLUDES THE BUILDING, MALL, LIGHTED UNDER CANOPY, ETC. SIGNS AS WELL AS ANY CANOPY LIGHTS (IF NOT THIS INCLUDES THE BUILDING, MALL, LIGHTED UNDER CANOPY, ETC. SIGNS AS WELL AS ANY CANOPY LIGHTS (IF NOT BEING CONTROLLED BY THE LANDLORD'S HOUSE PANEL). B) THESE CIRCUITS ARE TO BE RUN THROUGH THE GE RELAY PANEL. THESE CIRCUITS ARE TO BE RUN THROUGH THE GE RELAY PANEL. C) NOVAR WILL CONTROL THESE CIRCUITS BY A SEPARATE CHANNEL IN THE RELAY PANEL. NOVAR WILL CONTROL THESE CIRCUITS BY A SEPARATE CHANNEL IN THE RELAY PANEL. 5) CUSTOMER LIGHTING: CUSTOMER LIGHTING: A) SALES AREA: SALES AREA: 1) ONE HALF OF THE SALES AREA CEILING LIGHTS (ALTERNATE ROWS). ONE HALF OF THE SALES AREA CEILING LIGHTS (ALTERNATE ROWS). 2) ALL PERIMETER LIGHTING. ALL PERIMETER LIGHTING. 3) ALL PENDANT LIGHTING. ALL PENDANT LIGHTING. 4) JEWELRY COUNTER LIGHTING. JEWELRY COUNTER LIGHTING. 5) LAMP DEPARTMENT PLUGMOLD (ON WALLS AND FLOOR GONDOLAS). LAMP DEPARTMENT PLUGMOLD (ON WALLS AND FLOOR GONDOLAS). 6) FLOOR OUTLETS FOR LAMP DEPARTMENT. FLOOR OUTLETS FOR LAMP DEPARTMENT. 7) CEILING MOUNTED CHANDELIER FIXTURE OUTLETS. CEILING MOUNTED CHANDELIER FIXTURE OUTLETS. 8) ANY SPECIALTY LIGHTING (I.E. WALL SCONCES, ETC.). ANY SPECIALTY LIGHTING (I.E. WALL SCONCES, ETC.). B) OFF SALES AREA: OFF SALES AREA: 1) PENDANT LIGHTS IN THE FITTING ROOM PENDANT LIGHTS IN THE FITTING ROOM 2) LIGHTED MIRRORS IN THE FITTING ROOM LIGHTED MIRRORS IN THE FITTING ROOM C) THESE CIRCUITS ARE TO BE RUN THROUGH THE GE RELAY PANEL. THESE CIRCUITS ARE TO BE RUN THROUGH THE GE RELAY PANEL. 6) EMPLOYEE LIGHTING: EMPLOYEE LIGHTING: A) EMPLOYEE LIGHTING IS TO INCLUDE ALL (EXCEPT AS EXCLUDED BELOW) INTERIOR STORE LIGHTING AND BE RUN EMPLOYEE LIGHTING IS TO INCLUDE ALL (EXCEPT AS EXCLUDED BELOW) INTERIOR STORE LIGHTING AND BE RUN THROUGH THE GE RELAY PANEL. THE SALES AREA CEILING LIGHTS IS TO BE ALTERNATE ROWS. B) ITEMS NOT INCLUDED IN "EMPLOYEE LIGHTING" ARE NIGHT LIGHTING, EMERGENCY LIGHTING, EXIT LIGHTING, DOCK ITEMS NOT INCLUDED IN "EMPLOYEE LIGHTING" ARE NIGHT LIGHTING, EMERGENCY LIGHTING, EXIT LIGHTING, DOCK LIGHTS, "SECURITY LIGHTING", "SIGNS AND CANOPY LIGHTS", AND "CUSTOMER LIGHTING" AS DESCRIBED ABOVE. C) EMPLOYEE LIGHTING IS TO INCLUDE ALL EXHAUST FANS EXCEPT THE ELECTRICAL ROOM EXHAUST FAN THAT IS TO BE EMPLOYEE LIGHTING IS TO INCLUDE ALL EXHAUST FANS EXCEPT THE ELECTRICAL ROOM EXHAUST FAN THAT IS TO BE CONTROLLED BY A STAND-ALONE LINE VOLTAGE THERMOSTAT (SET AT 80° F). THESE CIRCUITS ARE TO BE RUNTHROUGH THE GE RELAY PANEL. 7) G.E. SOFTWIRE RELAY PANEL PROGRAMMING: G.E. SOFTWIRE RELAY PANEL PROGRAMMING: A) SOFTWIRING LIGHTING GROUPS SOFTWIRING LIGHTING GROUPS 1) THE SCM SHALL ALLOW ANY GROUP OF RELAYS WITHIN THE PANEL TO BE ASSOCIATED ("SOFTWIRED") TO A THE SCM SHALL ALLOW ANY GROUP OF RELAYS WITHIN THE PANEL TO BE ASSOCIATED ("SOFTWIRED") TO A CHANNEL USING THE FOLLOWING PROCEDURE: A) ...PRESS AND HOLD THE CHANNEL PUSH BUTTON FOR SEVERAL SECONDS. THE CHANNEL LED AND THE LEDS ...PRESS AND HOLD THE CHANNEL PUSH BUTTON FOR SEVERAL SECONDS. THE CHANNEL LED AND THE LEDS FOR RELAYS CURRENTLY CONTROLLED BY THAT INPUT WILL BEGIN TO FLASH. B) ...SELECT THE RELAYS TO BE CONTROLLED. THE LED FOR EACH RELAY "SOFTWIRED" TO THE CHANNEL ...SELECT THE RELAYS TO BE CONTROLLED. THE LED FOR EACH RELAY "SOFTWIRED" TO THE CHANNEL SELECTED WILL BE FLASHING ON/OFF. PRESS THE ASSOCIATED RELAY CONTROL BUTTON TO ADD/DELETE THAT RELAY TO/FROM GROUP. C) ...PRESS THE CHANNEL PUSH BUTTON AGAIN. THE LEDS WILL STOP FLASHING AND THE CHANNEL PUSH BUTTON ...PRESS THE CHANNEL PUSH BUTTON AGAIN. THE LEDS WILL STOP FLASHING AND THE CHANNEL PUSH BUTTON AND ASSOCIATED SWITCH INPUTS WILL NOW CONTROL THE RELAYS SELECTED. 2) TURNING A CHANNEL ON/OFF WILL SEQUENCE ALL OF THE RELAYS WITHIN THAT GROUP ON/OFF INDIVIDUALLY. TURNING A CHANNEL ON/OFF WILL SEQUENCE ALL OF THE RELAYS WITHIN THAT GROUP ON/OFF INDIVIDUALLY. B) CONTROLLING A SOFTWIRE GROUP CONTROLLING A SOFTWIRE GROUP 1) EACH CHANNEL SHALL HAVE AN ASSOCIATED PUSH-BUTTON WITHIN THE PANEL TO TOGGLE THE CHANNEL ON/OFF EACH CHANNEL SHALL HAVE AN ASSOCIATED PUSH-BUTTON WITHIN THE PANEL TO TOGGLE THE CHANNEL ON/OFF 2) EACH CHANNEL SHALL ALSO HAVE TWO SEPARATE SWITCH OR DRY CONTACT INPUTS THAT WILL ALLOW THE EACH CHANNEL SHALL ALSO HAVE TWO SEPARATE SWITCH OR DRY CONTACT INPUTS THAT WILL ALLOW THE CHANNEL TO BE CONTROLLED REMOTELY. 3) THE CHANNEL SHALL RESPOND TO THE LAST INPUT. THE CHANNEL SHALL RESPOND TO THE LAST INPUT. 4) THE UNIT SHALL ALLOW A "MASTER CHANNEL" TO BE CONFIGURED TO CONTROL SEVERAL OF THE ABOVE THE UNIT SHALL ALLOW A "MASTER CHANNEL" TO BE CONFIGURED TO CONTROL SEVERAL OF THE ABOVE CHANNELS BY SIMPLY INCLUDING ALL OF THE RELAYS OF THESE "SUB CHANNELS" WITHIN THE MASTER. C) GROUP STATUS GROUP STATUS 1) EACH CHANNEL PUSH-BUTTON SHALL INCLUDE A LED STATUS INDICATION. THE LED WILL BE ON WHENEVER ALL OF EACH CHANNEL PUSH-BUTTON SHALL INCLUDE A LED STATUS INDICATION. THE LED WILL BE ON WHENEVER ALL OF THE RELAYS WITHIN THE CHANNEL GROUP ARE ON; AND SHALL GO OFF WHEN ALL OF THE RELAYS WITHIN THE AND SHALL GO OFF WHEN ALL OF THE RELAYS WITHIN THE GROUP GO OFF. 2) EACH CHANNEL SHALL ALSO HAVE AN ASSOCIATE DRY CONTACT CLOSURE OF PILOT CONTACT WHICH TRACKS EACH CHANNEL SHALL ALSO HAVE AN ASSOCIATE DRY CONTACT CLOSURE OF PILOT CONTACT WHICH TRACKS THE LED OPERATION DESCRIBED ABOVE. D) CONTROLLING AN INDIVIDUAL RELAY CONTROLLING AN INDIVIDUAL RELAY 1) EACH RELAY SHALL HAVE AN ASSOCIATED CONTROL BUTTON WITH LED STATUS INDICATION MOUNTED WITHIN THE EACH RELAY SHALL HAVE AN ASSOCIATED CONTROL BUTTON WITH LED STATUS INDICATION MOUNTED WITHIN THE LOW VOLTAGE SECTION OF THE PANEL.
AutoCAD SHX Text
SINGLE DEDICATED OUTLET TO FACE OUTWARD AND BE MOUNTED BELOW THE DRAWER AND ABOVE THE ACCESS PANEL.
AutoCAD SHX Text
SINGLE DEDICATED OUTLET TO FACE OUTWARD AND BE MOUNTED BELOW THE DRAWER AND ABOVE THE ACCESS PANEL.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: UNUSED LEAD MUST UNUSED LEAD MUST BE PROPERLY INSULATED WITH WIRENUT OR OTHER APPROVED METHOD.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
SINGLE Q CHECK OUT STAND ELEVATION @ END CHECK OUT (TYPICAL)
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: REFER TO TJX DRAWING C6 POWER PLAN FOR EXACT QUANTITY & LOCATION OF ALL DEDICATED / ISOLATED GROUND RECEPTACLES SHOWN IN THE DIAGRAM BELOW.
AutoCAD SHX Text
SINGLE QUE REGISTERS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
POS AS WELL AS THE CABLE FOR THE TIME CLOCK, ACS AND
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AND SHALL BE KEPT A MINIMUM OF 5'-0" FROM FLUORESCENT
AutoCAD SHX Text
3 ALL LOW VOLTAGE WIRING TO BE INSTALLED ABOVE HUNG CLG.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
2 CABLES TO BE RUN IN ONE PIECE FROM REGISTER
AutoCAD SHX Text
I.G. GROUND TO BE TAGGED OR LABELED AT MAIN ENTRANCE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PANEL "CP" SHALL BE USED TO SUPPLY ONLY REGISTER EQUIP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
2 ALL WIRING SHALL BE TYPE "THW" OR "THHN" COPPER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
3/4" -1 NO. 8 CONNECT DIRECTLY TO MAIN SERVICE GROUND
AutoCAD SHX Text
AutoCAD SHX Text
ALUM. POWER POLE WIREMOLD # NP600C ANCHOR AT CLG. & COUNTER TOP. (IF APPLICABLE)
AutoCAD SHX Text
UPS UNIT SUPPLIED BY TJX COMPANIES INSTALLED BY GENERAL CONTRACTOR'S ELECTRICIAN.
AutoCAD SHX Text
*** ALL DELIVERY QUESTIONS SHOULD *** BE DIRECTED TO TJX SYSTEMS IMPLEMENTATION AT 508-475-8105
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Liebert GXT4 6kVA UPS and CP Panel for TJX Stores
AutoCAD SHX Text
CIRCUITS TO FEED, ISOLATED GROUNDED RECEPTACLES AND ALL REGISTER LOCATIONS.
AutoCAD SHX Text
TJX LIEBERT GXT4 6kva UPS installation guidelines LIEBERT CONTACT INFORMATION LIEBERT TECHNICAL SUPPORT PHONE: 800 - 222 - 5877 Option #1 Hardware Support EMAIL: [email protected] GENERAL INFORMATION: GCs or Electrical Contractors are not required to purchase the UPS. TJX provides all units from a third party location; DO NOT CALL LIEBERT WITH DELIVERY CONCERNS. The units are a Liebert GXT4 6kva tower UPS - 16.9” (H) x 6.8” (W) x 26.1” (D) and weigh 132 pounds total. The units arrive in (H) x 6.8” (W) x 26.1” (D) and weigh 132 pounds total. The units arrive in (W) x 26.1” (D) and weigh 132 pounds total. The units arrive in (D) and weigh 132 pounds total. The units arrive in three separate boxes via FEDEX Wiring diagram is included on the TJX criteria, sheet C7. Installation does NOT require Liebert to be onsite. INSTALLATION: Electrical Contractor responsibilities: Unpack/set/place the UPS, placement must conform to local and national codes. UPS ships in three boxes, UPS, Internal Battery pack and SNMP card. Please refer to the UPS Manual, ships with the unit, for proper installation. Starts on Page 12. Terminate wiring at input and output of UPS. Ensure distribution wiring, CP Panel, and disconnect are correctly installed. START UP Electrical Contractor responsibilities: Unit must be turned on and taken out of BYPASS after installation is complete. Confirm the UPS is the only source feeding the CP Panel Call LIEBERT at the above number to troubleshoot any issues with Start up Provide support for LIEBERT if wiring issues arise during Start Up. After UPS is Turned on and taken out of BYPASS without any issues, the TJX PM must be notified that UPS installation is complete and the UPS is functional without issues.
AutoCAD SHX Text
AutoCAD SHX Text
CIRCUIT NEEDED ONLY WHEN REQUESTED BY SYSTEMS FOR REMOTE COMPUTER EQUIPMENT CONNECTION AND IG OUTLET.
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL CP PANEL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NOTES: : 1. LIEBERT RECOMMENDED WIRE SIZE, INCLUDING GROUND LIEBERT RECOMMENDED WIRE SIZE, INCLUDING GROUND WIRE, @ 75° COPPER WIRE IS 10AWG (4mm). MAXIMUMWIRE ACCEPTED BY TERMINAL BLOCK IS 8AWG (6mm). 2. LIEBERT RECOMMENDS INSTALLING A UL489 APPROVED LIEBERT RECOMMENDS INSTALLING A UL489 APPROVED BREAKER UPSTREAM OF UNIT. 3. THE INSTALLER MUST PROVIDE CIRCUIT BREAKER THE INSTALLER MUST PROVIDE CIRCUIT BREAKER PROTECTION ACCORDING TO LOCAL CODES. THE UTILITY DISCONNECT SHOULD BE WITHIN SIGHT OF THE UPS OR HAVE AN APPROPRIATE LOCK OUT. MAINTAIN SERVICE SPACE AROUND THE UPS OR USE FLEXIBLE UPS OR USE FLEXIBLE CONDUIT. 4. THE INSTALLER MUST PROVIDE OUTPUT DISTRIBUTION THE INSTALLER MUST PROVIDE OUTPUT DISTRIBUTION PANELS, CIRCUIT BREAKER PROTECTION, OR EMERGENCY DISCONNECTS ACCORDING TO LOCAL CODES. 5. OUTPUT CIRCUITS MUST NOT SHARE A COMMON. OUTPUT CIRCUITS MUST NOT SHARE A COMMON. 6. CP PANEL WILL SERVICE ALL REGISTER POWER, CP PANEL WILL SERVICE ALL REGISTER POWER, BLADE SERVER, IDF, AND BMS POWER ONLY. NO ONLY. NO . NO OTHER CIRCUIT TO BE FED FROM CP.
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: : SUB-CONTRACTOR TO FURNISH AND INSTALL THREE (3), 120V DEDICATED CONTROL CIRCUITS. BMS #1, BMS #2 & BMS #3. THESE CIRCUITS SHALL BE SOURCED FROM PANEL "CP"
AutoCAD SHX Text
NOTE: : NOVAR SYSTEM REQUIRES (1) 20A/3P CIRCUIT BREAKER AT MDP FOR PHASE MONITOR.
AutoCAD SHX Text
DETAIL @ L.P. OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
COUNTER SUPPORT (TO BE MOUNTED DIRECTLY NEXT TO THE WALL OR 30 INCHES FROM THE WALL.)
AutoCAD SHX Text
ACOUSTICAL CEILING TILE
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
110V, 24HR PLUG MOLD STRIP MOUNTED CENTRALLY ON WALL ABOVE DESKTOP, APPROX. 41" AFF ON BREAKER LOCK, DEDICATED CIRCUITS AS REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CAT5 - CAN BUS
AutoCAD SHX Text
7 X AWG#18 - 6 ZONES CONTROLS USE ONE WIRE FOR EACH ZONE PLUS ONE COMMON
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT, INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
AutoCAD SHX Text
DESIGNER NOTE: DETAILS SHOWN ON THIS SHEET ARE FOR REFERENCE ONLY. ACTUAL DETAILS SHALL BE PROVIDED FROM THE TJX C-SET SHEET 'C7'.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ALARM SYSTEM ENCLOSURE PANEL "OCTO-INPUTS / RELAYS" 16"H x 16"W x 3.5"D
AutoCAD SHX Text
ALARM SYSTEM CONTROL PANEL (PRIMARY) 16"H x 16"W x 3.5"D
AutoCAD SHX Text
ALARM SYSTEM CONTROL PANEL (PRIMARY) 16"H x 16"W x 3.5"D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING; THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS. NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND SIGNATURE
AutoCAD SHX Text
ELECTRICAL DETAILS
NOTE TO DESIGNER: EF-4 TO BE INCLUDED ONLY IF WALL BETWEEN ELECTRICAL ROOM AND PROCESSING IS FULL HEIGHT - COORDINATE WITH C-SET
NOTE TO DESIGNER: INCLUDE MECHANICAL VENTILATION TABLE SHOWING COMPLIANCE WITH ALL APPLICABLE CODES NOTE TO DESIGNER:
ADJUST OUTSIDE AIR VALUES BASED ON VENTILATION REQUIREMENTS
º
º
½
NOTE TO DESIGNER: EQUIPMENT CAPACITIES INDICATED FOR REFERENCE ONLY. ACTUAL EQUIPMENT SELECTIONS SHALL BE BASED ON TJX SPECIFICATIONS AND HVAC LOAD CALCULATIONS
NOTE TO DESIGNER: REFER TO TJX OUTLINED SPECIFICATIONS ON AREAS WHERE ELECTRIC HEAT IS REQUIRED. ADDITIONALLY, PROVIDE REQ'D HEAT PER CLIMATE ZONES.
AutoCAD SHX Text
PROVIDE BURGLAR BARS IN ALL ROOF AND EXTERIOR WALL PENETRATIONS, INCLUDING PENETRATIONS REQUIRED FOR ROOF MOUNTED EQUIPMENT LARGER THAN 12"x12" OR 12"~. BARS SHALL BE 1/2" STEEL RODS @6" O.C. WELDED IN PLACE AT ALL INTERSECTIONS AND SIDES OF OPENINGS. BARS SHALL BE SECURELY EMBEDDED IN CONCRETE OR WELDED STEEL FRAMES AS REQUIRED BY CONSTRUCTION OF ROOF AND/OR WALL.
AutoCAD SHX Text
G.C. TO PROVIDE AND INSTALL BURGLAR BARS OVER EXISTING RTU CURBS WHERE EQUIPMENT IS TO BE REMOVED, IN ADDITION TO ABOVE NOTED REQUIREMENT. REFER TO DEMOLITION PLAN FOR CAPPED AND SEALED EQUIPMENT CURBS.
AutoCAD SHX Text
NOVAR INTERFACE SUMMARY (REFER TO TJX SPECIFICATIONS FOR DETAIL INFORMATION.) 1. GENERAL CONTRACTOR GENERAL CONTRACTOR 1.1. PROVIDE 4'X8' PLYWOOD BACKBOARD IN ELECTRIC ROOM FOR NOVAR TO MOUNT THEIR EQUIPMENT. PROVIDE 4'X8' PLYWOOD BACKBOARD IN ELECTRIC ROOM FOR NOVAR TO MOUNT THEIR EQUIPMENT. PHONE AND ETHERNET JACKS FOR THE NOVAR CONTROLLER WILL ALSO BE LOCATED ON THIS BOARD BY SEPARATE TJX VENDOR. 2. MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR 2.1. MOUNT 2X4 J-BOX WITH CONDUIT (WIREMOLD IF EXPOSED IN FINISHED AREAS) AT LOCATIONS MOUNT 2X4 J-BOX WITH CONDUIT (WIREMOLD IF EXPOSED IN FINISHED AREAS) AT LOCATIONS DESIGNATED ON NOVAR CONTROLS SITE SPECIFIC PLANS. THE J-BOXES ARE SHALL BE MOUNTED 60" AFF EXCEPT IN FITTING ROOM LOCATIONS WHERE J-BOXES SHALL BE MOUNTED 84" AFF. ON SALES FLOOR J-BOXES SHALL BE MOUNTED ON BACK SIDE OF COLUMNS WHEN VIEWED FROM FRONT OF STORE. 2.2. PROVIDE PERMANENT STRANDED 18/2 AWG NON SHIELDED CABLE (18/8 IF THE RTU IS EQUIPPED WITH PROVIDE PERMANENT STRANDED 18/2 AWG NON SHIELDED CABLE (18/8 IF THE RTU IS EQUIPPED WITH A CO2 SENSOR) FROM EACH ROOFTOP UNIT TO THE NOVAR ETM (T-STAT) LOCATION SHOWN ON THE NOVAR PLAN THAT SUPERSEDES ANY MECHANICAL PLAN LOCATIONS. ALL CONTROL DEVICES SHALL BE APPROPRIATELY IDENTIFIED AND PERMANENTLY ATTACHED. 2.3. TEMPORARY THERMOSTATS SHALL BE INSTALLED NEAR THE ROOFTOP UNITS. TEMPORARY THERMOSTATS SHALL BE INSTALLED NEAR THE ROOFTOP UNITS. 2.4. HVAC EQUIPMENT SHALL HAVE HAD MANUFACTURER'S RECOMMENDED STARTUP PROCEDURE HVAC EQUIPMENT SHALL HAVE HAD MANUFACTURER'S RECOMMENDED STARTUP PROCEDURE PERFORMED AND BE OPERATIONAL IN ALL MODES BEFORE ARRIVAL OF NOVAR CONTROLS REPRESENTATIVE FOR FINAL NOVAR INSTALLATION. 2.5. IN COLD WEATHER THE CONTRACTOR SHALL PROVIDE TEMPORARY THERMOSTAT TO OPERATE THE IN COLD WEATHER THE CONTRACTOR SHALL PROVIDE TEMPORARY THERMOSTAT TO OPERATE THE HEATERS IN RECEIVING. 2.6. BASEBOARD HEATERS SHALL BE FACTORY EQUIPPED WITH INTEGRAL THERMOSTATS AND INSTALLED BASEBOARD HEATERS SHALL BE FACTORY EQUIPPED WITH INTEGRAL THERMOSTATS AND INSTALLED IN ALL OFFICES, LOUNGE, RESTROOMS, AND SECURITY OFFICES WITH AT LEAST ONE EXTERIOR WALL WHEN LOCATED IN CLIMATE ZONES 4 AND 5. THE CIRCUITING FOR BASEBOARD HEATING SHALL BE THROUGH GE RELAY PANEL. 2.7. ELECTRIC VESTIBULE HEATERS SHALL BE FACTORY EQUIPPED WITH LOW VOLTAGE CONTROLS, ELECTRIC VESTIBULE HEATERS SHALL BE FACTORY EQUIPPED WITH LOW VOLTAGE CONTROLS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: POWER CONTACTORS, LOW VOLTAGE TRANSFORMER, AND TWO WIRE FIELD TERMINATION CONTROL POINT. 3. ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR 3.1. REFER TO ELECTRICAL PLANS FOR REQUIREMENTS AND COORDINATION INFORMATIONREFER TO ELECTRICAL PLANS FOR REQUIREMENTS AND COORDINATION INFORMATION
AutoCAD SHX Text
PROVIDE EQUIPMENT INDICATED ON THE DRAWINGS, AND AS REQUIRED FOR A COMPLETE FUNCTIONING SYSTEM. DEFINITIONS: FURNISH MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR INSTALLATION. INSTALL MEANS TO FURNISH MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR INSTALLATION. INSTALL MEANS TO MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR INSTALLATION. INSTALL MEANS TO INSTALL MEANS TO MEANS TO PLACE IN POSITION AND MAKE CONNECTIONS FOR SERVICE OR USE. PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE MEANS TO FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED USE. WARRANTY: PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE PARTS AND MATERIALS AS REQUIRED PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER SUBSTANTIAL COMPLETION OR OWNER ACCEPTANCE OF THE COMPLETED PROJECT. PROVIDE A SEPARATE LINE ITEM DEDUCT AMOUNT ON THE PROPOSAL FORM TO DELETE WARRANTY SERVICE, AT THE OWNER'S OPTION. COORDINATION: COORDINATE WITH THE WORK OF OTHER TRADES, EQUIPMENT FURNISHED BY OTHERS, REQUIREMENTS OF THE COORDINATE WITH THE WORK OF OTHER TRADES, EQUIPMENT FURNISHED BY OTHERS, REQUIREMENTS OF THE OWNER, AND WITH THE CONSTRAINTS OF THE EXISTING CONDITIONS OF THE PROJECT SITE. DUCT DIMENSIONS: UNLESS OTHERWISE NOTED, DUCT DIMENSIONS ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS. UNLESS OTHERWISE NOTED, DUCT DIMENSIONS ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS. SHEETMETAL DUCTWORK: PROVIDE SHEETMETAL DUCTWORK FABRICATED AND INSTALLED IN ACCORDANCE WITH ASHRAE PROVIDE SHEETMETAL DUCTWORK FABRICATED AND INSTALLED IN ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS, FOR 1" W.G. PRESSURE CLASS, SEAL CLASS "A". SHEETMETAL SHALL BE GALVANIZED SHEET STEEL OF LOCK FORMING QUALITY, WITH G90 ZINC COATING. SHEET STEEL SHALL COMPLY WITH ASTM A653 STANDARD SPECIFICATION FOR STEEL SHEETMETAL, ZINC COATED (GALVANIZED) OR ZINC-IRON ALLOY-COATED (GALVANNEALED) BY THE HOT DIP PROCESS, AND A924 STANDARD SPECIFICATION FOR GENERAL REQUIREMENTS FOR SHEET, METALLIC-COATED BY THE HOT DIP PROCESS. ALL ANGLE IRON USED FOR SUPPORT SHALL BE GALVANIZED. CONNECTIONS TO WALLS OR FLOOR SHALL BE AIR TIGHT WITH ANGLE IRON AND CAULKING. SEAL ALL DUCT SEAMS, TRANSVERSE AND LONGITUDINAL, AIR TIGHT. PROVIDE TURNING VANES AT ALL 90º ELBOWS. ELBOWS. ROUND SHEETMETAL DUCT: PROVIDE SPIRAL SEAM (ALL SIZES) OR SNAP LOCK (DUCT SIZES UP TO 10" ABOVE CEILINGS) PROVIDE SPIRAL SEAM (ALL SIZES) OR SNAP LOCK (DUCT SIZES UP TO 10" ABOVE CEILINGS) GALVANIZED STEEL COMPLYING WITH SMACNA STANDARDS. SPIRAL SEAM DUCTWORK SHALL HAVE SMACNA SEAM TYPE RL-1. DUCTWORK FITTING AND ACCESSORIES: ALL FITTINGS AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN ALL FITTINGS AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH THE LATEST PUBLISHED STANDARDS FROM SMACNA AND ASHRAE. FLEXIBLE DUCT: PROVIDE FACTORY ASSEMBLED CLASS 1 AIR DUCT (UL 181) WITH 1" THICK 1 PCF FIBERGLASS INSULATION AND PROVIDE FACTORY ASSEMBLED CLASS 1 AIR DUCT (UL 181) WITH 1" THICK 1 PCF FIBERGLASS INSULATION AND REINFORCED OUTER PROTECTIVE COVER/VAPOR BARRIER. FLEXIBLE DUCT SHALL MEET NFPA 90A WITH FLAME SPREAD UNDER 25, SMOKE DEVELOPED UNDER 50, AND SHALL BE RATED FOR MINIMUM 2" W.G. PRESSURE AND 0 TO 250ºF F TEMPERATURE. PROVIDE SCREW-OPERATED METAL ADJUSTABLE CLAMPING DEVICES. USE TWIST-LOCK TAP COLLARS AT CONNECTIONS INTO SHEETMETAL DUCTWORK. MAXIMUM EXTENDED LENGTH OF FLEXIBLE DUCT SHALL NOT EXCEED 4 FEET. EXPOSED DUCTWORK: EXPOSED DUCTWORK SHALL BE CLEANED OF DEBRIS AND OIL, THEN WIPED DOWN WITH VINEGAR EXPOSED DUCTWORK SHALL BE CLEANED OF DEBRIS AND OIL, THEN WIPED DOWN WITH VINEGAR OR OTHER SURFACE PREPARING CHEMICAL TO PREPARE DUCT FOR PAINT. DUCT SEALANT: PROVIDE POLYMERIC RUBBER TYPE SEALANT FOR USE ON BOTH INTERIOR LOCATED DUCTWORK AND PROVIDE POLYMERIC RUBBER TYPE SEALANT FOR USE ON BOTH INTERIOR LOCATED DUCTWORK AND DUCTWORK EXPOSED TO OUTDOOR CONDITIONS. SEALER SHALL HAVE HIGH BONDING STRENGTH FOR SURE, FIRST TIME SEALING OF JOINTS IN LOW, MEDIUM, AND HIGH PRESSURE DUCT SYSTEMS. SEALER SHALL BE HIGH IN SOLID CONTENT. PROVIDE A TWO PART TAPE SEALING SYSTEM, CONSISTING OF WOVEN FIBER TAPE IMPREGNATED WITH A GYPSUM MINERAL COMPOUND, AND A MODIFIED ACRYLIC/SILICONE ACTIVATOR THAT REACTS EXOTHERMICALLY WITH THE TAPE. TWO PART TAPE SEALING SYSTEM MUST BE RATED FOR BOTH INDOOR AND OUTDOOR APPLICATION. TAPE SHALL NOT CONTAIN ASBESTOS. DUCT INSULATION (ALL ROUND SUPPLY DUCT AND ROUND RETURN DUCT ABOVE CEILING): PROVIDE MINIMUM 1-1/2" THICK PROVIDE MINIMUM 1-1/2" THICK BLANKET TYPE FIBERGLASS INSULATION COMPLYING WITH ASTM C-553, TYPE II, WITH FACTORY APPLIED KRAFT BONDED TO ALUMINUM FOIL, REINFORCED WITH FIBERGLASS VAPOR BARRIER/JACKET. JACKET SHALL CONFORM TO ASTM C-1136, TYPE II. INSTALLED R VALUE SHALL BE 4.2 OR HIGHER WITH A 0.75 PCF DENSITY. DUCT LINER (ALL RECTANGULAR SUPPLY AND RETURN DUCT): PROVIDE MINIMUM 1" THICK, 3 PCF DENSITY, NEOPRENE PROVIDE MINIMUM 1" THICK, 3 PCF DENSITY, NEOPRENE COATED, LONG TEXTILE FIBER TYPE DUCT LINER, WITH COATING ON THE AIR STREAM SIDE CONFORMING TO NFPA 90A. DUCT LINER ADHESIVE SHALL BE AS RECOMMENDED BY DUCT LINER MANUFACTURER, AND SHALL COMPLY WITH ASTM C-916. DUCT LINER FASTENERS SHALL COMPLY WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS", LATEST EDITION. THERMAL CONDUCTIVITY SHALL BE EQUAL TO OR LESS THAN 0.26 AT 75°F. ROUND VOLUME DAMPERS: PROVIDE MINIMUM 20 GAUGE GALVANIZED STEEL FRAME AND BLADES, MINIMUM 3/8" SQUARE PROVIDE MINIMUM 20 GAUGE GALVANIZED STEEL FRAME AND BLADES, MINIMUM 3/8" SQUARE STEEL AXLE, MOLDED SYNTHETIC BEARINGS, WITH LOCKING POSITION REGULATOR. REGULATOR SHALL BE POSITIONED WITH SHEETMETAL BRACKET BEYOND DUCT COVERING. WHERE POSITIONING REGULATOR IS NOT ACCESSIBLE, PROVIDE COUPLING AND EXTENSION ROD WITH REGULATOR FOR CEILING OR WALL INSTALLATION, AS REQUIRED. RECTANGULAR VOLUME DAMPERS: PROVIDE MINIMUM 16 GAUGE GALVANIZED STEEL CHANNEL FRAME, 16 GAUGE GALVANIZED PROVIDE MINIMUM 16 GAUGE GALVANIZED STEEL CHANNEL FRAME, 16 GAUGE GALVANIZED STEEL BLADES, MINIMUM ½" HEXAGONAL AXLE, MOLDED SYNTHETIC BEARINGS, WITH 3/8" SQUARE PLATED STEEL CONTROL " HEXAGONAL AXLE, MOLDED SYNTHETIC BEARINGS, WITH 3/8" SQUARE PLATED STEEL CONTROL SHAFT. LINKAGES SHALL BE CONCEALED IN THE FRAME. OPERATING SHAFT SHALL EXTEND BEYOND FRAME AND DUCT TO A LOCKING QUADRANT WITH ADJUSTABLE LEVER. MAXIMUM BLADE WIDTH SHALL NOT EXCEED 6". DUCT TURNING VANES: PROVIDE FABRICATED TURNING VANES AND VANE RUNNERS, CONSTRUCTED IN ACCORDANCE WITH PROVIDE FABRICATED TURNING VANES AND VANE RUNNERS, CONSTRUCTED IN ACCORDANCE WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS". PROVIDE TURNING VANES CONSTRUCTED OF CURVED BLADES, SUPPORTED WITH BARS PERPENDICULAR TO BLADES, AND SET INTO SIDE STRIPS SUITABLE FOR MOUNTING IN DUCTWORK. FOLLOW SMACNA GUIDELINES FOR SPACING SUPPORT, AND CONSTRUCTION. ALL BLADES SHALL BE DOUBLE THICKNESS AIRFOIL TYPE. FLEXIBLE DUCT CONNECTORS: PROVIDE U.L. LABELED 30 OUNCE NEOPRENE COATED FIBERGLASS FABRIC DUCT PROVIDE U.L. LABELED 30 OUNCE NEOPRENE COATED FIBERGLASS FABRIC DUCT CONNECTORS AT DUCT CONNECTIONS TO ALL VIBRATING EQUIPMENT. DUCT ACCESS DOORS: PROVIDE HINGED ACCESS DOORS IN DUCTWORK WHERE REQUIRE