© 2011 ericson manufacturing, willoughby, ohio 44094
TRANSCRIPT
ERICSON MANUFACTURING TRAINING MODULES
TEMP POWER BASICS
PART 1 of 2Modules A, B & C
© 2011 Ericson Manufacturing, Willoughby, Ohio 44094
Temp Power
Temporary Power Products are any devices used to control electrical energy for short term durations and are not part of a building’s PERMANENT Electrical system.
These devices can include: Electrical Extension Cords, Electrical “Panels”, Electrical Voltage Transformers and a variety of connection electrical devices.
Temp Power
Power blockInput-Primary-Line
Output-Secondary-Load• Transforms
• Distributes
• or Both
Temporary Power Product
Temp Power
voltage “the size of the power”
amperage “the force of the power”
600, 480, 277 240, 208, 120 volts
15 to 400 amps
Temp Power
voltage “the size of the power”
amperage “the force of the power”
phase “the pipelines of the power”
600, 480, 277 240, 208, 120 volts
15 to 400 amps
1 phase 3 phase
Temp Power
voltage
“the size of the power”
Tools, motors, pumps, light bulbs, switches,
fuses, circuit breakers are all rated or DESIGNED
to operate at a given voltage or range of voltages
Household
Mostly 120VAC
Some 240VAC
Automobile
12 VDC
AC vs DC Voltage
AC or Alternating Current is generator created.
DC or Direct Current is created by Battery or AC/DC power supply.
Jobsite
600 or 480 VAC
208 or 240 VAC
Temp Power
Household
100 Watt Light bulb – 1.5 amps
Electric Range – 50 amps
Jobsite
Drill or grinder – 5 to 18 amps
Stringlight – 10 to 18 amps
amperage “the force of the power” Symbol = A
Motors to light bulbs require or PULL a certain amount of amps through the cord.
Amps are added on a circuit and called the “load”.
Temp Power
phase “the pipelines of the power” Symbol = ø
The basic count of hot lines in a single circuit.
1 Phase 120V = 1 Hot , 1 neutral & 1 safety ground
1 Phase 240V = 2 Hots, 1 neutral & 1 safety ground
3 Phase 208V = 3 Hots, 1 neutral & 1 safety ground
3 Phase 480V = 3 hots & 1 Neutral/Ground Bonded
Temp Power
Electric circuits require a hot and return (neutral) side to complete the circuit or loop.
Hot +
Neutral Return -Source
Temp Power
Rule: Electric wires (conductors) are sized or rated to carry a maximum amperage or current.
Amp chart is NEC 400 – wire sizing
#14 awg = 15 amps#12 awg = 20 amps#10 awg = 30 amps# 6 awg = 50 amps
Note: Wire “size” goes down as physical wire gets larger and can carry more amps
Temp Power
Rule: Too much current ( amps ) can burn up circuits – fire hazard.
Protection – Circuit Breakers & GFCI
VoltageSource
Wire size too small
Temp Power
Rule: Too much current ( amps ) can burn up circuits – fire hazard.
Protection – Circuit Breakers & GFCI
Circuit Breaker or Fuse
PROTECTS the equipment or wiring
CLICKVoltageSource
Temp Power
Rule: Too much current ( amps ) can burn up circuits – fire hazard.
Protection – Circuit Breakers & GFCI
Circuit Breaker or Fuse
PROTECTS the equipment or wiring
CLICKVoltageSource
CODE RULE:
Circuit Breakers or Fuses must be rated for the smallest rated part of the circuit.
Temp Power
Protection
Circuit Breakers protect equipment and wiring.
- NOT a life safety device!- Rated in full amps ( 15, 20, 30, 50 etc)- Must be on all branch circuits- Must be rated correctly- Does not do the same job as a GFCI
Temp Power
Protection
GFCIs protect people.
-Ground Fault Circuit Interrupter
- Quick life saving device- Sensitive to poor connections, cheap cordage, moisture
Temp Power
Protection
Circuit Breakers protect equipment and wiring.
- Not a life safety device- Rated in full amps ( 15, 20, 30, 50 etc)
GFCIs protect people.
- 6 ma trip point ( 6 millionth of an amp)- Quick life saving device- Sensitive to poor connections, cheap cordage, moisture
Temp Power
Rule: Electrical current will find any path to ground – Including through you!
Protection - Circuit Breaker ONLY
VoltageSource
Circuit Breaker
H
N
Ground
Electric current flows to and from tool as normal…
Temp Power
Rule: Electrical current will find any path to ground – Including through you!
Protection - Circuit Breaker ONLY
VoltageSource
Circuit Breaker
H
N
Ground PROBLEM !
TOOL DEVELOPS AN ELECTRIC FAULT and SENDS ENERGY THROUGH THE WORKER TO GROUND !
Temp Power
Rule: Electrical current will find any path to ground – Including through you!
Protection - add a GFCI
GFCIs watch for a mis-match in current on the Hot and Neutral
conductors.
CLICKVoltageSource
CODE RULE:
GFCIs are required for all 15, 20 and 30 amps 120V rated circuits on jobsites.
GFCI
Circuit Breaker
H
N
Ground
Temp Power
Transform vs Distribution
Transforming Power
480 or 600 volts is available at site.
Tools can’t run on “commercial power” levels.
The voltage requires transforming to reach 240, 208 or 120 volt ranges.
Temp Power
Power block
Input• 1510-P• 120V• 15 amps• 1 phase
Output• 1610-C• 120V• 15 amps• 1 Phase
Distribute only
Temp Power
Power block
Input• 1510-P• 120V• 15 amps• 1 phase
Output• 1610-C• 120V• 15 amps• 1 Phase
Cordset
Distribute only
Temp Power
Power block
Input• 240 Volts• 1 Phase• 50 Amps
Output• 120 Volts• 1 phase• 6 circuits @ 20 amps each
•Distributes
Oscar
Temp Power
Power block
Input• 240V• 1 Phase• 50Amps
Output•120V•1 phase•6 circuits @ 20 amps each
•Distributes
Oscar®
Temp Power
Power block
Input• 208V• 3 Phase• 200 Amps
Output• 120V• 1 phase• 18 circuits @ 20 amps each
•Distributes
Temp Power
Power block
Input• 208V• 3 Phase• 200 Amps
Output• 120V• 1 phase• 18 circuits @ 20 amps each
•Distributes
Temp Power
Jobsite Problem:
How do you run a tool rated at 120 Volts if only 480 Volts are available?
Answer: Transform the power to 120V.
Transformers either step up or step down voltage based on the design.
Temp Power
Input• 480V• 3 Phase• 60 Amps
Output•120/208V•3 phase•(18) 1 phase circuits @ 20 amps each
Transform section
Distributionsection
Temp Power
Basic Rule:
3 Phase input into a transformer derives 3 phase output. 1 Phase input derives 1 phase output.
480V 3 phase INPUT = 120/208V 3 phase OUTPUT
480V 1 phase INPUT = 240V 1 Phase OUTPUT
Temp Power
Size Matters:
Transformers are rated in KVA – this is the size rating as to the amount of amps they can produce.
Every 15 KVA = Max of (6) 20 amp 120 V circuits
Temp Power
How to determine the right Temp Power Product
Step 1 – Determine the NEED ( Distribute or Transform)
Step 2 – Determine the AVAILABLE POWER- Volts Amps Phase
Step 3 – Determine the EXPECTED ELECTRICAL OUTPUT
Temp Power How to determine - con’t
Step 4 – Determine the CONNECTIONS How will they connect in and out
Be specificUse NEMA valuesVolts amps phase
Step 5 – Determine the BUDGET
Distribute Point to Point Only
Distribute Multiple Taps
Cordsets
“Y” “W” Power Stringers
Distribute with GFCI Protection
GFCI 1060
Distribute / Split Phases / GFCI Protection
6000 7000 8000 Series
Distribute / High Power ( 480 or 600 V )
Oscars Gen Cords Big-E Jr
Big-E
480V Big-E600V Big-E
Transform / Distribute / GFCI Protect
e-Cart Jr. e-Cart