© 2006 American Standard Inc.
Tracer Summit User’s Group
5/22/2012
VSDs and their effect on HVAC system components
![Page 2: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/2.jpg)
e = mc²
© 2
00
6 A
merica
n S
tan
dard
Inc.
speed of light 299,792,458 m/s
water 2 m/s
air 10–20 m/s
![Page 3: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/3.jpg)
500,000 lbs/hrair
500,000 lbs/hrair
600,000 lbs/hrwater
600,000 lbs/hrwater
© 2
00
6 A
merica
n S
tan
dard
Inc.
![Page 4: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/4.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
work = mass × resistance
![Page 5: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/5.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
velocity
pathdiameter
pathlength
fluiddensity
frictionfactor
gravitationalconstant
Darcy-Weisbach EquationDarcy-Weisbach Equation
p = f L V²D 2 gc
![Page 6: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/6.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Darcy-Weisbach EquationDarcy-Weisbach Equation
resistance velocity²
![Page 7: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/7.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
System ResistanceSystem Resistance
return duct
diffusersand grillescoil
dampers
supply duct
![Page 8: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/8.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Fan LawsFan Laws
cfm rpm
p rpm² cfm²
hp rpm³
![Page 9: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/9.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Chiller Laws?Chiller Laws?
resistance velocity²
resistance “lift”
![Page 10: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/10.jpg)
© 2006 American Standard Inc.
Practical Application:Free Discharge Fans
VSDs and their effect on system components
![Page 11: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/11.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Free Discharge SystemFree Discharge System Draw-through cooling tower
Propeller fan
sumpsump
outdoor air
louvers
fill
propeller fan
![Page 12: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/12.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
cfm rpm
p rpm²
hp rpm³
General Fan PerformanceGeneral Fan Performance
![Page 13: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/13.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
frictionpressure
fixed pressure
airflow, %
100
20 40 60 80 1000
sta
tic p
ressu
re,
%system performance
Static Pressuresystem performance
Static Pressure
systemresistance
80
60
40
20
0
![Page 14: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/14.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
system performance
Free Discharge Systemsystem performance
Free Discharge System
airflow, %
100
20 40 60 80 1000
systemresistance
80
60
40
20
0
sta
tic p
ressu
re,
%
![Page 15: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/15.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
airflow, %
100
20 40 60 80 1000
fan performance curves
Fan Speed (N)fan performance curves
Fan Speed (N)
N1N1
N2N2
As fan speed varies …so does airflow volume
80
60
40
20
0
sta
tic p
ressu
re,
%
![Page 16: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/16.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
fan performance curves
Speed N vs. Efficiency fan performance curves
Speed N vs. Efficiency
airflow, %
100
20 40 60 80 1000
N1N1
1
2
1'2'
N2N2
80
60
40
20
0
sta
tic p
ressu
re,
%
![Page 17: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/17.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
performance curves
Fan and Systemperformance curves
Fan and System
airflow, %
100
20 40 60 80 1000
N1N11'
N2N2
180
60
40
20
0
sta
tic p
ressu
re,
%
![Page 18: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/18.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
fan performance curves
Cooling Towerfan performance curves
Cooling Tower
airflow, %
100
20 40 60 80 1000
fan
pow
er,
%
80
60
40
20
0
![Page 19: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/19.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
fan performance curves
Cooling Towerfan performance curves
Cooling Tower
airflow, %
100
20 40 60 80 1000
fan
an
d m
oto
r p
ow
er,
%
poten
tial e
nergy
savi
ngs
poten
tial e
nergy
savi
ngs1-speed
motor
80
60
40
20
0
![Page 20: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/20.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
fan performance curves
Cooling Towerfan performance curves
Cooling Tower
airflow, %
100
20 40 60 80 1000
fan
an
d m
oto
r p
ow
er,
%
1-speedmotor
2-speedmotor
80
60
40
20
0
![Page 21: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/21.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
fan performance curves
Cooling Towerfan performance curves
Cooling Tower
airflow, %
100
20 40 60 80 1000
80
60
40
20
0
fan
an
d m
oto
r p
ow
er,
%
VSD
![Page 22: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/22.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
cooling tower application
Fan Energy Comparisoncooling tower application
Fan Energy Comparison
source: Marley Technical Report H-001A
Control strategy Energy use factor
1-speed fan cycling(base)
100% kWh
2-speed fan cycling 39% kWh
variable-speed control 19% kWh
![Page 23: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/23.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
fan/tower performance curves
Free Cooling at Low Loadfan/tower performance curves
Free Cooling at Low Load
airflow, %
100
20 40 60 80 1000
fan
an
d m
oto
r p
ow
er,
%
100
80
60
40
20
tow
er c
ap
acity
, %80
60
40
20
0
towercapacity
“free” cooling
0
![Page 24: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/24.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
free discharge fans
Summaryfree discharge fans
Summary Performance approximates the
“cube of the speed”
Variable-speed drives (VSDs) are a great option for modulating capacity
When considering VSDs for chilled water plants, start at the cooling tower
![Page 25: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/25.jpg)
© 2006 American Standard Inc.
Practical Application:Ducted Indoor Fans
VSDs and their effect on system components
![Page 26: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/26.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
System ResistanceSystem Resistance
airflow
sta
tic p
ressu
re 3,500 cfm2.0 in. wg
![Page 27: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/27.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
System ResistanceSystem Resistance
p = f L V²D 2 gc
![Page 28: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/28.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
3,500 cfm2.0 in. wg
airflow
sta
tic p
ressu
reSystem ResistanceSystem Resistance
2,000 cfm0.65 in. wg
systemresistance
curve
systemresistance
curve
![Page 29: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/29.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
some devices don’t obey the rules for
System Resistancesome devices don’t obey the rules for
System Resistance
![Page 30: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/30.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
airflow
sta
tic p
ressu
re
systemresistance
curve
systemresistance
curve
valvesclosed
valvesopen
System ResistanceSystem Resistance
![Page 31: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/31.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
airflow
sta
tic p
ressu
re
surgeregion
design
modulationrange
system resistanceVAV SystemVAV Systemactual
![Page 32: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/32.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
1,100 rpm
1,100 rpm
Fan PerformanceFan Performance
airflow
sta
tic p
ressu
re
wide-openairflow
blocked-tightstatic pressure 1100 rpm
![Page 33: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/33.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
airflow
sta
tic p
ressu
reFan SpeedFan Speed
1100 rpm900 rpm700 rpm500 rpm
![Page 34: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/34.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
airflow
sta
tic p
ressu
re
1100 rpm900 rpm700 rpm500 rpm
VAV SystemVAV System
system resistance
fan speed
![Page 35: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/35.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
TT
VAV SystemVAV System
900 cfm 500 cfm
TT
air valves
System resistance changesas valves modulate …
![Page 36: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/36.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
fan modulation
Objectivesfan modulation
Objectives Produce adequate static pressure
Eliminate excess static pressure
Exploit diversity
Maximize energy savings at fan
Provide stable control
Keep everyone comfortable
![Page 37: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/37.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Static Pressure ControlStatic Pressure ControlInsufficient static pressure?
VAV box deliverstoo little airflow
![Page 38: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/38.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Static Pressure ControlStatic Pressure ControlExcessive static pressure?
• Wasted energy
• Poor comfortcontrol
• Poor acoustics
![Page 39: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/39.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Fan Control LoopFan Control Loop
supply fanstatic pressuresensor
SS
controller
![Page 40: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/40.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VAV System ModulationVAV System Modulation
airflow
sta
tic p
ressu
re
design
system resistance
actual
VAVmodulation
curve
1100 rpm800 rpm
![Page 41: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/41.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
static pressure control
Sensor at Fan Outletstatic pressure control
Sensor at Fan Outlet
SS
supply fan
controller
VAV boxes
![Page 42: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/42.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
supply fan
controller
static pressure control
Sensor Down 2/3 of Ductstatic pressure control
Sensor Down 2/3 of Duct
SS
VAV boxes
![Page 43: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/43.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
static pressure control
Sensor Down 3/4 of Ductstatic pressure control
Sensor Down 3/4 of Duct
supply fan
controller
SS
VAV boxes
![Page 44: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/44.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
static pressure control
Sensor Down 3/4 of Ductstatic pressure control
Sensor Down 3/4 of Duct
supply fan
controller
SS
VAV boxes
![Page 45: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/45.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
optimized static pressure control
Sensor at Fan Outletoptimized static pressure control
Sensor at Fan Outlet
supply fan speed orinlet vane position
communicating BAS
VAV damperpositions
staticpressure
SS
static pressuresetpoint
![Page 46: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/46.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
static pressure control methods
Performance Comparisonstatic pressure control methods
Performance Comparison
Controlmethod
Fanoutlet
Supplyduct
Optimized
Airflow
24,000 cfm(full load)
18,000 cfm
18,000 cfm
18,000 cfm
Full-loadpower
60%
100%
55%
43%
Fan inputpower
13 hp
22 hp
12 hp
9.5 hp
Fan staticpressure
2.7 in. wg
2.1 in. wg
1.9 in. wg
1.5 in. wg
![Page 47: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/47.jpg)
© 2006 American Standard Inc.
System Demonstration
VSDs and their effect on system components
![Page 48: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/48.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
why care about
Pump Energywhy care about
Pump Energy
According to the DOE ...
Pumps represent 5% of industrial energy consumption
Total cost of owning a pump is 90% energy consumption
Pump energy consumption generally can be reduced by as much as 20%
![Page 49: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/49.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
pumping chilled water
ASHRAE 90.1-2001pumping chilled water
ASHRAE 90.1-2001
Requires variable chilled water flow if:
Total pump power exceeds 75 hp
AND
System includes > 3 control valves
![Page 50: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/50.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
pumping chilled water
ASHRAE 90.1-2001pumping chilled water
ASHRAE 90.1-2001
Requires 30% design wattage at 50% flow if:
Any variable-flow pump motor > 50 hp
AND
Design head pressure > 100 ft
Typical solution: Variable-speed drive
![Page 51: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/51.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
chilled water system
Variable Primary Flowchilled water system
Variable Primary Flow
1
2
750 gpm
750 gpm
![Page 52: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/52.jpg)
1
2
750 gpm
750 gpm
chilled water system
Full-Load Pressure Drop
© 2
00
6 A
merica
n S
tan
dard
Inc.
tP
control valve
P
![Page 53: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/53.jpg)
chilled water system
Full-Load Pressure Drop
© 2
00
6 A
merica
n S
tan
dard
Inc.
triple-duty valve
1
2
750 gpm
750 gpm
![Page 54: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/54.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
, %
pumping system
Pump & System Curvespumping system
Pump & System Curves
pump
system
design point
![Page 55: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/55.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
, %
pump
system
design point
pump characteristics
Powerpump characteristics
Power
100
50
0
pump power
pow
er
![Page 56: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/56.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable-flow water system
How Does It Unload?variable-flow water system
How Does It Unload?
Depends on:
Chilled-water system curve
Pump curve
Pump control method Ride the curve
Different pump sizes
Vary the speed
![Page 57: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/57.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
, %
pump
system
design point
100
50
0
pump power
pump characteristics
Ride the Curvepump characteristics
Ride the Curve
part-loadpoint
pow
er
![Page 58: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/58.jpg)
chilled water system
Part Load: Ride the Curve
© 2
00
6 A
merica
n S
tan
dard
Inc.
tP
controlvalve
coilflow
1
2
750 gpm
750 gpm
![Page 59: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/59.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable-flow water system
How Does It Unload?variable-flow water system
How Does It Unload?
Depends on:
Chilled water system curve
Pump curve
Pump control method Ride the curve
Different pump sizes
Vary the speed
safe
zone
![Page 60: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/60.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Pump CharacteristicsPump Characteristics
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
, %
pump
system
design point
100
50
0
pow
er
pumppower
![Page 61: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/61.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
system
pu
mp
head
, %
pump
design point
pow
er
100
50
0
pump characteristics
Different Pump Sizespump characteristics
Different Pump Sizes
part-loadpoint
pumppower
![Page 62: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/62.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
system
pu
mp
head
, %
pump
pow
er
100
50
0
pumppower
pump characteristics
Different Pump Sizespump characteristics
Different Pump Sizes
![Page 63: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/63.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
system
pu
mp
head
, %
pow
er
100
50
0
pump characteristics
VFD = Different Pumpspump characteristics
VFD = Different Pumps
1750 rpm1488 rpm
1225 rpm
![Page 64: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/64.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable-speed pump
Control Methodsvariable-speed pump
Control Methods Pressure control (P) at pump
Pressure control (P) at end of system
Critical-valve pressure reset
![Page 65: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/65.jpg)
1
2
750 gpm
750 gpm
P
chilled water system
Part Load: P at Pump
© 2
00
6 A
merica
n S
tan
dard
Inc.
tP
![Page 66: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/66.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable-speed pump
Control Methodsvariable-speed pump
Control Methods Pressure control (P) at pump
Pressure control (P) at end of system
Critical-valve pressure reset
![Page 67: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/67.jpg)
1
2
750 gpm
750 gpm
chilled water system
Part Load: P at End of System
© 2
00
6 A
merica
n S
tan
dard
Inc.
P
tP P
![Page 68: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/68.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable-speed pump
Control Methodsvariable-speed pump
Control Methods Pressure control at pump
Pressure control at end of system
Critical valve pressure reset
![Page 69: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/69.jpg)
chilled water system
Part Load: Critical Valve Reset
© 2
00
6 A
merica
n S
tan
dard
Inc.
1
2
750 gpm
750 gpm
valveposition
tP
P
![Page 70: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/70.jpg)
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
excesspump
pressure
120
dynamicpressure
fixed pressure
fullload
partload
pump characteristics
Part Load: Ride the Pump Curve
© 2
00
6 A
merica
n S
tan
dard
Inc.
![Page 71: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/71.jpg)
pump characteristics
Part Load: P Control at Pump
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
excesspump
pressure
dynamicpressure
fixed pressure
allloads
What the pump needs to produce the required systempressure determines minimum pump pressure, motor speed
© 2
00
6 A
merica
n S
tan
dard
Inc.
![Page 72: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/72.jpg)
pump characteristics
Part Load: P Control at End of System
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
dynamicpressure
fixed pressure
© 2
00
6 A
merica
n S
tan
dard
Inc.
P
Pump P “slides” down thesystem curve …
![Page 73: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/73.jpg)
water flow, %
100
20 40 60 80 1000
80
60
40
20
0
pu
mp
head
pumppressur
e
© 2
00
6 A
merica
n S
tan
dard
Inc.
pump characteristics
Part Load: Critical Valve ResetPump P constantly reset to lowest possible value… almost all pressure drop is dynamic
previoussystem curve
![Page 74: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/74.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable-flow pumping
Summaryvariable-flow pumping
Summary Energy savings depends on:
Pump selections
Fixed vs. frictional pressure components
Control strategy
Energy savings can approach “cube of speed”
Great application for variable-speed drives
![Page 75: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/75.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable-flow condenser water
Pump Speedvariable-flow condenser water
Pump Speed Determining minimum speed
How variable flow affects: Pump
Cooling tower
Chiller
Controlling flow to improvesystem performance
![Page 76: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/76.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
condenser water pump
Minimum Speedcondenser water pump
Minimum Speed
Determinants:
Minimum condenser flow
Tower static lift
Minimum tower flow Nozzle selection
Performance
Compare curve with cubic
![Page 77: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/77.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
cooling tower
Static Liftcooling tower
Static Lift
static lift
![Page 78: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/78.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
cooling tower
Water Distributioncooling tower
Water Distribution
![Page 79: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/79.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
ExampleExample
1500 gpm system, 1770 rpm
Minimum flows:Chiller 658 gpmTower 750 gpm
Tower static lift 12.2 ft
Pump:Speed 974 rpmPump flow 875 gpm
![Page 80: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/80.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable condenser-water flow
Effect on Pump
capacity, gpm
0
20
pu
mp
head
, ft
400 800 1200 1600 2000 24000
40
60
80
100
1770 rpm
1505 rpm
1239 rpm
974 rpm
81%
75%
83%
75%60%
![Page 81: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/81.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
operating dependencies
Full Flowoperating dependencies
Full Flow
Tower design
Condenser watertemperature & flow
Heat rejection Wet bulb
Chiller design
Condenser watertemperature & flow
Load
![Page 82: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/82.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable condenser water flow
Effect on Towervariable condenser water flow
Effect on Tower
70
tow
er
en
teri
ng
wate
r, °
F
60
80
90
100
110
condenser water flow, %
50 60 70 80 90 100
100% fan
![Page 83: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/83.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
100
ch
ille
r p
ow
er,
kW
50
150
200
250
300
condenser water flow, %
50 60 70 80 90
96°FLCWT
1000
variable condenser water flow
Effect on Chillervariable condenser water flow
Effect on Chiller
84°FLCWT
Conditions:
• 70% load
• 70°F WB
• Full-speedtower fan
![Page 84: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/84.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
100
com
pon
en
t/syste
m p
ow
er,
kW
50
150
200
250
300
condenser water flow, %
50 60 70 80 90
chiller
100
variable condenser water flow
Effect on Systemvariable condenser water flow
Effect on System
0pump
tower
system
![Page 85: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/85.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
reducing flow & fan speed
Effect on Towerreducing flow & fan speed
Effect on Tower
70
tow
er
en
teri
ng
wate
r, °
F
60
80
90
100
110
condenser water flow, %
50 60 70 80 90 100
100%
80%
60%
50%
fan speed
conditions:
•70% load
•70°F WB
![Page 86: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/86.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
reducing flow & fan speed
Effect on Systemreducing flow & fan speed
Effect on System
100
syste
m p
ow
er,
kW
50
150
200
250
300
condenser water flow, %
50 60 70 80 90 100
100%
0
80% 60% 50%fan speed
conditions:
•70% load
•70°F WB
![Page 87: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/87.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
reducing flow & fan speed
Effect on Systemreducing flow & fan speed
Effect on System
100
syste
m p
ow
er,
kW
50
150
200
250
300
condenser water flow, %
50 60 70 80 90 1000
100%
80%
conditions:
•70% load
•50°F WB
60%
50%
fan speed
![Page 88: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/88.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
reducing flow & fan speed
Effect on Systemreducing flow & fan speed
Effect on System
100
syste
m p
ow
er,
kW
50
150
200
250
300
condenser water flow, %
50 60 70 80 90 1000
100%
conditions:
•30% load
•50°F WB
fan speed
80%
60%50%
![Page 89: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/89.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable condenser water flow
Summaryvariable condenser water flow
Summary
Determine what savings,if any, are possible
Are pumps alreadylow power?
Can reducing tower-fanspeed achieve most ofthe savings?
![Page 90: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/90.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable condenser water flow
Summaryvariable condenser water flow
Summary
If you decide to reduce flow: Find minimum condenser-
water flow rate
Examine system at variousloads and wet-bulbs …keep chiller out of surge
Document the sequence ofoperation
Help commission the system
![Page 91: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/91.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
variable condenser water flow
Guidancevariable condenser water flow
Guidance Can provide savings …
Finding proper operatingpoints requires more time,more fine-tuning
Two-step process:
1 Reduce design pump power
2 Is variable condenser-waterflow still warranted?
![Page 92: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/92.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
resistance velocity²
VSDs and Chiller LawsVSDs and Chiller Laws
Variable-speed drives benefit centrifugal compressors in water chillers
Review “chiller laws”
Explore scientific cause-and-effect relationships
Maximize benefits
resistance “lift”
![Page 93: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/93.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VSD and centrifugal chillers
A Simple AnalogyVSD and centrifugal chillers
A Simple Analogy
accelerator(speed controlof chiller motor)
brake(inlet guide vanesfor unloading)
![Page 94: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/94.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Motor runs atconstant speed,regardless of load
a simple analogy
Constant-Speed Chillera simple analogy
Constant-Speed Chiller
Inlet guide vanesrestrict refrigerant atoff-design conditions
![Page 95: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/95.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
a simple analogy
Variable-Speed Chillera simple analogy
Variable-Speed Chiller
Based on load,motor speeds upor slows down
![Page 96: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/96.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VSDs and centrifugal chillers
An AnalogyVSDs and centrifugal chillers
An Analogy
In each case:
Energy is wasted
Mechanical wear-and-tearis increased
![Page 97: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/97.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Typical Centrifugal Chiller
evaporator
condenser
compressor
controller
not shown:pressure-reducingdevice
capacity-modulating device
![Page 98: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/98.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Impeller
blade
coldrefrigerant
vapor
coldrefrigerant
vapor
hotrefrigerant
vapor
![Page 99: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/99.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Multistage Compressor
impellersinlet vanes
inlet vanes
![Page 100: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/100.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Centrifugal Compressor
impellerpassage
diffuserpassage
volute
![Page 101: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/101.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Lift versus Load
lift
lvg evaporator water
lvg condenser water
lift Pcnd – Pevp
lift Tlvg cnd – Tlvg evp
load gpm × (Tent evp – Tlvg evp)
56°F
41°F
85°F
99°F
800 gpm
load = 500 tons
2 gpm/ton
58°F(T)
![Page 102: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/102.jpg)
compressorworkcompressorwork
© 2
00
6 A
merica
n S
tan
dard
Inc.
Compressor Work and Chiller Efficiency
cooling capacity/“load”h
ead
/“lift
”
lvg evapwater
lvg condwater
500 tons
58°F
![Page 103: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/103.jpg)
refrigerantflow rate
refrigerantflow rate
© 2
00
6 A
merica
n S
tan
dard
Inc.
Impeller Dynamics
diameter
Vt rpm × diameter
Vr refrig flow rate
rotationalspeed
Vr
RVt
compressorwork
resultantvelocity
tangentialvelocity
radialvelocity
LIF
T
LOAD
![Page 104: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/104.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Compressor Response to Load
full load part load
Vr
VtR
Vr
VtR
![Page 105: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/105.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Compressor Response to Lift
full load part load
Vr
VtR
Vr
VtR
![Page 106: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/106.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Lessons LearnedLessons Learned To reduce lift:
Decrease condenser pressure by reducing leaving-tower water temperature
Increase evaporator pressure by raising chilled water setpoint
VSDs optimize chiller lift efficiency
41°Flvg evapwater
lvg condwater
45°F
75°F
99°F
compressorworkcompressorwork
![Page 107: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/107.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
various system components
Energy Usevarious system components
Energy Use
20
en
erg
y u
se,
%
40
60
80
100
load, %
40 60 80 1000
20
staticlift
chiller w/low lift
chilled water pump(P at end of loop)
condenser waterpump (stopped at875 gpm)
free discharge fan
![Page 108: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/108.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VSDs and centrifugal chillers
A Simple AnalogyVSDs and centrifugal chillers
A Simple Analogy
accelerator(speed controlof chiller motor)
brake(inlet guide vanesfor unloading)But misleading
and technicallyincorrect
![Page 109: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/109.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
75%75%
75°FECWT
chiller efficiency at part load
IPLV and NPLV Conditions chiller efficiency at part load
IPLV and NPLV Conditions
50%50%
65°FECWT
load
lift
25%25%100%100%
85°FECWT
![Page 110: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/110.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VSDs and centrifugal chillers
A Closer Look at IPLVVSDs and centrifugal chillers
A Closer Look at IPLV
VSDs improve part-lift performance, so running two chillers with VSDs at part load seems more efficient than one chiller at double the same load, but …
Load ECWTWeighting kW/Ton
100% 0.01 85°F 0.572
75% 0.42 75°F 0.429
50% 0.45 65°F 0.324
50% 0.45 65°F 0.393
![Page 111: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/111.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VSDs and centrifugal chillers
Performance at 90% LoadVSDs and centrifugal chillers
Performance at 90% Load
*Load equally divided
ECWT
85°F
80°F
75°F
70°F
65°F
Difference
–38.4
–30.0
–20.2
–9.5
+4.3
2 Chillers*
306.4
268.0
230.8
195.2
160.3
1 Chiller
268.0
238.0
210.6
185.7
164.3
Note: Data shows only chiller power.
![Page 112: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/112.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VSDs and centrifugal chillers
Performance at 90% LoadVSDs and centrifugal chillers
Performance at 90% Load
0
50
100
150
200
250
300
350
65 70 75 80 85
Conclusion: 1 chiller uses less power than 2 chillers
ch
ille
r p
ow
er,
kW
entering condenser water, °F
2 chillers:45% load each
1 chiller:90% load
![Page 113: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/113.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
Analyze the SystemAnalyze the System Model:
Building use
Local weather
Economizers
Utility rates
System design
Use programs like TRACE™, DOE 2.x, Chiller Plant Analyzer, HAP
![Page 114: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/114.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VSDs and centrifugal chillers
SummaryVSDs and centrifugal chillers
Summary VSDs improve chiller part-lift
performance Lots of operational hours
Reduced condenser water temperatures
Higher costs of electricity
IPLV is not an economic tool
![Page 115: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/115.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
wrap-up
VSD Effect Differswrap-up
VSD Effect Differs Cubic relationship to speed only
occurs in “free discharge” systems
Control parameters affect savings
In chillers, external parameters define lift (pressure difference)
![Page 116: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/116.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
wrap-up
VSD Effect Differswrap-up
VSD Effect Differs Cooling towers: Nearly cubic
HVAC fans: Not cubic Depends on control strategy
Fan pressure optimization is best
Chilled water pumps: Not cubic Affected by valves and control method
Consider pump pressure optimization based on critical valve
![Page 117: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/117.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
wrap-up
VSD Effect Differswrap-up
VSD Effect Differs Condenser water pumps: Not cubic
Must meet minimum flow or pressure Tower static lift Minimum condenser water flow Minimum tower flow
Reduced flow affects chiller and tower performance
Before applying a VSD, reduce pump design power (CW flow rate)
![Page 118: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/118.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
wrap-up
VSD Effect Differswrap-up
VSD Effect Differs Power for any chiller is reduced at
part load and lift
Chiller savings? Not even close to cubic VSD helps more at part-lift conditions
MUST reduce lift for VSD to slow down and give benefit
Use same condenser water temperatureto compare constant- and variable-speed chillers
![Page 119: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/119.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
VFDs and GensetsVFDs and Gensets
Trane Engineers Newslettervolume 35-1
“How VFDs Affect Genset Sizing” by Court Nebuda
www.trane.com/commercial/location.aspx?item=5
![Page 120: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/120.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
references for this broadcast
Where to Learn Morereferences for this broadcast
Where to Learn More 2005 ENL “Cooling Towers and Condenser
Water Systems”http://www.trane.com/bookstore/catalog.asp?sectionid=14
Bibliography
![Page 121: © 2006 American Standard Inc. Tracer Summit User’s Group 5/22/2012 VSDs and their effect on HVAC system components](https://reader038.vdocuments.mx/reader038/viewer/2022110304/551b6cb7550346d31b8b5e41/html5/thumbnails/121.jpg)
© 2
00
6 A
merica
n S
tan
dard
Inc.
mark your calendar
2006 ENL Broadcastsmark your calendar
2006 ENL Broadcasts May 3 HVAC systems and airside
economizers
Sep 13 HVAC design for placesof assembly
Nov 8 Energy-saving designs for rooftop systems